Siemens D2325CPS Installation Instructions Manual

Installation Instructions
Model D2325CPS Single Mode (1310nm) Fiber Optic Interface
INTRODUCTION
The Model D2325CPS from Siemens Industry, Inc. (See Figure 1) is a Fiber Optic interface for the MXL’s RS-485 network (MNET or XNET), FireFinder XLS/Desigo Fire Safety Modular/Cerberus PRO Modular network (HNET or XNET) and HUB-4 FSI. It uses a two-fiber (duplex) pair between each device. The D2325CPS can function as either a repeater or an end point unit.
POWER
(DO NOT USE) -4 (DO NOT USE) -3
-DATA-2 + DATA -1
+24 VDC
-2
-1
DATA REC
A
DATA XTMR
POWER
DATA REC
DATA XTMR
B
D2325CPS
Figure 1
D2325CPS Module
The D2325CPS can operate in either a daisy chain (See Figure 2) or star configuration (See Figure 3). This allows for network configurations that are not possible with the RS-485 network alone.
WARNING:
The D2325CPS module is not listed for use by Factory Mutual. Applications requiring fiber con­nectivity of voice modules/systems are therefore not Factory Mutual listed.
MOUNTING
The D2325CPS has four keyhole slots for #6 screws. Mount the device in the locations listed below using the four #6 screws provided.
A bracket (P/N 500-692880) is available for mounting the D2325CPS in any MXL enclosure that will accept a MOM-4 (See Figure 4). This bracket has the same footprint as the MOM-4 and accommodates two D2325CPS modules. An assembly kit is included with the bracket that contains four nuts and eight screws. Mount the bracket in the enclosure with the four nuts at the positions labeled X (See Figure 4). Start four of the 6-32 screws and slip the keyhole slots in the D2325CPS
over them. Tighten the four screws.
System 3 style rails that mount on an MBR-2 or MME-3 backbox (P/N MSR-1) are also available and can be used for mounting the D2325CPS with the System 3 MPFO Bracket. Up to three brackets can be installed on a single rail.
A bracket, Model D2300-MP, is available for mounting two D2325CPS modules in any FireFinder XLS/ Desigo Fire Safety Modular/Cerberus PRO Modular CAB enclosure. The D2300-MP fits in the same footprint as a CC-5 and mounts to the CAB-MP. A hardware kit is provided for attaching the D2300-MP to the CAB-MP and mounting two D2325CPS modules onto the D2300-MP. Mount the D2325CPS modules prior to installing the D2300-MP onto the CAB-MP. Note that when using two D2325CPS modules, the center two mounting holes on each D2325CPS share the two center studs on the D2300-MP (See Figure 5).
ELECTRICAL CONNECTIONS
POWER INPUT
WARNING:
Do not use the D2325CPS with CXL Systems.
Siemens Industry, Inc. Building Technologies Division Florham Park, NJ
P/N 315-050019-6
The D2325CPS uses filtered or unfiltered 24 VDC. The D2325CPS can only be powered from the sources listed in Table 1 on page 6.
