Data and design subject to change
without notice. / Supply subject to
availability
.
E Copyright by
Siemens Building Technologies AG
Wir behalten uns alle Rechte an
diesem Dokument und an dem in ihm
dargestellten Gegenstand vor. Der
Empfänger anerkennt diese Rechte
und wird dieses Dokument nicht ohne
unsere vorgängige schriftliche
Ermächtigung ganz oder teilweise
Dritten zugänglich machen oder
ausserhalb des Zweckes verwenden,
zu dem es ihm übergeben worden ist.
We reserve all rights in this document
and in the subject thereof. By
acceptance of the document the
recipient acknowledges these rights
and undertakes not to publish the
document nor the subject thereof in
full or in part, nor to make them
available to any third party without our
prior express written authorization,
nor to use it for any purpose other
than for which it was delivered to him.
Nous nous réservons tous les droits
sur ce document, ainsi que sur l’objet
y figurant. La partie recevant ce
document reconnaît ces droits et elle
s’engage à ne pas le rendre
accessible à des tiers, même
partiellement, sans notre autorisation
écrite préalable et à ne pas
l’employer à des fins autres que
celles pour lesquelles il lui a été
remis.
Ci riserviamo ogni diritto relativo al
presente documento e sull’oggetto
illustrato in esso. La parte che riceve
il documento si impegna a non
renderlo accessibile a terzi, né per
intero né in parte, senza la nostra
previa autorizzazione scritta ed a non
usarlo per altri scopi di quello per il
quale è stato rilasciato.
Fire & Security Products
Siemens Building Technologies Group
III
05.2003
Page 6
IV
Fire & Security Products
Siemens Building Technologies Group
05.2003
Page 7
About this document
Purpose
This document describes the project planning of the hardware modules of the control unit
CS1140. The consistent adherence to these instructions ia a prerequisite for a safe application.
Scope
This document contains information on all CS1140 components for EP7F, including part
numbers for ordering.
Target group
This product documentation and the work instructions are aimed at the following persons,
who have a particular function and have the corresponding training and qualification.
Group of personsActivityQualification
Project ManagerThe project manager is responsible
for the local project management.
He co–ordinates the schedules of
all groups of people working on a
project as well as resources. He
also continuously obtains the technical information required for project realization.
He has had the technical training
appropriate to his function and the
size of a project or the product line
used in the project and has attended the training courses for project
managers at the supplier’s works.
Reference documents
Information indocument
e1260Hardware description modules (CS1140 ’Modular’)
e1393Installation H26../H28.. housing
e1971Installation H37.. housing
e1273Installation H38.. housing
e1274Installation H47.. housing
e1275Installation H67.. housing
e1669Paging interface card K3I090, Technical manual
e5377Compact control unit CI1145
e4665Operating instructions AlgoPilot B3Q4..
e4598Operating instructions AlgoPilot B3Q6..
e5590Operating instructions extinguishing section B3Q4..
e5113Operating instructions extinguishing section B3Q6..
e4594Commissioning Hardware (CS1140 ’Modular’)
e5109Commissioning Extinguishing
e825Key figures for collective detection lines
e1204Fire detection in explosion-hazard areas
e1508Guideline for connection factors, line resistances, etc.
e1062Communication module, modem application
e1594C–Bus, technical description
e4282FlashTool Operation
x1099Modules overview with part numbers
e6516Inscription strip templates for indication & operation equipment
i
Fire & Security Products
Siemens Building Technologies Group
Work and operational safety
Before personnel begin work on the system, they must have read and understood the
related operating instructions, in particular Chapter 1 ”Safety regulations”.
1
e4595e−0
05.2003
Page 8
Disregard of the safety regulations
Before they are delivered, products are tested to ensure they function correctly when
used properly. Siemens disclaims all liability for damage or injuries caused by the incorrect application of the instructions or disregard of warnings of danger contained in the
documentation. This applies in particular to:
Personal injuries or damage caused by improper use and incorrect use;
Personal injuries or damage caused by disregarding safety instructions in the docu-
mentation or on the product;
Personal injuries or damage caused by poor maintenance or a lack of maintenance.
Conventions
(...)Additional information
..)Notes
”.....” / ’....’Definitions of designations
!Details see page ...., or document .....
jConfiguration sheets to fill out
Document identification
PlaceSignification
Title page– System names
Last page bottom left
bottom right
– Product type
– Document purpose
– The document number consists of: Language, number, index
– Version date
– Manual
– Register
The most recently released technical documentation for customers can be found in the
Siemens Intranet under the the following address: http://web4.cerberus.ch/.
Training
Siemens Fire & Security Products provides the necessary training for all products. You
can find information about courses in the Siemens Intranet under the following address:
http://web4.cerberus.ch/.
2
Fire & Security Products
Siemens Building Technologies Group
e4595e−0
05.2003
Page 9
1Safety regulations
This chapter describes the danger levels and the relevant safety regulations applicable for
the use of the
”About this document” thoroughly before beginning any work.
Cerberus
1.1Signalwords and symbols
1.1.1Signalwords and their meaning
The danger level-that is, the severity and probability of danger-is indicated by the signal
words listed below. Non-observance may lead to the consequences indicated:
DANGER
Imminent danger!
D May cause serious bodily injury or danger to life!
WARNING
Dangerous situation!
D May cause serious bodily injury or danger to life!
CAUTION
Possibly dangerous situation!
D May cause light injuries!
NOTE
Possibly harmful situation!
D May cause damage to the product or to objects in the immediate vicinity of the product!
products. Please read the work instructions as well as the chapter
1.1.2Symbols and their meaning
The symbols listed below indicate the nature and origin of the danger.
General danger
Electrical voltage
Example for a danger warning
DANGERExternal voltage
Disconnect the module from power supply.
1.1.3Classification and meaning of additional symbols
i
Tips and information
Refers to extremely important or critical decisions to be taken into account before
continuing the work.
Fire & Security Products
Siemens Building Technologies Group
3
e4595e1
05.2003
Page 10
1.2Safety-relevant working instructions
Country-specific standards
The products are developed and produced in compliance with the relevant international
and European safety standards. Should additional country-specific, local safety standards
or regulations concerning project planning, assembly, installation, operation and disposal
of the product apply in the place of operation, then these standards or regulations must also
be taken into account in addition to the safety regulations mentioned in the product documentation.
Electrical installations
DANGER Work on electrical installations
Any work on electrical installations may only be carried out by qualified electricians or
instructed persons working under the guidance and supervision of a qualified electrician, in accordance with the electrotechnical regulations.
D Control units must be disconnected from the power supply during commissioning or
maintenance work.
D Terminals with an external voltage supply must be provided with a sign ”DANGER – Ex-
ternal voltage”.
D Mains leads to the control unit must be installed separately and provided with a clearly
marked fuse.
D Earthing must be carried out in compliance with local safety regulations.
D When work is carried out in explosion–hazardous areas, the appropriate safety precau-
tions must be taken.
Assembly, installation, commissioning and inspection work
D If any tools or accessories such as ladders are required, safe and suitable devices must
be used.
D Prevention of spurious tripping of the remote transmission must be assured.
D Always inform the fire brigade before testing the remote transmission.
D The activation of fire control installations for test purposes must not cause damage to the
system or parts thereof.
D Fire control installations must only be activated after the test has been completed and the
system has been handed over to the customer.
D Third party systems or devices must only be activated in the presence of the responsible
person.
D When work on management stations and system terminals is performed, the safety regu-
lations of the connected sub–systems must be observed. This especially applies when
switching-off system components.
D In the case of extinguishing systems, always use the ”General installation instructions” as
a guideline. This guideline is available on request.
D Only use fuses with the specified fuse characteristics.
Testing the product operability
D Evacuate and cordon off extinguishing sector.
D Inform people about the possibility of occurring fog and noise.
D Inform people before testing of alarm devices; take the possibility of panic reactions into
account.
D Inform the alarm and fault receiving stations connected to the system before running the
tests.
4
Fire & Security Products
Siemens Building Technologies Group
e4595e1
05.2003
Page 11
Modifications to the system design and the product
Modifications to a system or to individual products may cause faults or malfunctioning.
Please request written approval from us and the relevant authorities concerning intended
system modifications and system extensions.
Modules and spare parts
D Locally procured modules and spare parts must comply with the technical specifications
laid down by the manufacturer . This compliance is always ensured for original spare parts
supplied by us.
D Only use fuses with the specific fuse characteristics.
D Wrong battery types and improper battery exchange may introduce the danger of explo-
sion. Only use the specified battery type or an equivalent battery type recommended by
the manufacturer.
D Batteries require environmentally safe disposal. They must be handed in at the local col-
lecting points.
D Please take into account that the extinguishing agent cylinders are pressurized and must
be exchanged in compliance with the local safety regulations.
Fire & Security Products
Siemens Building Technologies Group
5
e4595e1
05.2003
Page 12
6
Fire & Security Products
Siemens Building Technologies Group
e4595e1
05.2003
Page 13
2Main features CS1140
Fire detection system for modular configuration
min. 2000 detectors per CC1143; min. 700 detectors per CC1 142; min. 500 detectors
per CI1142 possible
For the processing of collective, addressable and interactive detectors
Logical and physical structure totally separated
Master module as main CPU (for larger systems)
Control console as main CPU (for small to medium-size systems)
Interfaces for VdS peripheral equipment, printer, PSA/pager, host systems, SPS
Different types of input and output modules
Autonomously functioning extinguishing control module
Special Mimic Display terminal activating module
Multidetector logic
Interactive detectors programmable with algorithms
Control unit electronics can be installed in 4 different series of cabinets
Up to 16 free selectable type of stations per C-Bus
Comfortable operation with softkeys and large LC display
Up to 64 independent logical AREAS (Organization levels)
Single-AREA or multi-AREA operation
Event memory with sub-menu / search functions
Integrated real time clock with auxiliary battery
Automatic summer/winter time switchover
Integrated emergency operation function
Flexible detector parameters setting via maintenance PC
Connectible systems
collective
DS11
AnalogPLUS
AlgoRex
interactive + Ex interactive
+ wireless (radio)
collective detectors
MS6 / MS7 / MS9
addressable detectors
MS9i / MS9i-PLUS / MS716i
older generation
CBA8000/TS9000
of detector systems
Control terminal
Main
CPU
B3Q...
WINDOWS based
configuration software
AlgoWorks
CS1140 control units palette
Main CPU
E3X10.
CC11
Control terminal
CT11CI11
Gateway
CK11
Fire & Security Products
Siemens Building Technologies Group
7
e4595e2
05.2003
Page 14
3Overview technical data CS1140
Operating voltage115/230VAC±15% 50...60Hz
Power consumption40...220VA (per converter B2F020)
Battery operation in the event of mains failure
– standard operating period
– optional
Environmental conditions
Temperature during operation
storage
Humidity
IP protection category (EN60529 / IEC529)
– Control unit
12...24h
up to 72h (see page 91)
0°C ... +40°C
–20°C ... +60°C
max. 95%, no condensation
complies with class 3K5 according to IEC721-3-3
IP50 H38 cabinet
IP30 H47/67 cabinet
– remote control console AlgoPilot
Dimensions
– Control unitin cabinet H38...
H47...
H67...
H98...
– separate control terminalin cabinet H26G220
H28G200
H37G...
Colour
– control unit cabinetsH38... / H47... / H67... / H98...
– operating unit front terminal B3Q...
– control terminal cabinetH26G220
RAL7035 light grey
1E110 dark grey
RAL7035 light grey
8
Fire & Security Products
Siemens Building Technologies Group
e4595e3
05.2003
Page 15
4Logical and physical structure
l
.
In the CS1140 fire detection system, the logical structure is completely separated from
the physical structure. This enables the greatest possible flexibility. Display and control
terminal are based on the geographical and organizational aspects and are independent
of the actual hardware installation of the detector network.
Geographical features ( → building structure)
Area
Section
Zone
Element
Main building
Ground
floor
Warehouse
Reception
Room
102
1st floor
Main
building
1st
floor
Room
103
Room
104
2nd floor
Ground floor
2nd
floor
Canteen
EDP
room
1st floor
Room 104
Logical structure
The logical structure is a con
figuration of the geographica
features of a system. It can
be modified easily to the
building structure, room utilization etc.
Within the same control unit
the logical structure is inde-
logical structurephysical structur
pendent of the wiring of the
detector network.
Level 3
Level 2
Device
Level 1
Level 2
Level 1
Function unitStation
Line 1
CT11
Control terminal
Line 2
Line 3
Line 4
Linking
C-Bus
D-Bus
I-Bus
DOW
DCW
Control unit
CC/CI
Linking
The lowest levels of both
structures are linked to each
other. It is determined which
physical devices (e.g. detectors) are in which logical or
geographical location.
Physical structure
The physical structure is a
configuration of the hardware
It results from the hardware
installation. The number of
used levels is depending on
the type of hardware.
9
Fire & Security Products
Siemens Building Technologies Group
e4595e4
05.2003
Page 16
5Bus systems
r
In the CS1140 fire detection system there are 5 communication levels:
I-Bus
internal data bus between individual modules in the control unit (line modules, control
modules etc.)
C-Bus
local data bus between control unit(s), control console(s) and Gateway(s)
D-Bus (or AnalogPLUS-Bus or collective detection line)
local detector bus; connects the detectors to the control unit
LON-Bus
local data bus for text display and control terminals, mimic display converter and LON
I/O card
Data Bus
local data bus for parallel indicator panel, synoptic panel or relais
Control terminal
CT11
CPU:
E3X10.
or
AlgoPilot B3Q...
D-Bus
interactive
detectors
I-Bus
E3I040
LON-Bus
Data bus
C-Bus
I-Bus
Line modules
E3M...E3M...E3M...
AnalogPLUS-Bus
AnalogPLUS
detectors
collective
detection line
collective
detectors
Gateway
CK11
E3H020
LON-Bus
DMS7000
LMS modula
(Host system)
CERLOOP / CERBAN
Control unit CC11, CI11
E3I040
B3Q580/
B3Q590/
B3Q595
K3I110
K3I050
In-/outputs
10
Fire & Security Products
Siemens Building Technologies Group
Data bus
B3R051
or
K3R072/
K3G060
e4595e5
05.2003
Page 17
5.1Bus overview
Data Bus
local data bus
panel or relais
SPI-Bus 2KHz
parallel ind. panel, synoptic
78kBaud
local data bus
for floor indicator panels
(direct current signal)
2 messages/sec
AnalogPLUS-Buscollective lineLON-Bus
for AnalogPLUS detectors for collective detectors
...24
max. 1000m
...32
max. 500m
as stub line
max. 1000m
as free topology
1 address
see document e1508
(max.50/150/250Ω/4µF)
...128
(max.150Ω/300nF)
see document e1508
6
max. 8 addresses
LON-Bus devices
(max. 25 detectors)
DBus devices (AnalogPLUS)
twisted
(+ 3 wires supply)
2
twisted
2
twisted
(un-twisted permissible)
2
twisted
(un-twisted permissible)
–
–
yes
–
–
(see page 72)
–
yes
via T-branch module
no
no
with line separator
each user connected
cyclic
master/slave
master/slave
event-controlled
master/slave
cyclic
master/slave
serial bus
– typ. all 250ms
(all 60s)
presence monitoring
–
– typ. all 64s
– interrupt on alarm
– Cerberus protocol
network
(LON protocol)
– Echelon Chip
conventional
– current gain principle
sensor/actor-Bus
– Cerberus protocol ’K31’
– Cerberus specific
– voltage levels
– serial 8bit
– start-up: daisy-chain
–
–
telegram
–
–
D-Bus
interactive
for interactive detectors
I-Bus
inside control unit
C-Bus
local system bus
Features
Field of application
4,8kBaud
see document e1508
max. 3m
1000kBaud
57kBaud
Speed of
transmission
...128
(max.120Ω/300nF)
(only inside cabinet)
max. 1000m
(G51 ø0,8: 1400m)
Length of line
DBus devices (interactive)
...16
I-Bus modules
...16
C-Bus devices
addresses
connected or
Number of users
2
twisted
26
flat cable
1)
2
(+3 wires for
twisted
emergency operation)
Number of wires
Type of cable
–
Loop line
yes
as required
–
–
yes
T-branch
cyclic
master/slave
each user connected
with/without line separator
–
with line separator
each user connected
Short-circuit proof
cyclic,
master/slave
master/master
event-controlled,
Network structure
– typ. all 3s
Scanning
1) calibrated according to cable impedance: 50W (MICC) / 110W (G51, ø0.8mm, not shielded)
sensor/actor-Bus
– interrupt on alarm
event controlled
presence monitoring
– Cerberus protocol ’K51’
– serial 8bit
C-Bus
– Cerberus protocol
– SPI/Motorola
serial Bus
– Cerberus protocol
– collision detection
Principle
download
detector parameter
–
–
– Manchester coding
Special feature
Fire & Security Products
Siemens Building Technologies Group
11
e4595e5
05.2003
Page 18
6C-Bus stations
The C-Bus network contains max. 16 stations (user connected)
within the limits stated below (CC, CI, CT, CK) are any stations in any arrangement possible
max. 64 AREAS
Control terminal
CT11
(max.15)
C-Bus network
– max. 16 stations
– 4 different types of stations
– loop line max. 1400m with G51 ø 0.8mm
CERLOOP
Gateway
DMS7000/LMS
(management
system)
CK11
(max.15)
C-Bus
Control terminal
Main CPU
modules
CI11
(max.16)
6.1Station
Function unit within C-Bus network
Several stations can be located in the same or in geographically dispersed cabinets
6.2Type of station
Differentiated by function and represented by a certain module
Certain modules can be used for different types of stations
Types of stations available:
CI11Combination of main CPU and operating unit (AlgoPilot)
CC11Main CPU
CT11Control terminal (AlgoPilot)
CA11Parallel control terminal
CK11Gateway (e.g. conversion of C-Bus protocol CERLOOP protocol)
I-BusI-Bus
Main CPU
Line–
Control–
modules
CC11
DetectorDetector
(max.15)
Line–
modules
Control–
modules
12
Fire & Security Products
Siemens Building Technologies Group
e4595e6
05.2003
Page 19
6.3Meaning of the suffix 41, 42, 43
CI1142
CC1142
CC1143
CT1142
AlgoPilot B3Q560
CT1142
Indicates the outline quantities (see chapter 7) respectively size of the equipped RAM:
In parallel to each standard control terminal (’CT’/’CI’), one parallel control terminal can
be connected.
