Siemens 125-1957 User Manual

Page 1
APOGEE Unit Vent Controller
0 to 10V Output Owner’s Manual
125-1957 Rev. CA, July 2007
Siemens Building Technologies, Inc.
Page 2
Page 3
Rev. CA, July 2007
NOTICE
The information contained within this document is subject to change without notice and should not be construed as a commitment by Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. assumes no responsibility for any errors that may appear in this document.
All software described in this document is furnished under a license and may be used or copied only in accordance with the terms of such license.
WARNING
This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance with the instructions manual, may cause interference to radio communications. It has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against such interference when operated in a commercial environment. Operation of this equipment in a residential area is likely to cause interference in which case users at their own expense will be required to take whatever measures may be required to correct the interference.
SERVICE STATEMENT
Control devices are combined to make a system. Each control device is mechanical in nature and all mechanical components must be regularly serviced to optimize their operation. All Siemens Building Technologies branch offices and authorized distributors offer Technical Support Programs that will ensure your continuous, trouble-free system performance.
For further information, contact your nearest Siemens Building Technologies, Inc. representative.
Copyright 2006 by Siemens Building Technologies, Inc.
TO THE READER
Your feedback is important to us. If you have comments about this manual, please submit them to
SBT_technical.editor.us.sbt@siemens.com
CREDITS APOGEE is a registered trademark of Siemens Building Technologies, Inc.
Insight for Minicomputers is a registered trademark of Siemens Building Technologies, Inc. Insight for Personal Computers is a registered trademark of Siemens Building Technologies, Inc.
Country of Origin: US
Page 4
Page 5
Table of Contents
How To Use This Manual ................................................................................................. iv
Manual Organization ......................................................................................................iv
Manual Conventions ................................................................................................... v
Manual Symbols .......................................................................................................... v
Datamate Software ..................................................................................................... v
Getting Help ................................................................................................................vi
Where To Send Comments .........................................................................................vi
Product Overview ............................................................................................................. 1
Introduction .................................................................................................................... 1
Ordering Notes ............................................................................................................ 1
Hardware Inputs .......................................................................................................... 2
Hardware Outputs ....................................................................................................... 3
Controller LED Indicators ............................................................................................ 4
Temperature Sensors ................................................................................................. 4
Actuators ..................................................................................................................... 5
Applications ....................................................................................................................... 6
Basic Operation ............................................................................................................. 6
Control Temperature Setpoints ................................................................................... 6
Day/Night Mode ........................................................................................................... 6
Valve Configuration ..................................................................................................... 7
Heating and Cooling Switchover ................................................................................. 7
Control Loops .............................................................................................................. 7
Morning Warm-up/Cool-down ..................................................................................... 8
ON/OFF Coil Valve Control ......................................................................................... 8
Electric Heat ................................................................................................................ 8
Fan Operation ............................................................................................................. 8
Fail-safe Operation ...................................................................................................... 8
Application 2281 – Heating and/or Chilled Water Cooling, ASHRAE Cycles I and II . 10
Application 2283 – Heating and/or Chilled Water Cooling, ASHRAE Cycle III .......... 13
Application 2284 – Heating and DX Cooling, ASHRAE Cycles I and II ..................... 16
Application 2286 - Heating and DX Cooling, ASHRAE Cycle III ................................. 18
Application 2287 – Heating and Cooling, Nesbitt Cycle W ......................................... 20
Overview ................................................................................................................... 20
Application 2299 – Slave Mode ................................................................................... 22
Overview ................................................................................................................... 22
I
Page 6
APOGEE Unit Vent Controller⎯0 to 10V Output Owner’s Manual
Point Database ................................................................................................................ 23
Troubleshooting .............................................................................................................. 33
Overview ...................................................................................................................... 33
Basic Service Information ......................................................................................... 33
Ordering Replacement Parts..................................................................................... 34
Preventive Maintenance ............................................................................................ 34
Safety Features ......................................................................................................... 34
Controller LEDs ......................................................................................................... 34
Glossary ........................................................................................................................... 35
Overview ...................................................................................................................... 35
ii
Page 7
Table of Contents
iii
Page 8
How To Use This Manual
This manual is written for the owner and user of the Siemens Building Technologies, Inc. Unit Vent Controller – 0 to 10V, often referred to as controller for the remainder of this manual. This manual is designed to help you become familiar with the controller and its applications.
This chapter covers manual organization, manual symbols and conventions used and how to access help.
Manual Organization
This manual contains the following chapters:
Chapter 1 Product Overview, describes the hardware components and accessories used with the controller.
Chapter 2 Applications, describes the control applications available in the controller.
Chapter 3 Point Database, defines the point database descriptors and includes
addresses and applications.
Chapter 4 Troubleshooting, describes basic corrective measures to take should you encounter a problem when using this controller. For issues not covered in this chapter, contact your local Siemens Building Technologies representative.
A Glossary describes the terms and acronyms used in this manual.
An Index is provided to assist you in finding information.
Siemens Building Technologies,Inc. iv
Page 9
Manual Conventions
The following table lists conventions used in this manual.
Convention Example
Manual Organization
Actions that you should perform are specified in boldface font.
Error and system messages are displayed in Courier New font.
New terms appearing for the first time are italicized.
Manual Symbols
The following table lists symbols that used to draw your attention to important information.
Notation Symbol Meaning
CAUTION:
WARNING:
Type F for Field panels. Click OK to save changes and close the dialog box.
The message Report Definition successfully renamed appears in the status bar.
The Open Processor continuously executes a user-defined set of instructions called the control program.
Indicates that equipment damage or loss of data may occur, if a procedure is not performed as specified.
Indicates that personal injury or loss of life may occur to the user, if a procedure is not performed as specified.
Datamate Software
Datamate is a customer software tool for all controller communications. There are two versions: Datamate Base, and Datamate Advanced. Datamate Base works on an IBM­compatible Personal Computer (PC), or a Handheld PC or Pocket PC™ running Windows CE. Datamate Advanced works only on an IBM-compatible Personal Computer.
With Datamate, you can back up, restore and edit any APOGEE Datamate Advanced allows you to edit points offline). Backing up and restoring a database is accomplished while connected to any APOGEE
®
field panel, or to the Automation Level Network (ALN) or Field Level Network (FLN) device in question. A modem and telephone lines can also be used. Databases can be saved for permanent storage or used as backup.
For more information on Datamate software, refer to the appropriate user guide for the version of Datamate you are using (Base or Advanced), or contact your local Siemens Building Technologies, Inc. representative.
Siemens Building Technologies, v
®
database (but only
Page 10
APOGEE Unit Vent Controller⎯0 to 10 V Output Owner’s Manual
Getting Help
For more information about the Unit Vent Controller, contact your local Siemens Building Technologies representative.
Where To Send Comments
Your feedback is important to us. If you have comments about this manual, please submit them to SBT_technical.editor.us.sbt@siemens.com
vi Siemens Building Technologies. Inc.
Page 11
1
Product Overview
Introduction
The Unit Vent Controller—0 to 10V Output is the Siemens Building Technologies, Inc. Terminal Equipment Controller (TEC) used in unit ventilator applications. See Figure 1. It provides Direct Digital Control (DDC) for five applications. The controller can operate as an independent, stand-alone, DDC room controller or be networked with an APOGEE field panel.
