Siemens 3AH3, 3AH33, 3AH30 Operating Instructions Manual

Page 1
© Siemens AG 1996. All rights reserved.
3AH3
Vacuum circuit-breaker 3AH30 ... 3AH33
OPERATING INSTRUCTIONS
Siemens Parts
Page 2
2 9229 9860 176 0E
2013-08-22
For your safety
Signal terms and defini-
tions
Hazards are classified in accordance with ISO 3864-2 using the following keywords:
DANGER, WARNING or CAUTION, where there is a risk of personal injury
NOTE, where there is a risk of material damage. Hazards are classified and indicated in the operating instructions and on the vacuum
circuit-breaker as follows:
Qualified personnel are, for the purposes of this manual or the warning notices on the vacuum circuit-
breaker, persons who are familiar with the transport, storage, placement, assembly, commissioning, operation and maintenance of the product and have the qualifica­tions corresponding to their activity, such as:
training and authorization to energise, de-energise, clear, earth and tag circuits and equipment in accordance with established safety practices.
training in the proper care and use of protective equipment in accordance with established safety practices;
training in providing first aid.
Product liability
DANGER
signal word used to indicate an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING
signal word used to indicate a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
signal word used to indicate a potentially hazardous situation which, if not avoided, could result in minor or moderate injury.
Note
indicates a potentially damaging situation. If the damaging situation is not avoided, the product or something in its vicinity
may sustain damage.
Note
Product liability claims are upheld only if the replacement of the purchased spare parts is performed by personnel that have been trained and certified by Sie­mens.
Page 3
9229 9860 176 0E 3 2013-08-22
Table of contents
For your safety .................................. ................................................................ ................................................. 2
Transport, storage and packing .............................. ............. ............. ............. ............. ............ ............. ....... 5
Transport ................................ ................ ................ ................ ................. ................ ..............................................5
Unpacking (I) .........................................................................................................................................................6
Unpacking (II) ..................................................................................................................................................... 10
Unpacking (III) .................................................................................................................................................... 12
Reusing the transport unit .................................................................................................................................. 15
Storage ...............................................................................................................................................................15
General information ....................................................................................................................................... 17
Range of application ...........................................................................................................................................17
Standards ..................................... ................. ................ ................ ................ ..................................................... 18
Design approval as per X-Ray Ordinance ..........................................................................................................18
Scope of delivery ................................................................................................................................................18
Description ........................................................................................................................................................ 19
Design ....................................... ................................................. .........................................................................19
Locking devices ................................................................................................................................................. 32
Rating plate ...................................... .......................................... ... ... .................................................................. 35
Technical data .....................................................................................................................................................35
Ambient conditions ............................................................................................................................................. 36
Installation altitudes ............................................................................................................................................36
Switching times .................................................................................................................................................. 37
Circuit diagrams ................................................................................................................................................. 38
Mounting ....................................... .......................... ............................. ............................. .................................. 43
Attachment in the switching cubicle .............................................................. ... ... .... ... .........................................43
Earthing ..................................... .................... ................... ................... .................... ........................................... 45
Electrical connection of the prime conductor ................................................................... .... ... ........................... 47
Operation .......................................... ................................ ............................. ..................................................... 49
Commissioning ...................................................................................................................................................49
First closing operation .........................................................................................................................................50
Closing ................................................................................ ................................................................................51
Opening ..............................................................................................................................................................51
Maintenance .................................... ................................................................... ............................................... 53
Maintenance and servicing .................................................................................................................................53
Interrupter service life ..... .... ... ... ... .... .......................................... ... ... .................................................................. 56
Accessories and spare parts ...............................................................................................................................56
Manufacturer's product liability ........................................................................................................................... 57
Disposal ..............................................................................................................................................................57
Service ................................... ............................................................................. ................................................57
Index of keywords .......................................................................................................................................... 59
Legend for all pages ...................................................................................................................................... 61
Note
Sections with Addendum (I), (II) or (III)
Sections with Addendum (I) refer to vacuum circuit-breakers with a rated operating current of < 3150 A. Sections with Addendum (II) refer to vacuum circuit-breakers packed with brackets with vertical connecting bars and a rated operating current of 4000 A. Sections with Addendum (III) refer to vacuum circuit-breakers with a rated operating current of  3150 A. If no addendum is given, the information is applicable for all 3AH3 vacuum circuit-breakers.
Siemens Parts
Page 4
4 9229 9860 176 0E
2013-08-22
Blank page
Page 5
Transport, storage and packing
9229 9860 176 0E 5 2013-08-22
Transport, storage and packing
Transport
Transport weight Refer to the delivery slip for the weight of the transport unit.
Place the transport unit on a level, non-slip and pressure-resistant surface for inter­mediate storage.
Transport vacuum circuit-breaker in the original transport unit up to the installation site or storage location.
Transporting with crane or fork lift
WARNING
Heavy transport weight
Transport unit may fall and fail and sling gear may break. Use lifting gear, transporting and sling gear suited to the requirements and load-
carrying capacity. Observe transport symbols.
Note
Observe stacking height
For transport, no more than three constructionally identical transport units must be piled on top of each other.
Observe the loads specified on the transport unit.
Note
Secure load
For transport, secure the load in such a way that the transport unit is not at risk.
Fig. 1 Transporting the pallet with carton (I) Fig. 2 Transporting the wooden case (III)
Siemens Parts
Page 6
Transport, storage and packing
6 9229 9860 176 0E
2013-08-22
Transporting with packing Transport the transport unit to the installation site or storage location
with a fork lift or
with sling gear suspended from a crane
- at an angle of twist of approx. 60° or
- with a spreader bar.
After receipt of delivery:
Checking the transport
unit
Check transport unit for damage.
Major damage must be documented photographically.
Ensure that any damage to the transport unit is confirmed by the transport com­pany.
Unpacking (I)
Working equipment Required tools:
- Knife/scissors
- Lifting equipment with lifting gear
- Pliers or lever.
Opening the transport unit Place the transport unit on a level, non-slip and pressure-resistant surface.
Remove lifting gear or transport means.
Remove plastic wrap.
Lever out fasteners from the carton and lift off carton.
CAUTION
Risk of injury from sharp edges!
Fasteners may break, leaving sharp edges. Always use a suitable tool to lever out fasteners.
Note
Do not cut open or damage the carton, since it is designed t o be reused and because of the belt straps located underneath.
Belt straps could be severed on the pallet floor when cutting open the carton. The vacuum circuit-breaker is attached to the pallet with belt straps. It is not pos-
sible to transport the vacuum circuit-breaker on the pallet without using belt strap s (see Fig. 5).
Fig. 3 Removing the carton
Page 7
Transport, storage and packing
9229 9860 176 0E 7 2013-08-22
Remove partitions and accessory pack and store safely in the packaging for later attachment.
Remove film from the vacuum circuit-breaker.
In the case of overseas packaging, push the lower film onto the pallet floor.
Check the delivery is complete.
Check vacuum circuit-breaker for damage.
If the vacuum circuit-breaker is damaged, ship it back in the original transport unit (see “Reusing the transport unit”, page 15).
Transporting with pallet,
without carton
The vacuum circuit-breaker can be transported with the pallet, without the carton.
Thread carrying straps under the pallet or
transport with fork lift.
Note
Do not use the vacuum circuit-breaker if parts are broken, i.e. if you find cracks, flaking, bent metal parts, damaged plug-in contacts, tears or bare cables.
Send it back in its original transport unit (see “Reusing the transport unit”, page 15).
Note
Carrying straps may scrape along the vacuum circuit-breaker and damage it. If necessary, cover carrying straps with edge protection. Select length and position of the carrying straps so that the pole heads are not
compressed.
Fig. 4 Removing partitions and film Fig. 5 Transporting with pallet possible
Siemens Parts
Page 8
Transport, storage and packing
8 9229 9860 176 0E
2013-08-22
Transporting without pallet Remove all tensioning belts and bits of fastening wood.
Remove accessory pack, if applicable.
Screw suitable eyebolts into the outer pole heads parallel to each other.
Hang sling gear into the eyebolts.
Carefully lift vacuum circuit-breaker off the pallet just enough that pieces of square timber can be placed underneath.
Note
When fastening the eyebolts to the pole heads, ensure that the contact surfaces are not damaged.
Fig. 6 Removing the tensioning belts Fig. 7 Screwing in eyebolts and lifting the vacuum
circuit-breaker
Note
Place pieces of square timber onto the pallet in such a way that the insulating operating rods, contact pressure springs, angle levers and dashp ots are not dam­aged when setting down.
