SHARP AF-08CRL Diagram

Page 1
SER VICE MANU AL
AIR CONDITIONER
AF-08CRL
S3211AF08CRL/
MODEL
In the interests of user-safety (Required by safety regulations in some countries) the set should be restored to its original condition and only parts identical to those specified should be used.
TABLE OF CONTENTS
SPECIFICATIONS ................................................................................................................................................ 2
WIRING DIAGRAM............................................................................................................................................... 3
EXTERNAL DIMENSIONS ................................................................................................................................... 4
HOW TO OPERATE ............................................................................................................................................. 5
INSTALLATIOIN INSTRUCTIONS ......................................................................................................................13
HOW TO REPAIR REFRIGERATION ................................................................................................................. 19
ELECTRICAL COMPONENT TEST .................................................................................................................... 21
MICROCOMPUTER CONTROL SYSTEM ..........................................................................................................22
TROUBLESHOOTING GUIDE ............................................................................................................................26
COOLING LOAD ESTIMATE FORM ...................................................................................................................31
RUNNING CONDITION .......................................................................................................................................33
PACKING AND ACCESSORIES ......................................................................................................................... 34
REPLACEMENT PARTS LIST ............................................................................................................................35
AF-08CRL
Page
SHARP CORPORATION This document has been published to be used for after
sales service only. The contents are subject to change without notice.
1
Page 2
AF-08CRL
SPECIFICATIONS
Models AF-08CRL Cooling capacity BTU/h 8000 Moisture removal Pints/h 2.3
ELECTRICAL DATA
Phase Single Rared frequency Hz 60 Rated voltage Volts 115 Rated current Amps 7.3 Rated input Watts 800 Power factor % 95 EER BTU/Wh 10.0
COMPRESSOR
Type (Hermetically sealed rotary type) Model, Motor output
2R12S3R126A-6A, 600W
REFRIGERANT SYSTEM
Evaporator Louver fin, Grooved tube, 7mm, Hair pin Condenser Louver fin, Grooved tube, 7mm, Hair pin Control O.D. x I.D. x Length x Q'ty(mm) 2.7 x 1.2 x 450 x 1 (Capillary tube) Refrigerant volume R-22(OZ) 15.9 (Factory change)
NET DIMENSIONS
Width Height Depth
inches(mm)
19-11/16(500) x 14-9/16(370) x 17-3/32(434)
Net Weight lbs 53
GROSS DIMENSIONS
Width Height Depth
inches(mm)
22-27/32(580) x 18-5/16(465) x 19-31/32(507)
Gross Weight lbs 60
FAN SYSTEM
Indoor side(Evaporator) Centrifugal fan Outdoor side(Condenser) Propeller fan Air flow rate(indoor side) CFM High / Med / Low
187 / 173 / 155
OTHERS
Safety devices Compressor: Overload relay
Fan motor: Internal thermal protector Air filter Polypropylene net Power cord length ft 6.0 Power plug type 125V, 10A
2
Page 3
ELECTRICAL PARTS
Models
AF-08CRL Running capacitor 250V-35µF Fan capacitor 250V-6µF Thermistor 15kΩ at 78˚F Fan motor OBM-2508K1 (MLB003) Overload relay MRA98706
WIRING DIAGRAM
AF-08CRL
POWER SUPPLY CORD
115V 60Hz
NON RIBBED
COMPRESSOR
RIBBED
BL
RUNNING CAPACITOR 250V 35
FAN MOTOR CAPACITOR 250V 6
µ
F
BL
BK
123654
BK
BL
THERMAL PROTECTOR
BK
GR
OVERLOAD PROTECTOR
MOTOR
GYREOR
M.C
µ
F
H
M
A.C
OUT
R
RE
GY
RE OR WH
WH
L
IN
C
CONNECTOR
FAN MOTOR
EARTH
GR
BK
BK
3A 125V
MRY
S
WH
GY
FU1 CONTROL BOARD UNIT
NR
CNR1 CNR2
8 7 1 3 5
BCN1
CNR3
C1
TR
RY1 RY2 RY3
WIRE COLOR
BK
BL
RE
WH
GR GY OR
CN1
YELLOW TH1
BCN2
BCN3
: BLACK : BLUE : RED : WHITE : GREEN : GRAY : ORANGE
THERMISTOR
(
ROOM TEMP
CN2
CN3
)
DISPLAY BOARD UNIT
Figure W-1
3
Page 4
AF-08CRL
EXTERNAL DIMENSIONS
19-11/16"
5
35-7/16" (full opened)
23-5/8" (full closed)
4-15/32"
Fig. E-1.
17-3/32"
1-15/32"
13-5/8"
15-11/16"
4
Page 5
PARTS NAMES
UNIT
AF-08CRL
HO W TO OPERA TE
3
4
2
1
CONTROL PANEL
2 1
COOL / FAN TEMP
3
SELECTOR
4 5 6 8
5
F
hr
TIMER
ON/OFF
ENERGY
SAVER
7 9
6
POWER
ON/OFF
10
11
11
1Front Cabinet 2Air Inlet (Indoor Side)
7
3Horizontal Louvers 4Vertical Louvers
8
5Air Outlet (Indoor Side) 6Control Panel 7Rear Cabinet
9
8Air Inlet (Outdoor side) 9Filter (Pull the filter handle
10
to the right to remove.)
0Filter Handle qPower Cord
1Receiver window for remote
control signal
2Display 3SELECTOR indicator 4SELECTOR pad 5TEMPERATURE setting pad
----Lower temp.
----Raise temp.
6TIMER ON/OFF pad 7TIMER indicator 8ENERGY SAVER pad 9ENERGY SAVER indicator 0POWER ON/OFF pad qPOWER indicator
5
Page 6
AF-08CRL
COOLING OPERATION
POWER indicatorSELECTOR indicator
Touch POWER ON/OFF pad.
1
The unit is preset at 74°F and HIGH COOL. This will show in the display
F
hr
when the power is first turned on.
POWER indicator and SELECTOR indicator (COOL) will light.
COOL / FAN TEMP
ENERGY
SELECTOR
TIMER
ON/OFF
SAVER
POWER
ON/OFF
POWER ON/OFF pad
To turn off the unit, touch POWER
2
ON/OFF pad again.
POWER indicator and SELECTOR indicator will go off.
TO CHANGE TEMPERATURE SETTING
During cooling operation
COOL / FAN TEMP
SELECTOR
F
hr
TIMER
ON/OFF
ENERGY
SAVER
POWER
ON/OFF
Touch the TEMPERATURE setting pad to adjust the temperature setting.
---Lower temp.
---Raise temp.
Temperature can be set within the range
TEMPERATURE setting pad
of 64°F to 86°F.
Display will change as you touch the pad.
NOTE:
The latest temperature setting will be memorized and will appear on the display the next time
the unit is turned on.
In cases of power outages or when the unit is disconnected; when the power is restored or the unit is plugged in, the unit and display will return to the preset conditions of 74°F and HIGH COOL. The unit will not automatically turn back on. The user must touch POWER ON/OFF to resume opertion.
6
Page 7
TO CHANGE FAN SPEED AND OPERATION MODE
AF-08CRL
SELECTOR indicator
F
hr
COOL / FAN TEMP
ENERGY
SELECTOR
TIMER
ON/OFF
SAVER
POWER
SELECTOR pad
NOTES ON OPERATION MODE:
MODE
HIGH COOL
SELECTOR DISPLAY
COOL
ON/OFF
During operation
Touch SELECTOR pad and select the operation mode and fan speed.
SELECTOR indicator and display will light in order as you touch.
HIGH COOL MED COOL
MED FANLOW FAN
Cooling operation with high fan speed.
LOW COOL
HIGH FAN
MED COOL
LOW COOL
HIGH FAN
MED FAN
LOW FAN
COOL
COOL
FAN
FAN
FAN
Cooling operation with medium fan speed.
Cooling operation with low fan speed.
Fan only operation with high fan speed.
Fan only operation with medium fan speed.
Fan only operation with low fan speed.
The latest operation mode will be memorized and the selector indicator and display will light when the unit is turned on.
