Siemens DB-ADPT Installation Instructions Manual

Fire Safety
Installation Instructions
Model DB-ADPT Detector/Base Adapter
The SIEMENS Model DB-ADPT detector/base adapter interfaces Series 11 detectors with previously installed DB-3S bases. For Series 3 air duct detector models AD-3P, AD-3ILP, and SA-3P, use Series 11 Air Duct Update Kit AD-11UK, which contains both the DB-ADPT and the required DA-304 air duct cover for Series 11 detectors.
WARNING:
When replacing a detector with a different model, be aware that existing detector accessories connected to the base or air duct housing that were compatible with the old detector may not be compatible with the new detector. Always read the Installation InstrucĀ­tions accompanying the detector to determine detecĀ­tor and accessory compatibility.
Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 07932
P/N 315-094200-6
Siemens Building Technologies, Ltd. 2 Kenview Boulevard Brampton, Ontario L6T 5E4 CN
INSTALLATION
For DB-3S Bases:
1. Remove the existing detector from the DB-3S base.
2. To install the DB-ADPT adapter into the DB-3S base, align the notch in the outer flange of the adapter to the raised surface on the outer ring of the base (Refer to Figure 1).
3. Push the adapter into the base and rotate clockwise to engage the electrical connections. The adapter will automatically stop and lock into place.
4. To make the adapter to DB-3S interface tamperproof in the base, use the Model DB-LK.
5. Install a Series 11 detector following the installation instructions included with the detector.
NOTE: If it becomes necessary to remove the
adapter, push the adapter up into the base while rotating the adapter counterclockwise. Continue to rotate counterclockwise until stop is reached. Then pull downward to disengage from the base. When the DB-LK lock is used, disengage the locking mechanism prior to removing the adapter.
2