The controller provides all termination, input/output, system and local communication connections. See Figure 1. The controller hardware consists of the controller with cover and mounting bracket.
Table 1. Unit Vent Controller – 0 to 10 V Output Applications.
Standard Applications
2281 Heating and/or Chilled Water Cooling, ASHRAE Cycles l and II 2283 Heating and/or Chilled Water Cooling, ASHRAE Cycle III 2284 Heating and DX Cooling, ASHRAE Cycles I and II 2286 Heating and DX Cooling, ASHRAE Cycle III 2287 Nesbitt Cycle W 2299Slave Mode (no control; available for set up, and point extension device)
Ordering Notes
Unit Vent Controller – 0 to 10 Volt Output 540-509
Siemens Building Technologies, Inc. 1
Page 12
APOGEE Unit Vent Controller⎯0 to 10V Output Owner’s Manual
COVER
CONTROLLER
BOARD
MOUNTING
HOLE
(2)
DO 1 DO 2 DO 3 DO 4 DO 5 DO 6 NO C NO C NO C NO C NO C NO C
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28
TEC0197R3
24 V-AC
CH
CH
POWER TRUNK
TERMINATIONS
Hardware Inputs
Analog
Averaging air temperature sensor
Room temperature sensor
Room temperature setpoint dial (optional)
Digital
DO 7
DO 8
NO C
NO C
DO LEDS
INPUT / OUTPUT TERMINATIONS
DI 3 DI 2 AI 3 + -
AO 1DI 4
AO 2
AO 3
+ -
+ -
TRANSMIT LED
RECEIVE LED
Figure 1. Unit Vent Controller - 0 to 10V Output.
LAN
TRUNK
+-
SRXTX RTS
+-
S
LAN
TRUNK
TERMINATIONS
BST
ROOM TEMPERATURE
SENSOR / MMI PORT
BST LED
MOUNTING
RAIL
Low Temperature Detection Thermostat (LTDT)
Night mode override (optional)
Wall switch (optional)
2 Siemens Building Technologies, Inc.
Page 13
Hardware Outputs
Introduction
Analog (0 to 10V)
Cooling valve actuator
Face-bypass damper actuator
Heating valve actuator
Outdoor air damper actuator
Digital
Auxiliary radiation electric coil contact; or, auxiliary radiation two-position valve actuator
Unit fan
First stage electric heat
Second stage electric heat
Third stage electric heat
Two-position cooling valve actuator
Application
2281, 2283, 2287 2281, 2283, 2284, 2286 2281, 2283, 2284, 2286, 2287 2281, 2283, 2284, 2286
Application
2281, 2283, 2284, 2286
2281, 2283, 2284, 2286, 2287 2281, 2283, 2284, 2286 2281, 2283, 2284, 2286 2281, 2283, 2284, 2286 2281, 2283, 2284, 2286
Two-position heating valve actuator
DX coil
Power Wiring
The controller is powered by 24 Vac and connects to the two screw terminals on the controller. Labeled “C” (Common) and “H” (Hot) on the terminal block labeled “24 VAC”. No earth-ground connection is required (Figure 2).
Communication Wiring
The controller connects to the field panel by means of a Floor Level Network (FLN) trunk. Communication wiring connects to the three screw terminals on the controller labeled “+” (positive), “-“ (negative), and “S” (Shield) (Figure 3).
2281, 2283, 2284, 2286 2284, 2286, 2287
Siemens Building Technologies, Inc. 3
Page 14
APOGEE Unit Vent Controller⎯0 to 10V Output Owner’s Manual
DO 1 DO 2 DO 3 DO 4 DO 5 NO C NO C NO C NO C NO C
1 2 3 4 5 6 7 8 9 10 11 1
1 2 3 4 5 6 7 8 9 10 11 12
TEC0253R2
24 V-AC
CEH
COMMON
24 VA C HOT
CONTROLLER POWER WIRING
NOTE: NO EARTH GROUND CONNECTION
Figure 2. Power Wiring. Figure 3. Communication Wiring.
Controller LED Indicators
The controller has eleven Light Emitting Diode (LED) indicators. See Figure 1. Table 2 lists the type, the abbreviation on the controller, and the indication of each LED.
LED Type Label
(if present)*
DO LED 1 to
LED 8
FLN TRUNK
(+)
(-)
+-
(-)
(+)
NO
(SHIELD) (SHIELD)
TEC0470R1
Table 2. Controller LEDS.
LED
Indication
Number
1 to 8 Indicates the ON/OFF status of the
DO associated with it. A glowing LED indicates that the DO is energized.
S
Receive RX 9 Indicates, when flashing, that the controller is
Transmit TX 10 Indicates, when flashing, that the controller is
Basic Sanity Test BST 11 Indicates, when flashing ON and OFF once
*Some LED labels and numerals may be hidden by the controller cover.
Temperature Sensors
Temperature sensors used with the Unit Vent Controller—0 to 10V Output include an electronic room, mixed air or discharge air temperature sensor.
Room Temperature Sensor
The Terminal Equipment Controller room temperature sensor connects to the controller by means of a cable pre-terminated at both ends with a 6-conductor RJ-11 plug-in connector. See Figure 1 for the location of the room temperature sensor/Man-Machine Interface (MMI) port.
receiving information from the field panel.
transmitting information to the field panel.
per second, that the controller is functioning property.
4 Siemens Building Technologies, Inc.
Page 15
Mixed Air/Discharge Air Temperature Sensor
The mixed air/discharge air temperature sensor is a 100K ohm thermistor that connects to the controller at the screw terminals for Al 3.
For more information about Siemens Building Technologies, Inc. temperature sensors, contact your local Siemens Building Technologies, Inc. representative.
Actuators
Damper Actuators
The damper actuator used with the Unit Vent Controller—0 to 10V Output is a 0 to 10V spring return electronic damper motor that positions an outside air damper. A 0 to 10V electronic damper motor can be used to position a face-and-bypass damper.
Valve Actuators
Introduction
The valve actuators used with the Unit Vent Controller—0 to 10V Output are modulating spring return and non-spring return electronic valve motors that position the valves.
Related Equipment
Relay Module
Damper Actuator(s)
Valve Actuator(s)
Mixed Air/Discharge Air Temperature Sensor (optional)
TEC Room Temperature Sensor
Contact your local Siemens Building Technologies, Inc. representative for product numbers and more information.
Siemens Building Technologies, Inc. 5
Page 16
2
Applications
Basic Operation
The Unit Vent Controller0 to 10V Output provides Direct Digital Control (DDC) technology for unit ventilator applications. The applications available in this controller are as follows:
Heating and/or Chilled Water Cooling, ASHRAE Cycles l and II
Heating and/or Chilled Water Cooling, ASHRAE Cycle III
Heating and DX Cooling, ASHRAE Cycles I and II
Heating and DX Cooling, ASHRAE Cycle III
Nesbitt Cycle W
Slave Mode (no control; available for set up,
and point extension device)
Control Temperature Setpoints
The controller maintains a specified temperature setpoint based on Day/Night mode, the heating/cooling mode, or the setpoint dial (if used).
Day/Night Mode
The controller maintains the specified day setpoint temperature during daytime hours and the specified night setpoint at night.