Page 9
Transport, storage and packing
9229 9860 176 0E 9 2013-08-22
Set the vacuum circuit-breaker down onto the square timbers.
Hang further sling gear into the transport boreholes.
Transport to installation site or leave suspended from crane for further work steps.
Fig. 8 Positioning the square timbers and setting
down the vacuum circuit-breaker
Fig. 9 Transporting without pallet
Siemens Parts
Page 10
Transport, storage and packing
10 9229 9860 176 0E
2013-08-22
Unpacking (II)
Variant with brackets
Remove carton as described in Fig. 1 and Fig. 3.
Working equipment Required tools:
- Knife/scissors
- Screwdriver
- Open-end wrench
- Lifting equipment with lifting gear.
Transporting with brackets Remove partitions and accessory pack and store safely in the packaging for
later attachment.
Attach suitable bolt in the middle pole head.
Attach sling gear to bolt and to transport boreholes.
Fig. 10 Removing partitions and film Fig. 11 Lifting the vacuum circuit-breaker
Page 11
Transport, storage and packing
9229 9860 176 0E 11 2013-08-22
Transporting without
brackets
Only lift the vacuum circuit-breaker far enough to put all sling gear under ten­sion.
Remove angle plate and bracket screws from the pallet.
Lift the vacuum circuit-breaker from the pallet.
Remove all screw connections from the brackets on the pole plate and the ter­minals.
Remove angle plate below mechanism box.
Transport to installation site or leave suspended from crane for further work steps.
Fig. 12 Removing screws from the pallet Fig. 13 Removing the angle plate and brackets
Siemens Parts
Page 12
Transport, storage and packing
12 9229 9860 176 0E
2013-08-22
Unpacking (III)
Working equipment Required tools:
- Screwdriver
- Knife/scissors
- Lifting equipment with lifting gear.
Opening the transport unit Place the transport unit on a level, non-slip and pressure-resistant surface.
Remove lifting gear or transport means.
Unscrew all the screws from the cover and lift it off.
Remove partitions and store safely in the packaging for later attachment.
Note
Do not use the vacuum circuit-breaker if parts are broken, i.e. if you find cracks, flaking, bent metal parts, damaged plug-in contacts, tears or bare cables.
Send it back in its original transport unit (see “Reusing the transport unit”, page 15).
Fig. 14 Removing the cover Fig. 15 Taking out the partitions
Page 13
Transport, storage and packing
9229 9860 176 0E 13 2013-08-22
Unscrew all the screws from the side walls.
Take the supports out of the transport unit.
Remove the side walls.
Remove accessory pack and store safely in the packaging for late r attachment.
Remove film from the vacuum circuit-breaker.
Check the vacuum circuit-breaker for damage.
Undo tensioning belts, if applicable.
Fig. 16 Removing the supports Fig. 17 Removing the side walls
Fig. 18 Taking out the accessory pack Fig. 19 Removing the film
Siemens Parts
Page 14
Transport, storage and packing
14 9229 9860 176 0E
2013-08-22
Transporting to the instal-
lation site
Hook crane hooks into the transport screws and into the openings on the mech­anism box.
Observe crane hook symbols.
Vertically lift out vacuum circuit-breaker.
Transport to installation site or leave suspended from crane for further work steps.
CAUTION
Crushing hazard
Hands may get crushed when lifting out the vacuum circuit-breaker. Do not reach between the transport box and the vacuum circuit-breaker.
Fig. 20 Preparing for lifting out Fig. 21 Lifting out
Note
Keep partitions and accessory pack ready for the installation.
Page 15
Transport, storage and packing
9229 9860 176 0E 15 2013-08-22
Reusing the transport unit
Reusing the transport unit To transport the vacuum circuit-breaker again, the pallet with carton or the wooden
case with the most components can be reused. Do not reuse severed tensioning belts or plastic wrap. Pack the vacuum circuit-breaker in reverse order:
Attach the vacuum circuit-breaker safely to the pallet using the appropriate tools.
Cover with film and seal with adhesive tape.
Attach accessories pack.
Attach carton securely to the pallet floor.
Screw the wooden case back together.
Before returning to the factory, ask the responsible sales representative for a returned goods number (see also “Service”, on page 57).
When returning a vacuum circuit-breaker, always indicate the type and serial number (see “Rating plate”, on page 35).
Storage
Note
Store the vacuum circuit-breaker in the following condition:
OPEN switching position
Closing spring discharged
Note
Risk of corrosion damage if stored improperly!
If the storage conditions listed below are met, the vacuum circuit-breaker can be stored for up to a year in its transport unit.
If the storage conditions are not met, the vacuum circuit-breaker ca nnot be stored in the transport unit any longer than 6 months.
If storage of longer than one year is planned, unpack the vacuum circuit-breaker from the transport unit. Further storage may necessitate fresh corrosion protec­tion, and it must be ensured that the vacuum circuit-breaker cannot be damaged.
Storage room Transport unit Storage
time
Temperature range
Comments Number of
units per stack
Enclosed, dry, well ventilated and as free from dust as possible, with a rela­tive humidity of less than 60 %.
unopened
max. 6months
-40°C to +55°C max. 4
unopened
max. 1 year
-5 °C to +40 °C max. 4
open over 1 year -5 °C to +40 °C
if necessary, with new corro­sion protection
Siemens Parts
Page 16
Transport, storage and packing
16 9229 9860 176 0E
2013-08-22
Blank page
Page 17
General information
9229 9860 176 0E 17 2013-08-22
General information
Smooth and safe operation of this device requires proper transport and storage, a nd professional installation and assembly, as well as careful operation and mainte­nance.
The basic version and all listed configurations of the vacuum circuit-breakers are type-tested devices as per IEC.
Range of application
3AH3 vacuum circuit-breakers are 3-pole interior circuit-breakers for a rated voltage range of 7.2 kV - 36 kV.
Under normal operating conditions, the vacuum circuit-breaker (as per IEC 62271-1 and VDE 0671-1) is maintenance-free up to 10 000 operating cycles.
Intended use 3AH3 vacuum circuit-breakers are suitable for switching any type of alternating cur-
rent circuits under normal operating conditions, such as:
Three-phase motors for reversing, turning and direct operation
Transformers
Capacitors
Resistor consumers
Suitable for high frequency of operation and unlimited on-time. 3AH3 vacuum circuit-breakers operate in continuous, periodic and short-term oper-
ation.
WARNING
Dangerous voltage and mechanical movements When operating electrical devices, certain parts will always be live, and
mechanical parts may move very quickly, even when remotely controlled.
If the warnings are not observed, serious injury or damage to material may be the result.
Only personnel with the relevant qualifications may work on or in the vicinity of this device. These personnel must be familiar with all the warnings and servicing measures specified in these operating instructions.
Note
In the event of subsequent attachments or integrations, e. g. locking parts in con­nection with switchgears, ensure that
fast-moving parts are not additionally loaded with mass or force, and
additional parts have sufficient clearance, especially from moving and live parts.
If vacuum circuit-breakers are to be equipped with additional functions by the cus­tomer, we recommend consulting the factory, since tried and tested solutions are frequently available (see also “Additional equipment” on page 23).
Siemens Parts
Page 18
General information
18 9229 9860 176 0E
2013-08-22
Standards
The 3AH3 vacuum circuit-breakers comply with the regulations:
IEC 62271-1 and
IEC 62271-100 All 3AH3 vacuum circuit-breakers comply with the specifications for C2-, E2- and
M2-class circuit-breakers in accordance with IEC 62271-100.
Design approval as per X-Ray Ordinance
The vacuum interrupters installed in th e vacuum circuit-breakers are of a design approved under the X-Ray Ordinance (RöV) of the Federal Republic of Germany. They meet the requirements of RöV of 8 January 1987 (BGbl. I, page 114) § 8 and Annex II No. 5 up to the level of the rated voltage stipulated according to DIN VDE/IEC.
Scope of delivery
Delivery includes:
Vacuum circuit-breaker 3AH3
Hand crank for circuit-breaker 3AX 1530-2B (optional)
If applicable, partitions with mounting drawing
Operating instructions and unpacking instructions
Circuit-breaker-specific circuit diagrams
Page 19
Description
9229 9860 176 0E 19 2013-08-22
Description
Design
Vacuum circuit-breaker The 3AH3 vacuum circuit-breaker consists of
the mechanism box (60.),
the 3 pole assemblies (19.) with vacuum interrupters (30.),
the cast resin post insulators (16.1 and 16.2) with reinforcing struts (28.) and
the insulating operating rods (48.) with contact pressure springs (49.) required for contact actuation.