6.5.1General features/Restrictions
The parallel operation terminal simulates (mirrors) the standard control terminal it is
connected to (same visibility definitions)
Simultaneous operating on parallel control terminal and respective standard control
terminal possible
Allows configuration of more than 16 control terminals per C-Bus
Serial communication (RS232), i.e. stub line connection only (not fail-safe)
connection is supervised on communication failure (on both side)
recommended modem types: Zyxel xxx. Other modems: to be avaluated locally on a
case-by-case basis
6.5.2Parallel control terminal ’CA’
Based on same hardware as Standard control terminal. Supported control terminal
types: B3Q460/48./560/660/670/680/685/565
From EP/F, all AlgoRex terminal variants and character sets are supported
Required FW-Variants see page 16
Fire & Security Products
Siemens Building Technologies Group
13
e4595e6
05.2003
Page 20
6.5.3’CT11 Visualizer for Windows’ remote operation software
Operating platform requirements in detail see document e6824
Supported control terminal types: B3Q460/48x/560/660/670/680/685/565
for details see also document e4940 and e5946
Standard control terminalParallel control terminal
C-BUS
CT/CI
AlgoPilot
B3Q321
FBA
E3I020
E3I020
(RS232) V24 ....1000m
max. length of line dependent
on type of modem
Modem
Dedicated line
Hardware AlgoPilot with special
software CA....xxx for B3Q6.. and
B3Q4.. details see pages 45, 46
Modem
E3I020
E3I020
24VDC
CA
AlgoPilot
B3Q321
FBA
CT/CI
AlgoPilot
CT/CI
AlgoPilot
E3I020
E3I020
E3I020
B3D021
E3I020
max. length of line dependent
Modem
Tel.
Modem
(RS232) ....15m
Standard PC with keyboard, software
’CT11’ visualizer for Windows’
Tel.
Modem
e.g. Service Notebook, software ’CT11
visualizer for Windows’, AlgoWorks for
Windows
on type of modem
Dedicated line
temporary public
telephone line
temporary public
telephone line
Tel.
Modem
Modem
Tel.
Modem
Visualizer
Remote Operation
(temporary)
14
Fire & Security Products
Siemens Building Technologies Group
e4595e6
05.2003
Page 21
6.6Logical AREAS
A R E A
12
CC
34
CI
78
5
6
....
CICI
CC
....
6162
CC
A R E A
6364
All AREAS control terminal
CKCK
within one main CPU (’CI’ or ’CC’) max. 4 AREAS can be configured
CPUs cannot link up with AREAS of other CPUs
CPU overlapping controls are possible
Control terminals (’CT’/’CI’) can be freely allocated to AREAS as required
Visibilities on gateways (’CK’) shall be set per station only, not per AREA! To avoid
CERLOOP addressing problems, one C-Bus station must not be split onto two gateways!
Fire & Security Products
Siemens Building Technologies Group
15
e4595e6
05.2003
Page 22
7Outline quantities of C-Bus participants
AlgoPilot B3Q560
This chapter describes the quantitative limits of the various station types.
Possibly performance related limitations depending on the outline quantities are not
taken into account.
For earlier EPs consult the corresponding release notes or the corresponding edition
of this document, but use chapter 7.1.3, ’Maximum number of criteria in zone control
4 and 6 (RAM)’ of this document.
The selection of the station type depends on the requirements. The following variants are
available (CI1145: see document e5377):
Country codes program files: 00 = international; T1 = China simplified; TE = China traditional; TL = Korea standard; T5 = Thailand
CIYTExxx
CIYTLxxx
CIYT5xxx
CTYT1xxx
CTYTExxx
CTYTLxxx
CTYT5xxx
CAYT1xxx
CAYTExxx
CAYTLxxx
CAYT5xxx
−
−
−
4x512Kx8Bit
4x512Kx8Bit
4x512Kx8Bit
CIQT1xxx
CIQTExx
CIQTLxxx
CIQT5xxx
(2x1024Kx8Bit)
CIWT1xxx
CIWTExxx
CIWTLxxx
CIWT5xxx
(2x1024Kx8Bit)
CTQT1xxx
CTQTExxx
CTQTLxxx
CTQT5xxx
(2x1024Kx8Bit)
CAQT1xxx
CAQTExxx
CAQTLxxx
CAQT5xxx
(2x1024Kx8Bit)
−
Z3S070
(2x512Kx8Bit)
Z3S070
(2x512Kx8Bit)
−
Z3S070
(2x512Kx8Bit)
and K3N010
(1x1024Kx8Bit)
−
Z3S070
(2x512Kx8Bit)
−
Z3S080
(2x256Kx8Bit)
4 x Z3S080
(2x256Kx8Bit)
2 x Z3S070
(2x512Kx8Bit)
4 x Z3S070
(2x512Kx8Bit)
−
Z3S070
(2x512Kx8Bit)
Z3S070
(2x512Kx8Bit)
−
Z3S070
(2x512Kx8Bit)
−
Z3S070
(2x512Kx8Bit)
or
2x
16
Fire & Security Products
Siemens Building Technologies Group
e4595e−7
05.2003
Page 23
7.1Main CPU limits (CI/CC)
0
Max. number of devices
7.1.1Maximum number of devices (RAM) per station
select station
with higher
RAM capacity or
an additional
station
no
number
of devices
< X ?
yes
The limits within the station types are given by
Verify all given limits for each required station
hard- and software.
by going through this flow chart
For the stationtypes CI1142, CC1142, CC1143, this limit is depending on the setup of the
logical structure.
The following graph allows to find this limit depending on the estimated average number
of ELEMENTS per ZONE.
average of 3 ELEMENTS per ZONE
Result: max. 3000 devices
! Do not go to the limits !
– Project changes
– Site expansions
– Upgrade to future versions
CI1142 (B3Q460/480/670)
200
Example:
600
300
average of 5 ELEMENTS per ZONE
configured in control unit: 300 devices
free memory: 600 devices (-200 spare)
(use of this value see chapter 7.2.1)
plan reserves for:
i
Fire & Security Products
Siemens Building Technologies Group
Important:
Above values correspond to the ones already given for EP5.
However, for the following configurations, these limits must be reduced further.
Number of ZONES per SECTION (average) < 3CI1142: –15%
CC1142: –
CC1143: –
Use of ELEMENT textsCI1142:–20%
CC1142:–10%
CC1143:–10%
17
e4595e−7
05.2003
Page 24
Special structures now need to be counted equivalent to the following number of
i
devices:
StructureNumber of de-
S D-Bus participants with an own D-Bus address (e.g. DOT1151,
DO1131, DM1154, DCW1151, DOW1171...)
S Each used input or output of interactive or AnalogPLUS I/O devices
Example:DC1157 with 3 Inputs 6 devices
DC1154 with 1 output and 1 input for confirmation message 4 devices
S Purely logical controls: Each ’element command’ or ’zone control’
not directly connected to a channel
S Collective lines (e.g. 1 line of module E3M080)
S Inputs of modules (e.g. E3X10x –> I4, E3L020 –> I2,
K3I110 –> LONin, external LON device –> LONin)
S Outputs of modules (e.g. E3X10x –> Q3, E3G050 –> Q1,
K3I110 –> LONout, external LON device –> LONout)
S Parallel indicator terminal/synoptic (equipped with up to 384 LEDs /
relays)
7.1.2Limits in the logical structure
The limits in the logical structure are given by the node-type, by the highest possible CSX
reduce number of
nodes or use an
additional station
number and the maximum amount of display-digits. These limits are given by the system
and are independent of the memory capacity.
Table ’Limits of the logical structure’
vices
1
2
2
2
2
2
20
no
number
of nodes
< X ?
yes
Maximum rating
AREAS per STATION
... 4
Maximum rating
SECTIONS per AREA
... 255
Maximum rating
ZONES per SECTION
... 255
7.1.3Maximum number of criteria in zones control 4 and 6 (RAM)
select station
with higher ca-
pacity or use an
additional station
To trigger a zone control 4 or 6, 1 to 16 criteria can be programmed.
Each criterion requires a certain amount of memory . Therefore the maximum number of
criteria is limited according to the following graphs.
Important:
If CPU-overlapping controls are used (zone control 6) all criteria which are NOT located
in the same control unit as the control zone have to be counted twice: once in the control
unit they are located and once in the control unit the zone ’control 6’ is located.
Notes:To optimize the performance of your system minimize the number of
CPU- overlapping controls as much as possible.
A maximum of 40 CPU overlapping controls (zone control 6) are admissi-
ble per C-Bus.
no
number
of controls
< X ?
yes
Maximum rating
ELEMENTS per ZONE
... 99
International 5: ... 255
1)
1)
18
Fire & Security Products
Siemens Building Technologies Group
e4595e−7
05.2003
Page 25
Example:
CI1142 with 150 control zones with an average of 9 control criteria.
The point of intersection for the number of control zones (150) and the number of criteria
per control zone (9) must be within the permitted range.
Diagram ’Maximum ratings of controls’ CI1142 and CC1142
Number of criteria
per control zone
16 criteria per control zone
16
14
12
10
example
9
8
6
= max. 150 control zones
4 criteria (average) per control zone
= max. 600 control zones
4
Permitted range
2
CI1142 / CC1142
0
10020004003008007006005009001000
150
Diagram ’Maximum ratings of controls’ CC1143
Number of criteria
per control zone
16 criteria per control zone
16
14
12
10
8
6
4
2
0
Permitted range
CC1143
40080001600120032002800240020003600 4000
= max. 600 control zones
4 criteria (average) per control zone
= max. 2400 control zones
Number of
control zones
Number of
control zones
Above diagrams ’Maximum ratings of controls’ apply also for EP5 (SR1), EP5 and
EP4.
7.1.4Max. number of ZONE time channel
Max. 16 ZONES time channel are permitted per station.
Fire & Security Products
Siemens Building Technologies Group
19
e4595e−7
05.2003
Page 26
7.1.5Maximum number of I-Bus-modules
select station with
higher capacity or
use an additional
station
of I-Bus-modules
no
number
< X ?
yes
Table ’Maximum number of I-Bus-modules’
Stationtype
I-Bus modules
1) Limited by software
2) Value based on experience (depends on cabinet size and/or 5V current consumption)
3) Battery charging unit (integrated in E3X10.) counts as one
7.1.6Limits of 5V supply
All I-Bus modules are supplied with 24V and 5V. The available current for the 5V, sup-
select station with
higher capacity,
use an additional
power supply or
an additional
station
plied from main CPU is limited:
Table ’5V-Current consumption of I-Bus modules’
consumption
of I-Bus-modules
no
< X ?
yes
I-Bus module
E3M071 (070)34mAE3G07010mA
E3M111 (110)25mAE3C011 (010)12mA
* not an I-Bus module, but supplied via the ’Main CPU’
CI1142
...16 1) ...8 2)
’Main CPU’
E3X10x
B3Q... / E3C011
Current consumption
from ’Main CPU’
E3M06034mAE3G06010mA
E3M08055mAE3G08035mA
E3M17145mAB3Q321 (320)8mA
E3M12065mAE3I020*100mA
E3L02010mAE3I04070mA
E3L03035mAK3I090*1mA
E3G0508mA
CC1142
...16 1) 3)
I-Bus module
Available current
I-Bus module
CC1143
...16 1) 3)
1100mA
250mA
Current consumption
from ’Main CPU’
the capacity of the main
CPU is checked
20
Fire & Security Products
Siemens Building Technologies Group
The given limits for the control terminal (CT/CI), the gateway (CK) and the AlgoWorks
utility programs have to be checked as well!
e4595e−7
05.2003
Page 27
7.2Control terminal limits (CT/CI)
define the required number of
control terminals by going
through this flow chart
7.2.1Maximum number of texts
reduce number of
visible AREAS or
use an additional
control terminal
The number of texts of other stations (i.e. AREAS) that can be displayed on one control
terminal (CT/CI) is limited.
The following calculation must be used:
twice the number of visible SECTIONS
+ the number of visible ZONES
+ the number of visible ELEMENTS with element text
= number of texts
Limit for ’CT1142’ (B3Q460/480/670, B3Q660/680/685)
The max. number of texts is fix 8500.
maximum
number of texts
no
< X ?
yes
the required number of
control terminals is defined
Limit for ’CI1142’ (B3Q460/480/670, B3Q660/680/685)
The max. number of texts is depending on the number of devices already configured in
the control unit.
Number of texts per 100 not configured devices in the control unit
Average number of ELEMENTS per ZONE: 5 = 540 texts per 100 devices
Free RAM space: 600 devices (according to example in graphic chapter 7.1.1)
–> maximum number of texts: 540 x 6 = 3240 texts
ELEMENTS per ZONE
540
Fire & Security Products
Siemens Building Technologies Group
The given limits for the station (CI/CC), the gateway (CK) and the AlgoWorks utility
programs have to be checked as well!
21
e4595e−7
05.2003
Page 28
7.3Gateway limits (CK)
check gateway configuration
7.3.1Limits of the memory (RAM)
CK1142:
use CK1143
type gateway
suited for CI1142, CC1142 stations
EPROM set: ’CKQ00xxx’
RAM sets: 4x Z3S080 or 2x Z3S070
Via one gateway a maximum of 8 C-Bus stations (CI/CC) can be addressed.
use second gate-
way of correct
type
If more than 8 C-Bus stations (CC/CI) are present, they must be split up on two gateways.
number of
stations > 8 ?
yes
no
the configuration of the
gateway is checked
Also for special applications, more than two gateways can be configured.
Visibilities of C-Bus stations (CC/CI) on gateways, must be set station wise, not area
wise!
The given limits for the station (CI/CC), the control terminal (CT/CI) and the Algo-
Works utility programs have to be checked as well!
22
Fire & Security Products
Siemens Building Technologies Group
e4595e−7
05.2003
Page 29
7.4AlgoWorks utility programs limits
7.4.1Limit of SmartHandy (SWE11-A)
Limit of SmartHandy software
The current SmartHandy software has a limitation of 2400 nodes, i.e. the total of all ELEMENTS, ZONES, SECTIONS and AREAS must not exceed 2400.
Trying to open a station with more than 2400 nodes will produce the SmartHandy error
message ’Too many DB records’ and the SmartHandy program will abort.
Limit of solid state disk
If there is not sufficient space on the internal disk of the WorkAbout to copy the station file
from AlgoWorks to the WorkAbout, AlgoWorks reports ’Disk full’ and
’Dxxxxx.DBF not transmitted’. Delete no longer needed files using the Work-
About menu functions.
Trying to open a station when there is not enough space on the internal disk (to create the
temporary file which the SmartHandy program needs), the WorkAbout error message
’Error in HANDY\LOADDB: Disk full’ is displayed. Delete no longer needed
files using the WorkAbout menu functions.
Fire & Security Products
Siemens Building Technologies Group
23
e4595e−7
05.2003
Page 30
8Specify hardware required
In order to be able to specify the hardware required, system key data must be specified
according the following procedure:
1. Specify number and type of detection lines
dependent on:
Detector series
Number of detectors, input and output modules
Building structure
2. Specify number and type of fire control installations
dependent on:
The fire protection installations to be activated
Location of the contacts (centralized or decentralized)
Individual types of contact (250VAC/10A or 30VDC/1A)
3. Specify number and type of operating units
dependent on:
Operating concept
Language on the operating unit front terminal
Parallel indicator panels, fire department control panels
4. Specify Accessories required
dependent on:
Printer interface and printer
PSA/Pager interface
Remote transmission equipment
Gateway, etc.
5. Specify emergency power supply battery capacity
dependent on:
Total quiescent current
Required emergency current operating period (according to country)
Type of remote transmission
6. Specify type of cabinet
dependent on:
Number and type of modules
Required accessories
Number and type of sets of batteries
7. Provide configuration sheet/sheets (see page 104 ff)
Select sheets corresponding to the configuration
Complete everything
24
Fire & Security Products
Siemens Building Technologies Group
e4595e8
05.2003
Page 31
9Choice of appropriate control unit cabinet
Á
Á
Á
Á
Á
Á
For a suitable normal application, the required control unit cabinet can be worked out
from the outline quantities for the main CPU.
