Wall switch, single UP 221 E 5WG1 221-2EB..
Wall switch, dual UP 222 E 5WG1 222-2EB..
Product and Applications Description
The wall switches UP 221 E / UP 222 E are available in
the following colors, matching the design of the wall
switch design line DELTA i-system:
Wall switch, single UP 221 E
electro white 5WG1 221-2EB01
titanium white 5WG1 221-2EB11
carbon metallic 5WG1 221-2EB21
aluminum metallic 5WG1 221-2EB31
Wall switch, dual UP 222 E
electro white 5WG1 222-2EB01
titanium white 5WG1 222-2EB11
carbon metallic 5WG1 222-2EB21
aluminum metallic 5WG1 222-2EB31
The wall switch UP 221 E / UP222 E is slid onto the bus
coupling unit UP together with its DELTA line / DELTA
vita / DELTA miro frame. At the same time the electric
connection between the wall switch UP 2221 E / UP 222
E and the bus coupling unit UP is established via a
physical external interface (PEI).
The wall switch requires a bus coupling unit and an
appropriate application program to work properly, i.e. the
wall switch UP 2221 E / UP 222 E (in combination with a
bus coupling unit UP) consists of the device (hardware)
and the application program (software).
The required bus coupling unit UP and DELTA line /
DELTA vita / DELTA miro frame are not included and
therefore have to be ordered separately (see current
catalog).
An application program is available for the different
tasks the wall switch can be applied to.
With an appropriate application program the wall switch
UP 221 E / UP 222 E can control actuators via its bus
coupling unit, e.g., for defined on and off switching, dimming fluorescent lamps or for raising and lowering venetian blinds and adjusting the louvres.
Opposite rockers are combined for switching purposes
e.g. for defined switching, dimming, controlling sliding
shutters and blinds, i.e. the left rocker is used for e.g.
switching on and the right rocker for switching off.
The LEDs positioned with the right rocker may be used
as status indicators.
With the ETS (EIB Tool Software) the application program is selected, its parameters and addresses are
assigned appropriately, and downloaded to the bus
coupling unit UP.
Wall switch, single UP 221 E 5WG1 221-2EB..
Wall switch, dual UP 222 E 5WG1 222-2EB..
Installation Instructions
• The device may be used for permanent interior installations in wall boxes in dry locations.
WARNING
V
• The device must be mounted and commissioned by an
authorised electrician.
• The device may be mounted to switch and socket
combination box mounts if VDE-certified devices are
used exclusively.
• The prevailing safety rules must be heeded.
• For planning and construction of electric installations,
the relevant guidelines, regulations and standards of
the respective country are to be considered.
Technical Specifications
Power supply
via bus coupling unit UP
Control elements
• Horizontal pairs of rockers constitute pairs of switches
(single or dual) are combined for switching purposes
e.g. for defined switching, dimming, controlling sliding
shutters and blinds, i.e. the left rocker is used for e.g.
switching on and the right rocker for switching off.
• Number of switching operations: > 20000 per rocker
Display elements
• 1 LED
as orientation light in the dark
• 1 Status LED (UP 221 E)
2 Status LED (UP 222 E)
Connections
10-pin connector (PEI):
for connection to a bus coupling unit UP
Physical specifications
• housing: plastic
• dimensions (L x W x D):
55 x 55 x 24 mm (incl. spring)
• weight: approx. 25 g
• installation: mounted on bus coupling unit UP
Electrical safety
• degree of pollution (according to IEC 60664-1): 2
• protection (according to EN 60529): IP 20
• overvoltage class (according to IEC 60664-1): III
• bus: safety extra low voltage SELV DC 24 V
• the device complies with
EN 50 090-2-2 and IEC 60664-1
Electromagnetic compatibility
complies with EN 50090-2-2
Environmental specifications
• climatic conditions: EN 50090-2-2
• ambient temperature operating: - 5 ... + 45 °C
• ambient temperature non-op.: - 25 ... + 70 ° C
• relative humidity (non-condensing): 5 % to 93 %
Markings
KNX/ EIB
Location and Function of the Display and
Operating Elements
Wall switch, single UP 221 E 5WG1 221-2EB..
Wall switch, dual UP 222 E 5WG1 222-2EB..
A1 Transparent frame with switch buttons
A2 Transparent plastic labeling film
A3 White label holder
A4 Mounting screws
A5 Switch main module
A6 Design frame (DELTA line/vita/miro)
A7 Wall mounted bus coupling unit UP
A8 Switch button
A9 LED for orientation lighting
A10 PEI interface on wall switch module
A11 PEI interface on bus coupling unit
A12 Status LED
Mounting and wiring
General description
The wall switch UP 221 E / UP222 E is slid onto the bus
coupling unit UP together with its DELTA line / vita / miro
frame. The electric connection between the wall s witch
UP 2221 E / UP 222 E and the bus coupling unit UP is
established via a physical external interface (PEI).
Mounting
−The bus coupling unit UP (A7) is mounted into
a flush-mount box (see installation instruction of
the bus coupling unit UP).
−Remove the transparent frame with the switch
buttons (A1) from the wall switch's main module
(A5) by inserting a screwdriver laterally into the
recesses and lifting the transparent frame upwards from the main module.
−Slip the wall switch's main module (A5) to-
gether with the design frame DELTA line /
DELTA vita / DELTA miro (A6) onto the bus
coupling unit UP.
−Attach the wall switch's main module to the bus
coupling unit UP (A7) with the screws delivered
in the package (A4).
−To write a label separate the white label holder
(A3) from the transparent frame. Label a transparent plastic labeling medium (A2) (e.g. Avery
Zweckform No. J4720 for inkjet printers or
Avery Zweckform No. L4770 for laser printers)
that you insert into the transparent frame (A1)
with the tranparent medium (A2) and the white
label holder (A3).
−Slide the transparent frame back onto the main
module (A5).
Unmounting
−Remove the transparent frame with the switch
buttons (A1) from the wall switch's main module
(A5) by inserting a screwdriver laterally into the
recesses and lifting the transparent frame upwards from the main module.
−Loosen the screws securing the wall switch's
main module to the bus coupling unit UP (A7).
−Remove the wall switch's main module (A5) to-
gether with the design frame DELTA line /
DELTA vita / DELTA miro (A6) from the bus
coupling unit UP (A7).
Dimension Diagram
Dimensions in mm
55
5
5
55
55
General Notes
• Any faulty device should be returned to the local
Siemens office.
• If you have further questions concerning the product
please contact our technical support.