Each of the 3 pole assemblies (19.) is carried by the cast resin post insulators (16.1 and 16.2) that are screwed to the pole plate (15.).
Fig. 22 Side view
15. Pole plate
16.1 Upper post insulator
16.2 Lower post insulator
19. Pole assembly, complete
28. Strut
30. Interrupter
48. Insulating operating rods
49. Contact pressure spring
60. Mechanism box
Siemens Parts
Page 20
Description
20 9229 9860 176 0E
2013-08-22
Pole assembly The pole assembly (19.) of the 3AH3 vacuum circuit-breaker consists of
the upper interrupter support (20.)
with the upper terminal (27.)
the vacuum interrupter (30.),
the lower interrupter support (40.) with the lower terminal (29.) and the clamp (29.2) with flexible connector (29.1);
as well as the angle lever (48.6.).
The centering (28.1) and the struts (28.) relieve the vacuum interrupters of external forces.
Contact system in the interrupters
A slight change in the contact stroke that occurs over the entire useful life of the interrupter has no effect on the function of the vacuum circuit-breaker. There is no need for a status indicator for the contact system.
Fig. 23 Pole assembly (I) Fig. 24 Pole assembly (II and III)
19. Pole a ssembly 29.1 Flexible connector
20. Upper inter rupter support 29.2 Clamp
27. Upper terminal 30. Interrupter
28. Strut 40. Lower interrupter support
28.1 Centering 48.6 Angle lever
29. Lower terminal
Page 21
Description
9229 9860 176 0E 21 2013-08-22
Mechanism box The mechanism box (60.) contains all the electrical and mechanical components
required to switch the vacuum circuit-breaker on or off. Insulating operating rods (48.) transfer the switching movement to the pole assemblies.
The mechanism box is closed with a removable cover (60.1).
There are openings in the cover (60.1) for the operating and indicator elements.
Functions The CLOSE pushbutton (53.) is used to close the vacuum circuit-breaker. The motor
(50.4) immediately charges the closing spring (62.). If the supply voltage for the motor fails, the closing spring can be charged with a hand crank (50.). There is an opening (50.1) for this in the cover, behind which you will find the hand crank cou­pling (50.5) of the gear unit (50.2).
Indicators The charged state of the springs is indicated via the spring state indicator (55.). The
position indicator (59.) shows th e CLOSED or OPEN state. The operating cycle counter (58.) indicates the number of operating cycles. An operating cycle consists of one closing and one opening. The rating plate (51.) is attached to the mechanism box and readable through an opening (51.1) in the cover.
Fig. 25 Operating and indicator elements
50.1 Opening for hand crank 58. Operating cycle counter
51. Rating plate 59. Position indicator CLOSED-OPEN
53. CLOSE pushbutton 60.1 Cover
54. OPEN pushbutton a) Tightening torque Md = 10 Nm
55. Spring state indicator
Siemens Parts
Page 22
Description
22 9229 9860 176 0E
2013-08-22
Fig. 26 Opened mechanism box
50.2 Gear unit
50.4 Motor M1
50.4.1 Position switch
50.5 Hand crank coupling
51. Rating plate
53.1 Closing solenoid Y9
54.1 Shunt release Y1
54.2 Shunt release Y2
54.3 Transformer-operated release Y4
54.4 Undervoltage release Y7
54.5 Transformer-operated release (0.1 Ws) Y6
55. Spring state indicator
58. Operating cycle counter
59. Position indicator CLOSED-OPEN
60. Mechanism box
61. Dashpot
62. Closing spring
63. Circuit-breaker shaft
64. Opening spring
66. Closing damper
68. Auxiliary switch S1
68.1 Operating rod (for auxiliary switch S1)
68.7 Low-voltage interface X0
69. Contactor relay K1
70. Earth terminal
71. Heater R01 (condensation water protection)
Page 23
Description
9229 9860 176 0E 23 2013-08-22
Equipment
Basic equipment The basic equipment of the 3AH3 vacuum circuit-breaker contains:
Additional equipment Every 3AH3 vacuum circuit-breaker can also be fitted with the follo wi ng e qui pme nt:
In addition to the serial shunt release (Y1), the vacuum circuit-breaker can be equipped with a maximum of 2 releases of the type 3AX11.
For the permitted possible combinations of the additional equipment as well as spe­cial designs, refer to catalogue HG11, or contact the responsible sales representa­tive.
Motor (M1) Contactor relay (electrical anti-pumpin g de vic e) (K1) Closing solenoid (Y9) shunt release (Y1) Auxiliary switch (optional) (S1)
•6NO + 6NC
•12NO + 12NC Position switch for signal “Closing spring charged” (S41, S42) Circuit-breaker tripping signal, cut-out switch (S6, S7) Low-voltage interface (optional) (X0)
Plug-connector with sleeve housing 64-pole
Plug-connector with sleeve housing 24-pole
Terminal strip (X1) Operating cycle counter Mechanical anti-pumping device Mechanical manual closing and opening
Shunt release
1)
3AX1101
1) Subsequent installation possible
(Y2, Y3)
Transformer-operated release 3AX1102
1)
(Y4, Y5)
Transformer-operated release 3AX1104 (0.1 AC)
1)
(Y6)
Undervoltage release 3AX1103
1)
(Y7)
Heater (condensation water protection)
1)
(R01)
Electrical manual closing
2)
Mechanical locking device
1)
Spring charge release
2)
2) No subsequent installation possible
Priority opening
2)
Siemens Parts
Page 24
Description
24 9229 9860 176 0E
2013-08-22
Motor M1
*) The operator's supply voltage may deviate from the rated su pply voltag e of the
vacuum circuit-breaker by -15 % to +10 %.
**) Built-in automatic circuit-breaker with C characteristic. Fig. 28 Recommendation for motor protection device
Contactor relay K1
After the supply voltage is applied and if the closing spring is discharged, the motor starts immediately and is automatically deactivated internally after charging has taken place.
Power consumption, maximum:
in the event of direct voltage approx. 750 W
in the event of alternating voltage 1400 W. In the short charging time, the motor temporarily oper-
ates in the overload range. See Fig. 28 for the rated cur­rent for the required motor short-circuit protection.
Note: The motor protection devices are not included in the delivery of the vacuum circuit-breaker and must be ordered separately.
Fig. 27 Motor (50.4)
Rated supply voltage U*)
VDC24DC48DC60DC110
AC 50/60 Hz
110
DC
220
AC 50/60 Hz
230
Recommended rated current of the protective device I**
)
A16106462 3
If simultaneous CLOSE and OPEN commands are con­tinuously applied to the vacuum circuit-breaker, it returns to the open position after being closed.
Via the function of the contactor relay K1, the vacuum circuit-breaker pauses there until the CLOSE command is given again.
This prevents continuous closing and opening (pump­ing).
Fig. 29 Contactor relay (69.)
Page 25
Description
9229 9860 176 0E 25 2013-08-22
Closing solenoid (Y9) 3AY1510
1st shunt release (Y1) 3AY1510
The closing solenoid Y9 unlatches the charged closing spring and switches the vacuum circuit-breaker on elec­trically. It is available for DC or AC voltage.
The closing solenoid Y9 is not designed for con tinuous operation and is automatically deactivated within the cir­cuit-breaker.
The operator's supply voltage may deviate from the rated supply voltage of the vacuum cir cuit-breaker by ­15 % to 10 %.
The closing solenoid Y9 can be operated using AC or DC voltage and is protected against overvoltage.
Power consumption is approximately 140 W / VA
Fig. 30 Closing solenoid (53.1)
In the case of the 1st shunt release Y1, the electrically fed tripping pulse is passed to the “OPEN” latch by means of a directly acting magnet armature, thus switch­ing off the vacuum circuit-breaker.
The 1st shunt release Y1 is not designed for continuous operation and is automatically deactivated within the circuit-breaker.
The operator's supply voltage may deviate from the rated supply voltage of the vacuum cir cuit-breaker by ­30 % to +10 % in the event of DC voltage and by -15 % to +10 % in the event of AC voltage.
The 1st shunt release Y1 can be operated using AC or DC voltage and is protected against overvoltage.
Power consumption is approximately 140 W / VA
Fig. 31 1st shunt release (54.1)
Siemens Parts
Page 26
Description
26 9229 9860 176 0E
2013-08-22
Auxiliary switch S1
Breaking capacity
Fig. 33 Breaking capacity of the auxiliary switch 3SV92
Two versions of the auxiliary switch S1 are available for delivery: with 6 or 12 NO/NC contacts each.
