CZM-4
Conventional Zone Module
• Four Conventional Initiating Device Circuits
• Supports the Use of:
30 Two Wire Photo or Ion Detectors Per Circuit
Projected Beam Detector (Limit 1 Per Circuit)
Unlimited Shorting Devices
Detector Relay Bases
Audible Bases
Remote Indicator Lamps
• Class A (Style D)
• Class B (Style B)
• On-Board Microprocessor
• 32 Character Custom Alphanumeric Message
Per Circuit
• Optional Alarm Verification by Circuit
• Walk Test by Circuit
• Circuits Power Limited per NEC 760
• Listed, ULC Listed, FM, CSFM, NYMEA
and City of Chicago Approved
Description
The Conventional Zone Module CZM-4 is used with the
MXL to provide four Class A (Style D) or Class B (Style
B) conventional initiating device circuits. Each circuit can
monitor up to 30 Siemens Fire Safety two wire photoelectric or ionization smoke detectors and an unlimited
number of normally open contact devices. Projected
Beam Detectors may also be used. The CZM-4 circuits
will support the use of Detector Relay Bases, Audible
Bases and Remote Indicator Lamps. Activation of any
device on a circuit will initiate a zone alarm condition
resulting in the operation of programmed functions. Any
circuit in the alarm or trouble condition will be identified
by a user specified 32 character alphanumeric message
displayed on the MXL LCD annunciator.
Each of the CZM-4’s circuits are designed to function in a
local “Degrade” mode during failure of the MXL main
processor or the loss of the system communication
network. While in the “Degrade” mode the CZM-4 is still
capable of reporting both alarm and trouble conditions and
activating local outputs.
Any or all of the CZM-4 circuits can be programmed to
operate with the “Alarm Verification” feature. This feature
allows the automatic verification of alarm conditions caused
by smoke detectors in order to prevent nuisance alarms.
The CZM-4 module plugs into one full slot in the MOM-2
or MOM-4 expansion card cage. Up to two CZM-4 modules may be plugged into a MOM-4 card cage.
CATALOG NUMBER
5003
Electrical Specifications
Electrical Connections
1. Initiating device circuits:
Voltage range 20-24.5 VDC
Supervisory current 4mA max. capacitor EOL
9mA max. resistor EOL
Alarm current 180mA max. per zone
2. Initiating devices per zone:
Up to 30 detectors, any combination of those in No. 3
below. Up to five waterflow switches may be used.
Any number of direct shorting devices may be used.
Wiring may be Style D (Class A) or Style B (Class B).
3. The UL identifiers for compatibility are the same as the
model names specified below. Compatible
Siemens Fire Safety detectors are:
Detector Installation Instructions
DI-3/3H P/N 315-081943
DI-A3/A3H P/N 315-081943
DI-4A/4H P/N 315-085257
DI-6 P/N 315-085257
DI-B3/B3H P/N 315-086590
P/N 315-086591
P/N 315-086592
PE-11/PE-11T P/N 315-094198
DT-11 P/N 315-095429
PE-3000/3000T P/N 315-086441
PE-3/3T P/N 315-086545
PBA-1191 P/N 315-094912
Dimensions
4. All circuits are power limited to NFPA 70 per NEC 760.
Each detector or group of detectors must use a two
wire circuit of at least 18 AWG thermoplastic fixture
wire enclosed in conduit, or 18 AWG limited energy
shielded cable without conduit, if permitted by local
building codes.
5. Total circuit resistance must not exceed 70 ohms, 40
ohms if relay bases are used.
Ordering Information
Refer to Installation Instructions P/N 315-090726
Siemens Building Technologies
Fire Safety
Fire Safety
8 Fernwood Road
Florham Park, NJ 07932
Tel: (973) 593-2600
FAX: (973) 593-6670
Website: www.sbt.siemens.com/fis
5/02
5M
SFS-IG
Printed in U.S.A.
Fire Safety
2 Kenview Boulevard
Brampton, Ontario
Canada L6T 5E4
Tel: (905) 799-9937
FAX: (905) 799-9858
May 2002
Supersedes sheet dated 8/99