STOP!Possible damage to propertyDamage to the drive system or its environ-
NOTEUseful information or a tip
Simplifies the handling of the
drive system
1.2Rights to claim under limited warranty
A requirement of fault-free operation and fulfillment of any rights to claim under limited
warranty is that you adhere to the information in the MOVI-PLC
fore, read the manual before you start operating the unit.
Make sure that the manual is available to persons responsible for the plant and its
operation, as well as to person who work independently on the unit. You must also
ensure that the documentation is legible.
ment
®
documentation. There-
1.3Exclusion of liability
4
You must comply with the information contained in the MOVI-PLC® documentation to
ensure safe operation of the MOVI-PLC
®
controller and to achieve the specified product
characteristics and performance requirements. SEW-EURODRIVE assumes no liability
for injury to persons or damage to equipment or property resulting from non-observance
of these operating instructions. In such cases, any liability for defects is excluded.
Manual – MOVI-PLC® I/O System
Page 5
Other applicable documentation
1.4Other applicable documentation
•Installation and startup only by trained personnel observing the relevant accident
prevention regulations and the following documents:
– "MOVIDRIVE
– "MOVITRAC
– "MOVIAXIS
–"MOVI-PLC
–"MOVI-PLC
– "Libraries for MOVI-PLC
– "MPLCUtilities Libraries for MOVI-PLC
–"MOVI-PLC
•Read through these documents carefully before you commence installation and
•As a prerequisite to fault-free operation and fulfillment of warranty claims, you must
adhere to the information in the documentation.
1.5General safety notes for bus systems
You are now in possession of a communication system that lets you adapt MOVI-PLC
controllers, MOVI-PLC® I/O systems and the controlled inverters to your specific system. As with all bus systems, there is a danger of invisible, external (as far as the inverter
is concerned) modifications to the parameters which give rise to changes in the unit
behavior. This may result in unexpected (not uncontrolled) system behavior.
General Information
– Fault Codes" manual
®
" manual
1
®
1.6Safety functions
MOVI-PLC® and the MOVI-PLC® I/O system may not perform safety functions.
For safety applications, refer to the information in the following publications.
•Safe disconnection for MOVIDRIVE
Use only those components in safety applications that were explicitly delivered in this
design by SEW-EURODRIVE!
1.7Hoist applications
•Hoist applications can only be implemented with MOVI-PLC® under the following
conditions:
– A special hoist startup of the inverters must be performed.
•Do not use MOVI-PLC
conjunction with hoist applications.
Use monitoring systems or mechanical protection devices as safety equipment to
avoid possible damage to property or injury to people.
®
/ MOVIAXIS® / MOVITRAC® B
®
and the MOVI-PLC® I/O system for any safety functions in
Manual – MOVI-PLC® I/O System
5
Page 6
2
System Description
MOVI-PLC® I/O system
2System Description
2.1MOVI-PLC® I/O system
The modular MOVI-PLC® I/O system expands the digital and analog interfaces of the
MOVI-PLC
32 I/O modules can be connected via backplane bus. The bus coupler communicates
with the MOVI-PLC
PLC
PLC
•MOVI-PLC
•Inputs and outputs directly integrated in the MOVI-PLC
®
controller. A MOVI-PLC® I/O system contains a bus coupler to which up to
®
®
I/O systems can be connected to a MOVI-PLC® controller. This means the MOVI-
®
controller can automatically access a large number of inputs and outputs.
via system bus. Up to 126 bus couplers and consequently MOVI-
®
I/O systems
®
controller
•Inputs and outputs of the controlled inverters
ETHERNET
[1]
MOVI PLC® I/O SystemMOVI PLC® I/O System
®
®
MOVITRAC
MOVI PLC
MOVIDRIVE® MOVIDRIVE
®
[2][3]
[1]Operator terminal (e.g. DOP11A)
[2]Asynchronous motor
[3]Servomotors
[4]System bus (connect MOVI-PLC
CAN1 and CAN2 of the MOVI-PLC
[4]
62069AXX
®
I/O systems and inverters separately to
®
controller)
6
Manual – MOVI-PLC® I/O System
Page 7
System Description
Scope of delivery of the individual components
2
Advantages of
the MOVI-PLC
I/O system
®
ule.