Application 2281
Application 2283
Application 2284
Application 2286 Application 2287
Application 2299
Day Heating Operation
The controller maintains the room temperature by resetting the unit ventilator's discharge temperature setpoint (2281/2284), modulating the available coil control device, controlling auxiliary radiation (if provided), positioning the outdoor air or face-bypass damper.
6 Siemens Building Technologies,Inc.
Page 17
Day Cooling Operation
The controller maintains the room temperature by resetting the unit ventilator's discharge temperature setpoint (2281), running the face-bypass damper at full all the time, modulating or cycling the available coil control device (DX coil – 2284) or positioning the outdoor air damper.
Night Heating Operation
The controller maintains the room temperature turning the fan and heating on and off as required.
Night Cooling Operation
The controller maintains the room temperature by turning the fan and cooling on and off as required.
Basic Operation
Night Mode Override Switch
If the RTS has an override switch, it can be used to command the controller into day mode for an adjustable amount of time. This only affects a controller in night mode.
Valve Configuration
2-Pipe Heating/Cooling – units with one valve, controlling a coil that may have hot water or
chilled water (depending on the season). 4-Pipe Heating or Cooling – units that are heating or cooling only, units with a heating and a
cooling coil, units with electric heating, etc.
Heating and Cooling Switchover
NOTE: For 2-pipe heating/cooling (Application 2281 and 2283), a field panel must
control the switchover between heating and cooling.
The heating/cooling switchover determines whether the controller is in heating or cooling mode by monitoring the room temperature and the demand for heating and cooling (as determined by the temperature control loops).
Control Loops
Room Loop – uses the control setpoint and room temperature to set the discharge setpoint
between the minimum and maximum discharge temperature (2281, 2284). Heating Loop – maintains room temperature setpoint by turning valves and/or electric heat
stages on and off.
Siemens Building Technologies, Inc. 7
Page 18
APOGEE Unit Vent Controller⎯0 to 10 V Output Owner’s Manual
Cooling Loop – maintains room temperature setpoint by turning valves on and off and using free cooling (mixed air control) when available.
Auxiliary Loop – modulates the auxiliary loop using the auxiliary setpoint and discharge setpoint (2284).
Mixed Air Loop – modulates the mixed air loop using the mixed air setpoint and mixed air temperature (2283).
DX Loop – modulates the cooling loop using the control setpoint and room temperature (2284).
Morning Warm-up/Cool-down
Morning warm-up or cool-down occurs after the controller switches from night mode to day mode, upon power-up, or if the controller is reset. During morning warm-up or cool-down, the controller provides maximum heating or cooling with the outdoor air damper closed until the temperature of the space reaches setpoint.
ON/OFF Coil Valve Control
When a face-bypass configuration is used, the coils may be turned on and off with two­position valves using DOs.
Electric Heat
If electric heat is used, it is controlled as follows:
HTG OUTPUT
(Point 60)
0% to 33% ON OFF OFF
34% to 66% ON ON OFF
67% to 100% ON ON ON
In addition, no stage may turn on or off until the time delay has elapsed. Stage one will always be the first stage to turn on and the last stage to turn off.
Stage 1 Stage 2 Stage 3
Fan Operation
Day Mode – The fan is on all the time. Night Mode – The fan only operates when required for heating or cooling.
Fail-safe Operation
A low temperature detection thermostat (LTDT) can be used to signal the controller when the temperature drops below the low temperature limit.
8 Siemens Building Technologies. Inc.
Page 19
Basic Operation
If the room temperature sensor input to the Unit Vent Controller fails or the LTDT equals ON, the controller goes through the following shutdown sequence:
Outdoor air damper is closed.
Heating is full ON (except electric, which is OFF).
Cooling is full OFF.
Face-bypass damper is open to face.
Fan is OFF.
Auxiliary radiation is OFF.
Two-position heating valve actuator is open.
Two -position cooling valve actuator is closed.
NOTE: DO 2 is not commanded by the fail-safe mode; all other DOs can be affected.
If the discharge air temperature sensor fails, the following conditions occur:
If the last valid value is greater than 150 degrees, the heat is turned off, the outdoor air damper is closed and the fan is turned on.
If the sensor does not come back within 10 minutes or if the last valid value is less than 150 degrees, the controller shuts down.
If a failed sensor returns or if the LTDT turns off, normal control resumes. Analog and digital outputs cannot be commanded when the controller is in fail-safe mode;
however, failed points may be overridden, allowing the controller to return from fail-safe mode. In this instance, room temperature control is not possible.
Siemens Building Technologies, Inc. 9
Page 20
APOGEE Unit Vent Controller⎯0 to 10 V Output Owner’s Manual
Application 2281 – Heating and/or Chilled Water Cooling, ASHRAE Cycles I and II
In Application 2281, the Unit Vent Controller0 to 10V Output controls a unit ventilator equipped with a chilled water coil for cooling, and/or a heating coil, which may be hot water, steam, or electric, for ASHRAE Cycles I and II. A face-bypass damper can be controlled, replacing both the modulating (0-10V) heating and cooling actuators. If a face-bypass damper is used, the two-position valves on the coils can be controlled. Heating only and cooling only units can also be controlled with this application by overriding HEAT.COOL (Point 5).
Other features available in this application include morning warm-up/cool down, night mode override, free cooling and auxiliary radiation in heating mode.
NOTE: The use of a low temperature detection thermostat (LTDT) is strongly
recommended for hot water and steam systems.
This application controls room temperature by resetting the discharge air temperature. It also controls an outdoor air damper according to the schedules as defined by ASHRAE Cycles I and II. The free-cooling/economizer function is turned on and off by the field panel using FREE CLG (Point 23). If free cooling is not available, the outdoor air damper will be kept at minimum position; otherwise, the outdoor air damper will modulate open in sequence with the heating and cooling actuators. The unit ventilator fan is also controlled in this application.
Figure 4. Application 2281 Control Drawing.
10 Siemens Building Technologies. Inc.
Page 21
Application 2281 – Heating and/or Chilled Water Cooling, ASHRAE Cycles I and II
Figure 5. Application 2281 Control Drawing.
Figure 6. Application 2281 Control Drawing.
Siemens Building Technologies, Inc. 11
Page 22
APOGEE Unit Vent Controller⎯0 to 10 V Output Owner’s Manual
Figure 7. Application 2281 Control Drawing.
Figure 8. Application 2281 Control Drawing.
NOTE: The auxiliary radiation is an independent loop and is not sequenced with the other
control loops.
12 Siemens Building Technologies. Inc.
Page 23
Application 2283 – Heating and/or
Chilled Water Cooling, ASHRAE Cycle III
Application 2283 – Heating and/or Chilled Water Cooling, ASHRAE Cycle III
In Application 2283, the Unit Vent Controller0 to 10V Output controls a unit ventilator equipped with a chilled water coil for cooling, and/or a heating coil, which may be hot water, steam or electric, for ASHRAE Cycle III. A face-bypass damper can be controlled, replacing both the modulating (0-10V) heating and cooling actuators. If a face-bypass damper is used, two -position valves on the coils may be controlled. Heating only and cooling only units can also be controlled with this application by overriding HEAT.COOL (Point 5).
Other features available in this application include morning warm-up/cool-down, night mode override, free cooling, and auxiliary radiation in heating mode.
NOTE: The use of a low temperature detection thermostat (LTDT) is strongly
recommended for hot water and steam systems.