Siemens Canada, Ltd. 1577 North Service Road East Oakville, Ontario L6H 0H6 Canada
SINGLE MODE DUPLEX OPTICAL FIBER
POWER BUDGET - MAX LOSS
-11 dB 9/125 FIBER
SINGLE MODE DUPLEX OPTICAL FIBER
POWER BUDGET - MAX LOSS
-11 dB 9/125 FIBER
CONNECTION
POWER
DATA
XTM
DATA
REC
B
D2325CPS
POWER
+24 VDC
-2
-1
NO
DATA
REC
DATA
XTMR
A
(DO NOT USE) -4
(DO NOT USE) -3
+DATA -1
-DATA-2
EOLR 120 OHMS, 1/4W P/N 140-820150
RS-485 32 NODES MAX SUPERVISED
SUPERVISED
PSR-1
POWER
DATA
XTMR
DATA
REC
B
D2325CPS
POWER
+24 VDC
-2
-1
DATA
XTMR
DATA
REC
A
(DO NOT USE) -4
(DO NOT USE) -3
+DATA-1
-DATA-2
EOLR 120 OHMS, 1/4W P/N 140-820150
RS-485 32 NODES MAX SUPERVISED
EOLR 120 OHMS, 1/4W P/N 140-820150
SUPERVISED
RCC-1
RCC-1
CONNECTION
POWER
DATA
XTMR
DATA
REC
B
D2325CPS
POWER
+24 VDC
-2
-1
NO
DATA
XTMR
DATA
REC
A
(DO NOT USE) -4
(DO NOT USE) -3
+DATA-1
-DATA-2
EOLR 120 OHMS, 1/4W P/N 140-820150
MMB
USE THE 120 ¼ W, 5% EOL RESISTOR ASSEMBLY, AS APPLICABLE: P/N 140-820150 (MMB-1/-2) OR P/N 140-049099 (MMB-3)
W,
Daisy Chain Configuration (MNET Shown)
Figure 2
2
32 NODES MAX
RS-485
SUPERVISED
PSR-1
EOLR 120 OHMS, 1/4W P/N 140-820150
CONNECTION
POWER
DATAPXTMR
DATAPREC
B
SINGLE MODE DUPLEX OPTICAL FIBER
POWER BUDGET - MAX LOSS
-11 dB 9/125 FIBER
NO
DATAPXTMR
DATAPREC
A
CONNECTION
DATA
XTMR
DATA
REC
B
NO
POWER
DATA
XTMR
DATA
REC
A
CONNECTION
POWER
DATA
XTMR
DATA
REC
B
SUPERVISED
TO ADDITIONAL D2325CPS
NO
DATA
XTM
DATA
REC
A
MODULES
D2325CPS
POWER
+24 VDC
-2
-1
USE THE 120 ¼ W, 5% EOL RESISTOR ASSEMBLY, AS APPLICABLE: P/N 140-820150 (MMB-1/-2) OR P/N 140-049099 (MMB-3)
(DO NOT USE) -4
(DO NOT USE) -3
+DATA-1
-DATA-2
W,
D2325CPS
POWER
+24 VDC
-2
-1
RS-485 32 NODES MAX SUPERVISED
MMB
D2325CPS
(DO NOT USE) -4
(DO NOT USE) -3
+DATA-1
-DATA-2
POWER
+24 VDC
-1
(DO NOT USE) -4
(DO NOT USE) -3
+DATA-1
-DATA-2
-2
PSR-1
EOLR
PSR-1
120 OHMS, 1/4W P/N 140-820150
Figure 3
Star Configuration (MNET Shown)
3
X
X
-1
-2
-DATA-2
+DATA-1
+24VDC
(DONOT USE) -4
(DONOT USE) -3
POWER
BRACKET
P/N 500-692880
D2325CPS
A
B
DATA
XTMR
DATA
REC
DATA
REC
POWER
-DATA-2
+DATA-1
(DONOT USE) -4
(DONOT USE) -3
DATA
XTMR
-1
-2
+24VDC
POWER
OMM-1
D2325CPS
A
B
DATA
XTMR
DATA
REC
DATA
XTMR
DATA
REC
POWER
WARNING
DISCONNECT POWER
PRIOR TO REMOVING TERMINAL
BLOCK PROTECTION
Figure 4
Mounting the D2325CPS in an MBR-2 or MME-3 Backbox
FIBER OPTIC CABLE
D2300-MP
POWER
DATA
XTMR
DATA
XTMR
DATA
REC
DATA
B
REC
A
POWER
DATA
XTMR
DATA
XTMR
DATA
REC
DATA
REC
B
A
D2325CPS D2325CPS
POWER
+24 VDC
-1
+DATA-1
-DATA-2
-2
POWER
(DO NOT USE) -4
(DO NOT USE) -3
+24 VDC
-2
-1
(DO NOT USE) -4
(DO NOT USE) -3
+DATA-1
-DATA-2
POWER LIMITED HNET/XNET
ROUTE AS SHOWN
Z O N E 1
Z O N E 2
DLC
RESET
POWER
CARDFAIL
HNETFAIL
GNDFAULT
ALARM
TROUBLE
ZONESSTATUS
CLASSA OPEN
CLASSA RETURN
SHORT
CLASSA OPEN
CLASSA RETURN
SHORT
HUNDREDS
TENS
ONES
HNET
NIC-C
RESET
POWER
CARDFAIL
CANFAIL
HNETFAIL
XNETFAIL
GNDFAULT
LOOPA FAIL
LOOPB FAIL
ACTIVENETWORKS
CAN
HNET
XNET
HNET/XNETSTYLE
STYLE7
STYLE4
GROUNDFAULT
ENABLED
DISABLED
NETWORK PORT
HUNDREDS
TENS
ONES
HNET
P5
1
P4
34
12
PSC-12
RESET
POWER
MODULE FAIL
CAN FAIL
HNETFAIL
GND FAULT
24V 12AFAIL
24V 4AFAIL
HUNDREDS
TENS
ONES
HNET
P9
_
+
TB4
2
1
_
+
_
TB1
1
7
BATTERY
O OFF
TB2
19
13
+
6
2
1
TB3
12
ON
P12
GND
24
N
H
18
CAB-1
Mounting the D2325CPS in a CAB-1 Backbox
Figure 5
4
POWER BUDGET - MAX LOSS
SUPERVISED
- 11 dB 9/125 FIBER
N.C.
