Shop fox D4530 User Manual

Model D4530
#16598TS
120V Magnetic ON/OFF
Switch
Instruction Sheet
Phone #: (360) 734-3482 • Online Tech Support: tech-support@shopfox.biz • Web: www.shopfox.biz
To reduce risk of serious burns, electrocution or death when installing this switch:
• Only use this switch to replace an existing machine switch that has the same physical configuration and equivalent electrical specifications/ratings.
• Installation must only be performed by an electrician or qualified service personnel, and all applicable electrical codes must be adhered to.
• Turn OFF and completely disconnect all power sources to the machine before installing the switch.
Figure 1. D4530 120V Magnetic ON/OFF Switch.
Introduction
The Model D4530 features a recessed magnetic ON ( | ) button. The switch assembly is designed to snap into a 1" x 2" rectangular hole.
• Do not use this switch in wet or damp locations, or near explosive fumes or flammable liquids. It is not sealed or rated for these environments.
• Make sure there is a verified machine ground on the circuit this switch is installed.
Specifications
Rated Voltage ................................... 120V
Rated Current Amperage ........................ 16A
COPYRIGHT © MAY, 2014 BY WOODSTOCK INTERNATIONAL, INC.
WARNING: NO PORTION OF THIS MANUAL MAY BE REPRODUCED IN ANY SHAPE OR FORM WITHOUT
THE WRITTEN APPROVAL OF WOODSTOCK INTERNATIONAL, INC.
D4530 120V Magnetic ON/OFF Switch
Installation
When installing the D4530 switch, use the wiring diagram in Figure 2 to ensure proper wire connections.
Important: Terminal A1 MUST be connected to either terminal 14 or 24 for the switch to work properly.
This switch is intended to be connected to stranded wire with insulated quick-discon­nect crimp-type female wire terminals hav-
1
ing a
All crimps must be "pull-checked" to ensure that wires are securely crimped and will not fall out with moderate tension or when exposed to normal machine vibration.
4" tab.
Machine
Verified Ground*
Hot Out
14
13
Hot
In
Power Source
Neutral
Out
A1
24
23
Neutral
In
Important
Connection
Rear View
of Switch
Figure 2. D4530 wiring diagram.
*The machine MUST be connected to a verified ground. In the event of certain malfunctions or breakdowns, grounding reduces the risk of electric shock by providing a path of least resistance for electric current.
-2-