This application controls room temperature by directly modulating the coil control devices. This application also controls an outdoor air damper according to the schedule as defined by ASHRAE Cycle III, to maintain a given mixed air temperature setpoint. The free cooling/economizer function is turned on and off by the field panel using FREE CLG (Point
23). If free cooling is not available, the outdoor air damper will be kept at minimum position; otherwise, the outdoor air damper will modulate to maintain the mixed air temperature setpoint. The unit ventilator fan is also controlled in this application.
Figure 9. Application 2283 Control Drawing.
Siemens Building Technologies, Inc. 13
Page 24
APOGEE Unit Vent Controller⎯0 to 10 V Output Owner’s Manual
Figure 10. Application 2283 Control Drawing.
Figure 11. Application 2283 Control Drawing.
14 Siemens Building Technologies. Inc.
Page 25
Application 2283 – Heating and/or
Chilled Water Cooling, ASHRAE Cycle III
Figure 12. Application 2283 Control Drawing.
Figure 13. Application 2283 Control Drawing.
Siemens Building Technologies, Inc. 15
Page 26
APOGEE Unit Vent Controller⎯0 to 10 V Output Owner’s Manual
Application 2284 – Heating and DX Cooling, ASHRAE Cycles I and II
In Application 2284, the Unit Vent Controller0 to 10V output controls a unit ventilator equipped with a DX coil for cooling, and/or a heating coil, which may be hot water, steam, or electric, for ASHRAE Cycles I and II. A face-bypass damper can be controlled, replacing the modulating (0-10V) heating actuator, but will modulate only in heating mode. If a face-bypass damper is used, two-position valves on the coils may be controlled. Cooling only units can also be controlled with this application by overriding HEAT.COOL (Point 5) to COOL.
Other features available in this application include morning warm-up/cool-down, night mode override, free cooling and auxiliary radiation in heating mode.
NOTE: The use of a low temperature detection thermostat (LTDT) is strongly
recommended for hot water and steam systems.
While in heating, this application controls room temperature by resetting the discharge air temperature. While in cooling, this application controls room temperature by cycling the DX unit. This application also controls an outdoor air damper according to the schedules as defined by ASHRAE Cycles l and II. The free-cooling/economizer function is turned on and off by the field panel using FREE CLG (Point 23). If free cooling is not available, the outdoor air damper will be kept at minimum position; otherwise, the outdoor air damper will modulate open in sequence with the heating actuator or the DX. The unit ventilator fan is also controlled in this application.
Figure 14. Application 2284 Control Drawing.
16 Siemens Building Technologies. Inc.
Page 27
Application 2284 – Heating and DX Cooling, ASHRAE
Cycles I and II
Figure 15. Application 2284 Control Drawing.
Figure 16. Application 2284 Control Drawing.
NOTE: The auxiliary radiation is an independent loop and is not sequenced with the other
control loops.
Siemens Building Technologies, Inc. 17
Page 28
APOGEE Unit Vent Controller⎯0 to 10 V Output Owner’s Manual
Application 2286 - Heating and DX Cooling, ASHRAE Cycle III
In Application 2286, the Unit Vent Controller—0 - 10V Output controls a unit ventilator equipped with a DX coil for cooling, and/or a heating coil, which may be hot water, steam, or electric, for ASHRAE Cycle Ill. A face-bypass damper can be controlled, replacing the modulating (0-10V) heating actuator, but will modulate only in heating mode. If a face-bypass damper is used, two -position valves on the coils may be controlled. Cooling only units can also be controlled with this application by overriding HEAT.COOL (Point 5) to COOL.
Other features available in this application include morning warm-up/cool-down, night mode override, free-cooling, and auxiliary radiation in heating mode.
NOTE: The use of a low temperature detection thermostat (LTDT) is strongly
recommended for hot water and steam systems.
This application controls room temperature by directly modulating the coil control devices. This application also controls an outdoor air damper according to the schedule as defined by ASHRAE Cycle III, to maintain a given mixed air temperature setpoint. The free­cooling/economizer function is turned on and off by the field panel using FREE CLG (Point
23). If free cooling is not available, the outdoor air damper will be kept at minimum position; otherwise, the outdoor air damper will modulate to maintain the mixed air temperature setpoint. The unit ventilator fan is also controlled in this application.
Figure 17. Application 2286 Control Drawing.
18 Siemens Building Technologies. Inc.
Page 29
Application 2286 - Heating and DX Cooling, ASHRAE Cycle III
Figure 18. Application 2286 Control Drawing.
Figure 19. Application 2286 Control Drawing.
Siemens Building Technologies, Inc. 19
Page 30
APOGEE Unit Vent Controller⎯0 to 10 V Output Owner’s Manual
Application 2287 – Heating and Cooling, Nesbitt Cycle W
Overview
In Application 2287, the Unit Vent Controller0-10V Output controls a unit ventilator equipped with a heating coil, which may be hot water or steam, for Nesbitt Cycle W. Auxiliary radiation coils are piped parallel to the heating coil and are not controlled separately by the application. A chilled water coil or a DX cooling coil may be controlled. Heating only units can also be controlled with this application by overriding HEAT.COOL (Point 5) to HEAT.
Other features available in this application include morning warm-up/cool-down, night mode override and free cooling.
NOTE: The use of a low temperature detection thermostat (LTDT) is strongly
recommended for hot water and steam systems.
This application controls room temperature by directly modulating the coil control device(s) and the outdoor air damper according to the schedule defined by Nesbitt Cycle W. The free­cooling/economizer function is turned on and off by the field panel using FREE CLG (Point
23). The unit ventilator fan is also controlled in this application.
Figure 20. Application 2287 Control Drawing.
20 Siemens Building Technologies. Inc.
Page 31
Application 2287 – Heating and Cooling,
Nesbitt Cycle W
Figure 21. Application 2287 Control Drawing.
Figure 22. Application 2287 Control Drawing.
Siemens Building Technologies, Inc. 21
Page 32
APOGEE Unit Vent Controller⎯0 to 10 V Output Owner’s Manual
Application 2299 – Slave Mode
Overview
Application 2299 is the slave mode application for the Unit Vent Controller—0 - 10V Output (P/N 540-509). Slave mode is the default application that comes up when power is first applied to the controller. Slave mode provides no control. Its purpose is to allow the operator to perform equipment checkout before a control application is put into effect and to set some basic controller parameters (CTLR ADDRESS, APPLICATION, etc.).
NOTE: Slave mode provides no control.
The input labeled "DI3/AI3" on the controller can be used either as a DI point or as an Analog Input (AI) point, but not both at the same time.
22 Siemens Building Technologies. Inc.
Page 33
3
Point Database
This chapter presents a description of the Unit Vent Controller database including point descriptors, point addresses, and a listing of applications in which each point is found.
Table 3. Point Database.
Descriptor Address Application Description
CTLR ADDRESS 01 2281, 2283,
2284, 2286, 2287, 2299
APPLICATION 02 2281, 2283,
2284, 2286, 2287, 2299
ROOM TEMP 04 2281, 2283,
2284, 2286, 2287, 2299
HEAT.COOL 05 2281, 2283,
2284, 2286, 2287
DAY CLG STPT 06 2281, 2283,
2284, 2286, 2287
DAY HTG STPT 07 2281, 2283,
2284, 2286, 2287
NGT CLG STPT 08 2281, 2283,
2284, 2286, 2287
Identifies the controller on the FLN trunk.