In fan only operation, the temperature display will go off.
When the SELECTOR is changed to fan only operation from cooling operation, it will take 5
seconds for the compressor to stop.
7
Page 8
AF-08CRL
ENERGY SAVER
During normal operation, the thermostat automatically controls cooling and the fan runs continuously. When the ENERGY SAVER is selected, the thermostat automatically controls cooling and the fan automatically stops when the compressor is not operating. (Fan will stop 30 seconds after the compressor stops. After the fan stops, the fan is programmed to rotate for approx. 2 minutes to detect room temperature. This will occur within a 20 min time span.)
During cooling operation
Touch ENERGY SAVER pad.
F
hr
COOL / FAN TEMP
1
ENERGY SAVER indicator will light.
SELECTOR
TIMER
ON/OFF
ENERGY
SAVER
POWER
ON/OFF
2
To cancel, touch ENERGY SAVER pad again.
ENERGY SAVER indicator will go
ENERGY SAVER pad
ENERGY SAVER indicator
off.
NOTE: ENERGY SAVER cannot be set during fan only (HIGH FAN, MED FAN, LOW FAN)
operation.
TO CHANGE AIR FLOW DIRECTION
The horizontal louvers are used to adjust the UP / DOWN direction of air flow, and the vertical louvers are used to adjust the LEFT / RIGHT direction of air flow for uniform and efficient cooling of the room.
Horizontal louvers
Vertical louvers
Adjust UP/DOWN air flow
Lever
Adjust LEFT/RIGHT air flow
8
Page 9
ON TIMER OPERA TION
This unit has a built-in timer that can be programmed to start the unit up to 12 hours in advance. You can set the timer to start in increments of 30 minutes (0.5 hours) up to 9.5 hours in advance of the start time, or in 1 hour increments from 10 to 12 hours in advance of the start time.
The unit will start automatically according to your setting.
AF-08CRL
SELECTOR indicator
F
hr
COOL / FAN TEMP
ENERGY
SELECTOR
TIMER ON/OFF pad
TIMER indicator
TIMER
ON/OFF
SAVER
(If you wish to start the operation 6 hours and 30 minutes later, set the delay time as shown above.)
POWER
ON/OFF
When the unit is not operating
Touch the TIMER ON/OFF pad to set the delayed start time.
1
The time setting will change as you touch the pad. The display will change as follows;
Preset(0.5h)
Previous setting
0.5h
CL(cancel)
The timer will be set, 5 seconds after the TIMER ON/OFF pad is touched for the last time.
SELECTOR indicator and TIMER indicator will light.
The time display will count down the remaining time.
The unit will start when the set time expires. The temperature setting will be displayed.
1.0h
1.5h 10h 11h12h
TO CANCEL THE TIMER SETTING
Touch the TIMER ON/OFF pad again after the timer is set, or press the TIMER ON/OFF pad until CL(cancel) appears on the display.
NOTES FOR TIMER SETTING AND OPERATION:
After setting the TIMER, change the temperature and fan speed settings as shown on pages 11 and 12. When the temperature is set in the timer mode, the temperature will show in the display for 5 seconds and then return to the time display.
The last setting used will be memorized and will appear on the display the next time you operate the unit with the TIMER function.
If a power failure occurs while the ON or OFF TIMER is set, the TIMER memory will be cancelled and will not resume even after power is reinstated. The unit will not automatically start.
OFF TIMER OPERATION can also be set with the REMOTE CONTROL.
9
Page 10
AF-08CRL
OFF TIMER OPERA TION
This unit has a built-in timer that can be programmed to shut the unit off up to 12 hours in advance. You can set the timer to stop in increments of 30 minutes (0.5 hours) up to 9.5 hours in advance of the stop time, or in 1 hour increments from 10 to 12 hours in advance of the stop time.
The unit will stop automatically according to your setting.
When the unit is operating
Touch the TIMER ON/OFF pad to set the delayed stop time.
F
hr
COOL / FAN TEMP
1
The time setting will change as you touch the pad. The display will change as follows;
ENERGY
SELECTOR
TIMER ON/OFF pad
TIMER indicator
TIMER
ON/OFF
SAVER
(If you wish to stop the operation 10 hours later, set the delay time as shown above.)
POWER
ON/OFF
Preset(0.5h)
Previous setting
0.5h
CL(cancel)
1.0h
1.5h 10h 11h12h
The timer will be set, 5 seconds after the TIMER ON/OFF pad is touched for the last time.
TIMER indicator will light.
The time display will count down the
remaining time.
The unit will stop when the set time expires. All indicators and displays will go out.
TO CANCEL THE TIMER SETTING
Touch the TIMER ON/OFF pad again after the timer is set or, press the TIMER ON/OFF pad until CL(cancel) appears on the display.
10
Page 11
USING THE REMOTE CONTROL
INSTALLING BATTERIES
Use two size-AAA (R03) batteries.
Remove the battery compartment cover.
1
Insert the batteries in the compartment,
2
making sure the and polarities are properly aligned.
Replace the cover.
3
NOTES:
The battery life is approximately one year with normal use.
When you replace the batteries, always use two new ones of the same type.
If the remote control does not operate normally after replacing the batteries, take out the
batteries and replace them again after 30 seconds.
If you will not be using the unit for a long time, remove the batteries from the remote control.
Battery compart­ment cover
AF-08CRL
ATTACHING THE REMOTE CONTROL HOOK
Remove the backing from the remote control hook.
Attach the hook onto the left side of the unit's front
cabinet.
To prevent loss, hook the remote control on the front cabinet when not in use.
Remote control hook
Rear Cabinet
Front Cabinet
HOW TO USE THE REMOTE CONTROL
Point the remote control towards the unit's re­ceiver window and press the desired button. A beep will sound when the unit receives the signal.
Make sure no objects, such as curtains, block the receiver window.
The remote control operates from up to 20 feet (6 meters) away.
The beep will also sound when each pad on the control panel is touched.
CAUTION:
Do not expose the receiver window to direct sunlight. This can adversely affect its operation. In such case, close the curtains to block the sunlight.
Use of a fluorescent lamp in the same room may interfere with the transmission of the signal.
The unit may be affected by signals emitted from the remote control of a television, VCR or other
equipment used in the same room.
Do not leave the remote control exposed to direct sunlight or near a heater. Protect the remote control from moisture and shock which can discolor or damage it.
11
Page 12
AF-08CRL
OPERATING WITH THE REMOTE CONTROL
TRANSMITTER
POWER
ON/OFF
TEMP.
TEMP.
SELECTOR
SET TIMER/OFF
POWER ON/OFF button
Push to start or stop the operation.
TEMPERATURE setting button
TEMP. TEMP.
---Raise temp. setting 1°F at a time.
---Lower temp. setting 1°F at a time.
SELECTOR button
Push to change fan speed and operation mode. Fan speed and operation mode selec­tions are shown to the right.
SET TIMER/OFF button
Push to set delay "OFF" timer during operation.
HIGH COOL MED COOL LOW COOL HIGH FAN
MED FAN LOW FAN
• The time setting will change as you push the button. The display will change as follows;
Preset(0.5h)
Previous setting
• The last OFF time setting is memorized by the unit and will appear on the display when the button is pushed.
• The timer will be set, 5 seconds after the SET TIMER/OFF button is pushed for the last time.
• If you wish to cancel the timer, push the SET TIMER/OFF button again after the time is set or, push the SET TIMER/OFF button until CL (cancel) appears on the display. A double beep will sound when the timer is cancelled.
• The "ON" TIMER cannot be set with the remote control. It can only be activated by the TIMER ON/OFF pad on the unit's control panel ( See page 9 ).
0.5h
CL(cancel)
1.0h
1.5h 10h 11h12h
To change temperature setting when ON/OFF timer is in use
1. Push a TEMPERATURE setting button. The current set temperature will be recalled on the unit's display.
2. Use the TEMPERATURE setting buttons to set the new temperature. The new set temperature will show on the display for 5 seconds and return to the time display.
12
Page 13
ACCESSORIES
No.