Type of station
БББББ
CI1142
CC1142
CC1143
Cabinet
H38G220
БББББ
j
Cabinet
H38G320
ÁÁÁÁ
J
Cabinet
H47...
БББББ
J
j/J
j
Cabinet
H67...
ÁÁÁÁ
J
J
J suitable
j partially suitable (check it out)
H38G220H38G320H47...H67...H98...
434
434
1130
520
602
520
602
735
300
CI1142
page 30
Cabinet
H98...
БББББ
J
J
600
2015
CI1142
page 26
Control terminal
essential in cabinet
front terminal
100
CI1142
page 28
155
Control terminal
not essential in
cabinet front terminal
CC1142/43
page 32
CC1142/43
page 36
300
300
CC1142/43
page 56
Fire & Security Products
Siemens Building Technologies Group
25
e4595e9
05.2003
Page 32
10CI1142 in cabinet H38... (flat)
Module chassis
Module chassis view ’Fire
N
E
a
p
2
M
E
T
a
c
c
Z
E
P
n
E
m
H38G220
520
602
88
100*
* incl. projecting door hinges
H38G220:
Set with
– cabinet
B2F020
– door
– module chassis
– earth terminals
B3Q...
AX1210
H23B040
AX1210
H23B010
Connection for
periphery
Compact, flat design control unit
Connection to the modules direct
Installation of accessories possible, but greatly restricted
Batteries 2x12V/15Ah
Control terminals built into front terminal (also serves as main CPU)
Installation of additional display devices impossible
Door right hinged, can be locked with 2 Allen screws
Component of
Z3I470
B3Q...
Z3I380
Module
Z1K030
ote:
3M60/071/171/120
nd E3C011 are not
ossible at positions
8+38
ounting of
3C011:
erminal block
nd holder
ontaining in
able set
3I470
MC Precaution:
osition 57 must
ot be fit with either
3I040 or E3G080
odules
view ’Modules’
47
E3...
57
E3...
View AView B
28
E3I020
38
E3M...
48
Z1K030
E3G070
58
Z1K030
E3C011
Z1K030
Z1K030
Z1K030
Z3I470
21
B2F020
AC/DC converter
31
(Battery 12V)
AX1210
51
(Battery 12V)
AX1210
Cabinet front view
Mains accessories
Z3I460
H38G220
AB
control installations relay’
45.1 .. 45.3
Z3B171
Z3B171
Z3B171Z3B171
55.1 .. 55.3
Z3B171
Z3B171
absolutely essential
recommended
space allocation
Details on cabinet H38...
see page 53
Important:
Comply with max. permissible number of ’nodes’ +
I-Bus modules!
Details see chapter 7
26
Fire & Security Products
Siemens Building Technologies Group
e4595e10
05.2003
Page 33
C-Bus
24V
E3I020
RS232
12
24V
AlgoPilot
B3Q...
or
K3I090
CT1142
(additional operating facilities)
Details see page 42
B3Q...Control terminal AlgoPilotall variants of the AlgoPilot see page 42
H26T...Plexiglass door to AlgoPilot B3Q...option see page 42
Z5B...Inscription setaccording to language see page 45, 46
E3G070546661Control module ’universal’for alarm devices and control outputs
H38G220 484914Cabinet set ’door with cutout’for details referring cabinets see page 53
H23B010 476210Coveressential or H23B040
H23B040 484590Information modulebrief operating instructions instead of H23B010
Z3I470484341Cable set for H38...essential
Z3I380475567I-Bus flat cable + supply cable ’long’required for connection from level to level (e.g. Pos 28 ↔ 38)
Z1K030484231Terminal block with p.c.b. chassis for CI11..required for each module (E3H020 2x)
Z3B171484383Relay module 1 x 250VAC/10Aintermediate relay for fire control installations (max. 6)
for details referring control modules see page 66
Fire & Security Products
Siemens Building Technologies Group
27
e4595e10
05.2003
Page 34
11CI1142 in cabinet H38... (deep)
Module chassis
Module chassis view ’Fire
N
E
a
p
2
l
.
-
M
E
T
a
c
c
Z
E
S
w
520
H38G320
602
H23B010
147
155*
* incl. projecting door hinges
H23B040
H38G320:
Set with
– cabinet
– door
B2F020
Component of
Z3I470
– module chassis
– mains terminals
B3Q...
B3Q...
Z3I380
AX12..
B3Q321
AX12..
B3R051
Connection for
periphery
Z1K030
Module
Compact control unit
Connection to the modules direct
Designed for few modules, large batteries and the installation of accessories
Batteries as required either 2x 12V/15Ah or 2x12V/27Ah
Control terminals built into front terminal (also serves as main CPU)
Installation of additional display devices possible
Door right hinged, can be locked with 2 Allen screws
view ’Modules’
27
ote:
3M60/071/171/120
nd E3C011 are not
ossible at positions
7+37
B3Q...Control terminal AlgoPilotall variants of the AlgoPilot see page 42
H26T...Plexiglass door to AlgoPilot B3Q...option see page 42
Z5B...Inscription setaccording to language see page 45, 46
E3G070546661Control module ’universal’for alarm devices and control outputs
H38G320 484943Cabinet set ’door with cutout’for details referring cabinets see page 53
H23B010 476210Coveressential or H23B040 or B3Q321 or B3R051
H23B040 484590Information modulebrief operating instructions instead of H23B010
B3Q321460213Fire department control terminal ’CH’only CH
B3R051490513Parallel indicator terminal ”2x24 indicators”option
Z3I470484341Cable set for H38...essential
Z3I380475567I-Bus flat cable + supply cable ”long”required for connection from level to level
Z1K030484231Terminal block with p.c.b. chassis for CI11..required per module (E3H020, E3L030 2 of each)
Z3B171484383Relay module 1 x 250V
AC/10Aintermediate relay for fire control installations (max. 16)
Pre-configured cabinet
CI1142-NL 546988Control unit in H38 housingpre-configured for ’NL’ requirements
for details referring control modules see page 66
29
Fire & Security Products
Siemens Building Technologies Group
Extendable system control unit
Separate connection terminal (without connection terminal not recommended)
Space for the installation of accessories
Batteries as required either 2x 12V/27Ah or 2x 12V/42Ah
Control terminals built into front terminal (also serves as main CPU)
Installation of additional display devices possible
Door right hinged with lock (type DOM)
Z1I060
or
Z1I020
or
Z1I030
Module
Note:
E3I020 if used,
mount at position 36!
If Z3I041 or B3P020
is used, on Pos. 36
E3M060/071/171/120
and E3C011 not
possible!
Mounting of
E3C011:
Terminal block
and holder
containing in
cable set Z3I510
EMC Precaution:
Relative to each
E3C011 module position, two positions
to the right and two
positions to the left
must not be fit with
either E3I040 or
B3Q...Control terminal AlgoPilotall variants of the AlgoPilot see page 42
H26T...Plexiglass door to AlgoPilot B3Q...optional see page 42
Z5B...Inscription setaccording to language see page 45, 46
E3G070546661Control module ’universal’for alarm devices and control outputs
H47G611 495385Cabinet set ’door with cutout’for details referring cabinets see page 54
H23B010 476210Coveressential or H23B040 or B3Q321 or B3R051
H23B040 484590Information modulebrief operating instructions
B3Q321565684Fire department control terminal ’CH’only CH
B3R051490513Parallel indicator terminal ”2x24 indicators”option
Z3I510484846Cable set for H47... / CI11...essential
Z1I020475499Connection cable 9 cond. with card holder, 0.5mfor internal pre-wiring
Z1I030475509Connection cable, 19 cond. with card holder, 0.5m for internal pre-wiring
Z1I060525802Connection cable, 4 cond. with card holder, 0.5mfor internal pre-wiring
Z3I380475567I-Bus flat cable+ supply cable ”long”essential for connection between level to level
Z3B171484383Relay module 1 x 250VAC/10Aintermediate relay for fire control installations (max. 8)
Z3I330475156Terminal block, 2x20 terminals3 are supplied with H47G611
Z3I420483818Intermediate connecting terminal blockfor additional free terminals
Z3G220525844Marinekit
Z3G240532950Set for increased vibrations
for details referring control modules see page 66
31
Fire & Security Products
Siemens Building Technologies Group
e4595e12
05.2003
Page 38
13CC1142/43 in cabinet H47...
Module chassis H47... can also be built into 3rd party housings (see page 57)
If Z3I041 or B3P020
is used, on Pos. 36
E3M060/071/171/120
and E3C011 not
possible!
Mounting of E3X10.:
Terminal block for
E3X10. containing in
cable set Z3I350
+ 2 x Z1I030
Control terminal
installed separately
H Extendable system control unit
H With separate main CPU (E3X10.)
H Separate connection terminal (without connection terminal not recom-
mended)
H Space for accessories
H Batteries as requires either 2x 12V/27Ah or 2x 12V/42Ah
H Control terminals usually connected separately (installation possible in
door)
H Door right hinged with lock (type DOM)
22
21
Z3I330
B2F020
H47G601 or H47G611
AC/DC converter
31
E3X10. + 2 x Z1I030 + Z3I350
(for E3X10.)
33
32
E3L020
E3I020
Z1I030
42
E3M...
Z1I...43E3M...
5255
(Battery 12V)(Battery 12V)
AX1201
AX1209
H23B010
H23B040
Cable duct
23
Z3I330
(lines)
24
Z3I330
Cable duct
34 3536 37
E3G050
Z1I030
Z1I030
Z1I...
E3...
Z1I...
4547 48
44
E3M...
Z1I...
E3M...
Z1I...
oror
AX1201
AX1209
B3Q321
B3R051
25
Z3B171
Z3B171
Z3B171
Z3B171
Z3B171
Z3B171
Z3B171
(diverse)
Z3B171
Mains
terminals
Connection
Fire control relay
1)
Z3I450
Modules
E3H020 + 2x Z1I030
E3...
E3...
Z1I...
Z1I...
Batteries
E3X10.
AX12..
Z3I350
can be plugged into
connection block
Supplied with cabinet sets H47G601/611
absolutely esssential
recommended space allocation
–one or two connection cables Z1I060, Z1I020 or
panel
Z1I030 are required for each module:
Line modules see page 59
LON module see page 72
Control modules see page 66
Extinguishing modules see page 79
Interfaces see page 75, 82, 86
One Z3I330 terminal block has space for:
either
–2x Z1I030 or
–8x Z1I060 or
–4x Z1I020 or
–1x Z1I030 and 2x Z1I020
1) Protection elements see page 95
Details on cabinet H47...
see page 54
Important:
Comply with max. permissible number of
’nodes’ + I-Bus modules!
for details see chapter 7
AX12..
Z1I060
or
Z1I020
or
Z1I030
module
32
Fire & Security Products
Siemens Building Technologies Group
E3X101546674Master moduleEPROM and RAM set separately
K3N010522818RAM extension card1MB-RAM additional to E3X101
Z3S070504823RAM-Set 2x512Kx8Bitto E3X101
E3X102629025Master moduleFlash-ROM and 1MB-RAM equipped
E3X103629038Master moduleFlash-ROM and 2MB-RAM equipped
B3Q...Control terminal AlgoPilotall variants of the AlgoPilot see page 42
H26T...Plexiglass door to AlgoPilot B3Q...Option see page 42
Z5B...Inscription setaccording to language see page 45, 46
CCQ00xxx 577627EPROM set to ’CC1142’for Main CPU E3X101
CCW00xxx 577630EPROM set to ’CC1143’for Main CPU E3X101 with K3N010
CCX00xxx (OSS)Flash-Programmfilefor Main CPU E3X102
CCY00xxx (OSS)Flash-Programmfilefor Main CPU E3X103
Interfaces as far as the space available allows installation
E3H020546658Gateway ’CERLOOP’double Europe card (requires 2 module spaces) see page 75
E3I020460239RS232 modulefor connection of printer B2Q191 or non-Cerberus printer
K3I090510820Pager interfacefor connection of paging system/pager and internal/external printer
Power supply for calculation of the emergency power operating period see page 91
B2F020470588Converter 115/230V
B1F120495233Converter 115/230V
AX1201225487Battery 12V/27Ah
AX1209462936Battery 12V/42Ah
Z3I450484273Mains socket ’CH’
Z3I041496290Surge protector setoption
Cabinet/Accessoriesfor details referring cabinets see page 54
H47G601 495372Cabinet set ’door without cutout’for seperate control terminal
H47G611 495385Cabinet set ’door with cutout’for installation in control terminal
H47E100 474885Module chassis compl.for installation in external cabinets
H23B010 476210Coveressential or H23B040 or B3Q321 or B3R051
H23B040 484590Information modulebrief operating instructions
B3Q321565684Fire department control terminal ’CH’only CH
B3R051490513Parallel indicator terminal ”2x24 indicators”option
Z3I350475538Cable set for H47/H67essential
Z3I380475567I-Bus flat cable + supply cable ”long”to connect module level with level
Z1I020475499Connection cable 9 cond. with card holder, 0.5mfor internal pre-wiring
Z1I030475509Connection cable, 19 cond. with card holder, 0.5m for internal pre-wiring
Z1I060525802Connection cable, 4 cond. with card holder, 0.5mfor internal pre-wiring
Z3B171484383Relay module 1 x 250VAC/10Aintermediate relay for fire control installations (max. 8)
Z3I330475156Terminal block, 2x20 terminals3 are supplied with H47G601/611
Z3I420483818Intermediate connecting terminal blockfor additional free terminals
Z3G220525844Marinekit
Z3G240532950Set for increased vibrations
Pre-configured cabinet
CC1142-NL546991Control unit in H47 housingpre-configured for ’NL’ requirements
AC>29.6VDC 6A
AC>24VDC 3Ageneral for fire control system supply
Fire & Security Products
Siemens Building Technologies Group
33
e4595e13
05.2003
Page 40
13.1Auxiliary power supply in second H47 housing
Cable duct
22
23
24
Z3I330
(diverse)
25
max. 8
Mains
terminals
Fire control relay
21
Z3I330
Z3I330
(for E3X10.)
B2F020
H47G601 or H47G611
31
33
32
(lines)
Cable duct
34 35 36 37
Application example:
Supplementary power
supply on module chassis H47E110 using
three H15Z300 battery
support plates
E3G050
E3L020
Z1I030
E3I020
Z1I030
42
E3X10. + 2 x Z1I030 + Z3I350
21
H47E110
B2F020
31
E3C011
Z3I870
41
E3C011
Z3I870
51
E3C011
Z3I870
44
E3M...
E3M...
Z1I...43E3M...
5255
(Battery 12V)(Battery 12V)
AX1201
AX1209
2225
(Battery 12V)(Battery 12V)
AX1201
Z1I...
Z1I...
oror
oror
AX1209
H15Z300H15Z300
3235
(Battery 12V)(Battery 12V)
AX1201
oror
AX1209
H15Z300H15Z300
5255
(Battery 12V)(Battery 12V)
AX1201
oror
AX1209
H15Z300
Z1I030
E3...
Z1I...
4547 48
E3M...
Z3I450
Z1I...
E3...
E3H020 + 2x Z1I030
AX1201
AX1209
AX1201
AX1209
AX1201
AX1209
AX1201
AX1209
H15Z300
Z1I...
Housing set H47G611
or
H47E100 and H47T111
Details see page 54
E3...
Z1I...
H47E110 and H47T101
Details see page 54
Remarks:
– Place housings next to or on top of each other (do not install at a
distance)
– the additional E3C011 are not used as I-Bus equipment
– use one Z3I870 cable set per supplementary power supply
for details of the power supply wiring principle
see page 87
Essential accessory
H47E110 476184Module chassis ’empty’
H47T101 495356Cabinet frame and door without cutout
B2F020470588Converter 115/230V
E3C011505479Battery charging unitsupersedes E3C010
H15Z300 476197Battery support platefor the second and further battery sets
AX1201225487Battery 12V/27Ah
AX1209462936Battery 12V/42Ah
Z3I870496944Cable setfor supplementary power supply
AC>29.6VDC 6A
34
Fire & Security Products
Siemens Building Technologies Group
e4595e13
05.2003
Page 41
13.2Cable sets for supplementary power supply in H47 housing
The Z3I870 cable set can always be used for the wiring of the supplementary power supply. The cable set contains all the necessary cable and wires for connections to the next
extension.
CC1142/43
for H47E100 and H47E110
Z3I350
E3X10.
Z3I870
1st. extension
E3C011
Z3I870
2nd. extension
E3C011
Z3I870
3rd. extension
E3X10.
B2F020
E3C011
E3C011
E3C011
E3C011
Fire & Security Products
Siemens Building Technologies Group
H Extendable system control unit
H With separate main CPU (E3X10.)
H Separate connection block
H Space for accessories
H Batteries as required either 2x 12V/27Ah or 2x 12V/42Ah
H Control terminals usually connected separately
H (installation possible in door)
H Door right hinged with lock (type DOM)
H67E101
Z3I350
AX12..
AX12..
Comments:
– E3I020 if used mount
at position 32!
