Siemens Cerberus DLO1191 User Manual

Page 1
Cerberus® DLO1191 Linear smoke detector
Technical description Planning Installation Commissioning
Siemens Building Technologies
Manual DS11
Section 3
Cerberus Security for People and Assets
Page 2
Data and design subject to change without notice. / Supply subject to availability
.
E Copyright by Siemens Building Technologies AG
We reserve all rights in this document and in the subject thereof. By acceptance of the document the recipient acknowledges these rights and undertakes not to publish the document nor the subject thereof in full or in part, nor to make them available to any third party without our prior express written authorization, nor to use it for any purpose other than for which it was delivered to him.
Page 3
09.2000
I
Siemens Building Technologies Cerberus Division
1 Overview 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 Characteristics 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2 Design 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Operating principle 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2 Technical data 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 Collective mode 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Interactive Mode 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 General data 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 Design and principle of operation 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Detector 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Structure of the infrared beam 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3 Alignment possibilities 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Reflectors 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.5 Compatibility 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.6 Description of block diagram 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.7 Functions in operation with interactive system 10. . . . . . . . . . . . . . . . . . . . . . . . .
3.7.1 Emergency operation 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.7.2 Line isolation function 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.7.3 Diagnostic facilities 10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.7.4 Self-test / functional state 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.8 General detector functions 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.8.1 Alarm algorithms 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.8.2 Fuzzy Logic 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.8.3 Possible diagnosis results 16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 Planning 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 General project engineering principles 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2 Operating conditions 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3 Fields of application 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3.1 Examples of suitable fields of application 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3.2 Examples of unsuitable fields of application 18. . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.4 Monitoring areas with flat ceilings 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5 Monitoring areas with sloping ceilings 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.5.1 Additional DLO1191’s on the slope of the ceiling 19. . . . . . . . . . . . . . . . . . . . . . .
4.6 Monitoring areas with joist constructions 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.6.1 Layout underneath joist construction 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.6.2 Layout within the joist area 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.6.3 Detection of smouldering fire in high rooms 22. . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.7 Guideline for distances between DLO1191 and reflector 22. . . . . . . . . . . . . . . . .
4.8 Panes of glass 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.8.1 Penetration of panes of glass 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.8.2 Application example 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.8.3 Reflectors mounted on glass walls 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.9 Minimum distances between two pairs of detectors 25. . . . . . . . . . . . . . . . . . . . .
4.10 Beam spacing from the ceiling 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.11 Maximum monitoring width 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.12 Measures for dividing long distances 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.13 Measures against condensation 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.14 Installation locations 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.15 Accessibility 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5 Installation 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 Mounting 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 Wiring 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2.1 Special filter 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2.2 Detector heater 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3 Interactive mode 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4 Collective mode 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page 4
II
Siemens Building Technologies Cerberus Division
09.2000
5.5 Connection 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6 Commissioning 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1 Settings 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2 Mechanical adjustment 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3 Electronic alignment 34. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4 Initialization 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.5 Addressing in the interactive system 35. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 Faults / overhaul 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1 Fault 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.1.1 Interruption to beam 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.2 Reflection 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.3 Checklist for trouble-shooting 36. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7.4 Functional check / overhaul 37. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8 Terminology 38. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Page 5
e1276e
1
Siemens Building Technologies Cerberus Division
09.2000
1 Overview
1.1 Characteristics
Directly connectible to the Cerberus interactive system AlgoRex
Switchable to collective systems Microprocessor-controlled signal processing Suitable for surveillance ranges from 5 to 100m Operates according to the principle of light-attenuation by smoke Response behavior selectable in 3 sensitivity stages Transmission of 4 danger levels per sensitivity setting Transmission of four function states:
normal, information, impairment, fault
Automatic digital compensation of ambient influences High immunity to extraneous light Transmitter and receiver installed in the same housing Easy installation, adjustment and commissioning Two-wire installation Comprehensive accessories New diagnostic capabilities with fuzzy logic Efficient signal processing algorithms with application-specific characteristics Comprehensive EMC concept based on the latest technologies
enables the detector to be installed in difficult environments
Integrated multi-coincidence circuit
suppresses extreme electrical and optical noise signals
Automatic and comprehensive self-test
Page 6
e1276e
2
Siemens Building Technologies Cerberus Division
09.2000
1.2 Design
The BeamRex DLO1191 comprises:
Base DLB1191A consisting of:
Terminal support with terminals
The base is required already at the time of installation. The base housing features six PG16 tapped cable inlets.
Detector module DLA1191A consisting of:
Transmitter Receiver Lens
Electronics The plug-in detector module is inserted just prior to commissioning. The lens can be optimally aligned to the reflector by means of the adjustment set.
Reflectors
Different reflectors are available for different distances:
5 to 30m Reflector foil DLR1193 (10 x 10cm) 1 pc. 30 to 50m Reflector foil DLR1192 (20 x 20cm) 1 pc. 50 to 65m Reflector foil DLR1192 (20 x 20cm) 4 pcs. 20 to 100m Prism made of glass DLR1191 (cat’s eye) 1 pc.
with built-in heating against condensation
Short distance filter
For shorter distances between 5 and 10 m an additional short distance filter is required:
5 to 8m DLF1191-AB 7 to 10 m DLF1191-AA Filter against external light influences DLF1191-AC
The detector is rarely influenced by external light. If, however, powerful external light causes interference, the filter DLF1191-AC can be used to eliminate this.
Accessories:
Detector heater DLH1191 for DLO1191, against condensation of the lens
Auxiliary tools:
Detector adjustment set DZL1191 consisting of:
Adjustment device
Test filter
Aiming device
Page 7
e1276e
3
Siemens Building Technologies Cerberus Division
09.2000
1.3 Operating principle
The linear smoke detector operates on the basis of the extinction principle, i.e. the reduc­tion in light intensity due to smoke is measured. The transmitter (IRED) emits a strongly focused infrared light bundle along the optical measuring section. Without smoke a large part of the beams attains the reflector and is sent back in the same direction toward the receiver. The arriving light produces an electrical signal on the photodiode of the receiver.