Accessories Q'ty
AF-08CRL
INSTALLATION INSTRUCTIONS
1
1
2
3
4
5
6 7 8
9 10 11
Right closure assembly 1 Left closure assembly 1 Window sash foam seal 1 Window sash foam seal 1
(adhesive type) Bottom gasket 1 Screws (L=1", 25.4mm) 7 Screws (L= 13/32", 10mm) 6 Base pan angle 2 Remote control 1 Battery 2 Remote control hook 1
2
3
4
5
10
6
6
7
8
2
11
2
7
9
SUGGESTED TOOLS
1. Screw driver (medium size Phillips)
2. Tape measure or ruler
3. Knife or scissors
13
Page 14
AF-08CRL
INSTALLATION
WARNING: Make sure the unit is turned off and unplugged before working.
Cut the window sash foam seal (adhesive type) to the proper length and attach it to
1
the underside of the window sash.
Jamb
Sill
Insert the right closure assembly and the left closure assembly into the top angle
2
and the bottom channels. Secure the right and left closure to the cabinet with six of the provided screws. (L=
13
/32", 10mm)
Closure assembly
Sash
Window sash foam seal (adhesive type)
Open the window sash and place the air conditioner on the sill.
3
Balance the unit on the sill and close the window sash securely behind the top angle.
WARNING:
At this step, make sure the unit is inclined approximately 1 cm ( If the unit is not properly inclined, the water collected in the bottom tray during opera­tion will not drain properly and may flow into the room where the air conditioner is in­stalled.
Insert the bottom gasket into the space between the window sill and the bottom of
4
the unit to seal outside air.
3
/8") to the back.
sill
unit
incline backwards approximately 1cm (3/8")
If there is space between the bottom channel and the sill, fill the gap with a thin board or other hard filler.
Bottom gasket
14
Page 15
5
6
Insert the closure assemblies on both sides into the rails of the jamb.
Jamb (Left)
Closure assembly (Left)
Sill
Loosen screws on both sides of the cabinet, then hang the base pan angle on and secure the screws again.
Indoor side
Indoor side
AF-08CRL
Closure assembly (Left)
1/2 inches (13mm)
Stool
7
8
9
Secure the base pan angle to the sill by using the hole of the front side on the angle with one screw. (L=1", 25.4mm)
Top angle
Secure the top angle of the unit and the top of the closure assemblies to the sash with three of the provided screws. (L=1",
25.4mm) And secure the bottom of the closure assemblies to the sill with two of the provided screws. (L=1", 25.4mm)
Cut the window sash foam seal to the proper length and seal the opening be­tween the top of the inside window sash and the outside window sash.
Window sash foam seal
15
Page 16
AF-08CRL
DISASSEMBLING PROCEDURE
CAUTION: DISCONNECT THE ROOM AIR CONDITIONER FROM THE POWER SUPPLY BEFORE ANY SERVICE
1. Unscrew the 2 screws holding the front panel on each side.
2. Remove the front panel by pulling the front panel at the lower corner toward you about one inch. Next lift up and pull it toward you.
5. Remove the control panel.
6. Take off the fan motor connector.
3. Unscrew the 8 screws holding the cabinet.
2 screws are on each side. 4 screws are on back side. 2 screws are on top side.
And remove the cabinet.
4. Remove the thermistor holder.
7. Unscrew the 5 screws. 3 screws are holding the control box at the top and right side. 1 screw is holding the power supply cord. 1 screw each screw on the evaporator.
8. Cut the wire fixing band, slide the control box rightward
and remove.
Slide
16
Page 17
AF-08CRL
9. Unfasten the one nut at the top of the compressor holding the terminal cover. Then remove the wiring connector of the compressor cord.
10. Unscrew the 4 screws holding the condenser. 1 screw is on right side. 1 screw is on left side. 2 screws are on back side.
And remove the condenser from the unit.
13. Unscrew the 7 screws. 4 screws are holding the evaporator on each side. 3 screws are holding the bulkhead to the base pan on each side and back side.
14. Lift up and take out the bulkhead.
11. Unfasten the nut holding the propeller fan by rotating it counter-clockwise. And remove the propeller fan.
12. Unscrew the 2 screws holding the condenser shround. And remove the condenser shround.
15. Unscrew the 1 screw holding the orifice.
16. Unscrew the 1 screw holding the top duct ass'y.
17
Page 18
AF-08CRL
17. Unscrew the 1 screw holding the centrifugal fan. 18. Unscrew the 3 screws holding fan motor.
DISASSEMBLING THE CONTROL BOX
1. Unscrew the 1 screw holding the control box cover.
CAUTION: DISCHARGE THE FAN MOTOR CAPACITOR
AND RUNNING CAPACITOR BEFORE TOUCHING THOSE CAPACITORS OR OTHER COMPONENTS OR WIRING.
2. Unscrew the 3 screws holding the printed wiring board.
4. Unscrew the 1 power supply cord grounding screw. Unscrew the earth screw. Unscrew the 1 screw holding the capacitor clamp and the fan motor capacitor.
5. Detach each connector by using long-noise pliers.
3. Cut the wire fixing bands holding the fan motor lead wires, the compressor cord and the power supply cord.
6. Unscrews the 2 screws holding the transformer and remove the control board with unhooking the 2 spacers.
18
Page 19
AF-08CRL
INNER CONE
TORCH STEM
SILVER ALLOY
Figure 3
Directing Torch Flame to Copper Tubing.
3/8"
g
HOW TO REPAIR REFRIGERATION
Before sealed system work can be preformed a refrigerant recovery EPA and LOCALLY approved certification is required, additionally, EPA and LOCALLY approved refrigerant recovery equipment is required.
SEALED SYSTEM REPAIR
Sealed system repairs should be properly diagnosed before entering into a repair of the system. It is important to follow proper procedures when doing a system repair for safety reasons and that the repair will result in a restoration of the system to proper factory standards.
SAFETY REMINDERS
1) Do not heat any system component with an open flame for any reason.
2) Do not solder until you are sure that all refrigerant has been removed from the system.
3) Do not heat the charging cylinder with an open flame. Use warm water only and do not exceed 125˚F(not too hot to keep your hand in.)
4) Do not over fill any charging cylinders, as they could explode when over filled.
5) Use proper wrenches.
6) Use safety goggles when working with refrigerants.
7) Keep a fire extinguisher within easy reach.
8) Watch flame direction when soldering so as not to burn clothing, wiring or other components.
9) Solder in a well ventilated area. If a high concentration of freon is present, an open flame will create phosgene gas which can be harmful.
GOOD FIT
PROPER JOINT FIT CLEARANCE
0.01" TO 0.03"
PROPER SOLDERING
Joint clearances should be maintained so that the brazing alloy will flow between the closely mated surfaces rather than forming large fillets. This films make the strongest joints, capillary attraction also work best with close tolerance. The best clearance is between 0.01" to 0.03" , the amount of lap will be approximately 3/8" depending on the swaging tool used. (Figure 1.)
CLEANING TUBING
To make a sound, leak tight joint, the brazing alloy when raised to brazing temperature, must wet and flow freely over the entire surface of the tubing in the joint area. To assure this, the tubing surfaces must be free of all dirt, grease, oil and oxides otherwise the alloy will not wet and flow properly over any surface with these elements present. Cleaning can be done with an abrasive cloth or steel wool. Never blow into the tubing because this will introduce a lot of moisture into the system. Open tubing joints should be covered if exposed for long periods of time.
PROPER FLUXING
Flux is necessary when using silver solder; it is not required when using silfos on copper to copper joints. To do a good job the flux should cover the tube surface completely. Be careful not to introduce any flux inside the tubing. Fluxing should be done after the tubing is mated together and just before brazing is done. Do not allow it to dry out. When brazing, the flux should become entirely liquid and clear, like water. The temperature will be at 1100˚F and only a little more heat will allow the alloy to flow freely into the joint.
Joint Clearance.
Figure 1
EMERY CLOTH
Cleaning Tubing.
ure 2
Fi
POOR FIT
KEEP TUBE IN DOWNWARD POSITION
19
Page 20
AF-08CRL
OUTER CONE
HOTTEST PART OF FLAME
INNER CONE
TORCH STEM
Figure 4
Composition of Torch Flame.