The identification number of the program running in the controller. Valid entries: 2281, 2283, 2284, 2286, 2287, 2299
Actual reading from the room temperature sensor.
Current mode of operation for applications that can be either a heating mode or a cooling mode.
The temperature setpoint in degrees that the controller maintains, during day periods in cooling mode, if a room temperature sensor setpoint dial is not present or is not used. Refer to STPT DIAL (Point 14). Valid entry range: 48° to 95°F (9°- 35°C)
The temperature setpoint in degrees that the controller maintains during day periods in heating mode if a room temperature sensor setpoint dial is not present or is not used. Refer to STPT DIAL (Point 14). Valid entry range: 48° to 95°F (9° to 35° C)
The temperature setpoint in degrees that the controller maintains during night periods in cooling mode. Valid entry range: 48° to 95°F (9° to 35°C)
NGT HTG STPT 09 2281, 2283,
2284, 2286, 2287
OADPR MINPOS 10 2281, 2283,
2284, 2286, 2287
Siemens Building Technologies, Inc. 23
The temperature setpoint in degrees that the controller maintains during night periods in heating mode. Valid entry range: 48° to 95°F (9°to 35°C)
The minimum position the damper will be commanded to during day mode.
Page 34
APOGEE Heat Pump Controller—Multi Stage Owner's Manual
Descriptor Address Application Description
RM STPT MIN 11 2281, 2283,
2284, 2286, 2287
RM STPT MAX 12 2281, 2283,
2284, 2286, 2287
RM STPT DIAL 13 2281, 2283,
2284, 2286, 2287, 2299
STPT DIAL 14 2281, 2283,
2284, 2286, 2287
AUX TEMP 15 2299 Actual reading from a 100K ohm thermistor connected to the
DISCH TEMP 15 2281, 2284,
2287
MA TEMP 15 2283, 2286 Actual reading from a 100K ohm thermistor connected to the
The minimum temperature setpoint in degrees that the controller can use from the setpoint dial. This overrides any temperature setpoint from the setpoint dial that falls below this minimum. Valid entry range: 48° to 95°F (9° to 35°C)
The maximum temperature setpoint in degrees that the controller can use from the setpoint dial. This overrides any temperature setpoint from the setpoint dial that rises above this maximum. Valid entry range: 48° to 95°F (9° to 35°C)
The temperature setpoint in degrees from the room temperature sensor (not available on all temperature sensor models). This setpoint will be used for control in day mode (heating or cooling) when enabled by STPT DIAL (Point 14). Valid entry range: 48° to 95°F (9° to 35°C)
YES indicates that there is a room setpoint dial on the room temperature sensor and it is to be used as the temperature setpoint for control in day mode. NO indicates that the appropriate preset setpoint (Points 6, 7, 8 or 9) will be used as the temperature setpoint for control in day heating or cooling mode. Valid input: YES or NO
controller's Al 3 input. When a thermistor is connected at Al 3, DI 3 is not available. Refer to Dl 3 (Point 25).
Actual reading from a 100K ohm thermistor connected to the controller's AI 3 input. When a thermistor is connected at Al 3, DI 3 is not available. Refer to DI 3 (Point 25).
controller's Al 3 input. When a thermistor is connected at Al 3, DI 3 is not available. Refer to DI 3 (Point 25).
1 VLV HTGCLG 16 2281, 2283 YES indicates that there is one valve controlling one coil which
may have hot or chilled water in it. (2-pipe heat/cool). NO indicates any other hardware setup. Valid input: YES or NO
FBP.MODVALVE 17 2281, 2283,
2284, 2286
WALL SWITCH 18 2281, 2283,
2284, 2286, 2287, 2299
DI OVRD SW 19 2281, 2283,
2284, 2286, 2287, 2299
24 Siemens Building Technologies, Inc.
FBP indicates that both heating and cooling will be modulated with a face-bypass damper. VALVE indicates all other configurations. Valid input: FBP or VALVE
YES indicates that the controller is to monitor the status of a wall switch that is connected to DI 2. NO indicates that the controller will not monitor the status of a wall switch, even if one is connected. Valid input: YES or NO
Actual indication of the status of the override switch (not physically available on all temperature sensor models) at the room temperature sensor. ON indicates that the switch is being pressed. OFF indicates that the switch is released. Valid input: ON or OFF
Page 35
Application 2299 – Slave Mode
Descriptor Address Application Description
OVRD TIME 20 2281, 2283,
2284, 2286, 2287
NGT OVRD 21 2281, 2283,
2284, 2286, 2287
AUX.NOAUX 22 2281, 2283,
2284, 2286
FREE CLG 23 2281, 2283,
2284, 2286, 2287
Dl 2 24 2281, 2283,
2284, 2286, 2287, 2299
DI 3 25 2281, 2283,
2284, 2286, 2287, 2299
DI 4 26 2299 Actual status of a contact connected to the controller. ON
LOW TEMP DET 26 2281, 2283,
2284, 2286, 2287
The amount of time (in hours) that the controller will operate in day mode, when the override switch is pressed, while the controller is in night mode.
Indicates the mode that the controller is operating in with respect to the override switch. NIGHT indicates that the switch has not been pressed and the override timer is not active. DAY indicates that the switch has been pressed and the override timer is active. The controller then uses a day mode temperature setpoint. This point is only in effect when DAY.NGT (Point 29) indicates night mode.
AUX indicates that auxiliary radiation is available. NOAUX indicates that auxiliary radiation is not available. Valid input: AUX or NOAUX
Point commanded by the field panel PPCL to enable or disable mixed air damper modulation (free cooling).
Actual status of a contact connected to the controller at DI 2. ON indicates that the contact is closed; OFF indicates that the contact is open. If a wall switch is used, it is connected to DI 2. Refer to WALL SWITCH (Point 18).
Actual status of a contact connected to the controller at Al 3/Dl
3. ON indicates that the contact is closed; OFF indicates that the contact is open. When a contact is connected at DI 3, Al 3 is not available. Refer to AUX TEMP (Point15).
indicates that the contact is closed; OFF indicates that the contact is open.
Actual status of the low temperature alarm, which is determined, by the current status of the low temperature detection thermostat. ON indicates that a low temperature has been detected. OFF indicates a normal condition.
DX COOLING 27 2287 YES indicates a DX coil is used in cooling mode. NO indicates a
chilled water valve is used in cooling mode. Valid input: YES or NO
ELEC.NOELEC 27 2281, 2283,
2284, 2286
FBP.2PSVCTL 28 2281, 2283,
2284, 2286
DAY.NGT 29 2281, 2283,
2284, 2286, 2287, 2299
WRMUP.COOLDN 30 2281, 2283,
2284, 2286, 2287
Siemens Building Technologies, Inc. 25
Indicates whether electric heating is being used. Valid input: ELEC or NOELEC
ENABLE allows two-position valves to close when the face­bypass damper has been closed (to full-bypass) for 2 minutes. DISABL disables the feature. Valid input: ENABLE or DISABL
Indicates the mode in which the controller is operating. Day temperature setpoints will be used in day mode. Night temperature setpoints will be used in night mode. This point is normally set by the field panel.
