Siemens 440 User Manual

MICROMASTER 440
0,12 kW - 250 kW
Operating Instructions (Compact) Issue 10/06
User Documentation

Warnings, Cautions and Notes

The following Warnings, Cautions and Notes are provided for your safety and as a means of preventing damage to the product or components in the machines connected. Specific Warnings, Cautions and Notes that apply to particular activities are listed at the beginning of the relevant chapters and are repeated or supplemented at critical points throughout these sections. Please read the information carefully, since it is provided for your personal safety and will also help prolong the service life of your MICROMASTER 440 Inverter and the equipment you connect to it.
WARNING
¾ This equipment contains dangerous voltages and controls potentially dangerous
rotating mechanical parts. Non-compliance with Warnings or failure to follow the instructions contained in this manual can result in loss of life, severe personal injury or serious damage to property.
¾ Only suitable qualified personnel should work on this equipment, and only after
becoming familiar with all safety notices, installation, operation and maintenance procedures contained in this manual. The successful and safe operation of this equipment is dependent upon its proper handling, installation, operation and maintenance.
¾ The DC link capacitors remain charged for five minutes after power has been
removed. It is not permissible to open the equipment until 5 minutes after the power has been removed. The drive unit discharges itself during this time.
¾ This equipment is capable of providing internal motor overload protection in
accordance with UL508C section 42. Refer to P0610 and P0335, i default. Motor overload protection can also be provided using an external PTC or KTY84.
¾ This equipment is suitable for use in a circuit capable of delivering not more
than symmetrical 10 kA (rms) (Frame Sizes A to C) or symmetrical 42 kA (rms) (Frame Sizes D to GX), for a maximum voltage of 230 V / 460 V / 575 V when protected by an H, J or K type fuse, a circuit breaker or self-protected combination motor controller (for more details see Operating Instructions Appendix F).
¾ Use Class 1 60/75 °C copper wire only with the cross-sections as specified in
the Operating Instructions.
¾ The mains input, DC and motor terminals, can carry dangerous voltages even if
the inverter is inoperative. Always wait 5 minutes to allow the unit to discharge after switching off before carrying out any installation work.
NOTE
¾ Before installing and commissioning, please read these safety instructions and
warnings carefully and all the warning labels attached to the equipment.
¾ Please ensure that all of the warning labels are kept in a condition so that they
can be easily read and replace missing or damaged labels.
¾ Maximum permissible surrounding ambient temperature is:
Frame Sizes A-F:
50 °C at constant torque (CT) and 100 % permissible output current 40 °C at variable torque (VT) and 100 % permissible output current
Frame Sizes FX and GX:
40 °C at 100 % permissible output current
2
t is ON by
MICROMASTER 440
2 Operating Instructions (Compact)
Issue 10/06 Contents

Contents

1 Installation............................................................................................................... 5
1.1 Clearance distances for mounting ............................................................................ 5
1.2 Mounting dimensions................................................................................................ 5
2 Electrical Installation.............................................................................................. 6
2.1 Technical Specifications ........................................................................................... 6
2.2 Power Terminals..................................................................................................... 13
2.3 Control terminals..................................................................................................... 21
2.4 Block diagram ......................................................................................................... 22
3 Factory setting...................................................................................................... 23
3.1 50/60 Hz DIP switch................................................................................................ 23
4 Communications................................................................................................... 24
4.1 Establishing communications MICROMASTER 440 STARTER........................ 24
4.2 Establishing communications MICROMASTER 440 AOP................................. 24
4.3 Bus interface (CB)................................................................................................... 25
5 BOP / AOP (Option) .............................................................................................. 26
5.1 Buttons and their Functions .................................................................................... 26
5.2 Changing parameters using as an example P0004 "Parameter filter function"...... 27
6 Commissioning..................................................................................................... 28
6.1 Quick commissioning.............................................................................................. 28
6.2 Motor data identification.......................................................................................... 32
6.3 Magnetizing current ................................................................................................ 32
6.4 Commissioning the application............................................................................... 34
6.4.1 Serial Interface (USS)............................................................................................. 34
6.4.2 Selection of command source ................................................................................ 34
6.4.3 Digital input (DIN).................................................................................................... 35
6.4.4 Digital outputs (DOUT) ........................................................................................... 36
6.4.5 Selection of frequency setpoint............................................................................... 37
6.4.6 Analog input (ADC)................................................................................................. 38
6.4.7 Analog output (DAC)............................................................................................... 39
6.4.8 Motor potentiometer (MOP) .................................................................................... 40
6.4.9 Fixed frequency (FF)............................................................................................... 41
6.4.10 JOG......................................................................................................................... 42
6.4.11 Ramp function generator (RFG) ............................................................................. 43
6.4.12 Reference/limit frequencies .................................................................................... 44
6.4.13 Inverter protection................................................................................................... 45
6.4.14 Motor protection...................................................................................................... 45
6.4.15 Encoder................................................................................................................... 47
6.4.16 V/f control................................................................................................................ 48
MICROMASTER 440 Operating Instructions (Compact)
3
Contents Issue 10/06
6.4.17 Field-orientated control ........................................................................................... 50
6.4.17.1 Sensorless vector control (SLVC)........................................................................... 51
6.4.17.2 Vector control with encoder (VC)............................................................................ 53
6.4.18 Converter-specific Functions .................................................................................. 55
6.4.18.1 Flying start .............................................................................................................. 55
6.4.18.2 Automatic restart..................................................................................................... 55
6.4.18.3 Holding brake.......................................................................................................... 56
6.4.18.4 DC brake................................................................................................................. 58
6.4.18.5 Compound braking.................................................................................................. 59
6.4.18.6 Dynamic braking ..................................................................................................... 60
6.4.18.7 Vdc controller.......................................................................................................... 60
6.4.18.8 Load torque monitoring........................................................................................... 61
6.4.18.9 PID controller .......................................................................................................... 63
6.4.18.10 Positioning down ramp ........................................................................................... 66
6.4.18.11 Free function blocks (FFB) ..................................................................................... 67
6.4.19 Data sets................................................................................................................. 69
6.4.20 Diagnostic parameters............................................................................................ 72
6.5 Series commissioning............................................................................................. 75
6.6 Parameter reset of factory setting........................................................................... 75
7 Displays and messages ....................................................................................... 76
7.1 LED status display .................................................................................................. 76
7.2 Fault messages and Alarm messages.................................................................... 77
MICROMASTER 440
4 Operating Instructions (Compact)
Issue 10/06 1 Installation