•Optimum integration into the programming software PLC Editor of the MOVITOOLS
•Powerful connection to the MOVI-PLC
®
controller via the SBus of the machine mod-
MotionStudio.
•A variety of combination options allows for implementing flexible and individual
machine solutions.
•The compact design and the modular structure reduce control cabinet space require-
ments to a minimum.
•Quick and easy installation or replacement in case of startup or service
2.2Scope of delivery of the individual components
OCC11B bus
coupler
ODI81B digital
input module
Bus coupler backplane bus – CAN.
Typ ePart number
OCC11B1821 479 7
I/O module with 8 binary inputs.
Typ ePart number
ODI81B1821 481 9
®
ODO81B digital
output module
OAI41B analog
input module
OAI42B analog
input module
OAI43B analog
input module
OAO41B analog
output module
I/O module with 8 binary outputs.
Typ ePart number
ODO81B1821 482 7
I/O module (voltage) with 4 analog inputs.
Typ ePart number
OAI41B1821 483 5
I/O module (current) with 4 analog inputs.
Typ ePart number
OAI42B1821 484 3
I/O module (multi input) with 4 analog inputs.
Typ ePart number
OAI43B1821 485 1
I/O module (voltage) with 4 analog outputs.
Typ ePart number
OAO41B1821 487 8
OAO42B analog
output module
Manual – MOVI-PLC® I/O System
I/O module (current) with 4 analog outputs.
Typ ePart number
OAO42B1821 488 6
7
Page 8
2
System Description
Accessories
OAO43B analog
output module
Terminal module
OTM21B
2.3Accessories
Connection cable
OKC11B
Backplane bus
connector OBP..B
I/O module (multi output) with 4 analog outputs.
Typ ePart number
OAO43B1821 489 4
Terminal module for 2 or 3-wire installation
Typ ePart number
OTM21B1821 490 8
Connection cable between MOVI-PLC® (X32 or X33 connection) and bus coupler
OCC11B.
Typ ePart number
OKC11B1810 482 7
Each I/O module and each terminal module is supplied with a single-socket backplane
bus connector. 10 x single-socket backplane bus connectors are supplied for reorders.
Typ ePart number
OBP11B ( 10 × single backplane bus connector)1821 491 6
OBP81B (1 × 8-socket backplane bus connector)1821 492 4
UWU52A
switched-mode
power supply
NOTES
•When connecting I/O modules to one bus coupler, replace 8 single-socket backplane connectors by one 8-socket backplane connector OBP81 B each (i.e. 16 I/O
modules → 2 × 8-socket backplane bus connectors, etc.).
•The 8-socket backplane connectors OBP81B have to be ordered separately.
You can use the UWU52A switched-mode power supply for DC 24 V voltage supply of
the MOVI-PLC I/O system.
Typ ePart number
UWU52A188 181 7
NOTES
•For installation notes and technical data of the UWU52A switched-mode power
supply unit, refer to the "Appendix" section.
•Observe the maximum rated output currents and the operating temperature.
8
Manual – MOVI-PLC® I/O System
Page 9
3Installation
3.1Mechanical installation
Notes on installing the modules of the MOVI-PLC® I/O system
STOP!
Observe the following points to prevent the I/O module from being damaged:
Switch off the voltage supply before you install or remove a module.
NOTES
•The individual modules are installed on a mounting rail. They are connected using
backplane bus connectors. The bus connector is placed into the profile rail that
carries the modules.
•The modules must always be installed directly next to each other. Gaps between
the modules are not permitted, else the backplane bus is interrupted.