Rated insulation voltage: 250 V AC/DC Insulation group: C as per VDE 0110 Continuous current: 10 A Closing capacity: 50 A
Fig. 32 Auxiliary switch (68.)
AC 40 to 60 Hz DC
Operating voltage Operating current Operating voltage Operating current
U (V) I (A) U (V) I (A)
Ohmic load Inductive load
(T = 20 ms)
Up to 230 10
24 10 10 48 10 9
60 9 7 110 5 4 220 2.5 2
Page 27
Description
9229 9860 176 0E 27 2013-08-22
Position switch
Circuit-breaker tripping signal, cut-out switch (S6, S7)
S21, S22 Position switches (switch off the motor after
charging)
S3 Position switch (opens when closing spring
is charged)
S41, S42 Position switches (report charging state)
Fig. 34 Position switch (50.4.1)
The position switch S6 makes contact briefly when the vacuum circuit-breaker is opened by means of an elec­trical release.
This contacting can be used for a signal. In the event of intentional mechanical open ing, the cut-
out switch S7 interrupts the contacting.
Fig. 35 Circuit-breaker tripping signal
Siemens Parts
Page 28
Description
28 9229 9860 176 0E
2013-08-22
Low-voltage interface X0, 64-pole
For connection of the control line, the standard version of the vacuum circuit-br eak­ers is equipped with a 64-pole low-voltage interface X0 (68.7).
The 64-pole plug (68.7.1) for the e xterna l termin al, is suitab le for crimp termina tion of control lines with a nominal cross-section of 1.5 mm
2
.
Terminal strip (optional) Instead of the 64-pole plug (68.7.1), a terminal str ip (68.7.2) can be ordered as inter-
face to the terminal at the customer's site.. Assignment of the ter minals is done according to the circuit diagram supplied.
Fig. 36 Low-voltage interface X0 Fig. 37 Terminal strip (optional )
Page 29
Description
9229 9860 176 0E 29 2013-08-22
A further shunt release, transformer-operated release, undervoltage release or instantaneous release can be installed as a 2nd release.
2nd shunt release (Y2) 3AX1101
Transformer-operated releases (Y4, Y5) 3AX1102, (Y6) 3AX1104
The second shunt release Y2 is installed whenever more than one shunt release is needed.
In this version, the electrical “open” command is passed by means of a magnet armature to the “OPEN” latch by release of an energy storage mechanism, thus opening the vacuum circuit-breaker. This opening solenoid is not designed for continuous operation. Any necessary varis­tors and rectifiers are integrated in the release.
Power consumption is approximately 60 W / VA
Fig. 38 2. Shunt release (54.2)
The transformer-operated releases Y4, Y5 or Y6 co nsist of an energy storage mechanism, an unlatching fixture and an electromagnetic system. If the tripping current is exceeded (90 % of the transformer-operated release's rated current), the energy storage mechanism is unlatched, thus initiating opening of the vacuum circuit­breaker.
For use of the transformer-operated release, matching transformers are also needed for matching, in addition to the main current transformers.
Power consumption for 0.5 A and 1 A 6 VA at ≤ 90 % of the transformer-operated release's rated current and with open armature.
Fig. 39 Transformer-operated releases (54.3)
Siemens Parts
Page 30
Description
30 9229 9860 176 0E
2013-08-22
Undervoltage release (Y7) 3AX1103
The undervoltage release Y7 has an electromagnet system that has voltage perma­nently applied to it when the vacuum circuit-breaker is in the closed state. If the volt­age drops below a certain value, the undervoltage release Y7 is unlatched, thus initiating opening of the vacuum circuit-breaker via the stored energy mechanism.
Random tripping of the undervoltage release Y7 is generally performed by an NC contact in the tripping circuit, but can also be done with the aid of an NO contact by short-circuiting the solenoid coil. If this latter method is used, the solenoid coil's short-circuit current is limited by the built-in resist or .
The undervoltage release Y7 can also be connected to voltage transformers. The undervoltage release Y7 automatically trips the vacuum circuit-breaker if the
rated supply voltage drops to an inadmissible value. Any necessary varistors and rectifiers are integrated in the release.
Power consumption 6.5 W or ≤ 7.5 VA
Note
The undervoltage release Y7 must only be operated with the supplied series resistor R1.
Note
For switching operations (mechanical or electrical), the undervoltage release 3AX1103… must be connected to control voltage, as otherwise closing is not pos­sible.
Fig. 40 Undervoltage release (54.4) Fig. 41 Typical circuit for connection of the undervolt-
age release Y7
A
B
R1 resistor S1 auxiliary switch Y7 undervoltage release
Page 31
Description
9229 9860 176 0E 31 2013-08-22
Heater (condensation water protection)
Electrical manual closing/electr. locking device
In the basic version, the vacuum circuit-breaker with on-site connection is closed by direct mechanical unlatching of th e clos ing spring. Instead of this mechanical man­ual closing, “electrical manual closing” is also available.
In this version, the closing circuit of the vacuum circuit-breaker module is electrically actuated by a sensing device and must also be enabled via a command element from the control room.
With on-site closing, this permits taking into account system-related interlocking and allows you to prevent unintentional closing by the control room, for example. This allows for interlocking the vacuum circuit-breaker module, for example, via the aux­iliary contact of a disconnector.
Vacuum circuit-breakers with electrical manual closing cannot be switched mechanically.
The heater limits condensation and corrosion of the vac­uum circuit-breaker.
To this end, the heater has to be connected to the sup­ply voltage (see circuit diagram included with the deliv­ery).
The heater's surface temperature is at the most 180 °C. Power consumption 50 W
Fig. 42 Heater (71.)
Siemens Parts
Page 32
Description
32 9229 9860 176 0E
2013-08-22
Locking devices
To lock vacuum circuit-breakers as a function of the switching position, the spring drive mechanisms of the vacuum circuit-breaker can be equipped with a locking device. This is also the case for vacuum circuit-breakers on switch gear trucks, in withdrawable sections or with disconnectors.
Conditions The vacuum circuit-breaker must only be switched on in operating or disconnected
position. The operating or disconnected position is the position of the vacuum circuit­breaker on the switchgear truck or withdr awable section in the switchgear. At the same time, the vacuum circuit-breaker may be moved on the switchgear truck or withdrawable section only when it is open.
Positions of the vacuum circuit-breaker in the switchgear
Disconnected position The isolating distance between the vacuum circuit-breaker contacts and the switch-
gear counter-contacts is attained fully.
Operating position The circuit-breaker is inserted fully into the switchgear and the vacuum circuit-
breaker contacts overlap completely with the switchgear counter-contacts.
Mechanical locking device (optional with spring drive mechanism)
A sensing and actuation component (b) on the system side detects the operating position (CLOSED/OPEN) of the vacuum circuit-breaker.
CLOSED switching posi-
tion
If the vacuum circuit-breaker is closed, actuation of the system's sensing and actu­ation component (b) is prevented. A mechanical system in the switchgear truck or withdrawable section reliably blocks movements of the circuit-breaker on the switch­gear truck or withdrawable section.
OPEN switching position If the vacuum circuit-breaker is open, the sensing and actuation component (b) on
the system side actuates, via the stroke (a), the vacuum circuit-breaker's mechani­cal locking device and reliably blocks closing of the vacuum circuit-br ea ke r.
Fig. 43 Mechanical locking device The installation dimensions (c + d) for the sensing and actuation component (b) a re
in the dimension drawing.
X CLOSED switching position a Stroke (min. 10 mm, max. 30 mm) Y OPEN switching position b Interrogation or actuation component (min. actuation force 70 N) Z View from below c + d see dimension drawing
Page 33
Description
9229 9860 176 0E 33 2013-08-22
Spring charge release
The springcharge release (72.) is an assembly that prevents removing the plug (68.7.1) from the vacuum circuit-breaker when it is closed.
Fig. 44 Spring chargerelease The lever (72.1) of the spring charge r elea se o n the m echa nism box lo cks the leve r
of the plug in idle position (a). When the lever of the springcharge releas e is brought into operating position (b),
opening is reliably done via the mechanics of the vacuum circuit-breakers and the closing latch is cancelled.
A no-load switching operation is done in the course of this. Only now is it possible to undo the plug of the low-voltage interface.
a)
b)
a) Idle position – CLOSED switching position b) Operating position – OPEN switching position
68.7 Low-voltage interface
68.7.1 Plug
72. Spring chargerelease
72.1 Lever of the springcharge release
Note
The spring charge release can also be combined with a mechanical locking device.