1 Installation

1.1 Clearance distances for mounting

The inverters can be mounted adjacent to each other. When mounting inverters one above the other, the specified environmental conditions must not be exceeded.
Independent of this, these minimum distances must be observed.
¾ Frame Size A, B, C above and below 100 mm ¾ Frame Size D, E above and below 300 mm ¾ Frame Size F above and below 350 mm ¾ Frame Size FX, GX above 250 mm
below 150 mm in front 40 mm (FX), 50 mm (GX)

1.2 Mounting dimensions

Frame
Size
H
A 160 (6.30) 2 x M4
B 174 (6.85) 138 (5.43) 4 x M4
C 204 (8.03) 174 (6.85) 4 x M5
H
W
Fig. 1-1 Mounting dimensions
D 486 (19.13) 235 (9.25) 4 x M8
E 616,4
F 810 (31.89) 300 (11.81) 4 x M8
FX 1375,5
GX 1508,5
Drilling Dimensions Tightening Torque
Bolts Nm
mm (Inch) W mm (Inch)
235 (9.25) 4 x M8
(24.27)
250 (9.84) 6 x M8
(54.14)
250 (9.84) 6 x M8
(59.38)
(lbf.in)
(22.12)
(26.54)
(115.02)
(115.02)
2,5
3,0
13,0
13,0
MICROMASTER 440 Operating Instructions (Compact)
5
2 Electrical Installation Issue 10/06