Receiver
Transmitter
Measuring section
ReflectorDetector
Fig. 1 Linear smoke detector without smoke If smoke penetrates the measuring section, part of the light beams is absorbed by the smoke
particles while another part is scattered by the smoke particles, i.e. the light beams merely change direction. The remaining light reaches the reflector. The remaining light is then reflec­ted and once again passes t hrough the m easuring section a nd is f urther attenuated. T hus only a small portion of the beam reaches the receiver and the signal (S
smoke
) becomes smaller.
Smoke particles
Scattering
Scattering
Scattering
Light beam Residual light
Absorption
Fig. 2 Measuring principle of the linear smoke detector with smoke
Extinction = Absorption + Scattering
Page 8
e1276e
4
Siemens Building Technologies Cerberus Division
09.2000
2 Technical data
Normal ambient conditions, if nothing else is specified: Temperature T
a
=20°C (293K)
Air pressure: p = 1000hPa (750 Torr)
2.1 Collective mode
Value
Parameters Symbol Unit min. typ. max. Conditions
Operating voltage (quiescent)
U
b
V 18 28
Maximum permissible voltage U
max
V 30
Switch-on current I
e
mA 2.8
Operating current (quiescent condition)
I
b
mA 1.5 2.8
Alarm voltage at IA = 1 ... 10mA U
A
V 5 11
Alarm current at Ub = 24V I
A
mA 40 75
Reset voltage U
R
V 2 6
Reset current I
R
µA 5 500
Reset time (UR = 2V) t
R
s 2
Response indicator Voltage Current
Flashing frequency
U
ie
I
ie
V
mA
Hz
3
1
6
60
100
permanent pulsed f ≥0.5Hz, Duty Cycle 50% depending on line module
Connection factor KMK 25 maximum 1 detector per
detection line
2.2 Interactive Mode
Value
Parameters Symbol Unit min. typ. max. Conditions
Operating voltage (quiescent)
U
b
V 21.2 33.3 modulated
Operating current (quiescent condition)
I
b
mA 1.5
Baud rate kBd 4.8 Response indicator
Flashing intervals: light
dark
Response indicator current
ms
s
mA
20
1.5 15
depending on control unit
Connection factor IMK 10 Isolator factor = 1
Page 9
e1276e
5
Siemens Building Technologies Cerberus Division
09.2000
2.3 General data
Value
Parameters Symbol Unit min. typ. max. Conditions
Distance between detector and reflector
Additional area (without approval)
L m 8
5
1008<10m filter DLF1191-AA
Filter DLF1191-AB
Response sensitivity reduced standard increased
D
1
% % %
65 50 30
Attenuation of the beam (forward and return path)
Compensation (if beam is attenuated)
Compensation speed
%
%/h
50
4 Self-test interval min. 15 Alarm integration s 6 16 Dependent on diagnosis Fault activation % >90 Attenuation of the beam IR transmitter
Wavelength Pulse frequency Pulse length
nm
Hz µs
880
6
25
Attenuation of the beam
Elektromagnetic compatibility V/m 50 1MHz...1GHz Operating temperature T
a
°C 25 +60
Humidity 30°C
>30°C
95% rel.
29g/m
3
Storage temperature T
l
°C 30 +75
Colour: pure white ~RAL9010
Detector heater DLR1191 / DLH1191
Supply voltage U
H
VDC 20 30
Operating current I
H
mA 33 50
Resistance R 600
Classification
Standards BS 5839: Part 5
CE conformity marking Application category IEC 721-3: 3K6 Test category IEC 68-1: 25/060/42 Protection category EN60529 / IEC529: IP65
Compatibility
To AlgoRex interactive fire detection system with AlgoLogic S11 To Cerberus control units with collective detector evaluation
Environmental compatibility:
Easy to overhaul Easy to uninstall and disassemble Plastic material identifiable through embossed code
Page 10
e1276e
6
Siemens Building Technologies Cerberus Division
09.2000
3 Design and principle of operation
3.1 Detector
Special filter
Connector adjustment device
Programming switch Detector heater terminal
Locking screw
Knurled screw
for vertical adjustment
Knurled screw for horizontal adjustment
Locking screw
Reed contact (initialization) Response indicator
Receiver lens
Transmitter lens
Sighting device Sighting device (foresight)
(mirror with backsight)
Fig. 3 Detector
3.2 Structure of the infrared beam
The infrared beam emitted by the transmitter to the reflector is not a strictly parallel bundle of rays. It exhibits a certain degree of scattering which makes it conical in shape. The radi­ation energy decreases towards the outside, so that the beam can be divided into the three effective, core and scattered regions. The reflector possesses the characteristic to retransmit the received light.
Effective region Core region Scattered region
DLO DLR
Fig. 4 Structure of the infrared beam
Page 11
e1276e
7
Siemens Building Technologies Cerberus Division
09.2000
The effective region corresponds to the ribbon connecting transmitter, reflector and re ­ceiver.
The core region contains sufficient radiation energy to operate the system. The energy in the scattered region is not sufficient to ensure reliable operation of the
system.
100m
DLO
DLR
ø1,5m
0,43°
Opening angle
0,43°
Diameter of the core region
Infrared beam
Fig. 5 Diameter of the core region
3.3 Alignment possibilities
The infrared beam can be adjusted by each 10° in horizontal direction and each 5° in vertical direction from the centre axis. When selecting the optimum mounting location bear in mind that this adjustment range can be fully used. Experience has shown that the detector and reflector should be arranged as parallel as possible especially with distances of >50m, as this makes adjustment simpler.
Diameter of the core region
100m
16m16m
DLR
10°
10°
DLR
DLO
Fig. 6 Horizontal adjustment range of the optical system max. 10° each side of the axis
Diameter of the core region
5° 5°
100m
8m
8m
DLR DLR
DLO
Fig. 7 Vertical adjustment range of the optical system max. 5° above and below the
axis
One rotation of the knurled screw moves the beam at 100m approx. 1.15m.