Siemens Parts
Page 34
Description
34 9229 9860 176 0E
2013-08-22
Priority opening
To lock the OPEN position, the drive mechanisms of the vacuum circuit-breaker can be equipped with “priority opening”. This is al so the case for vacuum circuit-bre akers on switch gear trucks, in withdrawable sections or with disconnectors.
Fig. 45 Priority opening The assembly “priority opening” has three positions. These positions are actuated
by an interrogation or actuation component in the system.
Trip-free position When actuating “priority opening” by putting into first position on the system (trip-free
position, b), opening is triggered, closing is prevented and reclosing is reliably pre­vented as well.
Spring-dump position In the second position (spring-dump position, c) the vacuum circuit-breaker re mains
in open condition. In addition, when actuating the locking device in the second position, the closing
spring is discharged by a no-load switching operation. The closing and the opening springs are n ow discharged and hence all of the energy
storages of the vacuum circuit-breaker are also discharged. The operating position (CLOSED/OPEN) of the vacuum circuit-breaker is not inter-
rogated with “priority opening”.
a) b) c)
a) Idle position b) Trip-free position c) Spring-dump position
*
) Interrogation or actuation component (min. actuation force 70 N)
Note
Compared to the mechanical locking device (see Fig. 32), actuation of the sys­tem's interrogation and actuation component is not prevented if the vacuum cir­cuit-breaker is closed.
Page 35
Description
9229 9860 176 0E 35 2013-08-22
Rating plate
Technical data
Fig. 47 Technical data
Dimensions and weights
The dimensions of the vacuum circuit-breaker can be taken from the relevant dimen­sion drawing. If required, these are available from your sales representative. The weight is given on the rating plate of the vacu um circuit-breaker (see Fig. 46) or can be taken from the relevant dimension drawing.
Fig. 46 Example – vacuum circuit-breaker rating plate 3AH3
a Manufacturer b Type designation c Works serial number d Rated voltage U
r
e Rated frequency f
r
f Rated short-circuit breaking current I
sc
g Rated power frequency withstand
voltage U
d
h Rated lightning impulse withstand
voltage U
p i Quality control seal k Year of manufacture m Rated operating current I
r
n Rated short-circuit duration t
k oMass m p Rated operating sequence r Classification to standard
Rated voltage* U
r
kV 7.2 12 15 17.5 24 36 (40.5)**
Rated operating current I
r
A 1250, 2500, 3150, 4000
2500, 3150,
4000
1250, 2000, 2500, 3150,
4000
2500, 3150,
4000
Rated lightning impulse withstand voltage (peak value) U
p
kV 60 75 95 95 110, 125
170
(185)**/(195)**
Rated power frequency withstand voltage (effective value) U
d
kV
20
(42)**
28
(42)**
36
(42)**
38
(42)**
50
70
(85)**/(95)**
Rated short-circuit breaking cur­rentI
sc
kA 50, 63 40, 50 31.5 40
Distance between pole centres mm 210, 275 275, 300 350 350 Rated operating sequence A, B, C A, B, C A**, B, C** A, B, C
A O - 3 min - CO - 3 min - CO; standard rated operating sequence B O - 0.3 s - CO - 3 min - CO; up to I
sc
= 31.5 kA possible
C O - 0.3 s - CO - 15 s - CO; up to I
sc
= 31.5 kA possible * In the event of a rated frequency fr of 50/60 Hz ** On request
Siemens Parts
Page 36
Description
36 9229 9860 176 0E
2013-08-22
Ambient conditions
Installation altitudes
Insulating capacity The insulating capacity of insulation in air decreases with rising altitude due to the
lower air density. In conformity with IEC 62271-102, the rated lightning impulse volt­age values given in Fig. 47 are valid up to an installation altitude of 1,000 m above sea level.
At altitudes of 1,000 m and higher, the insulation level must be corrected as shown in Fig. 49:
3AH3 vacuum circuit-breakers are suitable for use in the following climate classes in accordance with IEC 60721, Part 3-3:
Class
Climatic ambient conditions:
3K4
1)
,
3K6
2)
, 3Z2, 3Z5
Biological ambient conditions: 3B1
Mechanical ambient conditions: 3M2
Chemically active substances:
3C2
3)
Mechanically active substances:
3S2
4)
1) Peak value of the 24-hour means: +35 °C
2) Without ice formation and wind-driven precipitation
3) Without occurrence of salt fog and simultaneous condensation
4) Restriction: clean insulating parts
5) Average value, measured over 24 hours
6) Average value, measured over 1 month
Fig. 48 Ambient conditions
U U0 K
a
U Rated withstand voltage U under standard reference
atmosphere
U
0
Required rated withstand voltage for the installation location
K
a
Altitude correction factor
K
a
= em
(H – 1000)/8150
Calculating the altitude correction factor Ka: H = Installation altitude in metres m = 1 for AC voltage, lightning impulse voltage (between
phases, phase-to-earth, applied longitudinally)
Example
For a required rated withstand voltage of 75 kV at an alti­tude of 2,500 m, an insulation level of at least 90 kV under standard reference atmosphere conditions is required:
90 kV
75 kV e
1
(2500 – 1000)/8150

75 kV 1.2
Fig. 49 Altitude correction factor K
a
Page 37
Description
9229 9860 176 0E 37 2013-08-22
Switching times
Fig. 50 Switching times Closing time = period between starting (command) of the closing movement and
the moment of contact touch in all poles. Opening time = period between starting (command) o f the openin g movement a nd
opening of the last pole.
Arcing time = period from the start of the first arc to extinction of the arcs in all poles. Break-time = period between starting (command) of the opening movement and
extinction of the arc in the last pole to become extin ct (= opening time + arcing time). Close/Open time = period in an OPEN/CLOSE cycle between the moment of con-
tact touch in the first pole during closing and the time when contact touch has been cancelled in all poles during subsequent opening.
Dead-time = period from the end of the current flow in all poles up to th e start of cur­rent flow in the first pole.
Closing time < 75 ms Opening time
1. shunt release (Y1) < 60 ms
2. and 3rd release (Y2, Y4, Y6, Y7) < 55 ms Arcing time < 15 ms Break time
1. shunt release (Y1) < 75 ms
2. and 3rd release (Y2, Y4, Y6, Y7) < 70 ms Dead time 300 ms Close/Open time
1. shunt release (Y1) < 90 ms
2. and 3rd release (Y2, Y4, Y6, Y7) < 70 ms Minimum command duration Closing solenoid (Y9) 45 ms
1. shunt release (Y1) 40 ms
2. and 3rd release (Y2, Y4, Y6, Y7) 20 ms Shortest pulse time for breaker tripping signal
1. shunt release (Y1) > 15 ms
2. and 3rd release (Y2, Y4, Y6, Y7) > 10 ms Charging time if actuated electrically (M1) < 15 s Synchronous operation error between the poles 2 ms
Siemens Parts
Page 38
Description
38 9229 9860 176 0E
2013-08-22
Circuit diagrams
The circuit diagrams show all the available components with their wiring options. Fig. 51 to Fig. 57 show some non-binding examples of vacuum circuit-breakers. The circuit diagrams for the vacuum circuit-breaker are com piled depending on your
order.
Mechanical manual closing and electrical closing
Fig. 51 Example – circuit diagram connection via low-voltage interface, 64-pole,
basic version
Electrical manual closing and electrical closing
Fig. 52 Example – circuit diagram with connection via low-voltage interface 64-
pole
This legend is also valid for the following circuit diagrams.