•A row of modules is always installed from left to right and always begins with a bus
coupler.
•A module is not properly installed and electrically connected until it audibly locks in
place in the backplane connector.
•Plug-in locations to the right of the last module must not remain free.
Installation
Mechanical installation
3
Dimension
drawing for
mounting rail
You can use the following 35 mm standard profile rail (→ following figure) for installation.
SEW-EURODRIVE recommends to use version II to ensure sufficient space for the
retaining screws under the backplane bus connector.
II
35
27
1.5
15
27
I
35
1
7.5
61989AXX
Manual – MOVI-PLC® I/O System
9
Page 10
3
Installation
Mechanical installation
Mounting
position
You can install a maximum of 32 I/O modules vertically or horizontally. You can also add
terminal modules. Observe the permitted ambient temperatures:
•Horizontal installation: Ambient temperature of 0 °C to 60 °C
1
2
3
4
5
6
7
8
9
10
OAO41B
[2]
L+
1
2
3
4
5
6
7
8
9
10
ODI81B
DI8xDC24V
1
2
3
4
5
6
7
8
9
10
0
1
2
3
4
5
6
7
F
X3
45
DI8xDC24V 0,5A
1
0
2
1
3
2
4
3
5
4
6
5
7
6
8
7
9
10
X3
45
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
ODO81B
62004AXX
24V
DC
X3
45
[1]
75
ADR
PW
ER
RD
BA
1
2
3
4
5
C
6
A
7
N
8
9
X1
SF
+
10
X2
34
OAI41B
AI 4x12Bit VoltAO 4x12Bit Volt
L+
1
2
3
4
5
6
7
8
9
10
X3
45
[1]Bus coupler[2]I/O modules
•Vertical installation: Ambient temperature of 0 °C to 40 °C
[2]
[1]
123456789
123456789
1234567
0
L+
123456789
123456789
0123456
123456789
123456789
L+
123456789
123456789
CAN
7 5
ADR
ER
RD
PW
10
ODO81B
10
DI8xDC24V 0,5A
F
X3
45
10
ODI81B
DI8xDC24V
10
7
X3
45
10
OAO41B
10
X3
45
10
OAI41B
10
AI 4x12Bit VoltAO 4x12Bit Volt
SF
X2
34
X1
BA
+
X3
45
DC
24V
[1]Bus coupler[2]I/O modules
62005AXX
10
Manual – MOVI-PLC® I/O System
Page 11
Installation
Mechanical installation
3
Installation
clearance
Ensure a minimum clearance of 80 mm above and 60 mm below the middle of the backplane connector when installing the components.
80mm
60mm
62006AXX
NOTE
The switched-mode power supply used may require other installation distances.
Please observe the technical data of the switched-mode power supply in use.
Backplane bus
connector
Insert single-socket or 8-socket backplane bus connectors (→ following figure) into the
mounting rail for communication of the I/O modules and terminal modules. The individual plug-in locations for the module are defined by guide rails.
62086AXX
NOTES
•Each I/O module and each terminal module is supplied with a single-socket backplane bus connector. When connecting I/O modules and terminal modules to one
bus coupler, replace 8 single-socket backplane connectors by one 8-socket backplane bus connector OBP81B.
Example: For 20 I/O modules, use two 8-socket backplane bus connectors and four
single-socket backplane bus connectors.
•Also refer to the notes in the sections "Step-by-step installation of the MOVI-PLC
I/O system" and "Configuration of I/O modules".
•The switched-mode power supply is not plugged into the backplane bus connector
but is installed next to the MOVI-PLC
®
I/O system.
®
Manual – MOVI-PLC® I/O System
11
Page 12
3
Installation
Mechanical installation
Installation on
mounting rail
Press the backplane bus connector into the mounting rail until it audibly locks in place.
The following figure depicts four single-socket backplane connectors used as module
slots.