Page 12
e1276e
8
Siemens Building Technologies Cerberus Division
09.2000
3.4 Reflectors
Retroreflectors reflect the received light beam in parallel to the latter. For this reason the reflector does not have to be installed thereby mandatory right–angled to the infrared beam. Also vibrations and distortions of the reflector mounting wall do not cause any problems. Another advantage is that any extraneous light is also reflected in its own di­rection and consequently does not reach the receiver.
Reflector
Reflector
Reflector
max. ±20°
max. ±20°
Fig. 8 The reflector and reflector foil can be mounted inclined max. ±20° in all
directions
DLR1191 prism
The retroreflecting prism has the shape of a pyramid whose lateral faces are formed by isosceles orthogonal triangles. Light beams entering through the base are completely re­flected twice on the lateral faces and reflected back through the base.
The prism is installed in a housing that is identical to the one used for the detector base. The reflector is equipped with a reflector heater at the factory. If dew condensation is pos­sible the heater should be connected to a 24V supply.
Light beam
Fig. 9 DLR1191 reflector and reflection principle
DLR1192, DLR1193 reflector foil
This foil consists of microprismatic elements that are formed by transparent, synthetic resin sealed to a plastic substrate. In principle, the reflector foil has the same effect (func­tion) as the prism.
3.5 Compatibility
Interactive Collective
Fire detection system S11 S11, MS9 Control unit CS1140 CS11.., CZ10
Page 13
e1276e
9
Siemens Building Technologies Cerberus Division
09.2000
3.6 Description of block diagram
The transmitter 1 transmits the light pulses to the reflector 2. This transmits the light pulses back to the receiver
3
. The light pulses are proportional to the signal current,
which is amplified in the preamplifier
4
and fed to the customer-specific integrated circuit
(ASIC)
5
. The microprocessor (µP) 6 synchronizes the receiver pulses with the trans-
mitter pulses so that no external pulse is evaluated. The sensor-specific functions are contained in the ASIC. It is used to filter signals, pro-
cess signals using fuzzy algorithms, amplify signals and for the entire sequence control which is synchronized with the µP.
The µP communicates with the control unit via the line interface
7
via terminals 8 and the two-wire bus line. The detector receives commands which activate the type of opera­ting mode, diagnostic stages etc. via the data interface which is integrated in the line inter­face. The detector transmits response signals, the results of diagnostic polling and status signals back to the control unit.
With the help of the isolation function, sections which malfunction are isolated, so that in the event of a short circuit, the entire bus line does not break down. Upon short circuit, two electronic switches (FET) open automatically and isolate the line in the area where the malfunction has occurred until the short circuit has been eliminated.
The internal response indicator (AI)
9
and the external response indicator 10 provide in-
dication of alarm and are activated by the control unit. The 6 DIP switches
11
allow parameterization of the detector (see section 6.1).
The REED contact
12
serves to initialize the detector during commissioning (see section
6.4). A detector heating device, which prevents condensation of the lenses, can be connected
to detector heating terminal
13
.
The DZL1191 adjustment device can be connected via connector
14
. The purpose and
function of the adjustment device is explained in section 6.3 (electronic alignment)
11 12
9
1
13
4
3
8
10
1 2 3 4
Transmitter
2
Receiver
Reflector
5 6 7
ASIC µP
Pream-
plifier
Line
interface
4 5 6
+
_
YXWV
+
_
ZMB
+
+
24V
+
Reed internal AI
external AI
DIP switches
Adjustment
14
Detector heating
Test point for production Reserve
contact
device
device
Fig. 10 Block diagram
Page 14
e1276e
10
Siemens Building Technologies Cerberus Division
09.2000
3.7 Functions in operation with interactive system
3.7.1 Emergency operation
If the DLO1191 can no longer be polled by the control unit, for example, due to a µP fail­ure, it switches automatically to emergency operation. In the event of a fire this detector is still able to trigger a collective alarm.
3.7.2 Line isolation function
If a short circuit occurs on the detector bus line, detectors with separator prevent failure of the entire bus line because only the defective portion of a line is isolated. The DLO1191 features such a isolation function. Before and after the detector an electronic switch (FET) is installed in the bus line. This switch opens automatically in the event of a short circuit and the defective portion of the detector line is disconnected.
3.7.3 Diagnostic facilities
A detector can transmit four events to the control unit:
Danger level 0 (quiescent value) Danger level 1 (possible danger) Danger level 2 (probable danger) Danger level 3 (highly probable danger)
Danger level 1 For early warning where installation locations are critical, the number of times the thresh-
old to danger level 1 is exceeded is counted by the control unit. When the counter reaches a preset value an information «application warning» is displayed. This information is reg­istered in the event memory of the basic parameterization of the control unit.
Danger level 2 The occurence of danger level 2 causes the actuation of an information «Warning» in the
basic parameterization of the control unit. This information is also actuated in the event memory of the basic parameterization of the control unit.
Danger level 3 As a rule, this is a precondition for direct alarm actuation. Dual or multiple cross-zoning is
possible through corresponding programming of the control unit.
Response threshold 1...3 corresponds to danger levels (G1 ... G3) for standard sensitivity
Time
Signal [%]
0
10
20
30
40
50
60
70
80
90
100
110
0% compensation value
100% response threshold 3 (G3)
85% response threshold 2 (G2)
70% response threshold 1 (G1)
Signal
NF = Compensation
max. NF
Page 15
e1276e
11
Siemens Building Technologies Cerberus Division
09.2000
3.7.4 Self-test / functional state
Periodically or on request by the control unit a comprehensive detector self-test is initi­ated which monitors the signal amplifier and the EEPROM.
Also periodically monitored are the compensation value, line voltage, etc. The entire sig­nal path is monitored with the compensation value. If the compensation value is too high or too low, a corresponding signal is generated.
If the detector signals status changes, the control unit is able to read out the cause from the detector memory.
«Functional state 0» corresponds to «Normal state» «Functional state 1» corresponds to «Information»
e.g. thermal turbulence, repeated interruption of the beam, condensation «Functional state 2» corresponds to «Impairment»
e.g. compensation value too high/too low, voltage at reservoir capacitor is too low «Functional state 3» corresponds to «Fault»
e.g. data fault in the EEPROM, beam interruption, compensation value is invalid
3.8 General detector functions
3.8.1 Alarm algorithms
Compensation value
The compensation value (NFW) is the reference variable for the actual measurement sig­nal. All thresholds, diagnostic functions and self-checking are based on the current com­pensation value.