2 Electrical Installation

2.1 Technical Specifications

Input voltage range 1 AC 200 V – 240 V, ± 10 % (Unfiltered and with built in Class A Filter)
2AB Order No
6SE6440­Frame Size A B C
Output Rating (CT) Output Power [kVA]
CT Input Current 1) CT Output Current [A] Fuse Recommended for UL specified
Input Cable Min.
Input Cable Max.
Output Cable Min.
Output Cable Max.
(with built in filter)
Weight (unfiltered)
power terminals
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line
2UC
[kW] [hp]
3NA 3803 3803 3803 3805 3805 3807 3807 3812 3817
[mm2] 1,0 1,0 1,0 1,5 1,5 2,5 2,5 4,0 6,0 [AWG] 18 18 18 16 16 14 14 12 10
[mm2] 2,5 2,5 2,5 2,5 2,5 6,0 6,0 6,0 10,0 [AWG] 14 14 14 14 14 10 10 10 8
[mm2] 1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,5 [AWG] 18 18 18 18 18 18 18 18 16
[mm2] 2,5 2,5 2,5 2,5 2,5 6,0 6,0 6,0 10,0 [AWG] 14 14 14 14 14 10 10 10 8
[kg] 1,3 1,3 1,3 1,3 1,3 3,4 3,4 3,4 5,7 Weight [lbs] 2,9 2,9 2,9 2,9 2,9 7,5 7,5 7,5 12,5
[kg] 1,3 1,3 1,3 1,3 1,3 3,3 3,3 3,3 5,5 [lbs] 2,9 2,9 2,9 2,9 2,9 7,3 7,3 7,3 12,1
[Nm] 1,1 1,5 2,25 Tightening torques for [lbf.in] (10) (13,3) (20)
supply V of 240 V without line commutating reactor.
11-
2AA1
0,12 0,25 0,37 0,55 0,75 1,1 1,5 2,2 3,0 0,16 0,33 0,5 0,75 1,0 1,5 2,0 3,0 4,0
0,4 0,7 1,0 1,3 1,7 2,4 3,2 4,6 6,0 1,8 3,2 4,6 6,2 8,2 11,0 14,4 20,2 35,5 0,9 1,7 2,3 3,0 3,9 5,5 7,4 10,4 13,6
10 10 10 16 16 20 20 32 40
= 2 % referred to the rated drive converter power and a rated line supply voltage
k
12-
5AA1
* * * * * * * * *
13-
7AA1
15-
5AA1
17-
5AA1
21-
1BA1
21-
5BA1
22-
2BA1
23-
0CA1
* UL listed fuses such as Class NON from Bussmann are required for use in America
MICROMASTER 440
6 Operating Instructions (Compact)
Issue 10/06 2 Electrical Installation
Input voltage range 3 AC 200 V – 240 V. ± 10 % (with built in Class A Filter)
Order No. 6SE6440- 2AC23-
Frame Size C Output Rating(CT) Output Power [kVA] 6,0 7,7 9,6
CT Input Current 1) [A] 15,6 19,7 26,5 CT-Output Current [A] 13,6 17,5 22,0 VT Input Current 1) [A] - 28,3 34,2 VT-Output Current [A] - 22,0 28,0 Fuse [A] 25 32 35
Recommended 3NA 3810 3812 3814 For UL specified * * *
Input Cable, min.
Input Cable, max.
Output Cable, min.
Output Cable, max.
Weight
power terminals
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line
[kW] 3,0 4,0 5,5 [hp] 4,0 5,0 7,5
[mm2] 2,5 4,0 4,0 [AWG] 14 12 12
[mm2] 10,0 10,0 10,0 [AWG] 8 8 8
[mm2] 1,5 4,0 4,0 [AWG] 16 12 12
[mm2] 10,0 10,0 10,0 [AWG] 8 8 8 [kg] 5,7 5,7 5,7
[lbs] 12,5 12,5 12,5 [Nm] 2,25 Tightening torques for
[lbf.in] (20)
supply V of 240 V without line commutating reactor.
0CA1
= 2 % referred to the rated drive converter power and a rated line supply voltage
k
2AC24-
0CA1
2AC25-
5CA1
* UL listed fuses such as Class NON from Bussmann are required for use in America
MICROMASTER 440 Operating Instructions (Compact)
7
2 Electrical Installation Issue 10/06
Input voltage range 3 AC 200 V – 240 V. ± 10 % (Unfiltered)
Order No. 6SE6440- 2UC11
Frame Size A B C Output Rating(CT) Output Power [kVA] 0,4 0,7 1,0 1,3 1,7 2,4 3,2 4,6 6,0
CT-Input Current 1) [A] 1,1 1,9 2,7 3,6 4,7 6,4 8,3 11,7 15,6 CT-Output Current [A] 0,9 1,7 2,3 3,0 3,9 5,5 7,4 10,4 13,6 Fuse [A] 10 10 10 16 16 20 20 25 25
Recommended 3NA 3803 3803 3803 3805 3805 3807 3807 3810 3810 For UL specified
Input Cable, min.
Input Cable, max.
Output Cable, min.
Output Cable, max.
Weight Tightening torques
for power terminals
[kW] 0,12 0,25 0,37 0,55 0,75 1,1 1,5 2,2 3,0 [hp] 0,16 0,33 0,5 0,75 1,0 1,5 2,0 3,0 4,0
[mm2] 1,0 1,0 1,0 1,5 1,5 2,5 2,5 2,5 4,0 [AWG] 18 18 18 16 16 14 14 14 12
[mm2] 2,5 2,5 2,5 2,5 2,5 6,0 6,0 6,0 10,0 [AWG] 14 14 14 14 14 10 10 10 8
[mm2] 1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,5 [AWG] 18 18 18 18 18 18 18 18 16
[mm2] 2,5 2,5 2,5 2,5 2,5 6,0 6,0 6,0 10,0 [AWG] 14 14 14 14 14 10 10 10 8
[kg] 1,3 1,3 1,3 1,3 1,3 3,3 3,3 3,3 5,5 [lbs] 2,9 2,9 2,9 2,9 2,9 7,3 7,3 7,3 12,1
[Nm] 1,1 1,5 2,25 [lbf.in]
-2AA1
2UC12
-5AA1
* * * * * * * * *
2UC13
-7AA1
(10) (13,3) (20)
2UC15
-5AA1
2UC17
-5AA1
2UC21
-1BA1
2UC21
-5BA1
2UC22
-2BA1
2UC23
-0CA1