[2]
[1]
[3]
62007AXX
[1]Bus coupler slot
[2]I/O and terminal plug-in locations
[3]Guide rails
12
Manual – MOVI-PLC® I/O System
Page 13
Step-by-step installation of the MOVI-PLC® I/O system
Proceed as follows to install the keypad:
STOP!
Observe the following points to prevent the I/O module from being damaged:
Switch off the power supply before you insert or remove any modules.
NOTES
•If you operate various modules in a MOVI-PLC® I/O system, follow the specified
installation sequence of the modules from perspective of the bus coupler:
– First plug in the analog input modules directly next to the bus coupler
– Then plug in the analog output modules next to the analog input modules
– Finally plug in the digital modules
•Arrange the terminal modules as far to the right as possible. You can also plug
individual terminal modules at any location between the I/O modules.
•You can operate up to 32 I/O modules in a MOVI-PLC
coupler). If you do not use an analog input module, you can plug a total of 32 analog
output modules and digital modules in any combination without checking. Terminal
modules can be plugged additionally.
•When using analog input modules, it is important that the total current consumption
of all modules via the backplane bus does not exceed the output current of the bus
coupler backplane bus. Observe the information in the "Unit design and technical
data MOVI-PLC
•Observe the notes in the "Backplane bus connector" and "Configuration of I/O
modules" sections.
®
I/O system" section.
Installation
Mechanical installation
®
I/O system (i.e. at one bus
3
1. Install the mounting rail. Ensure the minimum clearance of at least 80 mm above and
60 to below the middle of the profile rail.
2. Insert the backplane bus connector into the profile rail until it audibly locks in place.
The bus connections protrude from the rail.
3. Start with the bus coupler at the left and plug in the required I/O modules and terminal
modules to the right of the bus coupler.
4. Place the module you want to install from top at an angle of approx. 45 degrees onto
the mounting rail and move the module downwards until it audibly locks in place on
the mounting rail (→ following figure). Only then will the module be properly
connected with the backplane bus.
CLACK
62026AXX
Manual – MOVI-PLC® I/O System
13
Page 14
3
Step-by-step removal of the MOVI-PLC® I/O system
Installation
Mechanical installation
Proceed as follows for removing modules:
STOP!
Observe the following points to prevent the I/O module from being damaged:
Switch off the power supply before you insert or remove a module.
NOTE
The backplane bus is interrupted at the point where the module was removed.
1. The enclosure of the module has a spring-loaded clip at the bottom by which the
module can be removed from the rail.
2. Insert a suitable screwdriver into the slot. The module is unlocked by pressing the
screwdriver in an upward direction (→ following figure, pos. I).
3. Remove the module toward you slightly turning it to the top (→ following figure, pos.
II).
I
II
14
62027AXX
Manual – MOVI-PLC® I/O System
Page 15
3.2Electrical installation
Installation
Electrical installation
3
EMC-compliant
installation
•When installing the modules, ensure that any inactive metal components are
grounded via a proper large-surface earth.
– Provide a wide area metal-on-metal contact between the unit housing and
ground.
– Establish a central connection between ground and the earthing/PE system.
– If possible, do not use any aluminum components.
•Ensure that wiring is routed properly during installation.
– Route power cables (power current, power supply) and signal cables in separate
cable ducts.
– Route signal cables as close as possible to ground surfaces (e.g. frames, metal
rails, sheet metal, etc.).
•Ensure that the shielding of lines is grounded properly.
– Signal lines must be shielded.
– Signal lines with analog signals must be shielded. If low-amplitude signals are
transferred, it may be advantageous to connect the shield on one side of the cable
only.
– Attach the shields of cables in the control cabinet over a large surface area to the
ground rail/PE rail. Secure the line shields using cable clamps.
– Ensure that the ground rail/PE rail has a low-impedance connection to the control
cabinet.
– Use metallic or metallized plug connector housings for shielded signal lines.
•Use incandescent lamps for illumination inside control cabinets. Do not use fluorescent lamps.