N.C.
DATA REC
DATA XTMR
DATA REC
DATA XTMR
DATA REC
DATA XTMR
DATA REC
DATA XTMR
A
B
A
B
D2325CPS
D2325CPS
END POINT
FACP
RS-485 NETWORK MNET/HNET/XNET (SEE FIGURES 7, 8 & 9)
REPEATER
FACP
POWER BUDGET - MAX LOSS
SUPERVISED
- 11 dB 9/125 FIBER
N.C.
N.C.
DATA REC
DATA XTMR
DATA REC
DATA XTMR
A
B
D2325CPS
END POINT
FACP
Figure 6
Wiring the D2325CPS as both a Repeater and End Point Unit
RS-485 RATINGS:
8V P-P 150mA MAX 80 OHMS MAX 18 AWG MIN
(DO NOT USE) (DO NOT USE)
D2325CPS
(DO NOT USE) (DO NOT USE)
+DATA
D2325CPS
(DO NOT USE) (DO NOT USE)
+DATA
D2325CPS
-DATA
-DATA
120 OHMS, 1/4W
P/N 140-820150
-DATA
+DATA
-4
-3
-2
-1
-4
-3
-2
-1
-4
-3
-2
-1
SUPERVISED
EOLR
STYLE 4 MNET
W,
USE THE 120 ¼ W,5% EOL RESISTOR ASSEMBLY, AS APPLICABLE: P/N 140-820150 (MMB-1/-2) OR P/N 140-049099 (MMB-3)
SUPERVISED
EOLR 120 OHMS, 1/4W P/N 140-820150
SUPERVISED
120 OHMS, 1/4W
1234
EOLR
P/N 140-820150
TB1
MMB
(DO NOT USE)
4
(DO NOT USE)
3
2
1
RS-485 RATINGS:
8V P-P 150mA MAX 80 OHMS MAX 18 AWG MIN
REFER TO NET-7 INSTALLATIONINSTRUCTIONS P/N 315-091914
TB1
STYLE 7 MNET
Wiring the RS-485 MNET Network in Style 4 and Style 7
NET-7
MOM-4
Figure 7
5
METSYSECRUOSREWOP
LXM21-95BT;5-41BT:2-BMM
redniFeriF
ogiseD/SLX
riF
ytefaSe
ORPsur raludoM
-ebreC/raludoM
1elbaT
For non-power limited wiring, the PLM-35 (Installation
21-95BT;-,+9BT:3-BMM
6-3;2-13BT:1-RSP
-,+4BT:21-CSP
-,+4BT:21-XSP
Instructions P/N 315-093495) must be used to comply with NFPA 70 per NEC 760. All wiring must be in accordance with Article 760 of NEC or local building codes.
For additional information on the MXL/MXLV System, refer to the MXL/MXLV Manual, P/N 315-092036.
ECRUOSREWOP
4-DAP/3-DAP-,+XUA
53-SP6-51BT
24 VDC CURRENT CALCULATION (MXL ONLY)
The 24 VDC output ratings for the MMB/SMB and PSR-1 are:
MMB-2/-3 6A at 24 VDC (MPS-6); 12A at 24 VDC (MPS-12) SMB-2 6A at 24 VDC (MPS-6); 12A at 24 VDC (MPS-12) PSR-1 6A at 24 VDC (MPS-6); 12A at 24 VDC (MPS-12)
The following modules all draw current from the 24 VDC supply. Add the value for each module that is installed in the enclosure where the D2325CPS is to be installed. Be sure to include the D2325CPS in this calculation.