Order No. 6SE6440- 2UC24-
Frame Size C D E F Output Rating(CT) Output Power [kVA] 7,7 9,6 12,3 18,4 23,7 29,8 35,1 45,6 57,0 67,5
CT-Input Current 1) [A] 19,7 26,5 34,2 38,0 50,0 62,0 71,0 96,0 114,0 135,0 CT-Output Current [A] 17,5 22,0 28,0 42,0 54,0 68,0 80,0 104,0 130,0 154,0
VT-Input Current 1) [A] 28,3 34,2 38,0 50,0 62,0 71,0 96,0 114,0 135,0 164,0 VT-Output Current [A] 22,0 28,0 42,0 54,0 68,0 80,0 104,0 130,0 154,0 - Fuse [A] 32 35 50 80 80 100 125 200 200 250
Recommended 3NA 3812 3814 3820 3824 3824 3830 3832 3140 3142 3144 For UL specified
Input Cable, min.
Input Cable, max.
Output Cable, min.
Output Cable, max
Weight Tightening torques
for power terminals
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line
[kW] 4,0 5,5 7,5 11,0 15,0 18,5 22,0 30,0 37,0 45,0 [hp] 5,0 7,5 10,0 15,0 20,0 25,0 30,0 40,0 50,0 60,0
3NE [mm2] 4,0 4,0 10,0 16,0 16,0 25,0 25,0 70,0 70,0 95,0
[AWG] 12 12 8 6 6 3 3 2/0 2/0 3/0 [mm2] 10,0 10,0 35,0 35,0 35,0 35,0 35,0 150,0 150,0 150,0
[AWG] 8 8 2 2 2 2 2 300 300 300 [mm2] 4,0 4,0 10,0 16,0 16,0 25,0 25,0 50,0 70,0 95,0
[AWG] 12 12 8 6 6 3 3 1/0 2/0 3/0 [mm2] 10,0 10,0 35,0 35,0 35,0 35,0 35,0 150,0 150,0 150,0
[AWG] 8 8 2 2 2 2 2 300 300 300 [kg] 5,5 5,5 17,0 16,0 16,0 20,0 20,0 55,0 55,0 55,0
[lbs] 12,1 12,1 37,0 35,0 35,0 44,0 44,0 121,0 121,0 121,0 [Nm] 2,25 10 50
[lbf.in]
supply V of 240 V without line commutating reactor.
k
2UC25-
0CA1
* * 1817-0 1820-0 1820-0 1021-0 1022-0 1225-0 1225-0 1227-0
(20) (89) (445)
= 2 % referred to the rated drive converter power and a rated line supply voltage
5CA1
2UC27-
5DA1
2UC31-
1DA1
2UC31-
5DA1
2UC31-
8EA1
2UC32-
2EA1
2UC33-
0FA1
2UC33-
7FA1
2UC34-
5FA1
* UL listed fuses such as Class NON from Bussmann are required for use in America
MICROMASTER 440
8 Operating Instructions (Compact)
Issue 10/06 2 Electrical Installation
Input voltage range 3 AC 380 V – 480 V. ± 10 % (with built in Class A Filter)
Order No. 6SE6440- 2AD22-
Frame Size B C D Output Rating(CT) Output Power [kVA] 4,5 5,9 7,8 10,1 14,0 19,8 24,4
CT-Input Current 1) [A] 7,5 10,0 12,8 15,6 22,0 23,1 33,8 CT-Output Current [A] 5,9 7,7 10,2 13,2 18,4 26,0 32,0 VT-Input Current 1) [A] – – – 17,3 23,1 33,8 37,0 VT-Output Current [A] – – – 20,2 29,0 39,0 45,2 Fuse [A] 16 16 20 20 32 35 50
Recommended 3NA 3805 3805 3807 3807 3812 3814 3820 For UL specified
Input Cable, min.
Input Cable, max.
Output Cable, min.
Output Cable, max.
Weight Tightening torques for
power terminals
[kW] 2,2 3,0 4,0 5,5 [hp] 3,0 4,0 5,0 7,5 10,0 15,0 20,0
3NE [mm2] 1,5 1,5 2,5 2,5 4,0 6,0 10,0
[AWG] 16 16 14 14 12 10 8 [mm2] 6,0 6,0 6,0 10,0 10,0 10,0 35,0
[AWG] 10 10 10 8 8 8 2 [mm2] 1,0 1,0 1,0 2,5 4,0 6,0 10,0
[AWG] 18 18 18 14 12 10 8 [mm2] 6,0 6,0 6,0 10,0 10,0 10,0 35,0
[AWG] 10 10 10 8 8 8 2 [kg] 3,4 3,4 3,4 5,7 5,7 5,7 17,0
[lbs] 7,5 7,5 7,5 12,5 12,5 12,5 37,0 [Nm] 1,1 1,5 2,25
[lbf.in]
2BA1
2AD23-
0BA1
* * * * * * 1817-0
(10) (13,3) (20)
2AD24-
0BA1
2AD25-
5CA1
2AD27-
5CA1
7,5 11,0 15,0
2AD31-
1CA1
2AD31-
5DA1
Order No. 6SE6440- 2AD31-
Frame Size D E F Output Rating(CT) Output Power [kVA] 29,0 34,3 47,3 57,2 68,6 83,8 110,5
CT-Input Current 1) [A] 37,0 43,0 59,0 72,0 87,0 104,0 139,0 CT-Output Current [A] 38,0 45,0 62,0 75,0 90,0 110,0 145,0 VT-Input Current 1) [A] 43,0 59,0 72,0 87,0 104,0 139,0 169,0 VT-Output Current [A] 45,0 62,0 75,0 90,0 110,0 145,0 178,0 Fuse [A] 63 80 100 125 160 200 250
Recommended 3NA 3822 3824 3830 3832 3836 3140 3144 For UL specified 3NE
Input Cable, min.
Input Cable, max.
Output Cable, min.
Output Cable, max.
Weight Tightening torques for
power terminals
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line
[kW] 18,5 22,0 30,0 37,0 45,0 55,0 75,0 [hp] 25,0 30,0 40,0 50,0 60,0 75,0 100,0
[mm2] 10,0 16,0 25,0 25,0 35,0 70,0 95,0 [AWG] 8 6 3 3 2 2/0 3/0
[mm2] 35,0 35,0 35,0 35,0 150,0 150,0 150,0 [AWG] 2 2 2 2 300 300 300
[mm2] 10,0 16,0 25,0 25,0 50,0 70,0 95,0 [AWG] 8 6 3 3 1/0 2/0 3/0
[mm2] 35,0 35,0 35,0 35,0 150,0 150,0 150,0 [AWG] 2 2 2 2 300 300 300
[kg] 17,0 17,0 22,0 22,0 75,0 75,0 75,0 [lbs] 37,0 37,0 48,0 48,0 165,0 165,0 165,0