•Create a single reference potential and ground all electrical equipment wherever
possible.
– Ensure that earthing measures are implemented effectively.
– Provide a star-shaped connection between system components and control
cabinets of the MOVI-PLC
way, you avoid ground loops.
– Where potential differences exist, you must install sufficiently large equipotential
bonding conductors between the different parts of the system and control
cabinets.
®
I/O system and the earthing/protection system. In this
Shielding of linesObserve the following points when shielding lines:
•Only use lines with braided shield.
The coverage of the shield should exceed 80 %.
•Always ground the line shields at both ends of cables. High frequency interference
can only be suppressed by grounding cables on both ends.
•Always use metallic or metallized connectors for signal lines for serial links. Connect
the shield of the signal line to the connector housing. Do not connect the shield to pin
1 of the plug strip of the I/O module.
•For stationary operation, we recommend that you strip the insulation from the shielded cable interruption-free and attach the shield to the shield/protective ground rail.
•Connect braided shields by means of metallic cable clamps. The cable glands must
have a good electrical and large surface contact with the shield.
Manual – MOVI-PLC® I/O System
15
Page 16
3
Installation
Electrical installation
•Attach the shield of a cable to the grounding rail directly where the cable enters the
control cabinet. Continue to route the shield right up to the I/O system but do not
connect the shield to ground at this point.
NOTES
•Where potential differences exist between earthing connection, it is possible to
establish a compensating current flow where the shield of a cable is connected at
both ends.
•Make sure you supply adequate equipotential bonding according in accordance
with relevant VDE regulations in such a case.
Wiring plug
connectors
The I/O terminal modules are equipped with a 10-pole connector. This connector
provides the electrical interface for the signal and supply lines of the modules.
You can connect cables with a cross section of 0.08 mm
2
to 2.5 mm2 to the modules.
Connectors with spring-clip technique are used for wiring purposes. The spring-clip
technique simplifies the wiring of signal and voltage supply cables.
Unlike screw terminal connections, spring-clip wiring is vibration proof. The connector
assignment of the individual modules is explained in the sections on the respective
modules.
The following figure shows an I/O module with a 10-pole connector.
.0
.1
1
2
3
4
5
6
7
8
9
10
1
.2
2
.3
3
.4
4
.5
5
.6
6
.7
7
8
9
I0
1
2
3
.0
.1
.2
.3
1
2
3
.4
16
[2][1][3][1]
62066AXX
[1] Pin no.
[2] Round opening for wires
[3] Rectangular opening for screw driver
Manual – MOVI-PLC® I/O System
Page 17
Procedure for wiring the plug connectors
Proceed in the following sequence:
NOTE
First connect the voltage supply lines, next the signal lines.
•To install the connector, press the two clips together. Now plug the connector onto
the module (→ following figure, step 1). The connector is properly installed when it
audibly locks in place.
•Insert a suitable screw driver at an angle into the rectangular opening of the plug
connector contact (→ following figure, step 2). Press and hold the screw driver in the
opposite direction to open the contact spring (→ following figure, step 3).
STOP!
The spring-clip is destroyed if you insert the screw driver into the round opening for the
wires.
Make sure that you only insert the screw driver into the rectangular opening of the
connector.
Installation
Electrical installation
3
•Insert the stripped end of the wire into the round opening. You can use wires with a
cross section of 0.08 mm
2
to 2.5 mm2 to the I/O terminal modules (→ following
figure, step 4).
•Remove the screw driver from the rectangular opening (→ following figure, step 5).
The wire is now clipped securely to the connector.
1.
1
2
3
4
5
6
7
8
9
10
.0
.1
1
.2
2
.3
3
.4
4
.5
5
.6
6
.7
7
8
9
I0
2.
3.
.0
.1
1
2
3
4
5
6
7
8
9
10
1
.2
2
.3
3
.4
4
.5
5
.6
6
.7
7
8
9
I0
1.
.0
.1
4.
5.