This point indicates whether or not the unit is currently in warm­up/cool-down. ON indicates the unit is in warm-up/cool down. OFF indicates the unit is not in warm-up/cool-down.
Page 36
APOGEE Heat Pump Controller—Multi Stage Owner's Manual
Descriptor Address Application Description
AOV1SPAN 31 2281, 2283,
2284, 2286, 2287
AOV1START 32 2281, 2283,
2284, 2286, 2287
AOV2 SPAN 33 2281, 2283,
2284, 2286, 2287
AOV2 START 34 2281, 2283,
2284, 2286, 2287
AOV3 SPAN 35 2281, 2283,
2284, 2286, 2287
AOV3 START 36 2281, 2283,
2284, 2286, 2287
AO DIR.REV 37 2281, 2283,
2284, 2286, 2287
AOV1 38 2281, 2283,
2284, 2286, 2287, 2299
Indicates the width of the voltage range where the actuator, controlled by AO1, moves.
Indicates the lower end of the voltage range where the actuator, controlled by AO1, moves.
Indicates the width of the voltage range where the actuator, controlled by AO2, moves.
Indicates the lower end of the voltage range where the actuator, controlled by AO2, moves.
Indicates the width of the voltage range where the actuator, controlled by AO3, moves.
Indicates the lower end of the voltage range where the actuator, controlled by AO3, moves.
Masking point used to determine NO/NC status of actuators attached to analog outputs.
Displays the voltage signal to AO1.
AOV2 39 2281, 2283,
2284, 2286, 2287, 2299
AOV3 40 2281, 2283,
2284, 2286, 2287, 2299
DO 1 41 2287, 2299 Digital output 1 controls a 24 Vac load with an ON or OFF
AUX RAD 41 2281, 2283,
2284, 2286
DO 2 42 2281, 2283,
2284, 2286, 2287, 2299
DO 3 43 2287, 2299 Digital output 3 controls a 24 Vac load with an ON or OFF
HTG 2POS VLV 43 2281, 2283,
2284, 2286
DO 4 44 2299 Digital output 4 controls a 24 Vac load with an ON or OFF
CLG 2POS VLV 44 2281, 2283 The actual status of the two -position cooling valve.
Displays the voltage signal to AO2.
Displays the voltage signal to AO3.
status. The actual status of auxiliary radiation two-position actuator.
Digital output 2 controls a 24 Vac load with an ON or OFF status.
status. The actual status of the two -position heating valve.
status.
26 Siemens Building Technologies, Inc.
Page 37
Application 2299 – Slave Mode
Descriptor Address Application Description
DX 44 2284, 2286,
2287
DO 5 45 2287, 2299 Digital output 5 controls a 24 Vac load with an ON or OFF
EHEAT 1 45 2281, 2283,
2284, 2286
DO 6 46 2287, 2299 Digital output 6 controls a 24 Vac load with an ON or OFF
EHEA T 2 46 2281, 2283,
2284, 2286
DO 7 47 2287, 2299 Digital output 7 controls a 24 Vac load with an ON or OFF
EHEAT 3 47 2281, 2283,
2284, 2286
DO 8 50 2299 Digital output 8 controls a 24 Vac load with an ON or OFF
FAN 50 2281, 2283,
2284, 2286, 2287
NGT HW HTG 53 2281, 2283,
2284, 2286, 2287
The actual status of the DX cooling compressor.
status. The actual status of the first stage of electric heat.
status. The actual status of the second stage of electric heat.
status. The actual status of the third stage of electric heat.
status. This point is a digital output used to control the fan. ON
indicates that the DO is energized; OFF indicates that the DO is de-energized.
YES indicates that the heating valve will be kept open in night mode in both heating and cooling modes (recommended for systems with hot water). NO indicates heating valve will be controlled normally. Valid input: YES or NO
NGT CLG MODE 54 2281, 2283,
2284, 2286, 2287
AUX OUTPUT 55 2281, 2283,
2284, 2286
AUX HTG TIME 57 2281, 2283,
2284, 2286
EHT STG DELY 58 2281, 2283,
2284, 2286
DO DIR.REV 59 2281, 2283,
2284, 2286, 2287, 2299,
HTG OUTPUT 60 2281, 2283,
2284, 2286, 2287
YES indicates that night cooling is available. NO indicates that night cooling is not available. Valid input: YES or NO
Indicates the percentage of time the auxiliary radiation will be ON. Valid values: 0 to 100%
The period of the auxiliary radiation pulse-width modulation algorithm. Valid values: 0 to 255 minutes
Delay between a stage of electric heat changing state and the next change of state of any stage. Valid input: 0 to 255 seconds
The configuration setup code for DOs. Allows the DOs to be direct or reverse acting (enabled equals energized or enabled equals de-energized).
If the heating control device is a valve or face-bypass damper, then the value of this point indicates the position of the heating actuator. If electric heat is used, then the value of this point determines how many stages are ON. Valid values: 0 to 100%
Siemens Building Technologies, Inc. 27
Page 38
APOGEE Heat Pump Controller—Multi Stage Owner's Manual
Descriptor Address Application Description
CLG OUTPUT 61 2281, 2283,
2284, 2286, 2287
OA DMPR POS 62 2281, 2283,
2284, 2286, 2287
CLG P GAIN 63 2281, 2283,
2284, 2286, 2287
CLG l GAIN 64 2281, 2283,
2284, 2286, 2287
CLG D GAIN 65 2281, 2283,
2284, 2286, 2287
CLG BIAS 66 2281, 2283,
2284, 2286, 2287
HTG P GAIN 67 2281, 2283,
2284, 2286, 2287
HTG l GAIN 68 2281, 2283,
2284, 2286, 2287
If the cooling control device is not DX, then the value of this point indicates the position of the cooling actuator. If DX cooling is used, then the value of this point determines whether DX is ON or OFF. Valid values: 0 to 100%
Indicates the position of the outdoor air damper actuator.
The proportional gain value for the cooling temperature control loop.
The integral gain value for the cooling temperature control loop.
The derivative gain value for the cooling temperature control loop.
The biasing of the cooling temperature control loop. Refer to CLG LOOPOUT (Point79).
The proportional gain value for the heating temperature control loop.
The integral gain value for the heating temperature control loop.
HTG D GAIN 69 2281, 2283,
2284, 2286, 2287
HTG BIAS 70 2281, 2283,
2284, 2286,
2287 ROOM P GAIN 71 2281, 2284 The proportional gain value for the room control loop. ROOM I GAIN 72 2281, 2284 The integral gain value for the room control loop. ROOM D GAIN 73 2281, 2284 The derivative gain value for the room control loop. ROOM BIAS 74 2281, 2284 The biasing of the room loop output point, DISCH STPT (Point
CMP MIN OFF 75 2284, 2286,
2287
CMP MlN ON 76 2284, 2286,
2287
AUX LOOPOUT 77 2281, 2284 The control loop output value that is used to determine AUX
The derivative gain value for the heating temperature control loop.
The biasing of the heating temperature control loop. Refer to HTG LOOPOUT (Point 80).
93). The minimum time, in minutes, which the unit ventilator's
compressor will remain OFF before turning ON again. Valid input: 0 to 255 minutes
The minimum time, in minutes, which the unit ventilator's compressor will remain ON before turning OFF again. Valid input: 0 - 255 minutes
OUTPUT (Point 55).