[Nm] 10 50 [lbf.in]
supply V of 400 V without line commutating reactor.
8DA1
1818-0 1820-0 1021-0 1022-0 1224-0 1225-0 1227-0
= 2 % referred to the rated drive converter power and a rated line supply voltage
k
2AD32-
2DA1
2AD33-
0EA1
(89) (445)
2AD33-
7EA1
2AD34-
5FA1
2AD35-
5FA1
2AD37-
5FA1
* UL listed fuses such as Class NON from Bussmann are required for use in America
MICROMASTER 440 Operating Instructions (Compact)
9
2 Electrical Installation Issue 10/06
Input voltage range 3 AC 380 V – 480 V. ± 10 % (Unfiltered)
Order No. 6SE6440- 2UD13
Frame Size A B C Output Rating(CT) Output Power [kVA] 0,9 1,2 1,6 2,3 3,0 4,5 5,9 7,8 10,1 14,0
CT-Input Current 1) [A] 2,2 2,8 3,7 4,9 5,9 7,5 10,0 12,8 15,6 22,0 CT-Output Current [A] 1,3 1,7 2,2 3,1 4,1 5,9 7,7 10,2 13,2 19,0 VT-Input Current 1) [A] - - - - - - - - 17,3 23,1 VT-Output Current [A] - - - - - - - - 19,0 26,0 Fuse [A] 10 10 10 10 10 16 16 20 20 32
Recommended 3NA 3803 3803 3803 3803 3803 3805 3805 3807 3807 3812 For UL specified
Input Cable, min.
Input Cable, max.
Output Cable, min.
Output Cable, max.
Weight Tightening torques for
power terminals
[kW] 0,37 0,55 0,75 1,1 [hp] 0,5 0,75 1,0 1,5 2,0 3,0 4,0 5,0 7,5 10,0
[mm2] 1,0 1,0 1,0 1,0 1,0 1,5 1,5 2,5 2,5 4,0 [AWG] 18 18 18 18 18 16 16 14 14 12
[mm2] 2,5 2,5 2,5 2,5 2,5 6,0 6,0 6,0 10,0 10,0 [AWG] 14 14 14 14 14 10 10 10 8 8
[mm2] 1,0 1,0 1,0 1,0 1,0 1,0 1,0 1,0 2,5 4,0 [AWG] 18 18 18 18 18 18 18 18 14 12
[mm2] 2,5 2,5 2,5 2,5 2,5 6,0 6,0 6,0 10,0 10,0 [AWG] 14 14 14 14 14 10 10 10 8 8
[kg] 1,3 1,3 1,3 1,3 1,3 3,3 3,3 3,3 5,5 5,5 [lbs] 2,9 2,9 2,9 2,9 2,9 7,3 7,3 7,3 12,1 12,1
[Nm] 1,1 1,5 2,25 [lbf.in]
-7AA1
2UD15
-5AA1
*
2UD17
-5AA1
*
2UD21
-1AA1
*
(10) (13,3) (20)
2UD21
-5AA1
*
2UD22
-2BA1
1,5 2,2 3,0 4,0 5,5 7,5
*
2UD23
-0BA1
*
2UD24
-0BA1
*
2UD25
-5CA1
*
2UD27
-5CA1
*
*
Order No. 6SE6440- 2UD31
Frame Size C D E F Output Rating(CT) Output Power [kVA] 19,8 24,4 29,0 34,3 47,3 57,2 68,6 83,8 110,5
CT-Input Current 1) [A] 23,1 33,8 37,0 43,0 59,0 72,0 87,0 104,0 139,0 CT-Output Current [A] 26,0 32,0 38,0 45,0 62,0 75,0 90,0 110,0 145,0 VT-Input Current 1) [A] 33,8 37,0 43,0 59,0 72,0 87,0 104,0 139,0 169,0 VT-Output Current [A] 32,0 38,0 45,0 62,0 75,0 90,0 110,0 145,0 178,0 Fuse [A] 35 50 63 80 100 125 160 200 250
Recommended 3NA For UL specified 3NE
Input Cable, min.
Input Cable, max.
Output Cable, min.
Output Cable, max.
Weight Tightening torques for
power terminals
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line
[kW] 11,0 15,0 18,5 22,0 30,0 37,0 45,0 55,0 75,0 [hp] 15,0 20,0 25,0 30,0 40,0 50,0 60,0 75,0 100,0
[mm2] 6,0 10,0 10,0 16,0 25,0 25,0 35,0 70,0 95,0 [AWG] 10 8 8 6 3 3 2 2/0 3/0
[mm2] 10,0 35,0 35,0 35,0 35,0 35,0 150,0 150,0 150,0 [AWG] 8 2 2 2 2 2 300 300 300
[mm2] 6,0 10,0 10,0 16,0 25,0 25,0 35,0 70,0 95,0 [AWG] 10 8 8 6 3 3 2 2/0 3/0
[mm2] 10,0 35,0 35,0 35,0 35,0 35,0 150,0 150,0 150,0 [AWG] 8 2 2 2 2 2 300 300 300
[kg] 5,5 16,0 16,0 16,0 20,0 20,0 56,0 56,0 56,0 [lbs] 12,1 35,0 35,0 35,0 44,0 44,0 123,0 123,0 123,0
[Nm] 2,25 10 50 [lbf.in]
-1CA1
3814 3820 3822 3824 3830 3832 3836 3140 3144 * 1817-0 1818-0 1820-0 1021-0 1022-0 1224-0 1225-0 1227-0
supply V of 400 V without line commutating reactor.
k
2UD31
-5DA1
(20) (89) (445)
= 2 % referred to the rated drive converter power and a rated line supply voltage
2UD31
-8DA1
2UD32
-2DA1
2UD33
-0EA1
2UD33
-7EA1
2UD34
-5FA1
2UD35
-5FA1
2UD37
-5FA1
* UL listed fuses such as Class NON from Bussmann are required for use in America
MICROMASTER 440
10 Operating Instructions (Compact)
Issue 10/06 2 Electrical Installation
Input voltage range 3 AC 380 V – 480 V, ± 10 % (Unfiltered)
Order No. 6SE6440- 2UD38-8FA1 2UD41-1FA1 2UD41-3GA1 2UD41-6GA1 2UD42-0GA1 Frame Size FX GX
Output Rating(CT) Output Power [kVA] 145,4 180 214,8 263,2 339,4
CT-Input Current 1) [A] 169 200 245 297 354 CT-Output Current [A] 178 205 250 302 370 VT-Input Current 1) [A] 200 245 297 354 442 VT-Output Current [A] 205 250 302 370 477
Recommended Fuse
Pipe cable shoe to DIN 46235
Input Cable, min.
Input Cable, max.
Output Cable, min.
