The information contained within this document is subject to change without notice and should not be construed as a
commitment by Siemens Building Technologies, Inc. Siemens Building Technologies, Inc. assumes no responsibility
for any errors that may appear in this document.
All software described in this document is furnished under a license and may be used or copied only in accordance
with the terms of such license.
WARNING
This equipment generates, uses, and can radiate radio frequency energy and if not installed and used in accordance
with the instructions manual, may cause interference to radio communications. It has been tested and found to
comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits are designed to
provide reasonable protection against such interference when operated in a commercial environment. Operation of
this equipment in a residential area is likely to cause interference in which case users at their own expense will be
required to take whatever measures may be required to correct the interference.
SERVICE STATEMENT
Control devices are combined to make a system. Each control device is mechanical in nature and all mechanical
components must be regularly serviced to optimize their operation. All Siemens Building Technologies branch offices
and authorized distributors offer Technical Support Programs that will ensure your continuous, trouble-free system
performance.
For further information, contact your nearest Siemens Building Technologies, Inc. representative.
Copyright 2006 by Siemens Building Technologies, Inc.
TO THE READER
Your feedback is important to us. If you have comments about this manual, please submit them to
SBT_technical.editor.us.sbt@siemens.com
CREDITS
APOGEE is a registered trademark of Siemens Building Technologies, Inc.
Insight for Minicomputers is a registered trademark of Siemens Building Technologies, Inc.
Insight for Personal Computers is a registered trademark of Siemens Building Technologies, Inc.
Country of Origin: US
Table of Contents
How To Use This Manual ................................................................................................. iv
This manual is written for the owner and user of the Siemens Building Technologies, Inc. Unit
Vent Controller – 0 to 10V, often referred to as controller for the remainder of this manual.
This manual is designed to help you become familiar with the controller and its applications.
This chapter covers manual organization, manual symbols and conventions used and how to
access help.
Manual Organization
This manual contains the following chapters:
•Chapter 1 Product Overview, describes the hardware components and accessories
used with the controller.
• Chapter 2Applications, describes the control applications available in the controller.
• Chapter 3Point Database, defines the point database descriptors and includes
addresses and applications.
•Chapter 4Troubleshooting, describes basic corrective measures to take should you
encounter a problem when using this controller. For issues not covered in this
chapter, contact your local Siemens Building Technologies representative.
• A Glossary describes the terms and acronyms used in this manual.
• An Index is provided to assist you in finding information.
Siemens Building Technologies,Inc. iv
Manual Conventions
The following table lists conventions used in this manual.
Convention Example
Manual Organization
Actions that you should
perform are specified in
boldface font.
Error and system
messages are displayed
in Courier New font.
New terms appearing for
the first time are
italicized.
Manual Symbols
The following table lists symbols that used to draw your attention to important information.
Notation Symbol Meaning
CAUTION:
WARNING:
Type F for Field panels.
Click OK to save changes and close the dialog box.
The message Report Definition successfully renamed
appears in the status bar.
The Open Processor continuously executes a user-defined set of
instructions called the control program.
Indicates that equipment damage or loss of data may
occur, if a procedure is not performed as specified.
Indicates that personal injury or loss of life may occur to the
user, if a procedure is not performed as specified.
Datamate Software
Datamate is a customer software tool for all controller communications. There are two
versions: Datamate Base, and Datamate Advanced. Datamate Base works on an IBMcompatible Personal Computer (PC), or a Handheld PC or Pocket PC™ running Windows
CE. Datamate Advanced works only on an IBM-compatible Personal Computer.
With Datamate, you can back up, restore and edit any APOGEE
Datamate Advanced allows you to edit points offline). Backing up and restoring a database is
accomplished while connected to any APOGEE
®
field panel, or to the Automation Level
Network (ALN) or Field Level Network (FLN) device in question. A modem and telephone
lines can also be used. Databases can be saved for permanent storage or used as backup.
For more information on Datamate software, refer to the appropriate user guide for the
version of Datamate you are using (Base or Advanced), or contact your local Siemens
Building Technologies, Inc. representative.
Siemens Building Technologies, v
®
database (but only
APOGEE Unit Vent Controller⎯0 to 10 V Output Owner’s Manual
Getting Help
For more information about the Unit Vent Controller, contact your local Siemens Building
Technologies representative.
Where To Send Comments
Your feedback is important to us. If you have comments about this manual, please submit
them to SBT_technical.editor.us.sbt@siemens.com
vi Siemens Building Technologies. Inc.
1
Product Overview
Introduction
The Unit Vent Controller—0 to 10V Output is the Siemens Building Technologies, Inc.
Terminal Equipment Controller (TEC) used in unit ventilator applications. See Figure 1. It
provides Direct Digital Control (DDC) for five applications. The controller can operate as an
independent, stand-alone, DDC room controller or be networked with an APOGEE field
panel.