The first compensation value (NFW) is set at the time of initialization. It is subsequently updated approx. every 60 minutes to compensate a slow drift of the measurement signal. This drift can be caused, for example, by contamination of the detector optics.
The maximum compensation is 50% of the total signal of 100%.
Response threshold
The response threshold corresponds to a danger level. An alarm algorithm is activated when the response threshold drops. According to the sensitivity setting, the response threshold is higher or lower.
Page 16
e1276e
12
Siemens Building Technologies Cerberus Division
09.2000
Response threshold 3 of the different sensitivities
Time
Signal [%]
0
10
20
30
40
50
60
70
80
90
100
110
0 % NFW
30% response threshold 3
50% response threshold 3
65% response threshold 3
(low)
(high)
(standard)
NFW = Compensation value
Smoothing
The measuring signal is measured with a 6Hz clock. The raw data are processed with so-called smoothing filters for subsequent evaluation. In this way extreme peak values caused by signal interference are ”smoothed”.
An alarm is triggered based on the smoothed signals.
Time
Raw data
Smoothing
Counts
Page 17
e1276e
13
Siemens Building Technologies Cerberus Division
09.2000
Smoothing filter
Time
Signal [%]
0
10
20
30
40
50
60
70
80
90
100
110
0% compensation value (NFW)
30% response threshold 3
(standard)
3 sec. 12 sec. 48 sec.
0 sec.
Measured value
A
A
AC
C C
50% response threshold 3
65% response threshold 3
(high)
(low)
Smoothings
B
NFW x 1.5
120
130
140
150
Three smoothing filters A, B and C are used. They are characterized by the time it takes to reach response threshold 3 of the corresponding sensitivity setting.
If the smoothed signal reaches response threshold 1 or 2, in the interactive system the corresponding mode is activated by means of the corresponding danger level. These le­vels are not evaluated in the collective system.
If the smoothed signal reaches response threshold 3, the alarms in the alarm counter are added up. Upon reaching the given value, danger level 3, i.e. an alarm is activated.
According to the diagnosis made, other alarm parameters are automatically selected:
Diagnosis Fire or slowly-developing fire alarm activation after 6s
(smoothing A + 20 alarm counts)
Diagnosis Noise or repeated interruption alarm activation after 16s
(smoothing C + 20 alarm counts)
Diagnosis Test filter alarm activation after 10s
(smoothing A + 40 alarm counts)
Smoothing filter B filters out reflections. Reflecting or shining surfaces, which are too near at the path of the beam, can impair the
detector.
Smoothing B > actual compensation value x 1.5 = reflection
Page 18
e1276e
14
Siemens Building Technologies Cerberus Division
09.2000
Application diagnoses
The detector has an automatic diagnosis evaluation facility based on complex fuzzy algo­rithms. The raw data are treated by 4 different filters. Each filter assesses a special cha­racteristic of the signal: Gradient, noise, asymmetry, jump.
Filter
Typical events and results for the 4 filters:
Time
U
Raw data
Fire
Time
Gradient indicator
G
Thermal turbulence
Time
U
Raw data
Time
R
Noise indicator
Repeated interruptions
Time
U
Raw data
Time
A
Asymmetry indicator
Test filter
Time
U
Raw data
Time
S
Jump indicator
Page 19
e1276e
15
Siemens Building Technologies Cerberus Division
09.2000
3.8.2 Fuzzy Logic
The different «filtered» and smoothed signals are combined with fuzzy logic. A diagnosis is prepared automatically and on-line.
Principle of the fuzzy logic
Gradient
Noise
Signal
Fuzzification
Regulating
Defuzzification
Jumps
Asymmetry
Signal
Condensation
Beam
EMI
Test filter
interruption
Modification
of alarm
criteria
Diagnosis/
misapplication
warning
Page 20
e1276e
16
Siemens Building Technologies Cerberus Division
09.2000
3.8.3 Possible diagnosis results
1. Fire
The detector registered a signal which corresponded to a normal fire with the necessary extinction and activated an alarm.
If this turns out to be a false alarm, then most probably an aerosol was present in the room which simulated the development of a genuine fire and caused the necessary extinction.
Possible remedy: – Less sensitive setting
2. Slowly developing fire The detector registered a signal which corresponded to a slowly developing fire and upon
sufficient extinction activated an alarm. In the event of a false alarm the diagnosis could point to possible condensation. Possible remedy: – Install detector heating
Less sensitive setting
3. Thermal turbulence / electromagnetic interference (EMI) Thermal turbulence points to powerful air circulation. This is mainly caused by air hea-
ters, baking ovens, furnaces etc. Thermal turbulence and/or powerful electromagnetic interference generate “noise”
which is filtered out by the algorithms. However , if it exceeds a certain strength and dura­tion, it can still lead to detector impairment.
Possible remedy: – Remove detectors from such an environment.
4. Repeated interruption Repeated interruption of the beam is caused by moving objects, such as cranes, ladders,
decorations etc. or also by powerful electromagnetic interference which has an effect on the detector.
Normally, in time this leads to fault signals being activated, but also results in unwanted alarms.
Possible remedy: Such applications must be avoided
5. Test filter If the test filter is held in the infrared beam, it causes a sudden decrease in signal strength
without however, reaching zero. This characteristic causes the detector to activate an alarm after approx. 10s.
Page 21
e1276e
17
Siemens Building Technologies Cerberus Division
09.2000
4 Planning
4.1 General project engineering principles
The linear smoke detector DLO1191 is due to its detection principle and its large monitor­ing surface for certain applications an attractive detector.
If local national regulations exist concerning application, have this priority!
4.2 Operating conditions
The distance between DLO1191 and reflector must be between 5m and 100m. There must be a permanent, clear line of vision between detector and reflector.
The monitoring IR beam may not be interrupted by moving articles, e.g. overhead cranes, ladders, transportable articles, spiders webs etc.
Turbidity of visibility caused by operations-related dust, steam or smoke develop­ment can impair the system.