HEATING THE TUBING
Direct the torch flame so that the larger tube receives most of the heat. Silver solder flows at 1200˚F and silfos flows at 1300˚F. Heat all around the tubing. The flame is composed of two cones, a smaller inner cone (pale blue) in calor and a much larger outer cone. The hottest part of the flame is at the tip of the inner cone. The flame should be directed at the joint with the tip of the cone just touching the surface of the tubing. Figure 3 and 4.
DEHYDRATING SEALED SYSTEM
Many servicers feel that since air conditioners run with evaporator temperatures above 33˚F, moisture will not present a problem. Nothing is further from the truth. Oxygen in moisture plus the heat produced during compression will react with the refrigerant oil to produce harmful acids in the system which will break down motor winding insulation, create sludge and pit component parts, reducing efficiency of the air conditioner and shortening the life of compressors. There it becomes mandatory that good dehydrating practices be adhered to at all times. Proper hook up procedures as shown in Figure 5 must be used in order to pull and good vacuum from the system. The use of a good vacuum pump is very important so that the boiling point of any water in the system will be lowered to a point where it will vaporize and be expelled from the system in the form of vapour.
Type of evacuation methods
1. Piston Type Compressor No good.
System parts must be above 110˚F.
2. Rotary Vacuum Pump Disavantages. Low CFMC. 4 oil gets dirty.
3. Single State Vacuum Pump will not clean oil. Oil must be changed often.
4. Two Stage Vacuum Pump will reach 50 microns. First stage is below atmospheric pressure.
TO RELATED SERVICE VALVE OR PROCESS TUBES OF THE UNIT.
ELECTRIC VACUUM GAUGE
LARGE DIAMETER BRAIDED VACUUM HOSES
HIGH VACUUM MANIFOLD
DIAL-CHARGE CHARGING CYLINDER
LOW SIDE GAUGE
HIGH SIDE GAUGE
Moisture is removed into second stage which works up to atmospheric pressure thus keeping oil clean. Manometer cannot be read to 1/2 mm. Micron gauge reads from 25,400 microns to 0.
HIGH VACUUM PUMPHook up for Evacuation and charging
Figure 5
It becomes clear that good equipment and maintained properly must be used in order to remove air and moisture from the system. When a vacuum of 1,000 to 500 microns is reached, block off the vacuum pump from the system. This is done by closing the value between the pump and system. If the micron gauge does not increase above 1,000, the system is free of moisture and no leak exists. If the micron gauge increases to higher levels moisture or a leak exists.
20
Page 21
AF-08CRL
RUNNING CAPACITOR
FAN CAPACITOR
LEAKS
Several methods are used to detect leaks in systems.
Electronic Leak Detectors are very sensitive and are able to detect leaks down to 1/2 ounce per year. A good electronic leak detector is generally far better in locating very small leaks. Halide Torch be sure the room is free from refrigerant vapours. Watch the flame for the slightest change in calor. A very faint green indicates a small leak. The flame will be unmistakably changed to green or purple when large leaks are encountered. To simplify leak detection pressurize the system to approximately 75 lbs. Some leaks can be located by a visual inspection of the system components and solder joints and if oil is found at any given location it generally is a sign that a leak exists at that point due to the fact that flame does carry oil with it travels through the system.
Soap Bubbles
Liquid detergents can sometimes assist in finding small leaks by brushing detergent on the suspect area and watching for bubbles. Before applying detergent be sure that the system is pressurized.
Tap line devices are permissible for diagnosis only they are not suitable when evacuating the system. After the diagnosis has been made they must be removed so that the system will be restored to a hermeticly sealed condition.
ELECTRICAL COMPONENT TEST
RUNNING CAPACITOR AND FAN CAPACITOR CAUTION:DISCHARGE THE RUNNING CAPACITOR AND FAN CAPACITOR BEFORE TOUCHING CAPACITOR
OR WIRING.
(1) Discharge capacitor by shorting terminals. (2) Take the wires off the capacitor terminals. (3) Set the selector switch of a volt-ohm-meter (or a tester)
on the resistance range.
(4) Connect the probes to the capacitor terminals and
watch the indicator swing.
The indicator does not swing at all ..... Open.
The indicator swings but does not return ..... Shorted.
The indicator swings, then returns a moment later .....
Good.
INSULATION TEST
Check the resistance between the terminals and case. Reading must be more than 10M at DC 500V.
OVERLOAD RELAY
Check continuity between terminals with volt-ohm-meter.
INSULATION TEST
Check resistance between terminals and the relay case. Reading must be more than 10M at DC 500V.
COMPRESSOR
(1) Take the wires off compressor terminals. (2) Set selector switch of volt-ohm-meter on the resistance range. (3) Put the probes on the terminals of the compressor and check continuity between each terminal.
INSULATION TEST
Check the resistance between the terminals and the copper tube. Reading must be more than 10M at DC 500V.
21
Page 22
AF-08CRL
MICROCOMPUTER CONTROL SYSTEM
1. Temperature control characteristic
1-1 COOL operation
In the COOL mode, the thermostat circuit is controlled by two thermostat lines (C1, C2).
C1
C2
Room temperature (°F)
86
84
64
62
64 86
Preset temperature (°F)
("THERMO" switch)
Figure Y-1
2. Operation mode
2-1 COOL operation
The compressor turns on or off, at thermostat lines C1 and C2. The fan motor is also controlled with the compressor.
States 1 & 3 States 2
: Compressor ON : Compressor OFF
3
C1
3. Fan speed
Fan speeds are given by the fan motor, H, “M andL, which are available in the following operation
mode.
Table Y-1
Selector Fan motor HIGH COOL H MED COOL M LOW COOL L HIGH FAN H MED FAN M LOW FAN L
4. 12-hours timer
4-1 OFF-TIMER operation
Set the delay timer during operation. The unit will turn off automatically according to your setting. Timer duration can be set by 0.5 hours to maximum 12 hours. Up to 9.5 hours, you can set by 0.5 hours increments and from 10 to 12 hours, by 1 hour increment. If you touch button POWER ON/OFF during OFF­TIMER operation, then the unit turns off and OFF­TIMER operation is cancelled.
4-2 ON-TIMER operation
Set the delay timer when unit is not operating. The unit will turn on automatically according to your setting. Timer duration can be set by 0.5 hours to maximum 12 hours. Up to 9.5 hours, you can set by
0.5 hours increments and from 10 to 12 hours, by 1 hour increment. If you touch button POWER ON/OFF during ON­TIMER operation, then the unit turns on and ON-TIMER operation is cancelled. ON-TIME and OFF-TIME display will count down the remaining time.
1
Room temperature (°C)
Room temperature transition
Preset temperature (°C)
Figure Y-2
2-2 FAN ONLY operation
The fan motor always turns on.
from 0.5 to 9.5 ..... 0.5 hours
from 10 to 12 ....... 1 hour
C2
5. Energy saver
During normal operation, the thermostat automatically controls cooling and the fan runs continuously whenever the air conditioner is in operation.
2
When the ENERGY SAVER is set, the thermostat automatically controls cooling and the fan automatically stop when compressor is not operating. (Fan will stop in 30 seconds after the compressor stops.)
ON
Compressor
ON
Fan
OFF
OFF
30 seconds
Figure Y-3
22
Page 23
6. Safety start
When you turn the air conditioner OFF and restart again soon, wait at least 3 minutes before the cooling operation starts.
7. Test mode
Keep pushing both buttons POWER ON/OFF and “ " ” and supply the power, the system will go to the test mode. In this mode, the output operation is switched by pushing buttons. Normal outputs are shown in Table Y-2.
AF-08CRL
For selfdiagnosis check mode
No. PUSH KEY (SWITCH)
PLUG IN the power supply cord
02
while pushing power ON/OFF key and (down) key.
1
TIMER
<SW6>
<SW5> <SW2> <SW1> <SW4>
2
3 4
ENERGY SAVER
5 6 7 8
1) If thermistor is normal (nether short nor open), LED is ON.