-Y1 -Y2 -Y4
-Y4 -Y5
-Y6 -Y7
-Y7
“OPEN” release
-Y1 -Y2 -Y4
-Y4 -Y5
-Y6 -Y7
-Y7
“OPEN” release
extended auxiliary switch
HA Manual opening HE Manual closing K1 Contactor relay (anti-pumping device) M1 Motor P Energy storage mechanism R1 Resistor S1 Auxiliary switch S10, S11 Position switch (mechanical anti-pumping device) S12 Position switch (prevents electrical closing if there is a
mechanical locking device)
S21, S22 Position switches (switch off the motor after charging)
S3 Position switch (opens when closing spring is charged) S41, S42 Position switches (signal charging status) S6, S7 Position switches (for circuit-breaker tripping signal) X0 Low-voltage interface Y1 1. shunt release Y2 2. shunt release Y4, Y5, Y6 Transformer-operated release Y7 Undervoltage release Y9 Closing solenoid V6 Integrated rectifiers for motor
Page 39
Description
9229 9860 176 0E 39 2013-08-22
1) Integrated varistor
2) Integrated rectifier for AC/DC ≥ 100 V
3) Line H07V-K1x2.5sw (as per EN 50525-2-31) when motors are used with DC 24 V/48 V and 60 V
4) Only if a mechanical closing lock is ordered at the same time
a) Motor winding for DC b) Motor winding with rectifier for AC c) Closing d) Closing with anti-pumping device
Fig. 53 Sample circuit diagram 64-pole (part 1) of the vacuum circuit-breaker
a) b) c) d)
Siemens Parts
Page 40
Description
40 9229 9860 176 0E
2013-08-22
1) Integrated varistor
2) Integrated rectifier for AC/DC ≥ 100 V
a) 1st shunt release with 64-pole plug-connector b) 1st shunt release with 24-pole plug-connector c) 2nd shunt release with 64-pole plug-connector d) 2nd shunt release with 24-pole plug-connector
Fig. 54 Sample circuit diagram (part 2) of the vacuum circuit-breaker
a) b) c) d)
Page 41
Description
9229 9860 176 0E 41 2013-08-22
1) Integrated varistor
2) Integrated rectifier for AC/DC ≥ 100 V
3) Attention: connect L+ for direct current (DC)
a) Undervoltage release b) Low-energy trip-coil c) 1st transformer-operated release d) Signal: spring state with 64-pole plug-connector e) Signal: spring state with 24-pole plug-connector f) Breaker tripping signal for 64-pole plug-connector
Fig. 55 Sample circuit diagram (part 3) of the vacuum circuit-breaker
a) b) c) d) e) f)
Siemens Parts
Page 42
Description
42 9229 9860 176 0E
2013-08-22
The unassigned auxiliary switch terminals are wired up with the 64-pole plug bottom, as shown.
Fig. 56 Example – auxiliary switch terminals
Fig. 57 Sample switching operation for connection of the undervoltage release Y7
Normal auxiliary switch Extended auxiliary switch
No wiring required if a) 2nd shunt release Y2 available b) Undervoltage release Y7 available
a) b)
System wiring Tripping via NO con-
tact
Tripping via NC contact
System wiring
Circuit-breaker wiring
Page 43
Mounting
9229 9860 176 0E 43 2013-08-22
Mounting
Attachment in the switching cubicle
The vacuum circuit-breaker is delivered in the OPEN switching position. Before installing the vacuum circuit-breaker, remove the transport aids (see “Unpacking (I)” on page 6 and “Unpacking (III)” on page 12).
Check data Before installing the vacuum circuit-breaker in a switching cubicle, check the details
on the rating plate (see “Rating plate” on page 35) in order to avoid confusion.
Mounting position The 3AH3 vacuum circuit-breaker can only be installed vertically (to the vacuum
interrupter), as an indoor withdrawable section and as an indoor fixed installation.
DANGER
High-voltage – danger to life
Touching live parts causes an electric shock.
Do not touch live parts!
When performing work on the switchgear, de-energise it and earth it.
The work described in the following sections must only be performed when the switchgear has been de-energised:
- Take safety measures to prevent reclosing.
- Observe industrial safety regulations.
- Ensure that the vacuum circuit-breaker is installed and commissioned only
by qualified personnel who are familiar with the operating instructions and observe the warning notices.
WARNING
Risk of injury due to wrong transport means!
Using wrong transport means may cause the vacuum circuit-breaker to fall and injure persons.
Observe weight.
Use means of transport suited to the requirements and load-carrying capac­ity.
The vacuum circuit-breaker must not fall over.
Sharp edges may cause injury.
Note
For preliminary work, the vacuum circuit-breaker must be
secured against falling over,
placed onto a suitable support or
suspended from a crane to prepare for installation.
Fig. 58 Mounting position
Siemens Parts
Page 44
Mounting
44 9229 9860 176 0E
2013-08-22
Mounting the partitions Carefully take the partitions out of the packaging (see Fig.4) and mount according
to the supplied mounting drawing.
Mounting the vacuum circuit-breaker
There are a total of 14 fixing holes on the pole plate (15.) and on the mechanism box (60.) for the various types of installation.
Use M12 screws – strength class 8.8 – for fastening. The binding dimension draw­ings are relevant.
The framework must be made to suit the operating conditions and have sufficient load bearing capacity and stability.
* bores for M12 screws
Fig. 59 Example of mounted partitions
Fig. 60 Fastening options Fig. 61 View Y and Z
9862-26
15.
9862-27
60.
Y
Z
Page 45
Mounting
9229 9860 176 0E 45 2013-08-22
Earthing
Connecting to earth Connect the vacuum circuit-breaker on the earth terminal (70.) to the high-voltage
protective earth as specified (DIN EN 50341).
Fully unscrew hexagon socket head screw M12 with washer on the earth termi­nal (70.).
Tighten ring terminal for the earth wire with th e M12 hexagon screw and washe r on the earth terminal (70.) with 40 Nm.
Connect low-voltage Connect the low-voltage connecting cables in the customer's switch cabinet in such
a way that safe operation as per supplied circuit diagram is guaranteed.
Note
If the 3AH3 vacuum circuit-breaker is installed into an earthed metal frame and is connected permanently and electrically conductive, no separate earthing is required.
Place serrated washers under the screw heads when fastening the vacuum cir­cuit-breaker in this case.
Fig. 62 Earth terminal Fig. 63 Connecting earth wire
Siemens Parts
Page 46
Mounting
46 9229 9860 176 0E
2013-08-22
Removing the transport securing device from the undervoltage release
Undervoltage release (Y7)
available?
The vacuum circuit-breaker with an underv olta ge release (Y7) 3AX1 103 is supplied with a transport securing device.
Remove the two top screws (60.2) of the mechanism box.
Remove the two bottom screws (60.2) of the mechanism box until the cover (60.1) can be taken off.
Slightly tilt the cover (60.1) of the mechanism box and lift off.
Shift the locking screw of the striker from position A to B (see reference note in mechanism box [60.] of the vacuum circuit-breaker).
Replace the cover (60.1) in the reverse order
and fasten the screws with a tightening torque of 10 Nm.
Fig. 64 Removing the cover Fig. 65 Removing the transport securing device
A
B
Page 47
Mounting
9229 9860 176 0E 47 2013-08-22
Electrical connection of the prime conductor
The busbars can be purchased from the Siemens Service Center.
Busbar connection
Adjust the busbars in such a way that, before fastening, they lie flat easily and fit the holes on the contact areas of the vacuum circuit-breaker.
Preparing contact areas Use a steel brush to carefully brush the contact areas (cross-wise) of the busbars
until they are metallically bright and wipe off any residue using a clean cloth. After cleaning, very lightly grease the bright contact areas with acid-free Vaseline
(e. g. Shell-Vaseline 8420) and screw together immediately.
DANGER
High-voltage – danger to life
Test the vacuum circuit-breaker in the switchbay with high-voltage applied only after faultless functioning has been ascertained (see “Commissioning” on page 49).
Note
Grease the busbars with contact grease prior to mounting.
Fig. 66 Cleaning the contact areas Fig. 67 Cleaning the contact areas of the busbars
Note
Clean silver spray-plated and copper spray-plated contact areas with a cloth, do not brush.
Different connection materials (AI/CU) must not be cleaned with the same clean­ing tools.
Silver-plated parts must not be bolted to aluminium bars/rails.
Siemens Parts
Page 48
Mounting
48 9229 9860 176 0E
2013-08-22
Corresponding to the rated current stren gth, use M12 screws and nuts – strength class 8.8 – for connection of the busbars and use the appropriate spring elements and washers.
When tightening the screws, hold the n uts against tightening torque of 70 Nm with a suitable screwdriver or socket wrench.
Screw-in depths in the upper and lower terminals
See dimension drawings.
Note
For vacuum circuit-breakers with connecting bars, it is recommended to use the stainless steel screws or non-magnetisable screws included in the accessory pack.
Fig. 68 Installing busbars flat Fig. 69 Installing busbars flat
Page 49
Operation
9229 9860 176 0E 49 2013-08-22
Operation
Commissioning
Before commissioning, check the f ollowing po ints to e nsure tha t the 3A H3 vacuu m circuit-breaker is functioning faultlessly:
DANGER
High voltage – danger to life Touching live parts causes an electric shock.
Do not touch live parts!
Ensure that the vacuum circuit-breaker is operated only by qualified person­nel who are familiar with the operating instructions and observe the warning notices.