28 Siemens Building Technologies, Inc.
Page 39
Application 2299 – Slave Mode
Descriptor Address Application Description
MA LOOPOUT 77 2283, 2286 The mixed air control loop output value that is used to
determine OA DMPR POS (Point 62).
OA LOOPOUT 77 2287 The outdoor air damper control loop output valve that is used to
determine OA DMPR POS (Point 62).
CTL TEMP 78 2281, 2283,
2284, 2286,
2287 CLG LOOPOUT 79 2281, 2283,
2284, 2286,
2287 HTG LOOPOUT 80 2281, 2283,
2284, 2286,
2287 AUX P GAIN 81 2281, 2284 The proportional gain value for the auxiliary control loop. MA P GAIN 81 2283, 2286 The proportional gain value for the mixed air control loop. OA P GAIN 81 2287 The proportional gain value for the outdoor air damper control
AUX l GAIN 82 2281, 2284 The integral gain value for the auxiliary control loop. MA l GAIN 82 2283, 2286 The integral gain value for the mixed air control loop. OA l GAIN 82 2287 The integral gain value for the outdoor air damper control loop. AUX D GAIN 83 2281, 2284 The derivative gain value for the auxiliary control loop. MA D GAIN 83 2283, 2286 The derivative gain value for the mixed air control loop. OA D GAIN 83 2287 The derivative gain value for the outdoor air damper control
AUX BIAS 84 2281, 2284 The biasing of the auxiliary loopout point, AUX LOOPOUT
MA BIAS 84 2283, 2286 The biasing of the mixed air loopout point, MA LOOPOUT
OA BIAS 84 2287 The biasing of the outdoor air damper loopout point, OA
The temperature used as input for the temperature control loops. This value will be the same as the value in ROOM TEMP (Point 4) unless it is overridden.
The cooling temperature control loop output value in percent.
The heating temperature control loop output value in percent.
loop.
loop.
(Point 77).
(Point 77).
LOOPOUT (Point 77).
SWITCH LIMIT 85 2281, 2283,
2284, 2286, 2287
SWITCH TIME 86 2281, 2283,
2284, 2286, 2287
Siemens Building Technologies, Inc. 29
The active temperature control loop output must be less than this value to switch between cooling mode and heating mode. Actual switchover depends on SWITCH DBAND (Point 90) being exceeded and is subject to SWITCH TIME (Point 86) being expired. Valid input: 0 to 100%
The time, in minutes, that must expire to switch between cooling mode and heating mode. Actual switchover depends on the active temperature control loop being below the value of SWITCH LIMIT (Point 85) and exceeding the value of SWITCH DBAND (Point 90). Valid input: 0 to 255 minutes
Page 40
APOGEE Heat Pump Controller—Multi Stage Owner's Manual
Descriptor Address Application Description
NGT DBAND 88 2281, 2283,
2284, 2286, 2287
MORN DBAND 89 2281, 2283,
2284, 2286, 2287
SWITCH DBAND 90 2281, 2283,
2284, 2286, 2287
AUX DSH STPT 91 2281, 2284 The setpoint of the auxiliary radiation control loop. CTL STPT 92 2281, 2283,
2284, 2286, 2287
DISCH STPT 93 2281, 2284,
2287 MA STPT 93 2283, 2286 The setpoint of the mixed air control loop. DSH MIN TEMP 94 2281, 2284 The minimum value to which DISCH STPT (Point 93) can be set
During night mode, this point indicates the number of degrees above or below (depending on heating/cooling mode) the night setpoint that the room temperature can raise or drop before the fan will be turn ON. Valid input: 0 to 255°F
The number of degrees of variance from the heating or cooling setpoint at which the controller will terminate morning warm-up or cool-down and begin normal operation. Valid input: 0 to 255'F
The temperature range in degrees that is compared to the difference between CTL TEMP (Point 78) and CTL STPT (Point
92). The difference exceeding this value is one of the conditions necessary to change modes between heating and cooling. Valid input: 0 to 255°F
The actual setpoint value being used as input for the active temperature control loop.
The setpoint of the discharge air control loop.
by the room control loop.
DSH MAX TEMP 95 2281, 2284 The maximum value to which DISCH STPT (Point 93) can be set
by the room control loop.
LOOP TIME 98 2281, 2283,
2284, 2286, 2287
ERROR STATUS 99 2281, 2283,
2284, 2286, 2287, 2299
The time, in seconds, between control loop calculations.
The status code indicating any errors detected during controller power up. A status of 0 indicates there are no problems.
30 Siemens Building Technologies, Inc.
Page 41
4
Troubleshooting
Overview
This chapter describes corrective measures you can take should you encounter a problem when using a Unit Vent Controller.
You are not required to do any controller troubleshooting. You may want to contact your local Siemens Building Technologies representative if a problem occurs or you have any questions about the controller.
NOTE: When troubleshooting, record what the problem is and what actions were
performed immediately before the problem occurred. Being able to describe the problem in detail is important, should you need assistance from your local Siemens Building Technologies representative.
Basic Service Information
Always remove power to the controller when installing or replacing it. Since the controller does not have a power switch, the recommended method of removing power to a locally powered controller is to turn OFF the power to the 24 Vac transformer. The recommended method of removing power to a controller on a power cable (even to service a single controller) is to turn OFF the power at the transformer.
NOTE: When removing power to a controller to perform maintenance or service, make
sure that the person in charge of the facility is aware of this and that appropriate steps are taken to keep the building in control.
Never remove the cover from the controller. There are no serviceable parts inside. If a problem is found with a controller, contact your local Siemens Building Technologies representative for replacement. An anti-static wrist strap is recommended when installing or replacing controllers.
Siemens Building Technologies, Inc. 31
Page 42
APOGEE Heat Pump Controller – Multi-Stage Owner's Manual
Ordering Replacement Parts
If a controller is not operating correctly, order a new controller. The product number for ordering a replacement controller is the controller product number preceded by an "R". The replacement product numbers for accessories are the same as new product numbers:
Unit Vent Controller – 0 to 10V Output 540-509 CE Compliant Unit Vent Controller – 0 to 10V Output 550-509
Preventive Maintenance
Most controller components are designed so that, under normal circumstances, they do not require preventive maintenance. Periodic inspections, voltage checks, and point checks are normally not required. The controller's rugged design makes most preventive maintenance unnecessary. However, devices that are exposed to dusty or dirty environments may require periodic cleaning to function properly.
Safety Features
The controller board stores the controller's address, applications and point values. In the event of a power failure or a reset, these values are retrieved from the controller's permanent memory and are used by the controller unless overridden by a field panel. If one of the following conditions occurs, the controller will activate safety features present in its fail-safe mode.
Sensor failure.
Loss of power. Upon controller power loss, communication with the controller is also
lost. The controller will appear as failed (
Controller LEDs
To determine if the controller is powered up and working, verify that the Basic Sanity Test (BST) Light Emitting Diode (LED) is flashing ON/OFF once per second. The controller contains eleven LEDs located on the circuit board. See the Controller LED indicators section of Chapter 1, Product Overview for more information about LEDs.
NOTE: The TX and RX LEDs indicate communication over the FLN.
*F*) at the field panel.