– B2F020 fits any mo-
dule space
If Z3I041 or B3P020
is used, on Pos. 36
E3M060/071/171/120
and E3C011 not possible!
Mounting of E3X10.:
Terminal block for
E3X10. containing in
cable set Z3I350
+ 2 x Z1I030
EMC Precaution:
Relative to each E3X10.
and E3C011 module position, two positions to
the right and two positions to the left must not
be fit with either E3I040
or E3G080 modules
cable duct
Z3I330
02
Z3I330Z3I330
121311
01
H67G601 or H67G611
(for E3X10.)
Z3I330
21
cable duct
B2F020
32 33 34 35 36
31
Z1I050
Z1I050
E3I020
42 43 44 45
E3M...
Z1I...
52 53 54 55 56
E3X10. + 2 x Z1I030 + Z3I350
E3M...
Z1I...
61
6265
(Battery 12V)
AX1201
E3...
Z1I...
AX1209
Z1I050
E3L020
E3L020
E3M...
Z1I...
Z1I...
E3...
E3M...
Z1I...
E3M...
Z1I...
oror
03
04
Z3I330Z3I330
terminals
Z3I450
14
Z3I570
37
E3...
Z1I...
E3...
47
E3H020 + 2x Z1I050
Z1I...
E3...
E3M...
E3...
57
E3...
Z1I...
Z1I...
E3...
(Battery 12V)
AX1201
AX1209
Mains
1)
max. 8
38
Z1I...
48
Z1I...
58
Z1I...
E3...
E3...
E3...
Connection panelModules
Fire control relay
Z1I...
Z1I...
Z1I...
Batteries
Supplied with cabinet sets H67G601/611
absolutely esssential
04
recommended space allocation
or
Z3I330
8xZ3B171
14
or
Z3I330
–one or two connection cables Z1I070, Z1I040 or
Z1I050 are required for each module:
Line modules see page 59
LON modulesee page 72
8xZ3B171
Control modules see page 66
Extinguishing modules see page 79
Interfaces see page 75, 82, 86
One Z3I330 terminal block has space for:
either
37
Mains
terminals
1)
Z3I450
–2x Z1I050 or
–8x Z1I070 or
–4x Z1I040 or
–1x Z1I050 and 2x Z1I040
1) Protection elements see page 95
Special feature:
H67E100 has 3 different hole patterns for mounting. As a
result, the relationship between connection block / modules
batteries can also be arranged differently
see page 38
Details on cabinet H67...
see page 55
Important:
Comply with max. permissible number of
’nodes’ + I-Bus modules!
for details see chapter 7
36
Fire & Security Products
Siemens Building Technologies Group
E3X101546674Master moduleEPROM and RAM set separately
K3N010522818RAM extension card1MB-RAM additional to E3X101
Z3S070504823RAM set 2x512Kx8Bitto E3X101
E3X102629025Master moduleFlash-ROM and 1MB-RAM equipped
E3X103629038Master moduleFlash-ROM and 2MB-RAM equipped
B3Q...Control terminal AlgoPilotall variants of the AlgoPilot see page 42
H26T...Plexiglass door to AlgoPilot B3Q...optional see page 42
Z5B.........Inscription setaccording to language see page 45, 46
CCQ00xxx 577627EPROM set to ’CC1142’for Main CPU E3X101
CCW00xxx 577630EPROM set to ’CC1143’for Main CPU E3X101 with K3N010
CCX00xxx (OSS)Flash programm filefor Main CPU E3X102
CCY00xxx (OSS)Flash programm filefor Main CPU E3X103
Interfaces as far as the space available allows installation
E3H020546658Gateway ’CERLOOP’double Europe card (requires 2 module spaces) see page 75
E3I020460239RS232 modulefor connection of printer B2Q191 or non-Cerberus printer
K3I090510820Pager interfacefor connection of paging system/pager and internal/external printer
Power supply for calculation of the emergency power operating period see page 91
B2F020470588Converter 115/230V
B1F120495233Converter 115/230V
AX1201225487Battery 12V/27Ah
AX1209462936Battery 12V/42Ah
Z3I450484273Mains socket ”CH”
Z3I041496290Surge protector setoption
Cabinet/Accessoriesfor details referring cabinets see page 55
H67G601 495550Cabinet set ’Door without cutout’for separate control terminal
H67G611 495660Cabinet set ’door with cutout’for installation in control terminal
H67G620 577863Cabinet set for marine
H67E101 509705Module chassis compl. for H67 ...for installation in external cabinets
H23B010 476210Coveressential or H23B040 or B3Q321 or B3R051
H23B040 484590Information modulebrief operating instructions
B3Q321565684Fire department control terminal ”CH”only CH
B3R051490513Parallel indicator terminal ”2x24 indicators”option
Z3I350475538Cable set for H47/H67essential
Z3I380475567I-Bus flat cable + supply cable ”long”to connect module level 4.. with level 3..
Z1I040475512Connection cable 9 cond. with card holder, 0.8mfor internal pre-wiring
Z1I050475525Connection cable, 19 cond. with card holder, 0.8m for internal pre-wiring
Z1I070525815Connection cable, 4 cond. with card holder, 0.8mfor internal pre-wiring
Z3B171484383Relay module 1 x 250VAC/10Aintermediate relay for fire control installations
Z3I330475156Terminal block, 2x20 terminals
Z3I420483818Intermediate connecting terminal blockfor additional free terminals
Z3I570495644Support rail ’TS35’ 133 mm with bracketfor up to 8 Z3B171 relays
Z3G270566120Marinekit
Pre-configured cabinet
CC1142-NL547000Control unit in H67 housingpre-configured for ’NL’ requirements
AC>29.6VDC 6A
AC>24VDC 3Agenerally for fire control system supply
Fire & Security Products
Siemens Building Technologies Group
37
e4595e14
05.2003
Page 44
14.1Installation possibilities on module chassis H67...
Special feature:
H67E100 has 3 different hole patterns for mounting. As a result, the relationship between connection block / modules /
batteries can also be arranged differently
Fire & Security Products
Siemens Building Technologies Group
e4595e14
05.2003
Page 45
14.3Combination possibilities
H47 + H67 cabinet
Z3G170 = 4x
32 module spaces
3 battery sets
or H98 cabinet
H67E101
H47E100/110
32 module spaces
5 universal brackets
Note:
The following modules
can not
be mounted on
G1E010:
– Z1I020....Z1I050
– Z1K020 / 030
– Z3I330
Details on module chassis:
H67E101 see page 55
H47E100 see page 54
H67E101
Profil rail on
rear panel of
H98G600
H67E101
or
H47E100/110
G1E010
5xG1E010
If the H67E101 module chassis is
built into a non-Cerberus housing
or in the H98-housing the
H67Z020 protective cover must
be used for CE conformity.
Note:
Raise the B2F020 converter one
level higher.
Important:
The H67Z020 only fits the
H67E101 and H67E111
module spaces 38/48/58 can not
be used
H67Z020 also includes a longer
cable from B2F020 –> E3X10.
Fire & Security Products
Siemens Building Technologies Group
H67E101
H67Z020
4 special slots to retain H67Z020
39
e4595e14
05.2003
Page 46
14.4Supplementary power supply
Cable duct
Z3I330
(for E3X10.)
Z3I330
02
121311
Z3I330Z3I330
03
Z3I330
Z3I330
Cable duct
B2F020
32 33 34 3538
Z1I050
Z1I050
E3L020
E3I020
43 44 45
42
Z1I050
E3L020
E3...
36
Z1I...
46
E3...
37
Z1I...
47
04
Mains
terminals
Z3I450
14
max. 8
Z3I570
E3...
Z1I...
Fire control relay
01
H67G601 or H67G611
21
31
Cabinet set H67G611
or
H67E101 + H67T111
Details see page 55
Connection panel
Modules
E3M...
Z1I...
E3M...
Z1I...
E3...
5255
(Battery 12V)
AX1201AX1201
E3X10. + 2 x Z1I050 + Z3I350
61
6265
(Battery 12V)
oror
AX1209AX1209
(Battery 12V)
AX1201
AX1209
H15Z300H15Z300
(Battery 12V)
AX1201
AX1209
H15Z300H15Z300
(Battery 12V)
Application example:
Auxiliary power supply
on H47E110 module
chassis using three
H15Z300 battery support plates
H47E110
E3C011
Z3I870
21
2225
B2F020
31
3235
E3C011
Z3I870
41
E3C011
Z3I870
5255
51
AX1201
AX1209
E3C011
Z3I870
H15Z300
Essential accessory
H47E110 476184Module chassis ’empty’
Z1I...
Z1I...
Z1I...
E3...
E3...
(Battery 12V)
H15Z300H15Z300
(Battery 12V)
AX1201AX1201
(Battery 12V)
AX1201
oror
AX1209
(Battery 12V)
oror
AX1201
AX1209
(Battery 12V)
AX1201
oror
AX1209
H15Z300
E3H020 + 2x Z1I050
Z1I...
E3...
Batteries
H47E110 und H47T101
Details see page 54
Remarks:
– Place housings one above the other (do not install at a distance)
– the additional E3C011 are not used as I-Bus equipment
– Use one Z3I870 cable set per auxiliary power supply
for details of the power supply wiring principle,
see page 87
H47T101 495356Cabinet frame + ’door without cutout’
B2F020470588Converter 115/230V
AC>29.6VDC 6A
E3C011505479Battery charging unit
H15Z300 476197Battery support platefor the second and further battery sets
AX1201225487Battery 12V/27Ah
AX1209462936Battery 12V/42Ah
Z3I870496944Cable setfor supplementary power supply
H98G600
Details see page 56
40
Fire & Security Products
Siemens Building Technologies Group
e4595e14
05.2003
Page 47
14.5Cable sets for supplementary power supply
The Z3I870 cable set can always be used for the supplementary power supply wiring.
The cable set contains all the necessary cable and wires for connection to the next extension.
CC1142/43
for H67E101 and H47E110
Z3I350
E3X10.
Z3I870
1st extension
E3C011
Z3I870
2nd extension
E3C011
Z3I870
3rd extension
E3C011
E3X10.
E3C011
B2F020
E3C011
E3C011
Z3I870
4th extension
E3C011
Fire & Security Products
Siemens Building Technologies Group
E3C011
for wiring details ³ see document e1260
41
e4595e14
05.2003
Page 48
15Control terminals AlgoPilot B3Q...
There are two different series of control terminals to choose from. Mixing of standard- and
comfort terminals in the same system is possible.
Application region
International
Nordic
CH
Asia/Pacific
Comfort terminalsStandard terminals
B3Q660B3Q460
B3Q680
B3Q685
B3Q480
B3Q485
Australia
France
(special french application only)
B3Q560
B3Q565
B3Q670
B3Q490
42
Fire & Security Products
Siemens Building Technologies Group
e4595e15
05.2003
Page 49
15.1Features
FeaturesComfort
terminals
Double-sized (240x128 dots), backlit LC-Display for
most intuitive and userfriendly operation
Context- and system state adjusted operation functions
via softkeys
Functionally grouped, ergonomical operating and indicating elements
Detailled event information like event type and location,
intervention instruction texts, system operating conditions etc.
(same message concept on both terminal series to keep
compatibility in mixed installations!)
Integrated emergency operation function
Insertable inscription strips in various languages
Access to system functions via four different operating
levels depending on user profile
Configurable for single or multi AREA operation
Access authorisation via password or key switch
Options:
– lockable plexiglass door H26T...
– RS232 module E3I020 or paging interface card
K3I090
– LON interface E3I040 for LON devices (floor control
terminals etc..)
– Parall indicator terminal B3R051
Standard
terminals
–
á Check outline quantities according chapter 7.2
Plexiglass door to AlgoPilot B3Q...
AlgoPilot B3Q6.../565
Z3S200
for the locking of doors
and/or access authorization
for operation
H26T030
Plexiglas door
AlgoPilot B3Q4.../560
Z3S010
for the locking of doors
and/or access authorization
for operation
H26T020
Plexiglass door
Comfort terminal
Standard terminal
Fire & Security Products
Siemens Building Technologies Group
43
e4595e15
05.2003
Page 50
Place of the E3I020 RS232 module and the Pager interface K3I090
RS232 module E3I020 is mounted at the rear of the control terminal by
AlgoPilot B3Q6../565
means of accessories Z1B020.
! Details E3I020 see document e1393
Pager interface K3I090 is mounted at the rear of the control terminal by
means of accessories Z1B060.
! Details K3I090 see document e1669
AlgoPilot B3Q4../560
Use flat cable F20A020
Place of the E3I040 LON interface
Supplied with Z1B020:
Plug-in terminal 12 cont.
Installation material
Protective cover
H28T110
AlgoPilot B3Q...
H28G200
LON interface E3I040 connected at the I-Bus of a
remote control terminal AlgoPilot ’CT’, only
mounted in the housing H28G200.
! Details E3I020 see document e1393
Supplied with Z1B070:
– Mounting bracket with card holder and
terminal block numbering in red
– I-Bus flat and supply cable
44
Fire & Security Products
Siemens Building Technologies Group
e4595e15
05.2003
Page 51
Modules and inscription sets to AlgoPilot B3Q6../565
Control terminals AlgoPilot
B3Q660565600Control terminal ’International’operating unit and main CPU combined
B3Q670565590Control terminal ’Australien’”
B3Q680569855Control terminal ’Nordic’”
B3Q685A5Q00003873 Control terminal ’CH’”
B3Q565565480Control terminal ’Asia/Pacific’”
Inscription sets available (if no inscription strips are available –> use templates from document e6516)
Z5B400475710Inscription set ’blank’
Z5B415570653Inscription set ’Portuguese’
Z5B435570666Inscription set ’Flemish’
Z5B505570679Inscription set ’Turkish’
Z5B525570682Inscription set ’German CH’
Z5B535570695Inscription set ’German D’
Z5B555570705Inscription set ’Italian I’
Z5B565570718Inscription set ’French CH’
Z5B585570721Inscription set ’French F’
Z5B595570734Inscription set ’Danish’
Z5B605570747Inscription set ’Finnish’
Z5B615570750Inscription set ’Norwegian’
Z5B625570763Inscription set ’Swedish’
Z5B635570776Inscription set ’English’
Z5B645570789Inscription set ’English GB’
Z5B665570792Inscription set ’Spanish’
Z5B685570640Inscription set ’Hebrew’
H26T030 570530Plexiglass door to AlgoPilotincl. mounting accessories
Z3S200570349Key switch module to AlgoPilot (KABA)for operating access
V2G050570611Cable for 9V lithium batteryto signal trouble upon mains failure and emergency power supply battery
B3R051490513Parallelanzeige ’2x24 Anzeigen’
Accessories for RS232 interface for all AlgoPilots
E3I020460239RS232 modulefor the connection of a printer see page 82
Z1B020475907Mounting accessories for E3I020essential when mounting E3I020 on the rear terminal of AlgoPilot B3Q...
F20A020 476317Flat cable micro 20 cond. 0.165mLink between E3I020 AlgoPilot B3Q..., if E3I020 on the rear of B3Q...
K3I090510820Pager interfacefor connection of paging system/pager and internal/external printer
Z1B060525984Mounting accessory for K3I090essential when mounting K3I090 on the rear of AlgoPilot B3Q...
Accessories for E3I040 for connection on I-Bus of AlgoPilots CT11 in housing H28G200
E3I040499310LON interfaceConverter between I-Bus and LON-Bus
Z1B070A5Q00001720 Mounting accessory for E3I040essential when mounting E3I040 in housing H28G200
Fire & Security Products
Siemens Building Technologies Group
45
e4595e15
05.2003
Page 52
Modules and inscription sets to AlgoPilot B3Q4../560
Control terminals AlgoPilot
B3Q460546551Control terminal ’Standard’operating unit and main CPU combined
B3Q480546577Control terminal ’Nordic’”
B3Q485546580Control terminal ’CH’”
B3Q490546593Control terminal ’Guinard’”
B3Q560546616Control terminal ’Asia/Pacific’”
CTQ00xxx 577601EPROM set ’international’for B3Q460, B3Q48x
CTQT1xxx (OSS)EPROM set ’China simplified’for B3Q560
CTQTExxx (OSS)EPROM set ’China traditional’”
CTQTLxxx (OSS)EPROM set ’Korea standard’”
CTQT5xxx (OSS)EPROM set ’Thailand’”
EPROM set for parallel control terminal (CA....)
CAR00xxx A5Q00003094 EPROM set for ’CA11’for B3Q460, B3Q48x
CAQT1xxx (OSS)EPROM set ’China simplified’for B3Q560
CAQTExxx (OSS)EPROM set ’China traditional’”
CAQTLxxx (OSS)EPROM set ’Korea standard’”
CAQT5xxx (OSS)EPROM set ’Thailand’”
EPROM set for control terminal and CPU combined (CI....)