Check through all of the items on the checklist and ensure correct functioning before commissioning.
Checklist
Notes
Does the information on the rating plate (see page 35) match the order data?
Ensure correct operating voltage. If necessary, clean the vacuum circuit-breaker (details on this in section
“Cleaning” on page 53). Check that screw connections are tightened securely. Check terminal strip plug-connection for tightness. Check functioning of the auxiliary switches.
If necessary, check and adjust customer's devices. If there is an undervoltage release (Y7) 3AX1103 : has the locking screw
of the striker been shifted from position A to B (see “Removing the trans­port securing device from the undervoltage release” on page 46)?
Test switching without supply voltage Charge the closing spring (62.) with the hand crank (50.) (see Fig. 70),
then actuate the CLOSE pushbutton (53.) and, once closing has been performed, actuate OPEN pushbutton (54.).
Test switching with supply voltage To perform test switching with the motor, switch on the supply voltage.
The motor starts up immediately and charges the closing spring (62.). Check the indicator for charge state of the closing spring (mechanically and electrically).
Electrically check through auxiliary switch S1 (68.) and position switch (50.4.1) in both end positions – operate the 3AH3 vacuum circuit-breaker to do so.
Check functioning of the closing solenoid Y9 (53.1) and all available sh unt releases by operating them electrically.
Siemens Parts
Page 50
Operation
50 9229 9860 176 0E
2013-08-22
First closing operation
If all functions have been checked and are ok, switch on high-voltage while observ­ing all of the safety regulations and operative requirements.
Charging the closing spring
If the supply voltage is applied, the closing spring (62.) is automatically charged by the motor (50.4).
Hand crank If the supply voltage fails, the closing spring (62.) can be charged with a hand crank
(50.).
1. For this, fit the hand crank (50.) onto the hand cran k coupling (50.5) throug h the opening (50.1) with the adapter pushed forward (50.6).
2. Turn clockwise until the spring state indicator (55.) cha nges over:
WARNING
Do not commission the vacuum circuit-breaker if there are malfunctions. If the malfunctions or the damage cannot be re medied, contact a sales repres ent-
ative or Siemens Service and, if necessary, send back the vacuum circuit­breaker.
WARNING
Risk of injury if hand cranks other than the original hand crank are used. When the supply voltage is present, the motor immediately recharges the spring
after a closing operation. If the hand crank does not have a slip coupling, the hand crank will also rotate.
To avoid injuries caused by the motor starting suddenly, the vacuum circuit­breaker must be charged only using the original hand crank.
Discharged Charged
Fig. 70 Charging the closing spring with the hand
crank
Fig. 71 Operating elements and spring state indicator
Page 51
Operation
9229 9860 176 0E 51 2013-08-22
The adapter (50.6) of the hand crank (50.) is designed in such a way that the hand crank becomes uncoupled when the motor supply voltage returns.
Closing
Provided there is no lock-out due to a mechanical locking device, send the closing command via the CLOSE pushbutton (53.) or the corresponding command ele ment until the vacuum circuit-breaker is closed and shows and signals the CLOSED switching position.
Change of the position indicator (59.):
After switching on and possibly releasing the CLOSE pushbutton (53.), the closing spring (62.) is immediately automatically charged by the motor and the indicator “Closing spring charged” (55.) becomes visible.
Change of the spring state indicator (55.):
Opening
The opening spring (64) is charged during the closing operation. To open, send the opening command via the OPEN pushbutton (54.) or the corre-
sponding command element until the vacuum circuit-breaker is open and sh ows and signals the OPEN switching position.
Change of the position indicator (59.) after electrical opening:
The spring state indicator (55.) does not change.
Discharging the closing spring
To discharge the closing spring:
the supply voltage must be deactivated
the vacuum circuit-breaker must be closed manually (see “Closing” on page 51) and then
opened manually (see “Opening” on page 51).
OPEN CLOSED

Charged Discharged Charged
Note
If an undervoltage release 3AX1103… is fitted, it must be connected to the control voltage for switching operations (mechanical or electrical), as otherwise closing is not possible.
CLOSED OPEN
Siemens Parts
Page 52
Operation
52 9229 9860 176 0E
2013-08-22
Blank page
Page 53
Maintenance
9229 9860 176 0E 53 2013-08-22
Maintenance
Maintenance and servicing
Maintenance
The 3AH3vacuum circuit-breaker is maintenance-free under normal operating con­ditions. We do, however, recommend you carry out regular visual inspections. The maximum permitted mechanical operating cycle number is 10 000.
Cleaning
The insulating parts must be clean if their insulating capacity is to be guaranteed. Rub insulating parts with a moist cloth.
As a cleaning agent, use only warm water with a mild, liquid household detergent added and leave to dry.
Joints and bearings that cannot be disassembled must not be washed out with a detergent prior to work.
DANGER
High voltage – danger to life Touching live parts is fatal or causes serious physical injury.
Before beginning maintenance work , note the five safety rules for high-voltage equipment specified in EN 50110-1, namely:
Isolate from the power supply*)
Secure against reclosing
Verify safe isolation from the power supply
Earth and short-circuit
Cover or cordon off neighbouring live parts *
)
On the vacuum circuit-breaker, actuate the OPEN, CLOSE and OPEN pushbut-
tons manually one after the other. This ensures that the vacuum circuit-breaker is open and the closing spring is discharged.
Note
The vacuum circuit-breaker should be taken out of the switch cabinet or switch­gear for servicing.
Siemens Parts
Page 54
Maintenance
54 9229 9860 176 0E
2013-08-22
Special operating conditions
If the vacuum circuit-breaker is operated under unfavourable conditions indoors (heavy and frequent condensation, dusty air, etc.), we recommend cleaning the insulating parts and possibly the outer parts of the circuit-breaker at shorter inter­vals.
For this, only the following agents may be used on the individual functional parts of the circuit breaker:
Lubricant:
Lubricants are available from the responsible Siemens representative:
Fig. 72 Bearings and sliding surfaces of the pole side
Bearings, sliding surfaces: Isoflex Topas L 32 Bearings and bearings of the auxiliary switch S1
that are inaccessible in terms of greasing:
Shell Tellus Oil 32
Order no.
180 g Isoflex Topas L 32 3AX11 33-3H
1 kg Shell Tellus Oil 32 (special oil) 3AX1 1 33-2D 1 kg Isoflex Topas L 32 3AX11 33-3E
Isoflex Topas L 32
t Bolts of the angle lever u Bolts and eyebolt of the insulating operating rod v Contact pressure spring, spring plate and spring bearing w Spring guide and bolts of the angle lever
Page 55
Maintenance
9229 9860 176 0E 55 2013-08-22
Fig. 73 Bearings and sliding surfaces of the operating mechanism
Isoflex Topas L 32 Shell Tellus Oil 32
a Crankpin for sensing device actuation b Bearing for deflection lever c Curve contour f Auxiliary switch d Close-latch j Circuit-breaker shaft bearing e Deflection of auxiliary switch p Opening spring bearing g Opening spring guide r Spring eyelet on closing spring h Deflection of auxiliary switch kOPEN-latch l Curve for OPEN-latch m End stop s Contact area of instantaneous release
Siemens Parts
Page 56
Maintenance
56 9229 9860 176 0E
2013-08-22
Interrupter service life
If switching operations occur frequently under overload or short circuit, the service life of the vacuum interrupters may be reached prematurely.
Replace the interrupters after reaching the maximum permitted operating cycle number of 10 000 mechanical or electrical load setting changes (up to the rated cur­rent).
When ordering vacuum interrupters, please always state the circuit-breaker type and serial number (see “Rating plate” on page 35).
Accessories and spare parts
Replacing spare parts To ensure that the device operates reliably, spare parts must be replaced only by
trained and certified personnel.
Fig. 74 Accessories available for order Always specify the vacuum circuit-breaker's type and serial no. (see “Rating plate”
on page 35) when ordering spare parts.
CAUTION
Risk of injury!
The vacuum circuit-breaker should be taken out of the switch cabinet or switch­gear for servicing.
Separate vacuum circuit-breakers from the control feed voltage or switch it off and disconnect the low-voltage plug or clip connection.
Accessory/spare part Order no. Comments
Operating instructions 9229 9860 100 Hand crank 3AX1530-2B
Lubricant
see “Special operating condi­tions” on page 54
Vaseline (contact grease) e. g. Atlantic white, Atlantic Mineralölwerk GmbH
Pasty consistency, flame point 210 °C, low acid
Page 57
Maintenance
9229 9860 176 0E 57 2013-08-22
Manufacturer's product liability
The manufacturer's product liability shall be excluded if at least one of the following criteria applies:
Original Siemens spare parts are not used.