Output Cable, max.
Weight
power terminals
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line
[kW] 90 110 132 160 200 [hp] 125 150 200 250 300
[A] 250 315 400 450 560 3NE 1227-0 1230-0 1332-0 1333-0 1435-0
[mm] 10 10 10 10 10
[mm2]
[AWG] [kcmil] [mm2]
[AWG] [kcmil] [mm2]
[AWG] [kcmil] [mm2]
[AWG] [kcmil]
[kg] 110 110 170 170 170 [lbs] 242 242 418 418 418
[Nm] 25 Tightening torques for [lbf.in] (222,5)
supply V voltage of 400 V without line commutating reactor.
k
1 x 95 or
2 x 35
1 x 4/0 or
or
2 x 2
1 x 185 or
2 x 120
1 x 350 or
or
2 x 4/0
1 x 95 or
2 x 35
1 x 4/0 or
or
2 x 2
1 x 185 or
2 x 120
1 x 350 or
or
2 x 4/0
2.33 % referred to the rated drive converter power and a rated line supply
1 x 150 or
2 x 50
1 x 300 or
2 x 1/0
1 x 185 or
2 x 120
1 x 350 or
2 x 4/0
1 x 150 or
2 x 50
1 x 300 or
2 x 1/0
1 x 185 or
2 x 120
1 x 350 or
2 x 4/0
1 x 185 or
2 x 70
1 x 400 or
2 x 2/0
1 x 240 or
2 x 70
1 x 500 or
2 x 2/0
2 x 95
2 x 4/0
2 x 240 2 x 240 2 x 240
2 x 400 2 x 400 2 x 400
1 x 185 or
2 x 70
1 x 400 or
2 x 2/0
1 x 240 or
2 x 70
1 x 500 or
2 x 2/0
2 x 95
2 x 4/0
2 x 240 2 x 240 2 x 240
2 x 400 2 x 400 2 x 400
MICROMASTER 440 Operating Instructions (Compact)
11
2 Electrical Installation Issue 10/06
Input voltage range 3 AC 500 V – 600 V, ± 10 % (Unfiltered)
Order No. 6SE6440- 2UE17-
Frame Size C D Output Rating(CT) Output Power [kVA] 1,3 2,6 3,7 5,8 8,6 10,5 16,2 21,0
CT-Input Current 1) [A] 2,0 3,7 5,3 8,1 11,1 14,4 21,5 24,9 CT-Output Current [A] 1,4 2,7 3,9 6,1 9,0 11,0 17,0 22,0 VT-Input Current 1) [A] 3,2 4,4 6,9 9,4 12,6 18,1 24,9 30,0 VT-Output Current [A] 2,7 3,9 6,1 9,0 11,0 17,0 22,0 27,0 Fuse [A] 10 10 10 16 16 25 32 35
Recommended 3NA For UL specified 3NE
Input Cable, min.
Input Cable, max.
Output Cable, min.
Output Cable, max.
Weight Tightening torques for
power terminals
[kW] 0,75 1,5 2,2 4,0 [hp] 1,0 2,0 3,0 5,0 7,5 10,0 15,0 20,0
[mm2] 1,0 1,0 1,0 1,5 1,5 2,5 4,0 6,0 [AWG] 18 18 18 16 16 14 12 10
[mm2] 10,0 10,0 10,0 10,0 10,0 10,0 10,0 35,0 [AWG] 8 8 8 8 8 8 8 2
[mm2] 1,0 1,0 1,0 1,0 1,0 2,5 4,0 4,0 [AWG] 18 18 18 18 18 14 12 12
[mm2] 10,0 10,0 10,0 10,0 10,0 10,0 10,0 35,0 [AWG] 8 8 8 8 8 8 8 2
[kg] 5,5 5,5 5,5 5,5 5,5 5,5 5,5 16,0 [lbs] 12,1 12,1 12,1 12,1 12,1 12,1 12,1 35,0
[Nm] 2,25 10 [lbf.in]
5CA1
3803-6 3803-6 3803-6 3805-6 3805-6 3810-6 3812-6 3814-6
2UE21-
5CA1
*
2UE22-
2CA1
*
2UE24-
0CA1
*
2UE25-
5CA1
*
(20) (89)
2UE27-
5CA1
5,5 7,5 11,0 15,0
*
2UE31-
1CA1
*
2UE31-
5DA1
*
1803-0
Order No. 6SE6440- 2UE31-
Frame Size D E F Output Rating(CT) Output Power [kVA] 25,7 30,5 39,1 49,5 59,1 73,4 94,3
CT-Input Current 1) [A] 30,0 35,0 48,0 58,0 69,0 83,0 113,0 CT-Output Current [A] 27,0 32,0 41,0 52,0 62,0 77,0 99,0 VT-Input Current 1) [A] 35,0 48,0 58,0 69,0 83,0 113,0 138,0 VT-Output Current [A] 32,0 41,0 52,0 62,0 77,0 99,0 125,0 Fuse [A] 50 63 80 80 125 160 160
Recommended 3NA For UL specified 3NE
Input Cable, min.
Input Cable, max.
Output Cable, min.
Output Cable, max.
Weight Tightening torques for
power terminals
1) Secondary conditions: Input current at the rated operating point - applies for the short-circuit voltage of the line
[kW] 18,5 22,0 30,0 37,0 45,0 55,0 75,0 [hp] 25,0 30,0 40,0 50,0 60,0 75,0 100,0
[mm2] 10,0 10,0 16,0 25,0 25,0 50,0 50,0 [AWG] 8 8 6 3 3 1/0 1/0
[mm2] 35,0 35,0 35,0 35,0 150,0 150,0 150,0 [AWG] 2 2 2 2 300 300 300
[mm2] 6,0 10,0 16,0 16,0 25,0 35,0 50,0 [AWG] 10 8 6 6 3 2 1/0
[mm2] 35,0 35,0 35,0 35,0 150,0 150,0 150,0 [AWG] 2 2 2 2 300 300 300
[kg] 16,0 16,0 20,0 20,0 56,0 56,0 56,0 [lbs] 35,0 35,0 44,0 44,0 123,0 123,0 123,0
[Nm] 10 50 [lbf.in]
supply V of 500 V without line commutating reactor.
8DA1
3820-6 3822-6 3824-6 3824-6 3132-6 3136-6 3136-6 1817-0 1818-0 1820-0 1820-0 1022-0 1224-0 1224-0
= 2 % referred to the rated drive converter power and a rated line supply voltage
k
2UE32-
2DA1
2UE33-
0EA1
(89) (445)
2UE33-
7EA1
2UE34-
5FA1
2UE35-
5FA1
2UE37-
5FA1
* UL listed fuses such as Class NON from Bussmann are required for use in America
MICROMASTER 440
12 Operating Instructions (Compact)
Issue 10/06 2 Electrical Installation