The mounting place of the detector must be statically absolutely stable, since the allow­able deviation of the monitoring beam amounts to max 0,43° (see section 3.2).
Concrete and brick walls mostly fulfill these characteristics. Pure wood and steel constructions are usually unsuitable, there temperature and hu-
midity variations, wind or snow pressure influence such constructions.
The monitoring beam must have free view at least 30cm on all sides, so that no un­wanted reflections develop.
Frontal incidence of sunlight, light from halogen lamps, etc. on the DLO1191 should be avoided if possible (to high temperature).
For the service staff the detector must be at any time well accessible.
Cleaning and adjusting works are badly executable on ladders. Suitable equipment for this purpose includes fixed catwalks, platforms, ”Skyworker” etc.
The alarm activation of the DLO is based on the light attenuation caused by smoke (ex­tinction). The accumulation of smoke in a fire is adequately dense usually only in the smoke plume, in order to produce sufficient extinction for alarm activation.
For this reason always mount the DLO1191 in the vicinity of the ceiling (see Fig. 21 for distances). It must not be too close to or too far from the ceiling.
For very high rooms we recommend to arrange additional DLO1191 on different lev­els (see section 4.6.3) and/or additionally to install flame detectors.
If careful attention is not given to these points, the linear smoke detector system cannot function correctly and sometimes later leads to insoluble problems with unwanted activation of fault and alarm signals.
Page 22
e1276e
18
Siemens Building Technologies Cerberus Division
09.2000
4.3 Fields of application
4.3.1 Examples of suitable fields of application
Basically whenever point type smoke detectors do not offer the best solution and where linear smoke detectors comply with the operating conditions in section 4.2 and thus have as regards application, installation and price.
Use Reason
Buildings with ceilings of historical interest Point type detectors on the ceiling unwanted
Installation on the ceiling not possible
Atria (Malls), detection at different levels Point type detectors due to height inacces-
sible and detection of smoldering fire is im-
possible Large and high halls Lower capital investment Churches No impairment of the ceiling by installation
and point type detectors Long corridors, cable and energy ducts with >3m
room height
Lower capital investment
Aircraft hangars with sturdy building construction and flame detectors alone are insufficient
Lower capital investment
Sawtooth roofs, where point type detectors must be lower suspended
Lower capital investment
4.3.2 Examples of unsuitable fields of application
Use Reason
Buildings of wooden or steel construction, without statically stable mounting surfaces
Insufficient building static, too large beam
deviation caused by changing environ-
mental influences Low rooms or halls with crane tracks Beam interruptions by moving persons or
objects Production rooms, garages with diesel engine ve-
hicles
False alarms through accumulation of
smoke, dust, steam etc.
Page 23
e1276e
19
Siemens Building Technologies Cerberus Division
09.2000
4.4 Monitoring areas with flat ceilings
Max. width of monitored area determined by height of room (section 4.11)
Distance from ceiling min. 30cm, max. 60cm for rooms <10m high (section 4.10)
Distance between DLO11.. and reflector 5 ... 100m
Min. gap between two parallel beams determined by distance DLO11.. and reflector (section 4.9)
min. 30cm
Fig. 11 Detector layout in areas with flat ceilings
4.5 Monitoring areas with sloping ceilings
To be defined as «sloping», a ceiling must have an angle of inclination of at least 11° which corresponds to 20cm/m. With gable roofs which have a slope of >0.5, always ar­range a monitoring beam in the gable area.
Example:
Calculation of the slope n
4.5.1 Additional DLO1191’s on the slope of the ceiling
The number of DLO1191s required results from the maximum permissible monitoring width shown in section 4.11
1/4 1/4 1/4 1/4
Fig. 12 Arrangement with 3 monitoring beams on a sloping ceiling
a
n
b
n +
a b
ǒ
4m
10m
+ 0,4
Ǔ
Page 24
e1276e
20
Siemens Building Technologies Cerberus Division
09.2000
1/3 1/6 1/6 1/3
Fig. 13 If the ceiling slopes only slightly (N <0.5), the monitoring beam in the gable is
unnecessary
Height of room
Booth distances determined by height of room
When the sides of the roof are un­equal, the unit must be displaced from the centre towards the less steep side.
Fig. 14 Positioning underneath unequal sloping ceilings With sloping ceilings the smoke is channelled into the gable, i.e. there is an increased
smoke concentration in this area. Therefore, the monitoring width per DLO1 191 can be increased according to section 4.11
Page 25
e1276e
21
Siemens Building Technologies Cerberus Division
09.2000
4.6 Monitoring areas with joist constructions
Note that the term «joists» also covers such structures as air conditioning ducts which are mounted up to 0.15m below the ceiling.
In principle linear smoke detectors must be placed in the inter-joist area. Due to economic reasons this is not possible, layout underneath joist constructions is also permissible ac­cording to 4.6.1
4.6.1 Layout underneath joist construction
The linear smoke detector can be mounted below the joists, if:
the joist height is less than 2O% of the total height of the room If the width of the inter-joist area is 50% of the maximum broad of surveillance or if the inter-joist area is 200m
2
When calculating the width of the monitored area that only the distance up to the joist construction counts as the height of the room h.
h: Height for determining max. width of monitored area
100%
h < 20%
min. 30cm
Fig. 15 Detector layout underneath joist construction
4.6.2 Layout within the joist area
When the joist construction is more than 2O% of the total height of the room, than the joists must be considered as room dividers and each section must be individually moni­tored.
100%
> 20%
When distance exceeds max. monitored area mount more than one DLO11.. per section
Min. gap between two parallel beams determined by distance
Fig. 16 Detector layout within joist construction
Page 26
e1276e
22
Siemens Building Technologies Cerberus Division
09.2000
4.6.3 Detection of smouldering fire in high rooms
In order that smouldering fires or smaller fires with weak thermal current can be detected even in high rooms, a second or a third IR beam must be arranged at the assumed height of the spread of smoke of a smouldering fire. This application can be useful for rooms >6m in height.