CDV42EVITCA
ELUDOM
1-MCAAm58 1-CSAAm14 2-CSAAm16
003-IMCAm0
4-MRCAm57 4-MSC
4-MZC
SPC5232DAm26
4-/2-BKMAm0 4-TENAm0 7-TENAm0
M7-TENAm0
7-IOMAm021
61-DOMxamAm058
61-DI
MxamAm23
1-MIPAm0
1-CTBAm44
1-MCRAm031
03-CAZW03taA3
1-CCOAm71
B8-1CZAm071 B8-2CZAm243
BA4-2CZAm761 BA4-3CZAm861
B8-TCZAm8
ELUDOM
TNERRUCYTITNAUQLATOT
xamA5.1+Am43
ti
ucricrep
Am027
mralanisenoz4
7
LATOT
6
(DO NOT USE)
(DO NOT USE)
D2325CPS*
-DATA
+DATA
EOLR
-4
-3
-2
-1
*
120 OHMS, 1/4W
P/N 140-820150
SUPERVISED
RS-485 RATINGS:
8V P-P 150mA MAX 80 OHMS MAX 18 AWG MIN
*
(DO NOT USE)
(DO NOT USE)
D2325CPS
-4
-3
-DATA
-2
+DATA
-1
120 OHMS, 1/4W
P/N 140-820150
SUPERVISED
EOLR
Figure 8
Wiring the RS-485 XNET Network
in Style 4 and Style 7 (MXL)
RS-485 NETWORK
The RS-485 MNET, XNET and HNET networks connect to the D2325CPS on the terminal block with the markings +DATA (1) and -DATA(2). Terminals 3 and 4 are not used. For Style 4 networks one D2325CPS is needed at each Fiber Optic drop. For Style 7 networks two D2325CPS modules are needed at each drop.End of line devices are required on each RS-485 pair in the system. Install them at the extreme ends of each pair. Refer to Figures 7 and 8 (MXL) and Figure 9 (FireFinder XLS/Desigo Fire Safety Modular/Cerberus PRO Modular) for wiring instruc­tions and ratings for both Style 4 and Style 7.
NOTE: Positive and negative ground fault detected
when terminals shorted to earth.
FIBER CONNECTIONS
The D2325CPS can function as both a repeater and an end point unit. When used as an end point, connect
to the fiber connectors labeled A. Make no connec­tion to the B connectors. In the repeater mode, use both pairs of connectors, A and B.
Two Fiber Optic cables are required between each pair of D2325CPS modules. Use a high quality duplex Fiber Optic cable containing 9/125 fiber. Duplex fiber optic cable has two cables in a single shield similar to electrical zip cord. Use ST style fiber connectors.
Please contact the fiber manufacturer regarding instructions for terminating the fiber.
*
OMIT THIS EQUIPMENT FOR STYLE 4 XNET
EOLR
120 OHMS, 1/4W
P/N 140-820150
1234
REFER TO NIM-1R OR NIM-1W INSTALLATION INSTRUCTIONS P/N 315-092953 OR P/N 315-099165, AS APPLICABLE
TB3
NIM-1R/-1W
MOM-4
When installing the fiber pairs, each fiber must connect between the transmit data (DATA XTMR) on one D2325CPS and the receive data line (DATA REC) on the other D2325CPS.
The D2325CPS fiber connection is classified as Style DCLB and Style DCLA per ULC-527.
INDICATORS
The D2325CPS has five LED indicators for Power and Status.
The LEDs are located on the side of the module with the Fiber Optic connectors. The Power LED is green and lights whenever there is 24 VDC. Both channels A and B have a yellow and green LED. The green LED indicates that the D2325CPS is transmitting data on that channel. The yellow LED lights when data is received.