CIQ00xxx 577614EPROM set ’international’for B3Q460, B3Q48x
CIQT1xxx (OSS)EPROM set ’China simplified’for B3Q560
CIWT1xxx (OSS)”””
CIQTExxx (OSS)EPROM set ’China traditional’”
CIWTExxx (OSS)”””
CIQTLxxx (OSS)EPROM set ’Korea standard’”
CIWTLxxx (OSS)”””
CIQT5xxx (OSS)EPROM set ’Thailand’”
CIWT5xxx (OSS)”””
Z3S070504823RAM-Set 512Kx8Bitfor B3Q460, B3Q48x, B3Q560
Z3S080504836RAM-Set 256Kx8Bitfor B3Q460, B3Q48x
Inscription sets available (if no inscription strips are available –> use templates from document e6516)
Z5B400475710Inscription set ’blank’
Z5B410475596Inscription set ’Portuguese’
Z5B420475606Inscription set ’Flemish’
Z5B430475619Inscription set ’Dutch’
Z5B440475622Inscription set ’Polish’
Z5B450475635Inscription set ’Czech’
Z5B460475651Inscription set ’Hungarian’
Z5B470475664Inscription set ’Slovenian’
Z5B480475677Inscription set ’Serbian’
Z5B490475680Inscription set ’Croatian’
Z5B500475693Inscription set ’Turkish’
Z5B510475703Inscription set ’Icelandic’
Z5B520476524Inscription set ’German CH’
Z5B530476537Inscription set ’German D’
Z5B540476540Inscription set ’Italian CH’
Z5B550476553Inscription set ’Italian I’
Z5B560476566Inscription set ’French CH’
Z5B570476579Inscription set ’French B’
Z5B580476582Inscription set ’French F’
Z5B590476595Inscription set ’Danish’
Z5B600483203Inscription set ’Finnish’
Z5B610483216Inscription set ’Norwegian’
Z5B620483229Inscription set ’Swedish’
Z5B630483232Inscription set ’English’
Z5B640483245Inscription set ’English GB’
Z5B650483795Inscription set ’Slovakian’
Z5B660475583Inscription set ’Spanish’
Z5B680484956Inscription set ’Hebrew’
H26T020 474953Plexiglass door to AlgoPilotincl. mounting accessories
Z3S010474966Key switch module to AlgoPilot B3Q.. (KABA)for operating access
V2G040475923Cable for 9V lithium battery to signal trouble upon mains failure and emergency power supply
Accessories for RS232 interface for all AlgoPilots
E3I020460239RS232 modulefor the connection of a printer see page 82
Z1B020475907Mounting accessories for E3I020essential when mounting E3I020 at the rear of AlgoPilot B3Q...
F20A020 476317Flat cable micro 20 cond. 0.165mLink between E3I020 AlgoPilot B3Q..., if E3I020 at the rear of B3Q...
K3I090510820Pager interfacefor connection of paging system/pager and internal/external printer
Z1B060525984Mounting accessory for K3I090essential when mounting K3I090 on the rear of AlgoPilot B3Q...
Accessories for E3I040 for connection on I-Bus of AlgoPilots CT11 in housing H28G200
E3I040499310LON interfaceConverter between I-Bus and LON-Bus
Z1B070A5Q00001720 Mounting accessory for E3I040essential when mounting E3I040 in housing H28G200
battery
46
Fire & Security Products
Siemens Building Technologies Group
e4595e15
05.2003
Page 53
15.2Installation possibilities
Built into H47/H67 cabinetsBuilt into H23/H26 cabinets
0
0
0
0
H23G230
Dimensions: (H23) W= 125
B3R051
AlgoPilot
B3Q...
for recessed mounting see page 51
Built into H28 cabinet
H28T110
by choice
B3Q321
B3R051
H23B020
H23B040
AlgoPilot
B3Q...
Dimensions: W = 520
H = 219
D=76
(H26) W= 366
H = 219
D=76
H26G220
H = 300
D=70
H28G200
AlgoPilot
B3Q...
AlgoPilot
B3Q...
by choice
B3Q321
B3R051
H23B010
H23B040
Dimensions: (H47) W= 434
Built into H37 cabinet
AlgoPilot
B3Q...
Dimensions: W = 51
H = 735
D = 300
(H67) W= 434
H=113
D = 300
H47T111
or
H67T111
H=54
D=20
H28T120
4 x B3R051
for recessed mounting see page 51
(with autonomous power supply)
H38G220
B2F020
E3C011
AX1210
AX1210
Dimensions: W = 515
B3Q...
Z3I470
H = 602
D = 88 (H38G220)
D = 147 (H38G320)
by choice
H23B010
H23B040
B3Q321 (only H38G320)
B3R051 (only H38G320)
H37G420
Built into 19” cabinetBuilt into H38 cabinet
G2A130
B3Q...
G2A140
by choice
H23B021
H23B040
B3Q321
B3R051
H37G410
Dimensions: W = 510
H = 540
D = 214
19”-Schrank
Fire & Security Products
Siemens Building Technologies Group
47
e4595e15
05.2003
Page 54
CT11
C-Bus
CC11, CI11, CK11
B2F020E3C011
I-Bus
Mains
Batteries
AX12..
B3Q321
LON-Bus
E3I040
Basic equipment
Option
separately connected
parallel indicator
activation of Mimic Display
see page 70
Parallel branching permissible
oder
E3I020
RS232
1
K3I090
2
F12A100
Data bus
B3R051B3R051
max.
1000m
B3R051B3R051
F12A100F12A100/470
24V supply line
Printer
–> see page 82
external printer
Pager
–> see page 86
internal or
B3R051:
– can be installed separately, however at max. 1000m
– max. 24 units, however max. 8 addresses
– free allocation of the LEDs (programming according to application)
– line and equipment no
t monitored
B3Q321
CT11
E3I020
RS232
12
C-Bus
24V
I-Bus
LON-Bus
E3I040
not monitored
CA11
E3I020
RS232
12
B3Q321
24V
I-Bus
for further details
see page 13
Modules
Control terminals AlgoPilot B3Q6../565
B3Q...Control terminal AlgoPilotall variants of AlgoPilot see page 42ff
CT/CI/CAFlash programm filefor ’CT’ / ’CI’ / ’CA’ ! see page 45
Z5B...Inscription setaccording to language see page 45
Control terminals AlgoPilot B3Q4../560
CT/CI/CAEPROM setfor ’CT’ /’CI’ / ’CA’ ! see page 46
Z3S070504823RAM set 512Kx8Bitfor ’CT1142’
Z3S080504836RAM set 256Kx8Bitfor ’CA1141’
Z5B...Inscription setaccording to language see page 46
V2G050570611Cable for 9V lithium batteryfor 3rd power source for B3Q6../565
V2G040475923Cable for 9V lithium batteryfor 3rd power source for B3Q4../560
E3I020460239RS232 modulefor connection printer or ’CA11’
Z1B020475907Mounting accessories for E3I020 / B3Q...for mounting E3I020 on the rear panel of AlgoPilot B3Q...
K3I090510820Pager interfacefor connection of paging system/pager and internal/external printer
Z1B060525983Mounting accessories for K3I090 / B3Q...for mounting K3I090 on the rear panel of AlgoPilot B3Q...
Z3I530484972Adapter for K3R071/72, B3R051to adapt flat cable to terminals
F12A100 495275Flat cable ’Micro’ 12 cond., 0.4mfor B3R051
F12A470 495288Flat cable ’Micro’ 12 cond., 1.5mfor B3R051
E3I040499310LON interfaceConverter between I-Bus and LON-Bus
Z1B070A5Q00001720 Mounting accessory for E3I040essential when mounting E3I040 in housing H28G200
B2F020470588Converter 115/230V
E3C011505479Battery charging unit
AX1210475570Battery 12V/15Ah
Z3I470484341Cable set for H38...for connection AlgoPilot B3Q... with E3C011
AC>29.6VDC 6A
48
Fire & Security Products
Siemens Building Technologies Group
e4595e15
05.2003
Page 55
15.3Connection lines between control unit and external operating units
Options:
Control terminal
AlgoPilot B3Q...
B3Q321 (Fire department control terminal)
B3R051 (Parallel indicators)
E3I040 (LON interface)
Printer, paging system/pager
Control terminal
AlgoPilot B3Q...
2..11 leads
When planning a system the following condition must be complied with:
At least one operating unit must comply with standard EN54, i.e. it must be equipped with
emergency operation and emergency power supply.
EN54 requirements:
The number of wires in the connection cable depends on the application and the distances between the stations:
Loop C-Bus
max. 1000m per Loop with ø 0.6mm (incl. return line)
max. 1800m per Loop with ø 0.8mm (incl. return line)
Control unit CC11/CI11
Communication as loop line design C-Bus as a loop line
Operating units also with emerg. operation 3 additional wires for emergency operation
second de-coupled 24V supply 3 additional wires or autonomous power
supply
Is the operating unit supplied with 24V from the control unit or autonomously?
Is an emergency power supply provided according to EN54?
Is the emergency operation circuit (emergency operation) installed?
Application
C-Bus24V supplyEmergency
power supply
24V supply from control unit
EN54 complied with
24V supply from control unit
without emergency operation and
emergency power supply
autonomous power supply
EN54 complied with
autonomous power supply
without emergency operation and
emergency power supply
Note:
– Emergency operation circuit required including between CPUs or for a separately connected Gateway
– Emergency operation circuit and emergency supply are not designed as a loop line
– Emergency supply via separate cable or C-Bus feedback
F
(2 wires)
F
(2 wires)
F
(2 wires)
F
(2 wires)
F
(3 wires)
F
(3 wires)
15.4Power supply (24V)
Operating units AlgoPilot B3Q... are designed for the voltage range 18..45VDC
The maximum current at 24V is 400mA
Max. length of line (approximate):
for cables ø 0.8mm 180m
for cable cross-section 1mm2 360m
The current consumption for the options (fire department control terminal, parallel indicator terminal, printer, paging system/pager) must be taken into account separately
F
(3 wires)
Emergency op-
eration circuit
F
(3 wires)
F
(3 wires)
Number of
wires
11
5
5
2
Fire & Security Products
Siemens Building Technologies Group
49
e4595e15
05.2003
Page 56
16Range of cabinets H23... / H26... / H28...
H23G230
H26G220
Front can not
be pivoted
H23G230:
Dimensions 125 x 219 x 76mm
Materialplastic
ColourPantone 421 grey
Protection categoryIP40
H26G220:
Dimensions 366 x 219 x 76mm
Materialplastic
ColourPantone 421 grey
Protection categoryIP40
for operating units
B3Q... / B3R051 /
cover plate H23B020
with lock (DOM)
for parallel indicator
terminals (4x
B3R051),
with lock (DOM)
for printer B2Q191with
lock (DOM)
H28G200
H28T110
H28T120
H28T020
H28...:
Dimensions 520 x 300 x 70mm
Materialsteel sheet
Colourcabinet: RAL7035 light grey
Door:1E110 dark grey
Protection categoryIP30
Details of the cabinets H23../H26.../H28...
see document e1393
for plan compartment (A4);
for installation of B3R051 /
cover H23B020 etc.,
with lock (KABA)
H28T130
with KABA lock
H28T150
All doors are hinged at left!
50
Fire & Security Products
Siemens Building Technologies Group
e4595e16
05.2003
Page 57
16.1Recessed mounting H23G230 and H28G200
H23G230
H23Z230
H28Z010
H28G200
H23U220
UPR28
H23G230
H23Z230
Wall recess
H23U230
Wall recess
UPR29
H28Z010
H28G200
H28Z010
H28G200
Details to the housing H23../H26.../H28...
see document e1393
Modules
Cabinets and doors
H23G230 475091Plastic cabinetfor additional indicators and operating units
H26G220 462800Plastic cabinetfor separately installed control terminals AlgoPilot B3Q...
H28G200 409944Cabinet (without door)for various applications
H28T020 410564Cabinet door for printer B2Q191
H28T110 474982Cabinet door for AlgoPilot B3Q... / B3R...
H28T120 474995Cabinet door for 4 B3R051 parallel indicator terminals
H28T130 475910Cabinet door for plan compartment and 1x B3Q321 / B3R051 etc.
H28T150 484367Cabinet door without cut-out panel with KABA key lock
H23B020 476278Cover for H28T110 / 130
H28Z010 410593UP frame setfor recessed mounting of cabinet H28G200
H28Z020 413600UP adapteradditionally required for recessed mounting of 2 H28G200 cabinets
H23U220 379126Recess box to B3R051for recessed mounting of cabinet H23G230
H23U230 532879Recess box to B3Q5xxfor recessed mounting of cabinet H23G230
H23Z230 532882Cover frame to B3Q5xx/B3R051for recessed mounting of cabinet H23G230
UPR28430434Recess boxfor 1 H28G200 cabinet (poss. required)
UPR29430447Recess boxfor 2 H28G200 cabinets (poss. required)
Fire & Security Products
Siemens Building Technologies Group
51
e4595e16
05.2003
Page 58
17Range of cabinets H37...
H37G410H37G420
H37G410:
Dimensions 540 x 510 x 200mm
Materialsteel sheet
ColourRAL7035 light grey
Protection categoryIP30
H37G430
H37G430:
Dimensions 540 x 510 x 200mm
Materialsteel sheet
ColourRAL7035 light grey
Protection categoryIP30
H37G420:
Dimensions 540 x 510 x 214mm
Materialsteel sheet
ColourRAL7035 light grey
Protection categoryIP30
H37T120
H37Z010
for AlgoPilot B3Q...
H37T000
cabinet and blank front for special applications
spacer for the assembly of 2 housings next to each other
Inner door for housing H37G420, front inprint in swedish
Details of the cabinets H37... see document e1971
Modules
Cabinet
H37G410 533959Cabinet for AlgoPilot B3Q... (flat door)incl. compartment for A3 size fire plans
H37G420 534107Cabinet for AlgoPilot B3Q... (designer door)incl. compartment for A3 size fire plans
H37G430 533962Cabinetfor special applications
H37T000 533467Blank frontfor special applications
H37T120 565723Inner door to housing H37G420Synthetic front inprint in swedish
H37Z010 533975Spacerfor 2 housings next to each other
52
Fire & Security Products
Siemens Building Technologies Group
e4595e17
05.2003
Page 59
18Range of cabinets H38...
H38G210
H38G310
Doors can be closed
with 2 Allen screws
H38G220
H38G210/220/230:
Dimensions 520 x 602 x 100mm
Materialsteel sheet
H38G230
ColourRAL7035 light grey
Protection categoryIP40
H38G310/320:
Dimensions 520 x 602 x 155mm
Materialsteel sheet
ColourRAL7035 light grey-
Protection categoryIP40
H38G320
Z1K030
for AlgoPilot B3Q...
for H23B010 or H23B040 see page 26
for B3Q321/B3R051/H23B010 or H23B040
see page 28 and 47
Details of the cabinets H38... see document e1273
Modules
Cabinet sets
H38G210 484901Cabinet set ’Door without cutout’ (flat)incl. module chassis
H38G220 484914Cabinet set ’Door with cutout’ (flat)incl. module chassis and 2 profile bars for 2 x 3 relays
H38G230 484927Cabinet set ’Plan compartment’incl. supporting bracket
H38G310 484930Cabinet set ’Door without cutout’ (deep)incl. module chassis and 1 profile bars for 16 relays
H38G320 484943Cabinet set ’Door with cutout’ (deep)incl. module chassis and 1 profile bars for 16 relays
Fire & Security Products
Siemens Building Technologies Group
53
e4595e18
05.2003
Page 60
19Range of cabinets H47...
H47G601
H47T101
H47G611
Including module chassis with:
–Cable ducts
–3 terminal blocks Z3I330
–Relay bar (max. 8x Z3B171)
–Mains terminals (pre-wired)
–Battery support plate
Doors can be closed
with DOM lock
H47T111
H47E100
430
H47E110
690 (16HE)
for AlgoPilot B3Q...
for B3Q321/B3R051/H23B010 or H23B040
see page 26, 32 and 47
Z3S090
Z1K020
Details of the cabinets H47... see document e1274
H15Z300
H47G601/611:
Dimensions 434 x 735 x 300mm
Materialsteel sheet
ColourRAL7035 light grey
Protection categoryIP30
Modules
Cabinet sets complete (with module chassis)
H47G601 495372Cabinet set ’Door without cutout’
H47G611 495385Cabinet set ’Door with cutout’
Cabinets, module chassis and accessories (individual parts)
H47T101 495356Cabinet frame and door without cutout
H47T111 495369Cabinet frame and door with cutout
H47E100 474885Module chassis to H47...incl. cable ducts, mains terminals and battery support plate
H47E110 476184Module chassis to H47... ’empty’for non-standard applications
H15Z300 476197Battery support platefor H47E110; max. 3 per module chassis (= 3 pairs of batteries)
Z1K020475486Terminal block with card-holderwithout cable (for direct connection to module)
Z3S090496957Spare part for key switch (without lock cylinder)for conversion from DOM KABA/KESO/SEA etc.
54
Fire & Security Products
Siemens Building Technologies Group
Dimensions 434 x 1 10 x 300mm
Materialsteel sheet
ColourRAL7035 light grey
Protection categoryIP30
for AlgoPilot B3Q...
for B3Q321/B3R051/H23B010 or H23B040
see page 26, 32 and 47
Details of the cabinets H67...
see document e1275
Modules
Cabinet sets complete (with module chassis)
H67G601 495550Cabinet set ’door without cutout’
H67G611 495660Cabinet set ’door with cutout’
H67G620 577863Cabinet set ’door without cutout’ for marine
Cabinets, module chassis and accessories (individual parts)
H67T101 495615Cabinet frame and door without cutout
H67T111 495628Cabinet frame and door with cutout
H67E101 509705Module chassis to H67...incl. cable ducts, mains terminals and battery support plate
H67Z020 496902Protective cover for H67E...