32 Siemens Building Technologies, Inc.
Page 43
Glossary
Overview
The glossary contains terms and acronyms that are used in this manual. For definitions of point database descriptors, see Chapter 3, Point Database. For definitions of commonly used terms as well as acronyms and abbreviations associated with the APOGEE Automation System, see the Siemens Building Technologies Technical Glossary of Building Controls Terminology and Acronyms, (125-2185). This book is available from your local Siemens Building Technologies representative.
Al
Analog Input. Physical point which accepts a continuous variable signal.
algorithm
Mathematical formula used to calculate an output value using varying inputs.
AO
Analog Output. Physical point that generates a continuous variable signal.
centralized control
Type of control offered by a controller that is connected, by means of a Floor Level Network (FLN), with an APOGEE field panel.
control loop
Proportional Integral Derivative (PlD) algorithm that is used to control an output based on a setpoint and an input reading from a sensor.
DDC
Direct Digital Control.
Dl
Digital Input. Physical output point that accepts a two-state signal (that is, ON/OFF, OPEN/CLOSED, YES/NO, etc.).
Siemens Building Technologies, Inc. 33
Page 44
APOGEE Unit Vent Controller⎯0 to 10V Output Owner’s Manual
DO
Digital Output. Physical output point that generates a two-state signal (that is, ON/OFF, OPEN/CLOSED, YES/NO, etc.).
English units
Foot-pound-second system of units for weights and measurements.
equipment controller
FLN device which provides additional point capacity to a field panel or provides individual room or mechanical equipment control. The Unit Vent Controller — 0 to 10V Output is an equipment controller.
field panel
FLN
intercept
FLN
Ioopout
Device containing a microprocessor for centralized control of system components and equipment controllers. A field panel samples and processes field data, initiates control actions, communicates with its operators, and generates reports, displays and warnings.
Field Level Network
Factor which converts analog values (used by the controller) to a form which the user can understand (engineering units). Slope and intercept constants are determined by the type of field input/output represented by the physical or virtual point.
Revised acronym for Floor Level Network. The term “Floor” is no longer used and has been replaced with “Field”.
Output of the control loop expressed as a percentage.
OFF text
Text indicating the de-energized state of a digital point (for example, OFF, CLOSED, NO).
34
Page 45
ON text
Text indicating the energized state of a digital point (for example, ON, OPEN, YES).
override switch
Button on Room Temperature Sensor that can be pressed by an occupant to change the status of a room from night mode to day mode for a predetermined time.
PID
Proportional, lntegral, and Derivative.
RTS
Room Temperature Sensor.
Overview
Sl units
Systeme International d'Unites. The international metric system.
slave mode
Default application that comes up when power is first applied to a Terminal Equipment Controller.
slope
Factor that converts analog values (used by the controller) to a form the user can understand (engineering units). Slope and intercept constants are determined by the type of field input/output represented by the physical or virtual point.
stand-alone control
Type of control offered by a controller that is providing independent DDC control to a space.
Terminal Equipment ControIler
Siemens Building Technologies product family of equipment controllers (one is the Unit Vent Controller — 0 to 10V Output) that house the applications software used to control terminal units, such as heat pumps, VAV terminal boxes, fan coil units, unit ventilators, etc.
35
Page 46
APOGEE Unit Vent Controller⎯0 to 10V Output Owner’s Manual
unbundle
Term used to describe the entering of a point that resides in a controller's database into the field panel's database so that it can be monitored at or controlled from the field panel.
36
Page 47
Index
A
actuators ............................................................ 5
address descriptions ........................................ 23
AI (see analog input)
algorithm .......................................................... 33
analog input .................................................. 2, 33
analog output ............................................... 3, 33
AO ........................................ (see analog output)
Application 2281 ............................................... 10
ASHRE Cycles I and II ................................. 10
auxiliary radiation .......................................... 12
Application 2283 ............................................... 13
ASHRE Cycle III ........................................... 13
Application 2284 ............................................... 16
ASHRE Cycle I and II ................................... 16
auxiliary radiation .......................................... 17
Application 2286 ............................................... 18
ASHRE Cycle III ........................................... 18
Application 2287 ............................................... 20
Nesbitt Cycle W ............................................ 20
Application 2299 ............................................... 22
Slave mode ................................................... 22
applications
control loops ................................................... 7
control temperature setpoints ......................... 6
day/night mode ............................................... 6
heating and cooling switchover ...................... 7
night mode override switch ............................. 7
D
damper actuator ................................................. 5
database ............................. (see point database)
Datamate Software ............................................ v
DDC .......................... (see Direct Digital Control)
DI ............................................. (see digital input)
digital input ................................................... 2, 33
digital output ................................................. 3, 34
Direct Digital Control .......................................... 1
DO .......................................... (see digital output)
E
English units ..................................................... 34
equipment controller ........................................ 34
F
fail-safe operation .............................................. 8
fan operation ...................................................... 8
field panel ......................................................... 34
FLN ............................ (see Floor Level Network)
Floor Level Network ......................................... 34
Floor Level Network (FLN)................................. 3
H
B
Basic Sanity Test (BST) ................................... 32
basic service information ................................. 31
BST LED .......................................................... 32
C
centralized control ............................................ 33
communication wiring .................................... 3, 4
control loop ....................................................... 33
controller
LEDs/LED indicators ................................ 4, 32
controller hardware ............................................ 1
Siemens Building Technologies, Inc. 37
hardware
power wiring ............................................... 3, 4
hardware, inputs and outputs ............................ 2
I
inputs and outputs
analog ......................................................... 2, 3
digital .......................................................... 2, 3
hardware ........................................................ 2
intercept ........................................................... 34
Page 48
APOGEE Unit Vent Controller⎯0 to 10V Output Owner’s Manual
L
LAN .................................................................. 34
LED .................................................................... 4
Light Emitting Diodes (LEDs) ........................... 32
BST ............................................................... 32
RX and TX .................................................... 32
loopout.............................................................. 34
O
OFF text ........................................................... 34
ON text ............................................................. 35
override switch ................................................. 35
P
parts, replacement ........................................... 32
PID .... (see proportional, integral, and derivative)
point database .................................................. 30
point database .................................................. 23
point addresses ............................................ 23
point descriptors ........................................... 23
power wiring ................................................... 3, 4
preventive maintenance ................................... 32
service information, basic ................................ 31
SI units ............................................................. 35
slave mode ....................................................... 35
slope ................................................................ 35
stand-alone control .......................................... 35
static discharge ................................................ 31
T
TEC ........... (see Terminal Equipment Controller)
temperature sensor ............................................ 4
discharge air ................................................... 5
mixed air ......................................................... 5
room ............................................................... 4
temperature sensors .......................................... 4
mixed air ......................................................... 5
room ............................................................... 4
Terminal Equipment Controller ........................ 35
troubleshooting ................................................ 31
basic service information.............................. 31
TX LED ............................................................ 32
U
unbundle .......................................................... 36
Unit Vent Controller ........................................... 1
R
related equipment .............................................. 5
replacement parts ............................................ 32
Room Temperature Sensor ............................... 4
RTS ................ (see Room Temperature Sensor)
RX LED ............................................................ 32
S
safety features .................................................. 32
V
valve actuator ..................................................... 5
W
wiring
communication wiring ................................. 3, 4
power wiring ............................................... 3, 4
38
Loading...