ELECTRICAL RATINGS
tnerruCeludoMCDV42evitcAAm26
tnerruCeludoMCDV42ybdnatSAm26
Input Power 18-31 VDC, 62mA max Battery Power 24 VDC, 62mA max RS-485 8V (P-P), 150mA max
7
(DO NOT USE)
(DO NOT USE)
-DATA
+DATA
EOLR
-4
-3
-2
-1
120 OHMS, 1/4W
P/N 140-820150
D2325CPS
RS-485 RATINGS: 8V P-P 150mA MAX 80 OHMS MAX 18 AWG MIN
NO EOLR REQUIRED AT THE NIC-C
STYLE 4 XNET
(DO NOT USE)
(DO NOT USE)
D2325CPS
-DATA
+DATA
-4
-3
-2
-1
SUPERVISED
DO NOT USE
12345678
910111213141516
DO NOT USE
NIC-C
ONE SLOT OF CC-5/CC-2
17 18 19 20 21 22 23 24
DO NOT USE
EOLR
120 OHMS, 1/4W
P/N 140-820150
(DO NOT USE)
(DO NOT USE)
D2325CPS
RS-485 RATINGS:
8V P-P 150mA MAX 80 OHMS MAX 18 AWG MIN
NO EOLR REQUIRED AT THE NIC-C
-DATA
+DATA
-4
-3
-2
-1
SUPERVISED
SUPERVISED
DO NOT USE
12345678
910111213141516
DO NOT USE
DO NOT USE
NIC-C
ONE SLOT OF CC-5/CC-2
STYLE 7 XNET
17 18 19 20 21 22 23 24
DO NOT USE
Figure 9
Wiring the RS-485 HNET or XNET Network in Style 4 and Style 7
(FireFinder XLS/Desigo Fire Safety Modular/Cerberus PRO Modular)
8
D2325CPS
RS-485 RATINGS: 8V P-P 150mA MAX 80 OHMS MAX 18 AWG MIN
(DO NOT USE) (DO NOT USE)
-DATA
+DATA
-4
-3
-2
-1
SUPERVISED
20 FT IN CONDUIT
STYLE 4 RS-485 HUB-4 FSI
EOLR
120 OHMS, 1/4W
P/N 140-820150
PORT 1
+
+B-B-
A
12345678
910111213141516
A
B
+
+
RS-485
INTERFACE
Port #3
A
A
B
-
-
x
HUB-4
+ A
A+B
RS-485
INTERFACE
x
Port #2
PORT 2
+B-B-
B-A
+
MODEM OR
RS-485
INTERFACE
Port #4
A
-
x
ONE SLOT OF CC-5/CC-2
17 18 19 20 21 22 23 24
(DO NOT USE) (DO NOT USE)
-DATA
+DATA
-4
-3
-2
-1
D2325CPS
(DO NOT USE) (DO NOT USE)
-DATA
+DATA
-4
-3
-2
-1
D2325CPS
EOLR
120 OHMS, 1/4W
RS-485 RATINGS: 8V P-P 150mA MAX 80 OHMS MAX 18 AWG MIN
P/N 140-820150
STYLE 7 RS-485 HUB-4 FSI
20 FT IN CONDUIT
SUPERVISED
EOLR
120 OHMS, 1/4W
P/N 140-820150
SUPERVISED
RS-485
INTERFACE
x
Port #2
+
+B-B-
A
12345678
910111213141516
A+B
+
RS-485
INTERFACE
Port #3
B
-
x
+
A
A
A+B+B-A
A
-
HUB-4
+ B-B-A
MODEM OR
RS-485
INTERFACE
x
Port #4
-
ONE SLOT OF CC-5/CC-2
17 18 19 20 21 22 23 24
Wiring the RS-485 HNET and XNET Network Style 4 and Style 7
(FireFinder-XLS/Desigo Fire Safety Modular/Cerberus PRO Modular)
Figure 10
9
Cyber security disclaimer
Siemens products and solutions provide security functions to ensure the secure operation of building comfort, fire safety, security management and physical security systems. The security functions on these products and solutions are impor­tant components of a comprehensive security concept.
It is, however, necessary to implement and maintain a comprehensive, state-of-the-art security concept that is custom­ized to individual security needs. Such a security concept may result in additional site-specific preventive action to ensure that the building comfort, fire safety, security management or physical security system for your site are operated in a secure manner. These measures may include, but are not limited to, separating networks, physically protecting system components, user awareness programs, defense in depth, etc.
For additional information on building technology security and our offerings, contact your Siemens sales or project department. We strongly recommend customers to follow our security advisories, which provide information on the latest security threats, patches and other mitigation measures.
http://www.siemens.com/cert/en/cert-security-advisories.htm
P/N 315-050019-6 Document ID A6V10244656
10
Loading...