H15Z300 476197Battery support platefor H67E110; max. 5 per module chassis (= 5 pairs of batteries)
Z1K020475486Terminal block and card holderwithout cable (for direct connection to module)
Z3S090496957Spare part for key switch (without lock cylinder)for conversion from DOM KABA/KESO/SEA etc.
Fire & Security Products
Siemens Building Technologies Group
55
e4595e20
05.2003
Page 62
21Range of cabinets H98...
e
for details see document x654 / ZH4.2
600
H98T000
2015
300
Door hinged right
H98G600:
Dimensions 600 x 21 10 x 300mm
Materialsteel sheet
ColourRAL7035 light grey
Protection categoryIP40
Installation of the modul
chassis H47E.../H67E...
for details see page 39
H28V000
Doors can be closed with
KABA lock 1057-25
H28V010
H98Z010
H15Z300
Note:
for CE imunity use
protective cover H67Z020
19”
H15Z200
H67Z020
G Free-standing cabinet of steel sheet and door without window
G For large control units or special applications
G Several free-standing cabinets can be combined in a group
G Door hinged right or left
G installation level:
− Rear panel module chassis H67E101/111 and H47E100/110 or
universal bracket G1E010
see page 39
− Pair of side panels H98Z010 per cabinet or group of cabinets
Mechanical modules for H98 cabinet
Free-standing cabinet H98...
H98G600 416128Cabinet 42HU with base
H98T000 416131Door 42HU, hinged at right, without window
H98T020 459415Door 42HU, hinged at left, without window
H98Z010 417606Pair of side panels to H98G600required per cabinet or group of cabinets
H15Z200 459716Manual compartment to H98T..to store system documentation
H67E101 509705Module chassis to H67.. completewith cable ducts and battery support plate
H67E111 509718Module chassis to H67... ’empty’for non-standard applications
H67Z020 496902Protective cover for H67E...if module chassis is built into a 3rd party cabinet (CE confirmity)
H47E100 474885Module chassis to H47.. completewith cable ducts and battery support plate
H47E110 476184Module chassis to H47.. emptyno cable ducts or battery support plate
H15Z300 476197Battery support plate for H47E..., H67E...
H67Z020 496902Protective cover for H67E...
Z3G170476223Mounting accessories for H47E100/110,H67E100for fixing on rear panel (moulded metal section) see page 39
G1E010384276Universal bracket 3HUfor the mounting of accessories
56
Fire & Security Products
Siemens Building Technologies Group
e4595e21
05.2003
Page 63
22Overview 19” accessories
Application of 3rd partycabinets
19”
19” cabinet
H47E100
Z3B180
19”
19” cabinet19” cabinet
H67E101
19”
G2A130
B3Q...
G2A140
G2F031
Z2G030
Modules
19” accessories
Z3B18047620719” adapter set for H47E.../H67E...
Z2G030378198Hinge 19”/6HEconsisting of hinge and spacer profile
G2A130475088Adapter plate 19”/6HEfor AlgoPilot B3Q...
G2A140484228Adapter plate 19”/6HEfor B3R051 / B3Q321 etc.
G2F031409290Front frame 19”/6HEfor printer B2Q191
Fire & Security Products
Siemens Building Technologies Group
57
e4595e22
05.2003
Page 64
23Principle of internal pre-wiring
Module chassis H47E...Module chassis H67E...
Connection cable
Z1I030 short 0.5m
19 cond.
Connection cable
Z1I050 long 0.8m 19 cond.
Connection cable
Z1I020 short 0.5m 9 cond.
Z1I060 short 0.5m 4 cond.
Connection cable
Z1I040 long 0.8m 9 cond.
Terminal block Z1IK020
for direct connection to periphery
Z1I070 long 0.8m 4 cond.
Terminal block Z1IK020
for direct connection to periphery
Modules
Cables, terminals
Z1I020475499Connection cable, 9 cond., 0.5mready-made cables with card holder for H47...
Z1I030475509Connection cable, 19 cond., 0.5mready-made cables with card holder for H47...
Z1I040475512Connection cable, 9 cond., 0.8mready-made cables with card holder for H67...
Z1I050475525Connection cable, 19 cond., 0.8mready-made cables with card holder for H67...
Z1I060525802Connection cable, 4 cond., 0.5mready–made cables with card holder for H47...
Z1I070525815Connection cable, 4 cond., 0.8mready–made cables with card holder for H67...
Z1K020475486Terminal block + card-holder for H47/H67without cable, for direct connection
58
Fire & Security Products
Siemens Building Technologies Group
e4595e23
05.2003
Page 65
24Line modules
There are different line modules for the various detection systems:
Programmable control output for 1 external response indicator in each detector base
allocated to another ZONE
Room 101
Room 102
ZONE 9
False ceiling
allocated to the detector
ZONE 7
Room 103
allocated to the detector
ZONE (Default)
ZONE 5
Room 104
Means of linking for external response indicators
Basic programming
AI external is allocated to the logic detector
ZONE
most frequent application variant
(Default)
synchronous with the detector AI internal
AI extern is allocated to detector in the base
e.g. for detectors in hollow floors or
false ceilings
allocated to another ZONE
AI external is treated as a control output
can thus be allocated to any logic
ZONE or several ZONES
Fire & Security Products
Siemens Building Technologies Group
61
e4595e24
05.2003
Page 68
24.3Detection line ”interactive” Ex
Number of addresses: max. 32, restrictions for certain types of devices 1)
T branches allowed
1 Stub line
non–Explosion
hazard area
the software can not proof wheter or not
Non–Ex–detectors are in the explosion
hazard area
Explosion hazard area
D-Bus max. 32 addresses / 70Ω
E3M171
Dxx115x
Dxx115x
Dxx115x
1) for details see documents e1508 and e1204
SB3
DM115x–Ex
24.4Detection line ”CBA8000/TS9000”
Number of addresses per line: max. 119
4 Loop lines
1
CBA8000/TS9000
DOT1151A–ExDT1151A–Ex
DT1151A–Ex
DOT1151A–Ex
1)
DF1151-Ex
E3M120
2
3
4
CBA-Bus max. 119 addresses / 30Ω
CBA8000/TS9000CBA8000/TS9000CBA8000/TS9000
62
Fire & Security Products
Siemens Building Technologies Group
e4595e24
05.2003
Page 69
24.5Detection line ”AnalogPLUS”
Number of addresses per line: max. 128, restrictions see 1)
All detectors, m anual c all p oints a nd i nput/output m odules w ith i ntegrated l ine s eparator
4 Loop lines
E3M111
24VDC
1
DBZ1197A
DM113x
2
DC1192
3
24VDC
SB3
4
DO1101–Ex
DT1101–Ex
collective
Ex
2)
DF1101–Ex
1) for details see document e1508
2) for details see document e1204
DO113x
DJ1192
DOT113x
DT/DOT/DO113x
DJ1191
DF1191/92
AnalogPLUS-Bus max. 128 addresses / 150Ω
24VDC
DC1192
DO113x
DJ1192
DC1136
CB320A
OH
HI
OP
SynoLINE300C
DC1192
collective detectors
DC1131
1)
DC1134
BFST
Control output for 1 external response indicator in each AnalogPLUS detector base
Room 101
fixed allocation (output active as soon
Room 102
ZONE 7
ZONE 9
False ceiling
Room 103
as the internal LED is flashing)
ZONE 5
Room 104
Fire & Security Products
Siemens Building Technologies Group
63
e4595e24
05.2003
Page 70
24.6Detection line ”MS9i addressing”
The E3M060 enables the integration of existing parts of a system with series
MS9i/MS7i detectors
Number of e lements ( addresses) p er l ine: m ax. 5 0, b ut t his d epends o n t ype o f e lement 1)
Control output for 1 external response indicator in each addressable detector base
Room 101
fixed allocation (output active as
Room 102
ZONE 7
ZONE 9
False ceiling
Room 103
soon as the internal LED is flashing)
ZONE 5
Room 104
64
Fire & Security Products
Siemens Building Technologies Group
e4595e24
05.2003
Page 71
24.7Detection line ”collective”
All detectors on a line have the same collective address (ZONE)
Line termination depending on application by means of transzorb or EOL22 (Ex)
Number of detectors per line:
Connectable types of detectors see compatibility overview (document e1260)
8 Stub lines
DJ1192
1
E3M080
2
3
4
5
DO110x
DM110x
DBZ1197A
No detectors permissible
DM110x
DT110x
F716
mixed detector series
AT50ATAN50
’old’ detector series
DLO1191
DLR11..
DF1191/92
SB2
F910
DT110x
R970
DO110x
DM110x
’new’ detector series
(DS11, MS9, MS716)
line termination : Transzorb 20V
line resistance : max.150Ω
’old’ detector series
(MS712, MS6)
line terminationEOL22
line resistance : max.250Ω
Restriction:
only with E3X100 permissible
see document e1204 and UP e109
DO1101–Ex
DT1101–Ex
DF1101–Ex
Ex
Line termination
EOL22 (Ex)
8
DO110x
Fire & Security Products
Siemens Building Technologies Group
24VDC
DC1192
SB3
for details see document e1204
DO1101–Ex
DT1101–Ex
DF1101–Ex
Ex
1) for details see document e825 for MS6/7/9
e1508 for DS11 collective
Line termination
EOL22 (Ex)
65
e4595e24
05.2003
Page 72
25Control modules
Á
Á
Á
Á
Á
Application of control modules
Activation of fire control installations
(shutting-down ventilation, closing fire dampers etc.)
Activation and monitoring of alarm device
Activation and monitoring of remote transmission equipment
Activation of Mimic Display panels
Overview of the available modules with control outputs
Modules
ÁÁÁÁ
E3X10.
E3G070
E3L020
E3G050
E3G060
K3R072
K3G060
K3I110
1) can also be used as control inputs (e.g. ’acknowledgement’)
2) these inputs/outputs also serve for the activation of the remote transmission equipment
3) for activation of Mimic Display panel, connected to the operating unit B3Q... or K3I050 (no I-Bus module) for details see page 70
4) applicable only with K3R072 Details see page 71
5) programmable
6) LON-Bus module Details see page 73
Monitored control lines
for alarm devices
ББББББ
2
2
6 5)
Driver outputs
programmable
ББББББ
8 + 1
7 1) 2)
16 1)
48 3)
Contact outputs
(volt free)
ББББББ
programmable
8
24 NO contact 4)
16 NO contact 5) 6)
Remote transmission
ББББББ
to remote transmission
equipment
interface
25.1Means of linking
Any statuses of entry nodes can be linked to control ZONES
Normally, only 1 control ELEMENT is contained in 1 control ZONE (= control output)
A user text is allocated to each control ZONE
– active
– switched off
– executed (’Acknowledgem.’)
– fault
AREA
SECTION
ZONE
Digital input
Operating level
Operatable functions:
– switch on/off
– activate/de-activate
Statuses:
– alarm
– info
– switched off
– on detector TEST
– fault
– etc.
’active’
Control
ZONE
E3G050
K3I110
E3L020
E3X10.
E3G070
E3G060
Acknowledgement circuit
not
monitored
monitored
66
Fire & Security Products
Siemens Building Technologies Group
e4595e25
05.2003
Page 73
25.2Control outputs station type CC11
Basic equipment
Basic equipment
CPU
E3X10.
24V
FÜ
1..........8
Z3B171
250VAC 10A
Fire controlinstallations
Driver
Additional control modules according to application
I-Bus
E3L020
DriverDriver
1..........16
Z3B171
250VAC 10A
25.3Control outputs station type CI11
Additional control modules according to application
I-Bus
CPU
B3Q...
E3G070
24V
FÜ
250VAC 10A
Fire control-
installations
1..........7
Z3B171
Driver
E3L020
DriverDriver
1..........16
Z3B171
250VAC 10A
Z1I030/050
E3G050
1.........8
30V
E3G050
1..........8
30V
DC 1A
DC 1A
E3I040
Converter
I-Bus/LON
LON-Bus
K3I110
1......16
30VDC 1A
E3I040
Converter
I-Bus/LON
LON-Bus
K3I110
1......16
30VDC 1A
E3G060
1..........6
E3G060
1..........6
max. 24V/2A
(max. 4A/E3G060)
max. 24V/2A
(max. 4A/E3G060)
Z1I030/050
E3I040
K3I110
E3X1xx
card holder
included in cable
set Z3I350
E3L020
Z1I030/050
E3G070
E3G060
E3G050
Fire & Security Products
Siemens Building Technologies Group
67
e4595e25
05.2003
Page 74
25.4Control outputs remote station type CT11
B3Q...
! Details mounting E3I040 see docu d1393
E3I040
Z1B070
K3I110
I-Bus
E3I040
converter
I-Bus/LON
LON-Bus
K3I110
1......16
30VDC 1A
Modules
E3X101546674Master modulefor alarm devices and control outputs
E3X102629025Master module””
E3X103629038Master module””
B3Q...Control terminal AlgoPilotall variants of the AlgoPilot see page 42
E3G070546661Control module ”universal”””
E3L020546645Control module ”Driver”16 control inputs or outputs
E3I040499310LON moduleConverter between I-Bus and LON-Bus
Z1B070A5Q00001720 Mounting accessory for E3I040essential for mounting E3I040 in housing H28G200
K3I110528812LON-I/O card16 programmable in-/outputs
E3G050460255Control module ”Contacts”8 control output contacts
E3G060542539Control module ”Monitored”6 monitored control lines for alarm equipment
Z1I030475509Connection cable, 19 cond., 0.5m1 of each per E3L020/E3G050/60/70 (in cabinet H47...)
Z1I050475529Connection cable, 19 cond., 0.8m1 of each per E3L020/E3G050/60/70 (in cabinet H67...)
Z3B171484383Relay module 1x 250V
AC/10Ato switch from external voltage
68
Fire & Security Products
Siemens Building Technologies Group
e4595e25
05.2003
Page 75
25.5CPU-overlapping controls
all-AREA
CPU
1
CC/CI
single-AREA
CTCT
C-Bus
CC/CI
CPU
CPU
23n
CC/CI
gateway
CPU
CK
CC/CI
A1
A2A3A4
= AREA
initiating data point
control ZONE/ELEMENT
control device
Limitation: see chapter 7.1.3
A5A6A7A8A9A10A11A12A..A..A..A..
must be within the same CPU
Fire & Security Products
Siemens Building Technologies Group
69
e4595e25
05.2003
Page 76
25.6Mimic Display panel outputs station type CT11 and CI11
LED flat cable F50F410
cable length 1m, 24 red LEDs
LED flat cable F50F410
Details see document e1260
1
cable length 1m, 24 red LEDs
K3R072
48
AlgoPilot B3Q...
AlgoPilot B3Q...
24V
F12A100
or
F12A470
Parallel branching permissible
24V
Data bus
Z3I530
(Adapter)
max.1000m
(not monitored)
1
K3R072
48
K3R072:
G short circuit-protected outputs
G output for local buzzer and LED operation
G inputs for button ’buzzer switch-off’ und ’lamp test’
G only suitable for the activation of LEDs
G outputs can only be allocated the statuses from one logical node
G max. 24 devices, however max. 8 addresses
Mimic Display panel
LED flat cable F50F410
LED flat cable F50F410
Mimic Display panel
Mimic display panel housing
K3R072
Dimensions:
104 x 200 x 43mm
Short-circuit proof in-/outputs only
for inside housing application
LED 1....24
wires 49+50 for ’LED operation’
K3R072
Z3I520
LED 25....48
wires 49+50 unused
Key ’Switch-off buzzer’
Key ’Lamp test’
Buzzer
AlgoPilot
max. permissible length
of the data bus 1000m
These in-/outputs can be in parallel with
other K3R072 if located in same cabinet
Modules
K3R072528605Mimic Display activation
Z3I520484969Cable set for K3R072comprises 12 cables (2-wire with connector, length=0.5m)
F50F410 529141LED flat cable for K3R07250-wire, 24 red LEDs, cable length 1m
Z3I530484972Adapter for K3R072/B3R051to adapt flat cable to terminals
F12A100 495275Flat cable Micro 12-pin, 0.4mfrom AlgoPilot B3Q... to K3R072/B3R051
F12A470 495288Flat cable Micro 12-pin, 1.5mfrom AlgoPilot B3Q... to K3R072/B3R051
70
Fire & Security Products
Siemens Building Technologies Group
e4595e25
05.2003
Page 77
25.7Relay outputs station type CT11 and CI11
Flat cable supplied with K3G060
1
48
K3R072
max. 24 units,
however max.
8 addresses
for details see document e1260
1
48
K3R072
max. 24 units,
however max.
8 addresses
1)
AlgoPilot B3Q...
AlgoPilot B3Q...