The controller provides all termination, input/output, system and local communication
connections. See Figure 1. The controller hardware consists of the controller with cover and
mounting bracket.
Table 1. Unit Vent Controller – 0 to 10 V Output Applications.
Standard Applications
2281 Heating and/or Chilled Water Cooling, ASHRAE Cycles l and II
2283 Heating and/or Chilled Water Cooling, ASHRAE Cycle III
2284 Heating and DX Cooling, ASHRAE Cycles I and II
2286 Heating and DX Cooling, ASHRAE Cycle III
2287 Nesbitt Cycle W
2299Slave Mode (no control; available for set up, and point extension device)
Ordering Notes
Unit Vent Controller – 0 to 10 Volt Output 540-509
Siemens Building Technologies, Inc. 1
APOGEE Unit Vent Controller⎯0 to 10V Output Owner’s Manual
COVER
CONTROLLER
BOARD
MOUNTING
HOLE
(2)
DO 1 DO 2 DO 3 DO 4 DO 5 DO 6
NO C NO C NO C NO C NO C NO C
The controller is powered by 24 Vac and connects to the two screw terminals on the
controller. Labeled “C” (Common) and “H” (Hot) on the terminal block labeled “24 VAC”. No
earth-ground connection is required (Figure 2).
Communication Wiring
The controller connects to the field panel by means of a Floor Level Network (FLN) trunk.
Communication wiring connects to the three screw terminals on the controller labeled “+”
(positive), “-“ (negative), and “S” (Shield) (Figure 3).
2281, 2283, 2284, 2286
2284, 2286, 2287
Siemens Building Technologies, Inc. 3
APOGEE Unit Vent Controller⎯0 to 10V Output Owner’s Manual
DO 1 DO 2 DO 3 DO 4 DO 5
NO C NO C NO C NO C NO C
1 2 3 4 5 6 7 8 9 10 11 1
1 2 3 4 5 6 7 8 9 10 11 12
TEC0253R2
24 V-AC
CEH
COMMON
24 VA C HOT
CONTROLLER POWER WIRING
NOTE: NO EARTH GROUND CONNECTION
Figure 2. Power Wiring. Figure 3. Communication Wiring.
Controller LED Indicators
The controller has eleven Light Emitting Diode (LED) indicators. See Figure 1. Table 2 lists
the type, the abbreviation on the controller, and the indication of each LED.
LED Type Label
(if present)*
DO LED 1 to
LED 8
FLN TRUNK
(+)
(-)
+-
(-)
(+)
NO
(SHIELD)(SHIELD)
TEC0470R1
Table 2. Controller LEDS.
LED
Indication
Number
1 to 8 Indicates the ON/OFF status of the
DO associated with it. A glowing LED
indicates that the DO is energized.
S
Receive RX 9 Indicates, when flashing, that the controller is
Transmit TX 10 Indicates, when flashing, that the controller is
Basic Sanity Test BST 11 Indicates, when flashing ON and OFF once
*Some LED labels and numerals may be hidden by the controller cover.
Temperature Sensors
Temperature sensors used with the Unit Vent Controller—0 to 10V Output include an
electronic room, mixed air or discharge air temperature sensor.
Room Temperature Sensor
The Terminal Equipment Controller room temperature sensor connects to the controller by
means of a cable pre-terminated at both ends with a 6-conductor RJ-11 plug-in connector.
See Figure 1 for the location of the room temperature sensor/Man-Machine Interface (MMI)
port.
receiving information from the field panel.
transmitting information to the field panel.
per second, that the controller is functioning
property.
4 Siemens Building Technologies, Inc.
Mixed Air/Discharge Air Temperature Sensor
The mixed air/discharge air temperature sensor is a 100K ohm thermistor that connects to
the controller at the screw terminals for Al 3.
For more information about Siemens Building Technologies, Inc. temperature sensors,
contact your local Siemens Building Technologies, Inc. representative.
Actuators
Damper Actuators
The damper actuator used with the Unit Vent Controller—0 to 10V Output is a 0 to 10V spring
return electronic damper motor that positions an outside air damper. A 0 to 10V electronic
damper motor can be used to position a face-and-bypass damper.
Valve Actuators
Introduction
The valve actuators used with the Unit Vent Controller—0 to 10V Output are modulating
spring return and non-spring return electronic valve motors that position the valves.
Related Equipment
• Relay Module
• Damper Actuator(s)
• Valve Actuator(s)
• Mixed Air/Discharge Air Temperature Sensor (optional)
• TEC Room Temperature Sensor
Contact your local Siemens Building Technologies, Inc. representative for product numbers
and more information.
Siemens Building Technologies, Inc. 5
Loading...
+ 33 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.