2) When A/D (R42) bit 7 = 1, LED is ON.
2) When A/D (R42) bit 6 = 1, LED is ON.
2) When A/D (R42) bit 5 = 1, LED is ON.
ON/OFF
POWER ON/OFF by REMOTE CONTROL
POWER SUPPLY OFF
BEPP
SOUND
1SELECTOR <SW3> 1
1 1 1 1 1
LED1
<LED2>
8.8 ON
OFF
01
02 03 04 05 05
OFF
FAN
HIGH
OFF OFF
2) 3) 4)
ON OFF OFF
ON OFF OFF OFF OFF OFF OFF OFF OFF OFF
Table Y-2
FAN MID
<LED3>
ON ON ON ON ON ON ON OFF
OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF
OFF OFF ON OFF OFF ON OFF
ON OFF OFF ON OFF OFF ON OFF ON OFF OFF ON OFF OFF OFF OFF ON OFF OFF ON OFF OFF OFF OFF OFF OFF OFF OFF
Table Y-3
LED LIGHTING CHECK ITEM
FAN LOW
<LED4>
COOL
<LED9>
FAN
<LED5>
TIMER
<LED7>
ENERGY
SAVER
<LED8>
POWER ON/OFF
<LED6>
1)
FAN
OUTPUT
LOW
MIDDLE
HIGH
OFF
LOW HIGH MIDDLE
OFF
COMP
OUTPUT
OFF
OFF OFF
OFF OFF OFF
ON OFF OFF
and REMARK
LED ALL ON
LED ALL OFF
FAN CHECK
COMPRESSOR CHECK REMOTE CONTROL CHECK
T(˚C) T(˚F) R(kΩ)
V(volts) 0 32.0 49.33 1.17 1 33.8 46.86 1.21 2 35.6 44.53 1.26 3 37.4 42.33 1.31 4 39.2 40.25 1.36 5 41.0 38.29 1.41 6 42.8 36.44 1.46 7 44.6 34.68 1.51 8 46.4 33.02 1.56 9 48.2 31.45 1.61
10 50.0 29.96 1.67 11 51.8 28.55 1.72 12 53.6 27.22 1.78 13 55.4 25.96 1.83 14 57.2 24.76 1.89 15 59.0 23.62 1.94 16 60.8 22.56 2.00 17 62.8 21.52 2.05 18 64.4 20.55 2.11 19 66.2 19.63 2.17 20 68.0 18.76 2.22
T(˚C) T(˚F) R(kΩ) V(volts)
21 69.8 17.93 2.28 22 71.6 17.14 2.33 23 73.4 16.39 2.39 24 75.2 15.68 2.44 25 77.0 15.00 2.50 26 78.8 14.36 2.55 27 80.6 13.74 2.61 28 82.4 13.16 2.66 29 84.2 12.60 2.71 30 86.0 12.07 2.77 31 87.8 11.57 2.82 32 89.6 11.09 2.87 33 91.4 10.63 2.93 34 93.2 10.19 2.98 35 95.0 9.78 3.03 36 96.8 9.38 3.08 37 98.6 9.00 3.13 38 100.4 8.64 3.17 39 102.2 8.30 3.22 40 104.0 7.97 3.27
V ....... Input the voltage of microcomputer (No. 10-port).
23
Page 24
AF-08CRL
HEATSINK
YELLOW
LED7, LED8
LED2 ~ LED5, LED9 GREEN
D17
RED
LED6
IC2
7812
IN OUT
D1 - D4
TR
0V
KRA101M
(DTA143ES)
Q5
+++
COM
C2 C3 C4 C5 C6 C7
D2
D1
C1
LED2 COOL/H
C8
25V
R2
15K
ZD1
HZ4A-2
25V
0.1µ
10V
100µ
COM
25V
47µ
25V
0.1µ
25V
0.1µ
25V
1000µ
250V
0.1µF
LED3 COOL/M
LED4 COOL/L
LED5 FAN
10
LED1
18
0.1µ
OUT
IC3
79L05
IN
R3
Q6
KRC101M
D3 D4
R1
22K
NR
271
LED6 ON/OFF
LED7 TIMER
LED8 ENERGY
9
88
1
Q9
Q8
5V
12V
C10
10K
C9
16V
0.01µ
(DTC143ES)
R4
20k
SAVER
LED9 COOL
Q10
Q8 ~ Q10
KRA222M
BCN2
C11
16V
10µ
C20
+
C12
25V
0.1µ
Q7: KRA106M
5V
R8
R18
IC4
C18
25V
+
C17
50V
(DTB123EA)
R23 47 1/2W
7654321
R6
C21
C22
5V
OSC
Q1: KRA105M
(DTA123JS)
(DTA143ZS)
Q7
BZ
2.7K
D5D8
D7 D6
R17
47µ
0.1µ
Q1
MRY
COMP
R16
R15
R14
R13
PHOTO
DETECTOR
UNIT
QWN-KEY UP-KEY POWER SELECTOR TIMER
E/SAVER
CN2
R7
10K
Q2
RY1
FAN H
C19 16V 10µF
+
R5
10K 10K
10K R28
28272625242322212019181716
HOLD
R92
R91
5V
OUT dd
IN
RESET
R70
X
4MHz
1X V
2345678
Q3
Q4
Q2, Q3, Q4
KRA106M
(DTA143ZS)
RY2
RY3
12V
FAN M
FAN L
R11 ~ R18
R12
R11
SW6
SW5
SW4 SW3 SW2
SW1
1000P 50V
C15
R90
R83
INT1
R71
R72
R40
R9
TEST
C16
5V
R81
R41
150 x 8
INT2
R42 9
D15 D14 D13 D12 D11 D10
5V
C23
10K
R24
R63
R62
R61
R60
TMP47C443N
R43
R50
R51
R52
1011121314
R10
15K(F)
+
432
324567891
BCN3CA1 CN3
15 R53
IC1
SS
V
5V
-5V
R22
C14
16V
10µ
CN1
1
5V
RA1
CA1: 1000pF x 8
RA1: 10k x 8
SW1: ENERGY SAVER
SW2: TIMER
SW3: SELECTOR
SW4: POWER
SW5: UP-KEY
SW6: DOWN-KEY
Electronic Control Circuit Diagram
3A
FU1
125V
MRY
POWER SUPPLY
115V AC
60Hz
C
OVERLOARD
PROTECTOR
COMPRESSOR
RS
MOTOR
RUNNING
CAPACITOR
250V 35µF
GRAY
BCN1
671
FAN MOTOR
CAPACITOR
250V 6µF
RY1
GRAY
BL BK
CNR1
RED
RY2
CNR2
3
ORANGE
RY3
CNR3
5
WHITE
WH GR RE GY BK BL
24
CNR1 - CNR3
WH
CONNECTOR
M
OR
H
RE
123654
YELLOW
(15k) TH1
ROOM
Temp
GREEN
C23, R9
NO INSERT PART
L
GY
BK
BL
BL
FAN
MA
MOTOR
BK
CA1: 1000pF x 8 (CAPACITOR ARRAY)
IF NOT SPECIFIED 1/5W, ±5% (RESISTOR)
IF NOT SPECIFIED 50V 1000pF (CAPACITOR)
IF NOT SPECIFIED 1SS133T-72 (DIODE)
: INDICATED POSITION IS FUNCTION TEST POINT
RA1: 10k x 8 (RESISTOR ARRAY)
Page 25
AF-08CRL
QPWBFB443JBZZ
18
JP28
JP35
1
10
JP30
JP29
9
QPWBFB443JBZZ
DPWBFA246JBKZ
C2
DPWBFA246JBKZ
Printed Wiring Board
25
Page 26
AF-08CRL
No cooling (Operation not at all.)
Measure the power supply voltage at receptacle.
120V(over 100V)
Is it sufficient current capacity of power equipment ? Is it small wiring for power supply equipment ?
sufficient
Is plug disconnecting ?
connecting
Check the power supply cord.
OK
under 100V
The house fuse or circuit breaker open ?
open
Is it proper current capacity of the house fuse or the circuit breaker ?