24V
F12A100
or
F12A470
Parallel branching permissible
24V
Data bus
Z3I530
(Adapter)
max.1000m
(not monitored)
1
24 outputs
max. 30V/1A
K3G060K3G060
24
1
24 outputs
max. 30V/1A
24
Flat cable supplied with K3G060
)/*
1
24 outputs
max. 30V/1A
K3G060K3G060
24
1
24 outputs
max. 30V/1A
24
)/*
External potential
(switchable via jumper X1......X24)
1)
1)
K3G060:
G 2 K3G060 can be connected to each K3R072
G 24 volt-free relay-make contact
G Contacts not monitored
G Contacts can be individually connected via jumper to externally supplied V+ or V– potential
Housing supplied by customer
24 Relay outputs
K3G060
K3R072
K3G060
24 Relay outputs
Modules
K3R072528605Mimic Display activation
K3G060528786Relay cardoption to K3R072
Z3I530484972Adapter for K3R072/B3R051to adapt flat cable to terminals
F12A100 495275Flat cable Micro 12-pin, 0.4mfrom AlgoPilot B3Q... to K3R072/B3R051
F12A470 495288Flat cable Micro 12-pin, 1.5mfrom AlgoPilot B3Q... to K3R072/B3R051
Fire & Security Products
Siemens Building Technologies Group
71
e4595e25
05.2003
Page 78
26LON-Bus devices
26.1Features
Activation via local communication Bus ’LON’
4 different types of device available
B3Q580= Text display terminal
B3Q590/595 = Text control terminal
K3I050= LON/Mimic Display converter
K3I110= LON I/O card
Connection via I-Bus/LON module E3I040 (converter between I-Bus and LON-Bus)
the function ’LON-Bus’ is possible once per station type ’CI/’CT’’ and ’CC’
max. 32 devices per LON-Bus (device type can be mixed as required)
monitored two-wire-Bus without loop line function
all devices require a separate feed line from E3I040
Wiring of the LON-Bus
as ’stub line’ up to 1000m (without T-branches)
as ’free topology’ up to 500m (length of line to all devices added)
with ’MICC’ : as ’stub line’ .....700m / as ’free topology’ .....300m
with special cable (Belden 85102 or 8471) and as ’stub line’ up to 2700m
only possible via twisted line (10 turns per meter)
CPU-overlapping functions possible
B3Q59x: bottom three LEDs are pluggable. Allows application with different LED colour.
26.2LON-Bus as stubline
E3X10.
or
B3Q...
Z1I030/050
E3I040
E3I040
Z1B070
LON-Bus
I-Bus
K3I110
E3I040
max. length of LON-Bus 1000m
24VDC
K3I050B3Q580
24VDC
Details see
K3R072page 70 or
B3R051page 48
Data bus
(not monitored)
K3R072
or
B3R051
CC11
CI11
CT11
B3Q590/
595
K3R072
or
B3R051
72
Fire & Security Products
Siemens Building Technologies Group
e4595e26
05.2003
Page 79
26.3LON-Bus as free topology
E3X10.
or
B3Q...
E3I040
LON-Bus
I-Bus
K3I110
26.4LON/Mimic Display p.c.b K3I050
G allows connection of Mimic Display
p.c.bs K3R072 or
parallel indicator units B3R051
(max.24 units, however max. 8 addresses)
G various local inputs/outputs
Input key ’buzzer switch-off’
The functions of the
Input key ’lamp test’
in-/outputs refer on the
K3R072 resp. B3R051
Output local buzzer
Output LED ’operation’
Dimensions: 106 x 200 x 14mm
K3I050
max. length of LON-Bus 500m
B3Q580
24VDC
K3I050
24VDC
Details see
K3R072page 70 or
B3R051page 48
50cm
Data bus
to K3R072/B3R051
Z3I530
Lon-Bus 24V
Z3I520
B3Q580
(not monitored)
K3R072
B3R051
K3I050
CC11
CI11
CT11
B3Q590/
595
or
K3R072
or
B3R051
H23G230
Z3B230
26.5LON I/O card K3I110
G Input/output card
– 16 programmable monitored control
inputs
– 16 programmable control outputs
Dimensions: 122 x 220 x 14mm
H23G230
K3I110
K3I110
73
Fire & Security Products
Siemens Building Technologies Group
e4595e26
05.2003
Page 80
26.6Indicator devices B3Q580 and B3Q590/595
0
Both devices have identical dimensions
G
G Recessed mounting see page 51
H23G230
H23G23
B3Q580
FunctionB3Q580 Text display terminalB3Q590/595 Text control terminal
LCD 2x40 characters backlight yellow
Alarm event indicatorallZONES from 1...4 selectable SECTIONSallZONES per station (not selectable)
Fault event indicatorselectable (yes/no via AlgoWorks)selectable (yes/no via AlgoWorks)
Selectable operating mode14 (selectable via AlgoWorks)14 (selectable via AlgoWorks)
Buzzer, can be silenced
3 programmable LEDs
Function key ’Onward switching’
Function key ’Acknowledge’ / ’Reset’
Key switch for operating access
For installation in housing H23G230
Slide-in inscription strips
Operating voltage9...45VDC9...45VDC
Current consumption at 24VQuiescent: 20mA / max: 100mAQuiescent: 18mA / max: 120mA
(also serves to silence buzzer + lamp test) (also serves to silence buzzer + lamp test)
B3Q590 (Nordic lock)
B3Q595 (KABA lock)
B3Q590 = Nordic
B3Q595 = KABA
Modules
E3I040499310LON moduleConverter between I-Bus and LON-Bus
K3I050496766LON/Mimic Display converterInterface between LON-Bus and Data Bus for K3R072 or B3R051
K3I110528854LON I/O card16 programmable control in-/outputs
B3Q580496177Text display terminal
B3Q590496180Text control terminal with Nordic lock
B3Q595534110Text control terminal with KABA lock
H23G230 475091Plastic housing
Z3I520484969Cable set to K3R072comprises 12 cables (2-wire with connector, length=0.5m)
Z3I530484972Adapter for K3R072/B3R051to adapt flat cable to terminals
Z3B230559001Support plate-setfor K3I050 in H23G230
Z1B070A5Q00001720 Mounting accessory for E3I040for mounting in housing H28G200
Inscription sets available(if no inscription strips are available –> use templates from document e6516)
Z5B710510448Inscription set ’Nordic’for B3Q580 (S, N, FIN, DK)
Z5B720510451Inscription set ’Europa’for B3Q580 (UK, GER, F, I)
Z5B730510464Inscription set ’Nordic’for B3Q590/595 (S, N, FIN, DK)
Z5B740510477Inscription set ’Europa’for B3Q590/595 (UK, GER, F, I)
Z5B750510574Inscription set ’CH’for B3Q590/595
74
Fire & Security Products
Siemens Building Technologies Group
e4595e26
05.2003
Page 81
27Gateway
27.1Main features
Connection C-Bus network DMS / LMS via V28 interface (RS232)
Conversion of C-Bus CERLOOP/CERBAN
For bridging distances of up to 1000m (double V28 modem integrated)
For distances >1000m use FSK/PSK modem
Per C-Bus network are several gateway possible, see chapter 7
Install preferably in the fire detection system control unit cabinet
Can also be autonomously operated with its own power supply
(E3C011 + B2F020 + batteries)
For the loop node CERLOOP, an additional hardware is necessary (K1H021...)
á Check outline quantities according chapter 7.3
CT11CT11
CC11
CI11
C-BUS
I-BUS
Line–Control–
Detector
module
CK1142/43
CERLOOP/
CERBAN
DMS/LMS
CERBAN (V28)
E3H020
K1H021
CERLOOP (V28)
K1D...
Note:
Each ’CC’/’CI’ control unit must be assigned a DMS location number (via programming in AlgoWorks)
* any DMS location numbers according to document e4075
E3H020
Fire & Security Products
Siemens Building Technologies Group
Z1I......Connection cable with card holderfor H47E... Z1I020/030; for H67E... Z1I040/050
CKQ00xxx A5Q00003096 EPROM set for CK1142software for C-Bus CERLOOP/CERBAN
CKW00xxx (OSS)EPROM set for CK1143software for C-Bus CERLOOP/CERBAN
Z3S080504836RAM set (2x 256Kx8Bit)for CK1142 required 4 sets
Z3S070504823RAM set (2x 512Kx8Bit)for CK1142 required 2 sets, for CK1143 required 4 sets
K1D081463773Dual modem p.c.b. V28for application with CERLOOP
K1D121470601Dual modem p.c.b. FSK/PSKfor > 1000m between E3H020 and DMS7000 (CERLOOP)
K1D140470614Modem p.c.b. FSK/PSKfor > 1000m between E3H020 and DMS7000 (CERBAN)
K1H021452234Communication p.c.b.for application with CERLOOP
Z1K050495220Card holderfor mounting K1D... / K1H021
F14A320 319652Flat cable 14-wire, 0.5mfor connection of K1H021 K1D... (CERLOOP)
F14E320 451439Y flat cable 14-wire, 0.5mfor connection of E3H020 K1H021 / E3H020 K1D...
–463498Solid-state relayessential with:
– K1D121 2x
– K1D081 4x
K1D081 (V28)
or
K1D121 (FSK)
A1/2
DMS / LMS
Batteries
AX12..
I-Bus
Note:
The E3H020 is factory side equipped with 8 RAMs (8x 256Kx8Bit) details see document e1260
76
Fire & Security Products
Siemens Building Technologies Group
e4595e27
05.2003
Page 83
28Remote transmission
Most fire detection systems are linked to a remote transmission system. Therefore in
case of alarm (alarm stage 2) the fire detection system must initiate the remote trans-
mission device (RT-device).
Remote transmission device
located in cabinet of control unit
required space depends on the type of remote transmission device
powered by 24VDC of the fire control unit
single channel (alarm + fault) or multi channel (several alarm channels)
disabling/enabling via AlgoPilot
Interfacing
via output contacts and special control in-/outputs of the E3X10. or E3G070
via remote transmission interface E3G091 when using as ’multi channel’
via VdS-module E3L030 to ’Hauptmelder’ (ÜE) (Germany)
also CPU-overlapping initiation possible (several CPUs tied to same RT-device)
K2
RT-device
E3X10./E3G070
Q1.........Qx
Interfacing via E3X10.
E3X10.
CPU
24V
Interfacing via E3G091
K2
24V
I-Bus
E3....
CC11
Interfacing via E3G070
AlgoPilot
B3Q... (CPU)
alarmfaultalarmfault
K2
RT-device
Interfacing via E3L030
CPU
I-Bus
E3G070
24V
CI11
I-Bus
E3L030
E3G091
RT-device
Fire & Security Products
Siemens Building Technologies Group
CC11
CI11
CC11
CI11
ÜE
77
e4595e28
05.2003
Page 84
28.1CPU-overlapping remote transmission
all-AREA
C-Bus
CC/CICC/CICC/CI
CPUCPUCPU
single-AREA
CTCT
gateway
CK
Area 1Area 2Area 3Area 4
common RT–device
for all AREAS
within CPU
initiating data point
control ELEMENT ’RT’
RT-device
– also functions via emergency operation circuit
common RT-device for several CPUs
78
Fire & Security Products
Siemens Building Technologies Group
e4595e28
05.2003
Page 85
29Extinguishing
29.1Main features extinguishing SECTION
Extinguishing section consists of:
Control module E3G080 (I-Bus module)
Operating unit B3Q440 ’Extinguishing’
option: monitoring card K5L020 for monitoring and control of additional magnetic ext.
valves
E3G080 is designed for one extinguishing SECTION
E3G080
C-Bus
E3X10.
Z3B171
CT11
E3G080
max. 600m 5 wires ø 0.8mm
Line and device monitored
B3Q440
CC11
I-Bus
K5L020
(Option)
E3M...
AlgoPilot
B3Q...
H23G230
E3G070
Z3B171
I-Bus
Z1I030/050
E3G080
details see document e1260
E3G080
K5L020
K5L020
(option)
Z1K030
CI11
E3M...
LON-Bus
24V
ST*
B3Q440
Extinguishing SECTIONExtinguishing SECTION
DM1103
DM1104
ST*
*ST =
–Ventilation switch-off
–Door magnet
–etc.
LON-Bus
24V
B3Q440
DM1103
DM1104
Manual release
– use yellow collective manual call point DM1103A (or 04) with DMA1192-AC
Modules for extinguishing
E3G080475949Control module ”Extinguishing”required for each extinguishing SECTION
E3G110504991Emergency operation linkOption for control module ”Extinguishing” E3G080 (see chapter
B3Q440475952”Extinguishing” operating unit max. 4 possible (including inscription set ’english’)
Fire & Security Products
Siemens Building Technologies Group
for other languages –> use Template from document e6516
79
e4595e29
05.2003
Page 86
29.2Option emergency operation link E3G110
ИИИИИИИИИИИИИИИИИИИИИИ
ИИИИИИИИИИИИИИИИИИИИИИ
ИИИИИИИИИИИИИИИИИИИИИИ
Á
Á
Á
Á
Á
Á
Á
Á
Á
Á
Á
Á
Á
Á
Á
Á
Á
Á
Á
Á
Á
Á
Á
Á
Á
Á
Enables automatic activation of extinguishing through interlinked areas even if the main CPU malfunctions.
The detectors in the extinguishing SECTION must be distributed over 2 independent detection lines.
CPU
E3X10.
or
B3Q...
K1
E3G080
K1
1......4
24/5V
I-Bus
E3G110
K1
ST1ST8
ST10
E3M071
K1
CC11, CI11
E3M071
K1
ST10
Z1I030/050
Manual activation
DM1103/04
B3Q440
Note: Only E3M060 (MS9i), E3M071 (interactive), E3M171 (interactive Ex),
E3M080 (collective) and E3M111 (AnalogPLUS) are equipped with connector «ST10»
29.3Key data
Sector valve ’delayed’
БББББББББББББ
БББББББББББББ
Main valve ’not delayed’
(activation of pneumatic circuit)
БББББББББББББ
Alarm horn
БББББББББББББ
Illuminated warning panel
БББББББББББББ
Manual actuation
Automatic activation
БББББББББББББ
БББББББББББББ
БББББББББББББ
Stop/blocking button
Signal contact ’Extinguishing agent leak’
Signal contact ’Extinguishing blocked’
Signal contact ’Extinguishing activated’
On-site operation
БББББББББББББ
БББББББББББББ
Fire control installation
Special features
БББББББББББББ
БББББББББББББ
БББББББББББББ
– activation delayed 0..240s
– permissible operating time 0..240s or until reset
БББББББББББББББББ
– monitored line
– line can be adjusted to sector valve
БББББББББББББББББ
– permissible operating time 0..240s
– monitored line
– line can be adjusted to main valve
БББББББББББББББББ
– can be switched off via extinguishing operating unit or control unit
– monitored line
– programmable actuating mode staedy/pulsating
БББББББББББББББББ
– can be switched off separately or is active until reset
– monitored line
– programmable actuating mode staedy/pulsating
БББББББББББББББББ
– direct to E3G080
– also functions with ’Emergency operation’ control unit
– line monitored
– via detector control unit, can be parameterized upon alarm
БББББББББББББББББ
alternative from:
–detectors in the same ZONE
БББББББББББББББББ
–detectors in different ZONES
–detectors in the same or in different ZONES
БББББББББББББББББ
– all detector systems can be installed (interactive / AnalogPLUS / collective)
– separate monitored line
– separate monitored line
– separate monitored line
– separate monitored line
– by means of ’Extinguishing’ operating unit B3Q440
– use recommended, but not essential
БББББББББББББББББ
– max. 4 operating units possible
БББББББББББББББББ
– via LON data bus with monitored line
– length of line up to 600m
– via control output control unit
– autonomously functioning I-Bus module
– integrated emergency operation function
БББББББББББББББББ
– parameters set via AlgoWorks
БББББББББББББББББ
– user functions stored on E3G080
– several extinguishing SECTIONS mutually interlocking
БББББББББББББББББ
– automatic calibration function
Interactive
detectors
E3G110
80
Fire & Security Products
Siemens Building Technologies Group
e4595e29
05.2003
Page 87
29.4Typical extinguishing system
Á
Á
Á
Á
Á
The requirements as regards monitoring depend greatly on the extinguishing agent
used and the structural quality of the mechanical hardware used
The system must comply with local regulations
7
13
3
Pipe network
with nozzles
10
1
6
9
8
5
4
2
Means of activation
Required functions
Pos.
Á
J essential
j recommended or necessary according to the mechanical hardware used or the local regulations
Function
1
Electrical activation
2
Pneumatic activation
3
Electronic alarm horn
ББББББББББББ
4
Pneumatic alarm horn
5
Illuminated warning panel
6
Manual actuation DM1103/04
7
Autom. ’multi-detector’ actuation
8
On-site operation
9
Stop or blocking button
10
Signal contact ’activated’
11
Signal contact ’Extinguishing agent leak’
12
Signal contact ’mechanically blocked’
13
Fire control installation
Details
Sector valve ’delayed’
Main valve ’undelayed’
possibly several devices according to
ББББББББББББ
background noise level
e.g. operated by means of control
outside each door
special button (yellow)
detector in ZONE type ’Extinguishing’
operating unit B3Q440
special button or door lock contact
electric pressure switch
cylinder weighing device or pressure
gauge
mech. blocking of battery of cylinders
door magnet etc.