2.2 Power Terminals

You can gain access to the mains and motor terminals by removing the front covers.
¾ Frame Size A (Fig. 2-1) ¾ Frame Sizes B and C (Fig. 2-2) ¾ Frame sizes D and E (Fig. 2-3) ¾ Frame Size F (Fig. 2-4) ¾ Frame Sizes FX and GX (Fig. 2-5) ¾ Connection terminals for Frame Sizes A - F (Fig. 2-6) ¾ Connection overview for Frame Size FX (Fig. 2-7) ¾ Connection overview for Frame Size GX (Fig. 2-8)
Frame Size A
1 2
3
Fig. 2-1 Removing front covers (Frame Size A)
MICROMASTER 440 Operating Instructions (Compact)
4
13
2 Electrical Installation Issue 10/06
Frame Sizes B and C
!
"
# $
Fig. 2-2 Removing front covers (Frame Sizes B and C)
MICROMASTER 440
14 Operating Instructions (Compact)
Issue 10/06 2 Electrical Installation
Frame Sizes D and E
1
2
3
Fig. 2-3 Removing front covers (Frame Sizes D and E)
MICROMASTER 440 Operating Instructions (Compact)
15
2 Electrical Installation Issue 10/06
Frame Size F
1
2
19 mm AF
Fig. 2-4 Removing front covers (Frame Size F)
3
MICROMASTER 440
16 Operating Instructions (Compact)
Issue 10/06 2 Electrical Installation
Frame Sizes FX and GX
1
3
2
4
Fig. 2-5 Removing front covers (Frame Sizes FX and GX)
MICROMASTER 440 Operating Instructions (Compact)
17
2 Electrical Installation Issue 10/06
Access to the power supply and motor terminals is possible by removing the front covers.
Fig. 2-6 Connection terminals for Frame Sizes A - F
MICROMASTER 440
18 Operating Instructions (Compact)
Issue 10/06 2 Electrical Installation
Hoisting eyes
Shield connection
Mains cable PE
Cable opening for
mains conection
U1/L1, V1/L2, W1/L3
Cable opening DCPA, DCNA
for connection of an
external braking unit
Mains cable
Phase U1/L1, V1/L2, W1/L3
Connection to
Y-Capacitor
Connection DCPA, DCNA
for external braking unit
Top adjustment rail
Top retaining screw
Connection for dv/dt filter
DCPS, DCNS
Status Display Panel
Elektronic box
Bottom adjustment rail
Bottom retaining screw
Fan screws
Fan
Shield connection
control leads
Fan fuses
Transformer adaption
Motor cable
Phase U2, V2, W2
Motor cable
PE Shield connection
Fig. 2-7 Connection overview for Frame Size FX
MICROMASTER 440 Operating Instructions (Compact)
19
2 Electrical Installation Issue 10/06
Hoisting eyes
Shield connection
Mains cable PE
Cable opening for
mains conection
U1/L1, V1/L2, W1/L3
able opening DCPA, DCNA
for connection of an
external braking unit
Phase U1/L1, V1/L2, W1/L3
Connection DCPA, DCNA
for external braking unit
Connection for dv/dt filter
Status Display Panel
Bottom adjustment rail
Bottom retaining screw
Mains cable
Connection to
Y-Capacitor
Top adjustment rail
Top retaining screw
DCPS, DCNS
Elektronic box
Fan screws
Fan
Shield connection
control leads
Fan fuses
Transformer adaption
Motor cable
Phase U2, V2, W2
PE Shield connection
Motor cable
Fig. 2-8 Connection overview for Frame Size GX
MICROMASTER 440
20 Operating Instructions (Compact)
Issue 10/06 2 Electrical Installation

2.3 Control terminals

Terminal Designation Function
1 Output +10 V 2 Output 0 V 3 ADC1+ Analog input 1 (+) 4 ADC1– Analog input 1 (–)
5 DIN1 Digital input 1 6 DIN2 Digital input 2 7 DIN3 Digital input 3
8 DIN4 Digital input 4 9 Isolated output +24 V / max. 100 mA 10 ADC2+ Analog input 2 (+)
11 ADC2– Analog input 2 (–) 12 DAC1+ Analog output 1 (+) 13 DAC1– Analog output 1 (–)
14 PTCA Connection for PTC / KTY84 15 PTCB Connection for PTC / KTY84 16 DIN5 Digital input 5
17 DIN6 Digital input 6 18 DOUT1/NC Digital output 1 / NC contact 19 DOUT1/NO Digital output 1 / NO contact
20 DOUT1/COM Digital output 1 / Changeover contact 21 DOUT2/NO Digital output 2 / NO contact 22 DOUT2/COM Digital output 2 / Changeover contact
23 DOUT3/NC Digital output 3 / NC contact 24 DOUT3/NO Digital output 3 / NO contact 25 DOUT3/COM Digital output 3 / Changeover contact 26 DAC2+ Analog output 2 (+)
27 DAC2– Analog output 2 (–) 28 Isolated output 0 V / max. 100 mA 29 P+ RS485 port
30 N– RS485 port
Fig. 2-9 Control terminals of MICROMASTER 440
MICROMASTER 440 Operating Instructions (Compact)
21
2 Electrical Installation Issue 10/06