Change the house fuse and the circuit breaker turn on.
insufficient
Ask the power supply company for check.
disconnecting
Connect plug properly.
imperfect contact
Change the power supply cord.
TROUBLESHOOTING GUIDE
not open.
Ask the power supply company for check.
Check the fuse on PWB ass'y.
OK
Measure the secondary voltage of transformer.
over 14V(AC)
Measure the voltage between
-12V and GND on PWB ass'y. OK(12V, DC)
Measure the voltage between
-5V and GND on PWB ass'y. OK(5V, DC)
If unit operate, dose the house fuse or the circuit breaker open ?
NO
open
Change the fuse on PWB ass'y.
under 14V(AC)
NG
NG
Change PWB ass'y.
YES
Measure the insulation resistance of compressor.
Measure the insulation resistance of fan motor.
OK(over 10M)
OK(over 10M)
NG(under 10M)
Change the compressor.
NG(under 10M)
Change the fan motor.
Checking complete.
Can the Compressor operate ?
can operate
26
can't operate
Change the compressor.
Page 27
No cooling (Fan operate but the compressor doesn't operate.)
AF-08CRL
Measure the power supply voltage at receptacle.
120V(over 100V)
I
s it sufficient current capacity of power equipment ? Is it small wiring for power supply equipment ?
sufficient
Measure the current in compressor circuit.
current
Check the overload relay.
OK
Check the running capacitor.
OK
under 100V
Ask the power supply company for check.
insufficient
Ask the power supply company for check.
no current
imperfect contact
Change the overload relay.
NG
Change the running capacitor.
Check the overload relay.
short
Is the connector disconnecting ?
connecting
Check the compressor relay.(MRY on PWB)
OK
open
Change the overload relay.
disconnecting
Connect properly.
NG
Change PWB ass'y.
Measure the resistance of compressor coil.
OK
Is there high heat source near the unit.
there isn't
Is the outdoor temperature too high ?
under 43˚C
Check the outdoor heat exchanger.
not dirty
NG
Change the compressor.
there is
Remove the high heat source or stop.
over 43˚C
Avoid sun light and ventilate well for outdoor heat exchanger.
dirty
Clean them with steam cleaner or another method.
Check the thermister.
OK
NG
Change the thermistor.
Checking method for the compressor relay. (MRY on PWB)
Turn off the power supply.
Measure the resistance of its coil.
OK(160 at 20˚C)
Turn on the power supplty as operating the compressor.
Measure the voltage to its coil.
OK(12V, DC)
OK
NG
NG
NG
Can the compressor operate ?
can operate
Checking complete.
can't operate
Change the compressor.
27
Page 28
AF-08CRL
No cooling (The compressor operate but the fan motor doesn't operate)
crack at the solder part
Repair with over solder. Connect the connector
Check BNC1 on PWB ass'y
OK
Check the fan motor capacitor.
OK
Measure the resistance of compressor coil.
OK
Is the fan locked ?
disconnecting the connector
properly.
NG
Change the fan motor capacitor
NG
Change the fan motor.
locked
Is the fan touched to another parts ?
no touch
Change the fan motor.
touch
Change fan or another parts, or adjust.
The compressor doesn't turn off.
Check the thermister connector.
OK
Check the thermister resistance.
OK
Check the compressor relay.
OK
Checking complete.
Checking complete
disconnecting
Connect the connector properly.
NG
Change the thermister.
NG
Change PWB ass'y.
Checking method for the compressor relay. (MRY and PWB)
Turn off the power supply.
Measure the contact resistance.
open
OK NG
short
28
Page 29
Insufficient cooling(Both compressor and compressor operate)
Check the temperature setting.
OK
too high
Set the lower temperature.
AF-08CRL
Check the air filter.
not dirty
Is there high heat source or any object restricting heat radiation near the unit.
there isn't
Check doors and windows.
close
Check the outdoor and indoor heat exchanger.
not dirty
Calculate heat load wit using Cooling load estimate form.
OK
Check rotating direction of centrifugal fan.(to clockwise)
OK
Check changing fan speed properly.
OK
dirty
Clean the air filter.
there is
Remove the high heat source or stop.
open
Doors and windows must be kept closed.
dirty
Clean them with steam cleaner or another method.
Undersized air conditioner
Change unit to proper sized air conditioner.
NG
NG
Check the fan motor connector.
OK
Measure the resistance of fan motor coil.
OK
NG
NG
Change the fan motor.
Connect properly.
Is the outdoor temperature too high ?
under 40
˚
Check the thermister.
OK
Measure temperature difference between inlet and outlet air at indoor.
˚
C
over 10
Checking complete.
over 40˚C
C
NG
Avoid sun light and ventilate well for outdoor heat exchanger.
Change the thermister.
˚
C
under 10
Is frost sticking to capillary tube ? Or is indoor heat exchanger no cold ?
NO
YES
Is the refrigerant leaked ?
NO
The capillary tube restrict, and change the capillary tube.
Measure the emperature difference between discharge tube and suction tube.
temperature difference
YES
Repair leakage and recharge the refrigerant.
No temperature difference
The compressor is defective.
Change the compressor.
29
Page 30
AF-08CRL
Excessive vibration or Abnormal noise
At fan only mode, Excessive vibration or Abnormal noise
NO
YES
Check the air filter
Check rotating direction of centrifugal fan.(to clockwise)
Is the fan deformed or broken.
Is loosened screw and nut fixing fan ?
not dirty
OK
OK
OK
dirty
Clean the air filter.
NG
Check the fan motor connector.
Measure the resistance of fan motor coil.
deform or broken
Change the fan
loosened
Tighten up.
OK
OK
NG
Connect properly.
NG
Change the fan motor.
Is each screws loosened ?
OK
Is pipe touching to another parts.
OK
Check mounting of compressor.
OK
Check compressor noise and vibration.
OK
Checking complete
Checking complete
loosen
Tighten up
touching
Repair with adjusting shape of pipes.
NG
Repair mounting or change compressor cushion.
too big
Change compressor.
30
Page 31
AF-08CRL
COOLING LOAD ESTIMATE FORM
INSTRUCTIONS FOR USING COOLING LOAD ESTIMATE FORM FOR ROOM AIR CONDITIONERS
(AHAM PUB. NO. RAC-1)
A. This cooling load estimate form is suitable for estimating the cooling load for comfort air conditioning installations
which do not require specific conditions of inside temperature and humidity.
B. The form is based on an outside design temperature of 95˚F dry bulb and 75˚F wet bulb. It can be used for areas in
the continental United States having other outside design temperature by applying a correction factor for the particular locality as determined from the map.
C. The form includes "day" factors for calculating cooling loads in rooms where daytime comfort (such as living rooms,
offices, etc.).
D. The numbers of the following paragraphs refer to the correspondingly numbered item on the form:
1. Multiply the square feet of window area for each exposure by the applicable factor. The window area is the area of the wall opening in which the window is installed. For windows shaded by inside shades or venetian blinds, use the factor for "Inside Shades". For windows shades by outside awnings or by both outside awnings and inside shades (or venetian blinds), use the factor for "Outside Awnings". "Single Glass" includes all types of single thickness windows, and "Double Glass" includes sealed air space types, storm windows, and glass block. Only one number should be entered in the right-hand column for item 1, and this number should represent only the exposure with the largest load.
2. Multiply the total square feet of all windows in the room by the applicable factor.
3a. Multiply the total length (linear feet) of all walls exposed to the outside by the applicable factor. Doors should be
considered as being part of the wall. Outside walls facing due north should be calculated separately from outside walls facing other directions. Walls which are permanently shaded by adjacent structures should be considered as being "North Exposure". Do not consider trees and shrubbery as providing permanent shading. An insulated frame wall or a masonry wall 8 inches or less in thickness is considered "Light Construction". An insulated frame wall or a masonry wall over 8 inches in thickness is considered "Heavy Construction".
3b. Multiply the total length (linear feet) of all inside walls between the space to be conditioned and any unconditioned
spaces by the given factor. Do not include inside walls which separate other air conditioned rooms.