12
Extinguishing agent
11
FM200
ÁÁ
CO
2
J
J
J
J
J
j
j
j
j
j
J
J
J
Á
J
J
J
J
j
j
j
j
j
j
Fire & Security Products
Siemens Building Technologies Group
81
e4595e29
05.2003
Page 88
30Printer interface
30.1Features
Provided with station types CT11, CI11, CC11
Designed for Cerberus printer or commercially available printer with ISO or EPSON
character set
Additional hardware required for level adaptation according to application
Printer B2Q191 can be connected direct (when mounted inside cabinet)
The printer can be individually switched on/off via the operating unit
Always allocated to all existing AREAS for the station used
Individual parameterization for each printer interface
The e vent m emory c an b e p rinted o nly i f t he p rinter i s c onnected t o a station CI11 or CT11
30.2Application variant CT11
AlgoPilot B3Q...
ST2
C-Bus
AlgoPilot B3Q...
ST2
C-Bus
F20A020
24VDC
(9...36V
F20A410
max. 1m
24VDC
DC)
(TTL)
I-Bus
ST1
RS232
max.1000m
B2Q191
K2
I-Bus
B2Q191
A3
K2
E3I020
ST2
K3
or
CT11
CT11
F20A020
B3Q...
F20A410
in cabinet H26/H28
B3Q...
E3I020
ST2
Z1B020
to printer
Requirement:
The printer B2Q191 must be in the same cabinet as the
operation unit B3Q... or in an immediately adjacent cabinet
With this application:
Ground wire to be removed from ’K3-5’ and connected to
chassis ground (otherwise results in ground fault)
82
Fire & Security Products
Siemens Building Technologies Group
B2Q191
in cabinet H26/H28
e4595e30
05.2003
Page 89
30.3Application variant CC11
CC11
to printer
E3X10.
C-Bus
E3X10.
C-Bus
ST2
(9...36VDC)
ST2
F20A020
24VDC
(TTL)
F20A410
max. 1m
24VDC
I-Bus
ST1
RS232
max.1000m
B2Q191
K2
I-Bus
A3
B2Q191
K2
E3I020
Z1I030/050
X2
E3I020
or
K3
E3X10.
F20A020
CC11
Requirement:
The printer B2Q191 must be in the same cabinet as the
main CPU (E3X10.) or in an immediately adjacent cabinet.
With this application:
Ground wire to be removed from ’K3-5’ and connected to
chassis ground (otherwise results in ground fault)
E3X10.
Modules
B2Q191484888Logging printer 9...36VDC
E3I020460239RS232 modulelevel adaptation HCMOS RS232
Z1I030475509Connection cable 19 cond. with card holder, 0.5malso for internal wiring in cabinet H47...
Z1I050475525Connection cable 19 cond. with card holder, 0.8malso for internal wiring in cabinet H67...
Z1B020475907Mounting accessoriesto mount E3I020 at the rear of AlogPilot B3Q...
F20A020 476317Flat cable ’Micro’ 20 cond., 0.165m
F20A410 495327Flat cable ’Micro’ 20 cond., 1m
F20A410
to printer
B2Q191
Fire & Security Products
Siemens Building Technologies Group
83
e4595e30
05.2003
Page 90
30.4Application variant CI11
AlgoPilot B3Q...
ST2
C-Bus
AlgoPilot B3Q...
ST2
C-Bus
F20A140
24VDC
DC)
(9...36V
F20A140
24VDC
(9...36VDC)
I-Bus
ST1
RS232
max.1000m
B2Q191
K2
I-Bus
ST1
RS232
max.1000m
B2Q191
K2
E3I020
X2
K3
E3I020
X2
K3
or
or
CI11
CI11
to printer
Z1K030
to printer
E3I020
in cabinet H38
F20A140
Z1I030
in cabinet H47
F20A140
B3Q...
B3Q...
E3I020
Modules
B2Q191484888Logging printer 9...36VDC
E3I020460239RS232 modulelevel adaptation HCMOS RS232
Z1K030484231Terminal block+ card holderto mount E3I020 on a module space in H38...
Z1I030475509Connection cable 19 cond. with card holder, 0.5malso for internal wiring in cabinet H47...
Z1I050475525Connection cable 19 cond. with card holder, 0.8malso for internal wiring in cabinet H67...
F20A140 496863Flat cable ’Micro’ 20 cond., 0.650m
84
Fire & Security Products
Siemens Building Technologies Group
e4595e30
05.2003
Page 91
30.5Logging printer B2Q191/B1Q101
Logging printer for event logging
Integrated paper take-up reel unit
Thermo-matrix printer
Interface and printer monitored
for further details see document e1260
H-cabinet
B2Q191
H28G200
H28T020
B1F120
B1Q101
B2Q191
B2Q191
19” free-standing cabinet
G2F031
B2Q191
G2F031
H28V000/010
Printer with its own power supply
Z1K040
in cabinet H28, without battery
Modules
B2Q191484888Logging printer 9...36VDC
B1F120495233Converter 230VAC –> 24VDC 3A (...140VA)
H28G200 409944Cabinet base 520 x 300 x 70mm
H28T020 410564Cover to H28G200
G2F031409290Front frame 19”/6HUfor the installation of the printer in the 19” cabinet
H28V000 379582Mounting adapters for 19” adaptation 6HUto G2F031
H28V010 379566Hinge for G2F031 / G2A130to G2F031
Z1K040490665Card-holderfor mounting B1F120 on H28T020 (dismantle card holder)
B1Q101504580Logging printer 19” / 3HE, 9...36V
Z3B040379249Paper take-up device (Option for B1Q101)
–379977Spare paper rolls (4 pieces)
Fire & Security Products
Siemens Building Technologies Group
DConly for the installation in 19” cabinet (see document e1510)
85
e4595e30
05.2003
Page 92
31Paging interface
31.1Features
The paging interface card K3I090 is a universal module, and is used to analyse the data
sent from a control unit to its printer output and transmit these data in ESPA 4.4.4 format
to the paging system.
The optional printer is connected to the paging interface card. If a printer is available, the
data are passed on to the printer direct. The interconnected paging interface card is invisible for the control unit and the printer.
The paging interface card analyses the printing data according to defined rules and character strings at a certain position. The rules are stored in the paging interface card. If a
character string is correct, the contents of the print message are edited for pager display
or passed on to the paging system unchanged.
Details see document e1669
86
Fire & Security Products
Siemens Building Technologies Group
e4595e31
05.2003
Page 93
32Power supply
Concept
The power supply for the CS1140 fire detection system consists of:
Converter(mains voltage system voltage 29,6V)
Battery charging unit(integrated in E3X10. or by means of E3C011)
Batteries (lead)(capacity as required)
Special functions
automatic battery load test
Battery charging characteristic can be programmed according to make
Application
Determine required battery capacity individually see page 91
Protection of mains lead only in special cases see page 95
max. 42Ah per battery charging unit ( > 42Ah = auxiliary power supply)
Parallel operation of several battery charging units possible
Battery lead without EMI-protection (battery cannot be mounted separately)
32.1Power supply for the control unit
CC11 Battery charging unit is integrated in the E3X10. master module
CI11 Battery charging module E3C011 required
– battery charging unit contained in E3X10.
– is one of the max. 16 I-Bus modules
Mains
CC11
Batteries
TF*
AX12..
Battery charging unit
29,6V
E3X10.
* TF = Temperature sensor for battery temperature monitoring
40...220VA
I-Bus
B2F020
CI11
29,6V
AlgoPilot
B3Q...
B2F020
40...220VA
Mains
E3C011
I-Bus
Batteries
AX12..
TF*
Fire & Security Products
Siemens Building Technologies Group
87
e4595e32
05.2003
Page 94
32.2Auxiliary power supply
Auxiliary batteries for the basic power supply:
24V
C-Bus
CT11
Mains
Basic emergency power supply1st extension2nd extension3rd extension4th extension
1
Batteries
AX12..
TF*
Battery charging
B2F020
max. 1x E3C011 with battery set as an addition
Additional batteries with auxiliary power supply:
max. 3 battery sets per B2F020 possible
Mains
25
TF*
E3C011
Batteries
AX12..
B2F020
Batteries
TF*
E3C011
3
AX12..
TF*
4
Batteries
AX12..
Batteries
TF*
E3C011E3C011
unit
E3X10.
I-Bus
CC11
Monitoring via I-Bus or separate HW monitoring path
AX12..
– separate battery charging unit
– as regards ”battery charging” identical to E3X10.
– I-Bus module
Auxiliary power supply without battery e.g for door magnets
* TF = Temperature sensor for battery temperature monitoring
for details concerning auxiliary power
supply see also pages 34 – 40
Mains
CC11
I-Bus
B2F020
40...220VA
Batteries
TF*
Battery charging unit
29,6V
AX12..
E3X10.
B1F120
...140VA
max. 3A / 24VDC
Door magnets
Modules
B1F120495233Converter 115/230VAC 24VDC 3A (...140VA)only usable for supply of door magnets etc.
B2F020470588Converter 115/230V
E3C011505479Battery charging unit
E3X102629025Master module1MBx8Bit RAM
E3X103629038Master module2MBx8Bit RAM
AX1201225487Battery 12V / 27Ahcapacity based battery make ’ALARMCOM’ (FIAMM)
AX1209462936Battery 12V / 42Ahcapacity based battery make ’ALARMCOM’ (FIAMM)
AX1210475570Battery 12V / 15Ah
Mains protection elements (surge protector and mains filter) see page 95
AC 29,6VDC 6A (...220VAC)
88
Fire & Security Products
Siemens Building Technologies Group
e4595e32
05.2003
Page 95
32.3Operation with power supply from control unit
from CC11 operating unit is connected to E3X10.
from CI11 operating unit is connected to AlgoPilot B3Q...
CT11CT11
Output 1
Output 2
+ / – / Earth
CC11
Output 1
Output 2
+ / – /Earth
24V / 2A24V / 2A
E3X10.
Note: A 2nd supply output is only necessary for operating units which must comply with EN54 (at least 1 operating unit per system)
I-Bus
AlgoPilot B3Q...
I-Bus
32.4Operating unit with autonomous power supply
for AlogPilot B3Q... control terminals installed at a considerable distance
operating unit and power supply can be installed in H38 cabinets see page 47
Mains
CI11
C-Bus
AlgoPilot B3Q...
* TF = Temperature sensor for battery temperature monitoring
29,6V
B2F020
I-Bus
E3C011
Batteries
AX12..
TF*
CT11
89
Fire & Security Products
Siemens Building Technologies Group
e4595e32
05.2003
Page 96
32.5Power supply for remote transmission equipment and accessories
with CC11 Equipment is connected to E3X10.
with CI11 Equipment is connected to E3G070
CC11
E3X10.
other equipment
(e.g. printer)
I-Bus
RT: 24V / 2ARes: 24V / 2A
Cable set Z3I390
required
RT
RT = Remote transmission
AlgoPilot B3Q...
for RT:
Cable set Z3I390
required
I-Bus
Modules
B3Q.........Control terminal AlgoPilotall variants of the AlgoPilot see page 42
E3X101546674Master moduleEPROM and RAM separately
E3X102629025Master moduleFlash-ROM and 1MB-RAM equipped
E3X103629038Master moduleFlash-ROM and 2MB-RAM equipped
E3G070546661Control module ’universal’for alarm devices and control outputs
E3C011505479Battery charging unit
B2F020470588Converter 115/230V
Z3I390475729Cable set ”Remote transmission CH”
AX1201225487Battery 12V / 27Ah
AX1209462936Battery 12V / 42Ah
AX1210475570Battery 12V / 15Ah
AC 29,6VDC 6A
E3G070
24V / 0.63A
24V / 0,63A
Remote transmission
or other equipment
(e.g. printer)
CI11
90
Fire & Security Products
Siemens Building Technologies Group
e4595e32
05.2003
Page 97
33Emergency power supply
Configuration CS1140
Quiescent
33.1Specifying battery capacity
Battery rated capacity
The battery rated capacity is based on the discharge over a period of 20 hours
Faster discharge causes a loss of capacity:
discharge over 12-hour period:9% loss (K = 1.1)
Ageing of battery
With increasing age, the battery suffers a loss of capacity
Allow a safety factor for ageing
(Total quiescent current × 1.25 or battery capacity × 0.8)
> 24h in conformity with DIN VDE 0833, part 2, no safety factor is necessary
Calculation
Battery capacity must be calculated individually!
Formula: Ah = A × h × 1.25 (poss. × K)
Ah = Battery capacity in Ah
A= The sum of the quiescent current for all modules
h= Required operating period in hours
1.25 = Safety factor for ageing
K= Capacity loss if discharge is over considerably less than 20 hours
– equipped with 1 operating unit AlgoPilot B3Q...
– discharge over a 12-hour period, 9% loss of capacity taken into account
– factor 1.25 for ageing taken into account at 12h and 24h (72h without safety factor)
– without remote transmission equipment
– only quiescent current taken into account
– quiescent current for additional battery charging module E3C011 taken into account (where necessary )
704mA
924mA
Battery capacity requirement for
12h24h72h
11,6Ah21,1Ah50,6Ah
15,2Ah27,7Ah66,5Ah
Fire & Security Products
Siemens Building Technologies Group
91
e4595e33
05.2003
Page 98
33.3Quiescent current table
quiescent current when on battery operation (24V)
as basis for individual calculation of emergency power supply
the current for the 5V supply is included in these values
ModuleQuiescent current at 24VDC (typical)Additional current with alarm condition
E3I04015mAwithout external 24V load0
K3I05015mA+0mAor 4mA per activated LED
K3I09050mA0
K3I11024mAmax. 184mA all Rel. activated incl. service LED
1) only valid for device with APMK = 1 / IMK = 1 (multiply value for devices > 1). Example DC1151: 0,5mA x 12 = 6mA
00
0only active for emergency operation and
alarm
115mA(=50mA + 0,5mA per D-Bus device) 1)
(without external 24V load)
70mAwith 32 detectors (=50mA without detectors
+ 0,5mA) per D-Bus device 1)
210mA(=50mA + 0,31mA per D-Bus device) 1)
(A+ without external 24V load)
227mA247mA with 82kW terminated
+ 23mAper activated control line, without
external load
+ 15mAper activated channel for emergency
operation
0
0
0
+ 120mAper line in alarm condition
+2mAper activated LED
0per activated relay
+ 10mAper activated relay
+ 0,5mAper input with closed contact
33.4Available emergency power supply batteries
AX1201225487Battery 12V/27Ahcapacity based on battery make ’ALARMCOM’ (FIAMM)
AX1209462936Battery 12V/42Ah ”
AX1210475570Battery 12V/15Ah
AX1212484325Battery 12V/12Ah
92
Fire & Security Products
Siemens Building Technologies Group
e4595e33
05.2003
Page 99
34Alarm concept
The alarm concept must be worked out individually for each system
The important thing is to pass on the alarm message quickly to the appropriate group of
recipients
The requirements vary between
«Discreet alerting» of the reconnaissance squad, e.g. via staff paging system
«Alarm / evacuation» for people familiar with the location
«Alarm / evacuation» for people unfamiliar with the location
«Area evacuation», e.g. building storey
34.1Cerberus alarm concept (CAC)
The Cerberus alarm concept prevents the unnecessary turnout of the fire department
for minor incidents
The CAC is based on an alarm organization involving the presence or absence of personnel:
Presence of operating personnel or ”Day”
Absence of operating personnel or ”Night”
The response of the operating personnel is monitored by two independent time circuits
(V1 and V2) monitored
The CAC is an integrated part of the CC11/CI11 control unit . The required parameters
can be entered via the user functions
Alarm
event
Remote alarm
Principle of the Cerberus alarm concept
During the ”Day” operating mode, if an alarm is activated its source is located and the
decision is taken ”Emergency” or ”Minor incident”
During ”Night” operating mode, all signals immediately generate a ”Remote alarm”.
The activation of a manual call point always immediately generates a ”Remote alarm”.
Alarm Ι
Confirm message
Reconnaissance countdown V1
Investigate fire location
Monitoring time V2
Alarm ΙΙ
Operating personnel:presentabsent
V1
no
?
yes
V2
reset
?
no
Emergency
F
Minor
incident
acknowledged
present or
absent
F
Fire & Security Products
Siemens Building Technologies Group
93
e4595e34
05.2003
Page 100
Determine the alarm organization
the CS1140 fire detection system CS1140 has up to 64 programmable organization
levels (AREAS)
a number of ”Alarm variants” are possible (can be selected per ZONE)
the time countdown memories ”V1” and ”V2” must be specified individually
the time countdown memory ”V2” can be defined per ZONE (if required)
various special local functions are provided
the alarm organization is programmed individually (via maintenance PC)
Organization of system operation
The place of operation of the fire detection system must be determined from an organizational point of view
If required a second operating facility must be provided
If operating units are particularly exposed, they must be fitted with a lockable plexiglass
door (H26T... + Z3S...)
The type of event and the location are displayed on the operating unit in plain text
The locations (rooms etc.) are individually defined by means of the ”User text” (via
maintenance PC)
If required, an additional event-related instruction, a so-called counter-measures
text, can be allocated
The fire detection system may only be operated by instructed personnel (operating access is therefore protected by password or key switch)
Details of control terminal AlgoPilot see page 42
94
Fire & Security Products
Siemens Building Technologies Group
e4595e34
05.2003