3m up to 60%
Reflectors
of the room height
DLO1191
Fig. 17 Detection of smouldering fires in high rooms on different levels
Examples:
Room height
(highest level)
lowest level intermediate level
6m 12m 20m
3 – 4m 6 – 7m 6 – 7m
– –
~12m
4.7 Guideline for distances between DLO1191 and reflector
Distance DLO1191 à reflector
Types and number of reflectors
5 – 10m 10 – 30m 30 – 50m 50 – 65m
20 – 100m
Short distance filter + 1 DLR1193
1 DLR1193 1 DLR1192 4 DLR1192 1 DLR1191
If a number of reflectors are used they must be arranged close together and in the form of a square. Distances are approximate, i.e. they depend on detector and reflector toler­ances and can easily vary by a few metres. The important thing is that sufficient signal strength is achieved.
Page 27
e1276e
23
Siemens Building Technologies Cerberus Division
09.2000
4.8 Panes of glass
4.8.1 Penetration of panes of glass
With the reflector principle, the penetration of panes of glass is subject to certain restric­tions.
1. Panes of glass must be absolutely smooth, clear and firmly installed.
2. Panes of glass must never be positioned at a right angle to the optical axis, in which
the pane of glass has the effect of a mirror and can reflect the beam back to the re­ceiver (angle of incidence = angle of reflection).
3. As much as possible penetrate only one pane of glass. Maximum 2 panes of 5mm glass may be penetrated.
4. Each pane of glass reduces the distance by 20m.
5. The detection is certain, if the signal decreases to <2 when the reflector is covered
(see section 6.3 electronic alignment).
DLO DLR E S
Pane of glass
Partial light scatter
Partial light scatter
DLO
DLR
E S
Pane of glass
correct, the receiver is not affected incorrect, the receiver is affected
min. 10°
Fig. 18 With the penetration of panes of glass, check the angle in relation to the optical
axis
Page 28
e1276e
24
Siemens Building Technologies Cerberus Division
09.2000
4.8.2 Application example
DLO DLR
E S
Glass wall
DLO DLR
Glass wall
Partial light scatter
Partial light scatter
DLR
Plan
Front elevation
DLR
DLR
correctly positioned
incorrectly positioned
DLR
DLR
DLO
Glass wall
correct
incorrect
position
position
Fig. 19 Application example for the penetration of panes of glass
4.8.3 Reflectors mounted on glass walls
If reflectors are mounted on glass walls, there is a danger that the glass and not the reflec­tor will reflect the beam. This situation may only occur after commissioning if the glass wall moves slightly . However, it does not occur if the beam strikes a glass wall at an angle greater or less than 90°.
Recommendation: In such cases hit the beam in a light angle of 5° – 10°to the reflector, in order that such reflections which cause interference can be avoided.
Page 29
e1276e
25
Siemens Building Technologies Cerberus Division
09.2000
4.9 Minimum distances between two pairs of detectors
The monitoring beam must not be mounted closer than 30cm to the ceiling, walls, installa­tions and stored material.
In order to prevent the mutual interference of two or more DLO1191 detectors where there is an increasing distance between DLO1191 and reflector, maintain an ever-in­creasing transverse distance between DLO1191 and reflector:
Distance DLO11.. and reflector
100
80
60
40
20
0 123456[m]
(m)
Fig. 20 Min. distance between two parallel IR beams
4.10 Beam spacing from the ceiling
In order that the IR beam can detect the smoke, it is normally mounted immediately be­neath the cushion of warm air. The higher the room, the further away the DLO1191 and the reflector should be mounted from the ceiling.
0.3 0.5 1.0 1.5
0
20 18 16 14 12 10
8 6 4 2
(m)
(m)
Room height
Sloping ceiling
(N > 0,2)
Flat ceiling
(N < 0,2)
Fig. 21 Distance from IR beam ⇒ ceiling
The steeper the gable roof, the greater the distance must be between the IR beam in the gable and the ridge.
Page 30
e1276e
26
Siemens Building Technologies Cerberus Division
09.2000
4.11 Maximum monitoring width
The monitoring width can be increased with increasing room height.
Room height or mounting height
20 15
12 10
8 6
4
3
(m)
(m)
8 101112131415
9
max. monitoring width
Fig. 22 Monitoring width dependent on the room height If the monitoring beam is set at a low level in order to detect smouldering fire, then instead
of room height the distance between floor and detector applies. However, to cover in­creased risks a narrower monitoring width can be chosen.
4.12 Measures for dividing long distances
DLO DLO
DLR
DLO1191s can negatively influence each other if mounted face-to-face. In such an ar­rangement a sufficiently large plate must be mounted between the reflectors.
4.13 Measures against condensation
If the DLO1191 or the reflector is mounted on cool outside walls, in rooms in which high humidity and rapid increase in temperature (e.g. sunshine on non-insulated roof) are to be expected, the detector heating unit DLH1191 must be used to prevent. Condensation of the front cover cause trouble or false alarms. For this application and for short dis­tances, use the reflector DLR1191 with built-in heating.
Page 31
e1276e
27
Siemens Building Technologies Cerberus Division
09.2000
4.14 Installation locations
When installation locations are rigid and vibration-free even a large temperature fluctua­tion (e.g. between day and night) has only slight influence on steel girders and therefore does not greatly alter the structure of a building. However , if the installation location is not rigid, the closely bundled infrared beam can quickly wander from the receiver and so cause an alarm or trouble signal. Unstable installation locations include:
the walls of rooms constructed of steel which expand and contract due to the tempera­ture coefficient of steel
masonry walls on which a steel roof has been constructed
In such cases the DLO1191 must be mounted on the rigid structural element, meanwhile the reflector can be mounted on the instable wall.
Reflector
incorrect
DLO11..
0,43°
28.8mm
3.83m
Roof length = 80m
Fig. 23 Deflection of the IR beam caused by heat on the steel roof
The linear expansion of steel: l (mm) x T (°C) x linear coefficient of expansion (0.000012) = mm
Example:
80,000 x 30 x 0.000012 = 28.8mm
Reflector
DLO11..
correct
Fig. 24 Possible solution by mounting of the DLO1191 on the stable surface and mount-
ing of the reflector on the instable wall
Page 32
e1276e
28
Siemens Building Technologies Cerberus Division
09.2000
4.15 Accessibility
The DLO1191 must always be easily accessible also in high halls for commissioning and servicing. Suitable equipment for this purpose includes fixed ladders, catwalks, etc. or safe mobile equipment such as stacker trucks, sky-workers etc.