Fitters carrying out replacements have not been trained and certified by Sie­mens.
Parts have been incorrectly fitted or adjusted.
Adjustments are not made in accordance with Siemens specifications.
After installation and adjustment, no final test is performed with a tester approved by Siemens including documentation of the test results.
To keep documentation complete, it is important that measurement results are sub­mitted to the responsible sales representative.
Disposal
The materials of the vacuum circuit-breake r should be recycled. Disposal of the vac­uum circuit-breaker with minimum environmental impact is possible on the basis of existing legal regulations.
Metal The circuit breaker's metal components can be recycled as mixed scrap, although it
is more environmentally sustainable to dismantle the unit as thoroughly as possible into sorted scrap and residual mixed scrap.
Electronics Electronic scrap must be disposed of in accordance with applicable regulations.
Materials The vacuum circuit-breaker consists of the following materials:
Steel (partly phosphatised, galvanised and yellow chromated)
Copper (partly silver-plated)
Plastics (epoxy resin, polyamide, polyester, polycarbonate, ABS-PC mixture; partly glass fibre reinforced)
Rubber materials
•Ceramics
•Lubricant
Packaging If the packaging is no longer needed, it can be fully recycled.
Hazardous substances When delivered by Siemens, the product does not contain any hazardous sub-
stances within the scope of the Hazardous Substances Ordnance applicable to the territory of the Federal Republic of Germany. For operation outside the Federal Republic of Germany, the applicable local laws and regulations must be complied with.
Further information Contact your Siemens Service Center if you require further information.
Service
For details of contacts for service work, consult Siemens IC LMV SE Service at
Telephone: +49 180/5247000
Fax: +49 180/5242471 or
on the Internet at the Web address: www.siemens.com/energy-support
by e-mail: support.energy@siemens.com
or any local sales representative.
Siemens Parts
Page 58
Maintenance
58 9229 9860 176 0E
2013-08-22
Blank page
Page 59
Index of keywords
9229 9860 176 0E 59 2013-08-22
Index of keywords
A
Accessories available for order
............................. 56
Altitude correction factor
....................................... 36
Ambient conditions
................................................ 36
Angle lever
............................................................ 20
Auxiliary switch
............................................. 22 23
B
Basic equipment
................................................... 23
Bearings and sliding surfaces
............................... 55
Busbars
................................................................. 48
C
Centering
.............................................................. 20
Circuit-breaker shaft
.............................................. 22
Circuit-breaker tripping signal
....................... 23, 27
Climate classes
..................................................... 36
Closing damper
..................................................... 22
Closing solenoid
.................................... 22 23, 25
Closing spring
............................................... 22, 31
Contact pressure spring
........................................ 19
Contact stroke
....................................................... 20
Contact system
..................................................... 20
Contactor relay
.............................................. 22 23
Contactor relay K1
................................................ 24
Cover
.................................................................... 21
Cut-out switch
....................................................... 27
D
Dashpot
................................................................. 22
Disconnected position
........................................... 32
Distance between pole centres
............................. 35
E
Earth terminal
................................................ 22, 45
Electrical manual closing
.............................. 23, 31
G
Gear unit
............................................................... 22
H
Hand crank
............................................................ 50
Hand crank coupling
............................................. 22
Heater (condensation water protection)
22 23, 31
High-voltage protective earth
................................ 45
I
Installation altitudes
.............................................. 36
Insulating capacity
................................................ 36
Insulating operating rods
....................................... 19
Interrupter
..................................................... 19 20
Interrupter support
................................................ 20
Interrupter, service life
.......................................... 56
Interrupter, vacuum check
.................................... 56
L
Locking devices
.................................................... 32
Low-voltage interface
.................................... 22 23
M
Mechanical anti-pumping device
........................... 23
Mechanical locking device
............................ 23, 32
Mechanical manual closing
......... ... ... ... .... ... . 23, 31
Mechanical manual opening
.............................. .... 23
Mechanism box
....... .... ... ... ... .... ... ................. 19, 22
Motor
........... ... ... ... ... .... ... .............................. 22 24
Mounting position
........ ... ... ... .... ... ... ....................... 43
O
Opening spring
......................................... ... ... ... .... 22
Operating cycle counter
..................... ... .... ... . 22 23
Operating position
............. ... .... ... ... ... ... ................. 32
Operating rod
.................. ... ... .... ... ... ... .................... 22
P
Plug-connector with sleeve housing
...................... 23
Pole assembly
.......................................... ... . 19 20
Pole plate
..................... ... ... ... .... ... ... ....................... 19
Position indicator CLOSED-OPEN
........................ 22
Position switch
...................................... 22 23, 27
Post insulator
............................... .......................... 19
Priority opening
..................... .... ... ... ... ... .... ............. 23
R
Range of application
................................. ............. 17
Rated frequency
.......................................... ... ... .... 35
Rated lightning impulse withstand voltage
............ 35
Rated operating current
.................................. ....... 35
Rated operating sequence
............. ... ... .... ... ... ... .... 35
Rated power frequency withstand voltage
............. 35
Rated short-circuit breaking current
......... ... ... ... .... 35
Rated short-circuit duration
......... ... ... ... .... ... ... ....... 35
Rated voltage
.......... .... ... ... ... .... ... .......................... 35
Rating plate
.......... ... .... ... ... ... .... .................... 22, 35
S
Shunt release
.......... .... ... ... ... .... ... .......................... 22
shunt release
........................................ 23, 25, 29
Spring charge release
....... ... .... ... ... ... ... ........ 23, 33
Spring state indicator
................................... . 21 22
Standards
.......................................... ... .... ... ... ... .... 18
Strut
............................................. ... ... .................... 19
Switching times
..................... .... ... ... ... ... .... ............. 37
T
Terminal strip
............................... ................. 23, 28
Transformer-operated release
.............. 22 23, 29
Transformer-operated release (0.1 Ws)
................ 22
U
Undervoltage release
........................... 22 23, 30
V
Vacuum interrupter, contact system
...................... 20
Siemens Parts
Page 60
Index of keywords
60 9229 9860 176 0E
2013-08-22
Blank page
Page 61
Legend for all pages
9229 9860 176 0E 61 2013-08-22
Legend for all pages
15. Pole plate
16.1 Upper post insulator
16.2 Lower post insulator
19. Pole assembly, complete
20. Upper interrupter support
27. Upper terminal
28. Strut
28.1 Centering
29. Lower terminal
29.1 Flexible connector
29.2 Clamp
30. Interrupter
40. Lower interrupter support
48. Insulating operating rods
48.6 Angle lever
49. Contact pressure spring
50. Hand crank
50.1 Opening for hand crank
50.2 Gear unit
50.4 Motor M1
50.4.1 Position switch
50.5 Hand crank coupling
50.6 Hand crank adapter
51. Rating plate
51.1 Opening for rating plate
53. CLOSE pushbutton
53.1 Closing solenoid Y9
54. OPEN pushbutton
54.1 Shunt release Y1
54.2 Shunt release Y2
54.3 Transformer-operated release Y4
54.4 Undervoltage release Y7
54.5 Transformer-operated release (0.1Ws) Y6
55. Spring state indicator
55.1 Opening for spring state indicator
58. Operating cycle counter
58.1 Opening for operating cycle counter
59. Position indicator CLOSED-OPEN
59.1 Opening for position indicator CLOSED­OPEN
60. Mechanism box
60.1 Cover
61. Dashpot
62. Closing spring
63. Circuit-breaker shaft
64. Opening spring
66. Closing damper
68. Auxiliary switch S1 (6NO+6NC)
68.0.1 Extended auxiliary switch S1 (12NO + 12NC)
68.1 Operating rod (for auxiliary switch S1)
68.7. Low-voltage interface X0
68.7.1 Plug
68.7.2 Terminal strip
69. Contactor relay K1
70. Earth terminal
71. Heater R01 (condensation water protection)
72. Spring charge release
72.1 Lever of the spring charge release
90. Mechanical locking device
Siemens Parts
Page 62
62 9229 9860 176 0E
2013-08-22
Blank page
Page 63
9229 9860 176 0E 63 2013-08-22
Blank page
Siemens Parts
Page 64
Published by
Siemens AG
Infrastructure & Cities Sector Low and Medium Voltage Division Medium Voltage & Systems Schaltwerk Berlin
Nonnendammallee 104 13629 Berlin
Loading...