2.4 Block diagram

PE
4.7 k
External 24 V
DIN1
5
DIN2
6
DIN3
7
DIN4
8
DIN5
16
DIN6
Motor PTC KTY84
0 - 20 mA
max. 500
0 - 20 mA
max. 500
17
PNP
or
NPN
28
+
24 V
_
30 V DC / 5 A (resistive) 250 V AC / 2 A (inductive)
Relay1
Relay2
Relay3
1
2
3
4
10
11
5
6
7
8
16
17
9
28
14
15
12
13
26
27
20
19
18
22
21
25
24
23
29
30
ADC1+
ADC1-
ADC2+
ADC2-
DIN1
DIN2
DIN3
DIN4
DIN5
DIN6
PTCA
PTCB
DAC1+
DAC1-
DAC2+
DAC2-
COM
NO
NC
COM
NO
COM
NO
NC
P+
N-
+10 V
0 V
Output +24 V max. 1 00 mA (isolated) Output 0 V max. 1 00 mA (isolated)
A/D
D/A
D/A
RS485
CB
Option
A/D
A/D
Opto Isolation
COM link
automatic
CPU
1/3 AC 200 - 240 V 3 AC 380 - 480 V 3 AC 500 - 600 V
BOP link
Frame sizes
A to F
Frame sizes
FX and GX
ADC1ADC
0 - 20 mA current
0 - 10 V voltage
12
RS232
150.00
Hz
Fn
I
Jog
P
0
BOP/AOP
Not
used
12
DIP switch
(on Control Board)
2
DIP switch (on I/O Board)
60 Hz
50 Hz
PE
~
=
PE
SI
L/L1, N/L2
or
L/L1, N/L2,L3
or
L1, L2, L3
=
3 ~
U,V,W
M
DC-
DCNA
DCPA
DCNS
DCPS
B+/DC+
B-
R
External braking
Connection for
module connection
dv/dt filter
Fig. 2-10 Block diagram
MICROMASTER 440
22 Operating Instructions (Compact)
Issue 10/06 3 Factory setting

3 Factory setting

The MICROMASTER 440 frequency inverter is set in the factory so that it can be operated without any additional parameterization. To do this, the motor parameters set in the factory (P0304, P0305, P0307, P0310), that correspond to a 4-pole 1LA7 Siemens motor, must match the rated data of the connected motor (refer to the rating plate).
Further factory setting:
¾ Command sources P0700 = 2 (Digital input, see Fig. 3-1) ¾ Setpoint source P1000 = 2 (Analog input, see Fig. 3-1) ¾ Motor cooling
P0335 = 0
¾ Motor current limit
P0640 = 150 %
¾ Min. frequency
P1080 = 0 Hz
¾ Max. frequency
P1082 = 50 Hz
¾ Ramp-up time
P1120 = 10 s
¾ Ramp-down time
P1121 = 10 s
¾ Control mode
P1300 = 0
Analog output
Input/Output Terminals Parameter Function
Digital input 1 5 P0701 = 1 ON / OFF1 (I/O) Digital input 2 6 P0702 = 12 Reversing ( ) Digital input 3 7 P0703 = 9 Fault acknowledge (Ack) Digital input 4 8 Digital input 5 16 Digital input 6 17 Digital input 7 Via ADC1 Digital input 8 Via ADC2

3.1 50/60 Hz DIP switch

The default motor base frequency of the MICROMASTER inverter is 50 Hz. For motors, which are designed for a base frequency of 60 Hz, the inverters can be set to this frequency using the DIP50/60 switch.
¾ OFF position:
European defaults (Rated motor frequency = 50 Hz, Power in kW etc.)
¾ ON position:
North American defaults (Rated motor frequency = 60 Hz, Power in hp etc.)
Fig. 3-1 Pre-assignment of the inputs
P0704 = 15 Fault acknowledge P0705 = 15 Fixed setpoint (direct) P0706 = 15 Fixed setpoint (direct) P0707 = 0 Fixed setpoint (direct) P0708 = 0 Digital input disabled
DIP50/60
Remove I/O board
MICROMASTER 440 Operating Instructions (Compact)
23
4 Communications Issue 10/06

4 Communications

4.1 Establishing communications MICROMASTER 440 STARTER
The following optional components are additionally required in order to establish communications between STARTER and MICROMASTER 440:
¾ PC <-> frequency inverter connecting set ¾ BOP if the USS standard values (refer to Section 6.4.1 "Serial Interface (USS)")
are changed in the MICROMASTER 440 frequency inverter
PC <-> frequency inverter connecting set MICROMASTER 440
USS settings, refer to 6.4.1 "Serial Interface (USS)"
STARTER
Menu, Options --> Set PG/PC interface
--> Select "PC COM-Port (USS)" --> Properties --> Interface "COM1", select a baud rate
NOTE
The USS parameter settings in the MICROMASTER 440 frequency inverter and the settings in STARTER must match!
4.2 Establishing communications MICROMASTER 440 AOP
¾ Communications between AOP and MM440 are based on the USS protocol,
analog to STARTER and MM440.
¾ Contrary to the BOP, the appropriate communication parameters - both for the
MM440 as well as for AOP - should be set if the automatic interface detection was not carried-out (refer to Table 4-1).
¾ Using the optional components, the AOP can be connected to the
communication interfaces (refer to Table 4-1).
Table 4-1
AOP at the BOP link AOP at the COM link
MM440 parameters
- baud rate
- bus address AOP parameters
- baud rate
- bus address Options
- direct connection
- indirect connection
No option necessary BOP/AOP door mounting kit (6SE6400-0PM00-0AA0)
P2010[1]
P8553
P2010[0]
P2011
P8553 P8552
Not possible AOP door mounting kit (6SE6400-0MD00-0AA0)
MICROMASTER 440
24 Operating Instructions (Compact)
Loading...
+ 54 hidden pages