Fig. 25 Difficult and dangerous work using a ladder
Fig. 26 Precise and safe work using a permanent platform
Page 33
e1276e
29
Siemens Building Technologies Cerberus Division
09.2000
5 Installation
5.1 Mounting
Surface mounting directly on the wall (minimum clearance to ceiling and other ob­stacles at least 30 cm)
153,5
135
135
4,5
Base DLB1191
45
PG16
115
Detector module DLA1191
Mounting plane DLO1191: Response indicator always at the bottom!
Fig. 27 Installation of the DLO1191
Mounting plane DLR1191
Reflector heating must be mounted beneath
Reflector DLR1191
45
65
PG16
153,5
135
135
4,5
Fig. 28 Installation of the DLR1191 reflector
Page 34
e1276e
30
Siemens Building Technologies Cerberus Division
09.2000
5.2 Wiring
The detector is installed with a twisted 2-wire line from base to base. Ring and stub lines are admissible.
The DLB1191 base contains a terminal block with 6 terminals for connecting the detector to the line and for connecting the external response indicator.
5.2.1 Special filter
For distances 10m insert the corresponding short distance filter (7–10m DLF1191-AA, 5–8m DLF1191-AB).
In the e vent o f i nfluence f rom e xternal l ight, i nsert t he c orresponding f ilter ( DLF1191-AC) ( not possible, if short distance filter is inserted).
Special filter
Fig. 29 Insertion of special filter
5.2.2 Detector heater
In the event of danger of condensation the installation of the detector heater is recom­mended (Note: Supply voltage 24V necessary).
A terminal block is supplied together with the detector heater for connecting the detector heater and is latched in the base opposite the terminal block.
Connection adjustment unit
Connection detector heater
Fig. 30 Connection of the detector heater
Page 35
e1276e
31
Siemens Building Technologies Cerberus Division
09.2000
5.3 Interactive mode
In interactive mode the number of linear smoke detectors is limited. Connection factor IMK = 10 for one DLO11911
5.4 Collective mode
In collective mode only one detector may be connected to a detector line. Connection factor KMK = 25
5.5 Connection
Connection diagram interactive mode
Auxiliary supply for detector heater (option) 24V
Response indicator
+
_
YXWV
+
_
ZMB
DLB1191
+
+
+
Detector bus
+
«MB» = IRED pulse signal (for adjusting the lenses during detector production)
«Z» = auxiliary terminal
Fig. 31 Connection diagram for interactive mode
Connection diagram collective mode
«MB» = IRED pulse signal (for adjusting the lenses during detector production)
«Z» = auxiliary terminal
Detection line
Response indicator
termination
Auxiliary supply for detector heater (option) 24V
Line
+
+
+
_
YXWV
+
_
ZMB
DLB1191
+
Fig. 32 Connection diagram for collective mode
Page 36
e1276e
32
Siemens Building Technologies Cerberus Division
09.2000
6 Commissioning
6.1 Settings
Remove the detector cover Set the DIP switches
The DLO1191 can be operated either on an interactive DS11 line or a collective line. The choice between collective and interactive line is made with DIP switch [S4].
The detector has 3 sensitivity settings («Reduced», «Standard», «Increased»). The re- sponse threshold is set with DIP switch [S1], [S2].
The transmitter intensity (strong, weak) can be set with DIP switch [S3]. The DIP switch [S3] which governs the transmitter intensity is set to «strong» by default. If
the signal amplitude is too high (display on the adjustment unit: Range = 13, signal > 50), the transmitter can be set to «weak». If the measurement section is 10m, a supplemen­tary filter must be installed.
Function S1 S2 S3 S4 S5 S6
Reduced sensitivity
OFF
ON
Standard sensitivity
ON
OFFONOFF
Increased sensitivity
ON
OFF
Weak transmitter signal
ON
Strong transmitter signal
OFF
Collective system
ON
Interactive system
OFF
Reserve «S6 ON»
Alarm at beam interruption
(< 60s)
ON
*
«S6 OFF» Fault at beam interruption
(< 30s)
OFF
* Operating conditions according to BS 5839: Part 5
Fig. 33 Settings
Page 37
e1276e
33
Siemens Building Technologies Cerberus Division
09.2000
6.2 Mechanical adjustment
Install the alignment device on the detector. The mirror with backsight and the foresight must be firmly mounted to be free from play!
Unfasten the locking screw. Align the detector lens to the reflector.
The detector lens can be adjusted with the knurled screws. Rough adjustment via backsight and foresight so that the target (reflector) and the fore-
sight opening are aligned with the reticule. Attaching a pocket torch to the reflector side or illuminating the reflector with a spotlight simplifies the rough adjustment procedure.
Switch on the detection line. Connect the adjustment unit to the detector.
Attention: At first use insert a new battery! Switch the adjustment unit to «ON» and «AUTO-RANGE». The correct range will be
measured automatically. When the mechanical adjustment is correct, a signal > 2 should be available on the ad-
justment unit. This signal changes strongly when the knurled screw is turned. Remove the aiming device.
Knurled screw for vertical adjustment
Knurled screw for horizontal adjustment
Reflector
Foresight
Mirror
Eye
Locking screw
Locking screw
with backsight
Fig. 34 Mount the aiming device and align the detector to the reflector
Page 38
e1276e
34
Siemens Building Technologies Cerberus Division
09.2000
6.3 Electronic alignment
Switch to «AUTO-RANGE». With the knurled screws fine-adjust the detector lens to the maximum signal (adjust-
ment set display switched to «RANGE»). The knurled screws should be turned slowly in order to avoid large signal jumps. When the maximum value is obtained (must be between min. 4 and max. 13), switch to
«FIX-RANGE» and adjust to the maximum value «SIGNAL». Caution! If the signal val­ue is >60, switch back to «AUTO-RANGE» in order to adjust the range, and then re­adjust to the maximum value «SIGNAL».