4. Multiply the total square feet of roof or ceiling area by the factor given for the type of construction most nearly describing the particular application. (Use one line only.)
5. Multiply the total square feet of floor area by the factor given. Disregard this item if the floor is directly on the ground or over a basement.
6. Multiply the number of people who normally occupy the space to be air conditioned by the factory given. Use a minimum of 2 people.
7. Determine the total number of watts for lights and electrical equipment, except the air conditioner itself, that will be in use when the room air conditioning is operating. Multiply the total wattage by the factor given.
8. Multiply the total width (linear feet) of any doors or arches which are continually open to an unconditioned space by the applicable factor. NOTE: Where the width of the doors or arches is more than 5 feet, the actual load may exceed the calculated
value. In such cases, both adjoining rooms should be considered as a single large room, and the room air conditioner unit or units should be selected according to a calculation made on this new basis.
9. Total the loads estimated for the foregoing 8 items.
10. Multiply the sub total obtained in item 9 by the proper correction factor, selected from the map, for the particular locality. The result is the total estimated design cooling load in BTU per hour.
E. For best results a room air conditioner unit or units having a cooling capacity rating (determined in accordance with
the NEMA Standards Publication for Room Air Conditioners, CN 1-1960) as close as possible to the estimated load should be selected. In general, a greatly oversized unit which would operate intermittently will be much less satisfactory than one which is slightly undersized and which would operate more nearly continuously.
F. Intermittent loads such as kitchen and laundry equipment are not included in this form.
31
Page 32
AF-08CRL
HEAT GAIN FROM QUANTITY
1. WINDOWS: Heat gain from sun. Northeast Southeast South Southwest
Southeast West Northwest North
2. WINDOWS: Heat gain by conduction. (Total of all windows) Single glass Double glass or glass block
3. WALLS: (Based on linear feet of wall.)
a. Outside walls Noth exposure Other than North exposure
b. Inside Walls (between conditioned and unconditioned spaces only)
4. ROOF OR CEILING: (Use one only.)
a. Roof, uninsulated b. Roof, 1 inch or more insulation
c. Ceiling, occupied space above. d. Ceiling, insulated with attic space above e. Ceiling, uninsulated, with attic space above
5. FLOOR: (Disregard if floor is directly
on ground or over basement.)
6. NUMBER OF PEOPLE:
7. LIGHTS AND ELECTRICAL
EQUIPMENT IN USE
Use
only
the
largest
load Use only
BTU/Hr (Quantity x Factor)
FACTORS
DAY
No
Shades
sq ft sq ft sq ft
sq ft sq ft sq ft
60 80 75
75 110 150 120
sq ft
These factors are for single glass only. For glass block, multiply the above factors by 0.5: for double-glass or storm windows, multiply the above factors by 0.8.
sq ft sq ft
Inside
Shades
25 40 30 35 45 65 50
0
0
Outside Shades
20 25 20 20
30 45 35
0
14
7
(Area a Factor)
only
Light Construction Heavy Construction
20 30
sq ft sq ft sq ft
sq ft sq ft
sq ft
ft ft
ft
30 60
30
19
8 3
5
12
3
600
watts
3
8. DOORS AND ARCHES CONTINUOUSLY OPENED TO UNCONDITIONED SPACE: (Linear feet of width.)
9. SUB-TOTAL
10. TOTAL COOLING LOAD: (BTU per hour to be used for selection of room air conditioner(s).)
EUGENE
RENO
SACRAMENT
FRESNO
LAS VEGAS
ft
x x x x x x x x x x
(Item 9) x (Factor from Map) =
FARGO
GREEN BAY
WICHITA
PUEBLO
PHOENIX
SAN ANTONIO
BIRMINGHAM
300
ROCHESTER
ALBANY
NEW HAVEN
COLUMBIA
ATLANTA
32
Page 33
RUNNING CONDITION
Note:
1. Select mode of the Running Condition of a Room Air Conditioner.
SELECTOR .................................................................................................... HIGH COOL
THERMOSTAT .............................................................................................. 64˚F
2. Data of Performance Curve is measured between 40%RH and 70%RH.
If you measure the Room Air Conditioner above or below this rating, the data may miss the range of the
performance curve.
3. Outlet air temp. is influenced by the method of measurement. Measurement examples are shown.
4. Use power input data when checking the Running Condition.
RUNNING CONDITION FOR
PERFORMANCE CURVE
AF-08CRL
900
800
700
600
500
7
6
Line current(Amp.) Power input (W)
5
30
(86)
20
(68)
10
(50)
Outlet air temp˚C (˚F)
25 30 35
(77) (86) (95) (104)
Outside air temp.˚C (˚F)
40%RH
70%RH
40%RH
70%RH
70%RH
40%RH
40
33
Page 34
AF-08CRL
PACKING AND ACCESSORIES
TOP PAD ASSEMBLY (DPADBA006JBFZ)
Top pad L
4
3
5
6
Top pad R
Accessories Operation manual Window sash foam seal Window sash seal Bottom gasket
6
Screws Base pan angle Right closure assembly Left closure assembly
5
Enegry card (TLAB-C219JBEZ)
Detail is assembling Energy card
Packing case (SPAKCB003JBEZ)
Front side
"Front side" mark
2
Protect (SSAKHA245YDE0)
Power supply cord
1
Bottom pad assembly (CPADBA052JBKZ)
34
Page 35
AF-08CRL
REPLACEMENT PARTS LIST
REF. NO. PART NO. DESCRIPTION Q'TY CODE
CABINET AND UNIT PARTS
