Siemens DB-11, DB-11E Installation/wire Connection Manual

Figure 3 Wiring Diagram for DB-11/-11E using HFP-11 and HFPT-11 Detectors
Model DB-11/-11E
(P/N 500-094151/500-094151E)
Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 07932
Siemens Building Technologies, Ltd. 2 Kenview Boulevard Brampton, Ontario, Canada L6T 5E4
Figure 2 Wiring Diagram for DB-11/-11E using FP-11, FPT-11, FS-DP, FS-DPT, and FS-DT Detectors
1a6
-
--
----
+
+++ +++
TO INITIATING CIRCUIT OF SBT, INC. COMPATIBLE CONTROL UNIT
OPTIONAL REMOTE ALARM INDICATOR MODELS RLI-1 / RLI-2
TO NEXT BASE
TO NEXT BASE
DO NOT USE AN END OF LINE DEVICE
DB-11/-11E (NO REMOTE DEVICE)
5
6
1a
1b
5
6
1a
1b
RELAY* CONTACTS 3A, 120 VAC 3A, 30 VDC
DB-11XRS (REMOTE RELAY BASE)
*The relay contacts are shown in the Non-Alarm/System Reset condition.
5+
NO
C
NC
6–
5+
NO
C
NC
6–
DO NOT USE AN END OF LINE DEVICE
TO INITIATING CIRCUIT OF SBT, INC. COMPATIBLE CONTROL UNIT
OPTIONAL REMOTE ALARM INDICATOR MODELS RL-HW / RL-HC
TO NEXT BASE
TO NEXT BASE
DO NOT USE AN END OF LINE DEVICE
DB-11/-11E (NO REMOTE DEVICE)
LINE 1**
LINE 2**
TB1
TB3
TB2
5
6
1a
1b
5
6
1a
1b
RELAY* CONTACTS 3A, 120 VAC 3A, 30 VDC
DB-HR (REMOTE RELAY BASE)
*The relay contacts are shown in the Non-Alarm/System Reset condition.
**HFP-11/HFPT-11 is a polarity insensitive detector. Line 1 and Line 2 can be either line of the loop.
5+
NO
C
NC
6–
5+
NO
C
NC
6–
DO NOT USE AN END OF LINE DEVICE
Figure 1 Wiring Diagram for DB-11/-11E using PE-11, PE-11T, and DT-11 Detectors
CAUTION:
1. Do not use looped wire under base terminal 5. Break wire run to provide supervision of connection.
2. When a remote relay is used to control a critical system function, the relay and its associated detector and optional module(s) must be the ONLY devices on the initiating circuit.
Installation/Wiring Instructions
MODEL DB-11/-11E DETECTOR BASE
Fire Safety
1b
6 5
END OF LINE DEVICE
(NOTE POLARITY
WHEN APPLICABLE)
1a
1b
1b
5
5
6
+
-
+
-
(SEE CAUTION 1)
MULTIPLE REMOTE DEVICES
If remote devices are supported by the initiating circuit, each detector/base may
have up to 2 remote devices with the following configurations and restrictions only:
Remote
Device 1
RR-11
RR-11 RLC-11, RLW-11 RLC-11, RLW-11
Remote
Device 2
RLC-11, RLW-11 RSAC-11, RSAW-11 RSAC-11, RSAW-11
RLC-11, RLW-11
Restrictions
See Caution 2 See Caution 2 Wire from base to RSAC-11/RSAW-11 to RL-11
SEE REMOTE DEVICE INSTRUCTIONS FOR WIRING DETAILS:
DEVICE
RR-11 RLC-11, RLW-11 RSAC-11, RSAW-11
INSTALLATION
INSTRUCTIONS
P/N 315-094924 P/N 315-094925 P/N 315-094926
TO INITIATING CIRCUIT OF SBT, INC. COMPATIBLE CONTROL UNIT
DB-11/-11E (NO REMOTE DEVICE)
DB-HR (REMOTE RELAY BASE)
DETECTOR AND BASE PLACEMENT
Detector and base locations shall follow the drawings provided or approved by Siemens Building Technologies, Inc. or its authorized distributors. This is extremely important! The detector placements shown on these drawings were chosen after a careful evaluation of all facets of the protected area. When drawings are not available, refer to Detector Placement section of detector Installation/Wiring Instructions and to
NFPA Standard 72 and CAN/ULC-S524.
BASE WIRING
Siemens Building Technologies, Inc.'s detectors should be interconnected as shown in Figures 1, 2 or 3 and wired to the control panel following the wiring connection drawing installed on the inside face of each control panel cover. NOTE: H Series devices are wired to the DLC (refer to DLC Installation Instructions, P/N 315-033090.) Note any
limitations on the number of detectors and restrictions on the use of remote devices permitted for each circuit.
DETECTOR MOUNTING USING THE DB-11/-11E BASE
The detector is provided with a separate base which attaches
to a standard 4 inch square, 4 inch octagonal, or single gang electrical box, with the box size and depth required by the NEC for the number and size of conductors used. Wire size: max  14 AWG, min  18 AWG.
Installation Instructions P/N 315-094193-7
Model DB-11/-11E
(P/N 500-094151/500-094151E)
Figure 4 Mounting The DB-11 Base
Siemens Building Technologies, Inc. 8 Fernwood Road Florham Park, New Jersey 07932
Siemens Building Technologies, Ltd. 2 Kenview Boulevard Brampton, Ontario, Canada L6T 5E4
BASE MOUNTING HOLES
MOUNTING HOLE COVERS
USE DBJ-11 JUMPER
KIT, P/N 500-699167
FOR CONTINUITY
CHECK WITH PE-11,
PE-11T OR DT-11
DETECTORS
ALARM LED
LOCATION WITH
DETECTOR
INSTALLED
IN BASE
6
5
1a
1b
D
O
N
O
T
P
A
I
N
T
FACTORY INSTALLED JUMPER
BASE MOUNTING HOLE
ALARM LED
LOCATION WITH
DETECTOR INSTALLED
IN BASE
Figure 5 Mounting The DB-11E Base
Refer to Figures 4 and 5, as applicable.
1. Route all wires outward from outlet box.
2. When ALARM LED viewing is critical, position the LED mark in the base in the intended direction.
3. Route wires through the hole in the center of the base and mount base to outlet box. Make connections directly to the base terminals. Refer to Figures 1, 2 and 3 for details.
4. After all bases are installed, check loop continuity. Refer to the System Manual for the loop continuity check procedure. To allow for the continuity check with PE-11, PE-11T or DT-11 detectors, use DBJ-11 Jumper Kit, P/N 500-699167 (between terminals 1a and 1b) to complete the loop. Do not use a jumper for FP-11/HFP-11/FS family devices.
5. Continuity jumper must be removed from each base prior to installing detector.
6. To insure proper installation of the detector head into the base: a. Route wires away from connector terminals. b. Take up all slack in the outlet box. c. Properly dress and position all wires flat against the base. d. Check that screw terminals are tight.
7. (DB-11 only) Break off the two mounting hole covers, and insert in two outer base mounting holes.