The «RANGE» and «SIGNAL» indication on the adjustment device should both be at­tain a maximum value. If «Range» is 13 and «Signal» 60, the transmitter signal (switch S3) must be set to weak.
Engage the locking screws. Switch the adjustment set to «FIX-RANGE».
Cover the reflector.
With a dark cover interrupt the IR beam: the signal should decrease to <2. If this is not the case the detector has not been aligned correctly to the reflector but to reflecting ob­stacles in the environment of the measurement section. Repeat the adjustment proce­dure!
Disconnect the adjustment set from the detector. Reinstall the detector cover.
Connection adjustment set
#
#
#
Fig. 35 Adjustment set
Page 39
e1276e
35
Siemens Building Technologies Cerberus Division
09.2000
6.4 Initialization
To initialize the detector, a reed relay located near the internal response indicator (A) is activated with a magnet. The initialization is signalled with a flashing response indi­cator.
Reed relay rear of the
Magnet
response indicator
Fig. 36 Initialization with the magnet
During the initialization the working range of the electronics («RANGE»), the compensa­tion value, all smoothing algorithms and diagnostics, and the status are set to an initial value. All required thresholds are calculated. At the same time a self-test is performed.
Initialization with the magnet. Place the magnet directly behind the response indicator (AI) in order to activate the
Reed relay (Attention! Black point = magnet).
As soon as the response indicator flashes, the compensation value is formed (approx. 30 sec.). During this time the measurement should not be interfered with: No manipulations on the detector and no interruption of the IR beam.
When the initialization is completed, the AI turns off. If any procedural error has been made, a new initialization can be started at any time with the magnet.
Test alarm with test filter. Place the test filter immediately in front of the detector and cover the entire measure-
ment window. When an alarm is triggered, the response indicator flashes after approx. 5 seconds (interactive), or after approx. 10 seconds (collective).
The commissioning is now completed.
6.5 Addressing in the interactive system
The addressing is the same as in stationary equipment. The addresses of the individual detectors are assigned in the sequence in which each detector is set into alarm condi­tion. But first the control unit must be switched to «Address distribution mode».
A test alarm can also be combined with the addressing.
Page 40
e1276e
36
Siemens Building Technologies Cerberus Division
09.2000
7 Faults / overhaul
7.1 Fault
If the detector is removed a fault is triggered (detection line interruption). Close the detec­tor monitoring contact in the base of the interactive system.
Too powerful a signal: «RANGE» 13, Signal 60: Set switch S3 to weak. Too weak a signal: «RANGE» 4, Signal 50: Set switch S3 to strong or enlarge the
reflector dimension.
7.1.1 Interruption to beam
An interruption to the beam can be evaluated as an alarm or a fault depending on the S6 Dip-switch setting.
If it is evaluated as a fault, this function can be correctly tested by covering the reflector with non-reflective material. When covering the reflector, depending on the material used, reflections of up to approx. 10m can still cause an alarm by the material reflecting a weakened signal to the receiver.
Interruptions of the beam by moving objects are to be avoided. These can lead to inadver­tent alarms or disturbances.
7.2 Reflection
If a specular surface comes too close to the measurement section or near the detector, a reflection can occur. Reflections can lead to an amplified signal.
This can cause unwanted faults with both systems (interactive, collective).
7.3 Checklist for trouble-shooting
Is the building structure stable? Is the detector solidly mounted and are all screws tightened? Is the correct type of reflector installed? Are the Dip switches S1 – S6 set correctly? Is the correct voltage connected to the detector Are the range and signal really adjusted to the absolute maximum? Does the signal fall to 0 if the reflector is covered? Was the detector initialized after adjustment with cover mounted? Is the beam sometimes interrupted by obstacles (crane, decorations, spiders webs
etc.) Is the beam sometimes subject to mist, steam or dust? Is there danger of condensation? Does the sun or another powerful light source impinge on the detector direct? Do radiators have an influence on the beam (thermal turbulence)?
Page 41
e1276e
37
Siemens Building Technologies Cerberus Division
09.2000
7.4 Functional check / overhaul
The detector self-test subjects the DLO1191 automatically to an extensive electronic functional check. Nevertheless it is necessary to physically check the functions on site in regular intervals by triggering the detector with a suitable test filter (usually once per year). Detectors that do not respond or which are mechanically damaged must be re­placed.
If an information or fault signal is transmitted during operation, the status bits in the EEPROM of the detector can be read out with the service computer. A preliminary diag­nosis on the cause can be established based on this information.
All detector hoods and reflectors should be cleaned regularly with a soft piece of cloth which is either dry or soaked with Plexiklar , or a mild soap solution, depending on the en­vironmental conditions and severity of contamination at the installation site. Do not use any solvents or steam jets.
Page 42
e1276e
38
Siemens Building Technologies Cerberus Division
09.2000
8 Terminology
AlgoLogic Protected trade-mark
(Algorithm + Logic)
Algorithm Special calculation method in the detector processor for
optimizing the smoke sensitivity , noise immunity, and operational reliability
BS British Standard CC11 AlgoControl fire detection system control unit for the S11 fire
detection system
DIP switch Microswitch DLO1191 Linear smoke detector EEPROM Electrically Erasable and Programmable Read Only Memory EMC Electro Magnetic Compatibility EMI Electro Magnetic Influence FET Field Effect Transistor Fuzzy logic Imprecise logic IMK Load factor for interactive elements IR Infrared IRED Infra-Red Emitting Diode KMK Load factor for collective elements NFW Compensation value (reference variable) µp Microprocessor Range Working range of the electronics S11 Fire detection system S11
Page 43
Back_e
39
Siemens Building Technologies Cerberus Division
09.2000
Page 44
Back_e
40
Siemens Building Technologies Cerberus Division
09.2000
e1276ee1276d Doc. no
Edition
Replaces
09.2000
Siemens Building Technologies Cerberus Division
Siemens Building Technologies AG Cerberus Division CHĆ8708 Männedorf Alte Landstrasse 411 Tel. Fax www.cerberus.ch
+41 1 - 922 61 11 +41 1 - 922 64 50
Cerberus Security for People and Assets
Loading...