1- 1 CMOTLB003JBEZ Fan motor 1 BM 1- 2 DCHS-A364JBTB Base pan ass’y 1 BA 1- 3 PFPFPB137JBE0 Base pan insulator 1 AF 1- 4 PFPFPB138JBE0 Base pan insulator 1 AF 1- 5 CCAB-A318JBKZ Cabinet ass’y 1 BB 1- 6 CWAK-C205JBKZ Top duct ass’y 1 AS 1- 7 HPNLCA805JBFC Control panel 1 AE 1- 8 HPNLCA816JBEA Control panel 1 AF 1- 9 PSEL-B825JBE0 Insulator 1 AE 1-10 LBND-A042JBE0 Wire fixing band 3 AC 1-11 LHLDW0364JBE0 Wire holder 1 AA 1-12 PSHE-A172JBE0 Protect sheet 1 AC 1-13 NFANPA078JBF0 Propeller fan 1 AU 1-14 NFANSA027JBF0 Centrifugal fan 1 AU 1-15 PFILMA164JBEA Air filter 1 AK 1-16 PKESPA034JBF0 Condenser shroud 1 AV 1-17 PKESPA057JBF0 Orifice 1 AK 1-18 PSEL-A827JBE0 Evaporator insulator 1 AB 1-19 PSEL-A994JBE0 Orifice insulator 1 AB 1-20 PSEL-A828JBE0 Motor insulator 1 AB 1-21 TLABMA309JBRZ Feature card 1 AD 1-22 PSEL-C085JBEZ Tube insulator 1 AC 1-23 PSKR-A104JBF0 Bulkhead 1 AS 1-24 PSRA-A078JBF0 Drain tray 1 AD 1-25 MJNTPA090JBFA Louver link 1 AC 1-26 MLOV-A333JBFA Horizontal louver 4 AC 1-27 MJNTPA089JBFA Louver joint 1 AC 1-28 MLOV-A321JBFA Vertical louver A 1 AC 1-29 MLOV-A322JBFA Vertical louver B 3 AC 1-30 MSPR-A148JBEZ Louver spring 2 AF 1-31 LANG-A213JBTA Top inst.angle 1 AF 1-32 LPLTMA087JBP0 Condenser cover 1 AB 1-33 GWAKPA151JBFA Front panel 1 AV 1-34 PSEL-B845JBE0 Insulator 1 AB 1-35 TLABBA110JBRA Sharp badge 1 AB 1-36 TLABKA564JBE0 Number card 1 AC 1-37 TLAB-C219JBEZ Energy card 1 AC 1-38 TSPC-E155JBRZ Name badge 1 AC 1-39 LHLD-A315JBF0 Thermistor holder 1 AE 1-40 PFPFPB745JBE0 Comp-cushion 1 AE 1-41 DSKR-A124JBKZ Bulkhead ass’y 1 AY 1-42 LANG-A472JBPZ Cabinet angle 2 AC
CONTROL BOX PARTS
2- 1 DPLT-A056JBWZ Cont. box angle ass’y 1 AK 2- 2 LBNDKA058JBWZ Capacitor clamp 1 AD 2- 3 DPLT-A038JBW0 Cont. box cover ass’y 1 AK 2- 4 DPWBFA246JBKZ Control board unit 1 BF 2- 5 PSPA-A084JBE0 Spacer 2AC 2- 6 PSPA-A085JBE0 Spacer 1AC 2- 7 QACC-A260JBZZ Power supply cord 1 AS 2- 8 QFS-AA048JBE0 Fuse 1AB 2- 9 TLABCB604JBRZ Wiring diagram 1 AA 2-10 QW-VZC561JBE0 Lead wire 1 AD 2-11 QW-VZD376JBE0 Compressor cord 1 AR 2-12 RC-HZA256JBE0 Fan motor capacitor 1 AM 2-13 RC-HZA136JBE0 Running capacitor 1 AU 2-14 RH-HXA006JBZZ Thermistor 1 AK 2-15 LBND-A042JBE0 Wire fixing band 3 AC 2-16 QW-VZC366JBE0 Lead wire 1 AD 2-17 PPLT-A300JBEZ Insulating sheet 1 AF 2-18 PPLT-A305JBEZ Insulating sheet 1 AA
CYCLE PARTS
3- 1 PCMPRA327JBEZ Compressor 1 CA 3- 2 PCON-A483JBEZ Condenser 1 BP 3- 3 PEVA-A423JBEZ Evaporator 1 BM 3- 4 DCPY-A282JBKZ Capillary tube ass’y 1 AP 3- 5 RHOG-A130JBE0 Overload relay 1 AW
35
Page 36
AF-08CRL
REF. NO. PART NO. DESCRIPTION Q'TY CODE
3- 6 PSEL-A150JBE0 Gasket washer 1 AA 3- 7 CPIP-A012JBKZ Suction tube ass’y 1 AU 3- 8 PPIPCC085JB10 Lead tube 1 AC 3- 9 PPIPCF110JB1Z Discharge tube 1 AM 3-10 GLEG-A073JBE0 Compressor cushion 3 AD 3-11 MSPR-A005JBE0 Protector spring 1 AB 3-12 PCOV-A002JBE0 Terminal cover 1 AE 3-13 PSEL-A006JBE0 Terminal gasket 1 AC
ACCESSORY PARTS
4- 1 TINSEA301JBRZ Operation manual 1 AE 4- 2 DX-BZA016JBK0 Screws kit 1 AW 4- 3 SSAKAA018YDE0 Bag 1AB 4- 4 XCTSD40P10000 Tapping screw 6 AA 4- 5 XMPSD40P25000 Wood screw 7 AA 4- 6 LANGAA030JBTA Base pan angle 2 AD 4- 7 PSEL-A351JBE0 Window insulator 1 AB 4- 8 PSEL-A931JBE0 Window insulator 1 AH 4- 9 PSEL-A932JBE0 Window insulator 1 AE 4-10 LANGAA012JBFE Right closure frame 1 AH 4-11 SPADBB452YDE0 Cardboard 1 AD 4-12 SSAKHA246YDE0 Bag 1AH 4-13 CRMC-A526JBEZ Remote control 1 AT 4-14 LHLD-A389JBFB Controller holder 1 AC 4-15 PPLTPA016JBFB Closure 2 AK 4-16 UBATUA027JBE0 Battery pack 1 AE 4-17 CFZK-B937JBKZ Closure ass’y 1 BA 4-18 LANGAA011JBFE Left closure frame 1 AH
PACKING PARTS
5-1 DPADBA006JBFZ Top pad ass’y 1 AK 5-2 CPADBA052JBKZ Bottom pad ass’y 1 AP 5-3 SPAKCB003JBEZ Packing case 1 AQ 5-4 SSAKHA245YDE0 Protect 1 AB 5-5 SSAKAA053YDE0 Bag 1AB 5-6 SPAD-A075JBE0 Comp holder HA 2 AC
SCREWS AND NUTS
6-1 LX-NZA002JBE0 Special nut 1 AA 6-2 LX-BZA236JBE0 Special screw 1 AC 6-3 XTPSD40P08000 Tapping screw 3 AA 6-4 XHTSD40P10000 Tap tight screw 5 AA 6-5 XHTSD40P08000 Tap tight screw 4 AA 6-6 XBPSD40P12J00 Machine screw 2 AB 6-7 LX-BZA140JBE0 Special screw 4 AB 6-8 LX-BZ0107CBE0 Special screw 1 AB 6-9 LX-CZA038WRE0 Special screw 4 AB 6-10 LX-NZA026JBE0 Special nut 3 AC 6-11 LX-NZA074JBE0 Special nut 1 AB 6-12 XCTSD40P06000 Tapping screw 2 AA 6-13 XCTWJ40P16000 Tapping screw 2 AA 6-14 LX-BZA172JBE0 Special screw 3 AB 6-15 XTTSD40P10000 Tapping screw 2 AA 6-16 XTTSD40P12000 Tapping screw 3 AA 6-17 XTTSD40P14000 Tapping screw 10 AA 6-18 XTTSD40P20000 Tapping screw 3 AA
HOW TO ORDER REPLACEMENT PARTS
To have your order filled prompty and correctly, please furnish the following information.
1. MODEL NUMBER 2. REF. NO. 3. PART NO. 4. DESCRIPTION
36
Page 37
AF-08CRL
1-24
1-42
1-4
1-3
1-35
1-2
6-17
6-17
6-9
6-9
2-7
5-3
5-6
5-1
5-4
1-36
5-2
5-5
1-14
6-2
1-38
1-33
1-15
6-13
6-13
1-17
6-8
6-17
1-30
1-26
1-5
1-13
1-31
1-16
1-20
1-1
1-10
1-23
1-41
1-11
6-18
1-40
6-18
6-4
6-15
6-4
6-15
6-9
6-12
6-17
6-14
6-14
6-11
1-9
6-7
1-34
6-7
4-4
4-3
4-15
4-18
4-10
4-17
4-2
4-7
4-5
6-17
1-22
4-8
4-9
4-1
4-6
4-16
4-12
4-11
4-14
4-13
1-37
1-21
1-12
1-29
1-28
1-27
1-6
1-25
1-42
A
B
C
D
12345
CABINET PARTS
6
A
B
C
D
E
E
F
F
G
G
H
H
123456
37
Page 38
AF-08CRL
12345
A
CONTROL BOX PARTS
6
A
1-8
1-7
B
B
2-4
2-18
C
2-1
2-6
C
6-5
2-5
6-3
D
D
6-16
6-6
2-4
2-2
2-13
2-12
6-4
E
6-4
E
2-7
2-14
F
2-8
2-15
6-5
2-17
2-10
6-5
2-3
F
2-9
6-16
G
G
H
123456
H
38
Page 39
AF-08CRL
12345
A
CYCLE PARTS
6-1
3-6
6
A
3-12
B
1-19
3-11 3-5 3-13
2-16
2-11
B
1-18
3-2
6-10
C
3-3
3-1
3-9
6-7
C
6-17
3-7
D
3-8
1-32
D
3-4
1-10
6-17
1-39
6-10
2-10
E
3-10
6-17
E
6-5
F
G
F
G
H
123456
H
39
Page 40
AF-08CRL
COPYRIGHT © 2002 BY SHARP CORPORATION
ALL RIGHTS RESERVED.
No part of this publication may be reproduced, stored in retrieval systems, or transmitted in any form or by any means, electronic, mechanical, photocopying, recording, or otherwise, without prior written permission of the publisher.
40
02 SHARP CORP. 3S0.85E) Printed in U.S.A.
Loading...