1
2
3
4
5
6
7
8
9
10
1
.2
2
.3
3
.4
4
.5
5
.6
6
.7
7
8
9
I0
Manual – MOVI-PLC® I/O System
62041AXX
17
Page 18
4
Unit Design and Technical Data of the MOVI-PLC® I/O System
CAN bus coupler OCC11B
4Unit Design and Technical Data of the MOVI-PLC® I/O System
4.1CAN bus coupler OCC11B
Part number1821 479 7
DescriptionThe CAN bus coupler OCC11B (→ following figure) connects the MOVI-PLC
system with the MOVI-PLC
®
controller via the system bus from SEW-EURODRIVE. It
supports all CAN transmission rates.
[2]
75
ADR
[1]
DC
24V
X3
45
PW
ER
RD
BA
+
OCC11B
X1
C
A
N
[3]
1
[4]
2
62073AXX
[1]LED status indicators
[2]Address adjuster for setting baud rate and module ID
[3]CAN bus plug connector
[4]Port for external DC 24 V supply voltage
®
I/O
Diagnostics LEDThe CAN bus coupler OCC11B comes equipped with 4 diagnostics LEDs.
LEDColorLED status / meaning
PWGreenLights up if operating voltage is present.
ERRedLights up if error occurs during backplane bus transfer
RDGreen•Flashes with 1 Hz if self-test was positive and initialization successful
BAYellow•Off if self-test was positive and initialization successful
18
•Lights during data transmission via SBus
•Flashes with 1 Hz in "pre-operational" status
•Lights up in "operational" status
•Flashes with 10 Hz in "prepared" status
Manual – MOVI-PLC® I/O System
Page 19
Unit Design and Technical Data of the MOVI-PLC® I/O System
®
CAN bus coupler OCC11B
CombinationsA combination of diagnostics LEDs indicates various states.
LED statusMeaning
PW on
CAN plug
connector
assignment
ER on
RD on
BA on
PW on
ER flashes with 1Hz
RD flashes with 1 Hz
BA flashes with 1 Hz
PW on
ER flashes with 10Hz
RD flashes with
10 Hz
BA flashes with 10Hz
PW on
ER off
RD flashes with 1 Hz
BA off
The CAN bus coupler OCC11B is connected to the MOVI-PLC
terminal) using a 9-pin plug connector ("CAN" socket).
9-pin plug connector "CAN"PINAssignment
Error during RAM or EEPROM initialization.
Baud rate setting activated.
Incorrect CAN baud rate setting.
(no ACK from the bus master)
CAN bus cabling•For connecting the OCC11B bus coupler to the MOVI-PLC
terminal), use the prefabricated cable of SEW-EURODRIVE (length: 1.5 m) with integrated terminating resistors.
– Part number of the prefabricated cable: 1810 482 7
OCC11B
CAN
1
6
7
8
9
•You can connect more MOVI-PLC
MOVI-PLC
7
2
3
4
5
120
2
3
®
controller. To do so, remove the 120 Ω terminating resistor.
YE
GN
BR
WH
1500 mm
120
®
I/O systems to the X32/X33 connector of the
®
controller (X32 or X33
MOVI-PLC
X32/X33
123
2
3
1
123
62082AXX
Manual – MOVI-PLC® I/O System
19
Page 20
4
Unit Design and Technical Data of the MOVI-PLC® I/O System
CAN bus coupler OCC11B
NOTES
•CAN bus uses a shielded three-wire line as transmission medium.
•In systems with more than two stations, all stations are wired in parallel. The bus
cable must be looped without interruption for this purpose.
•The bus cable must always be connected with a terminating resistor of 120 Ω on
the line ends to avoid reflections and consequently transmission problems.
Voltage supplyThe CAN bus coupler OCC11B comes equipped with an integrated power supply unit.
The power supply unit must be supplied with DC 24 V. The supply voltage supplies the
bus coupler electronics and the connected I/O modules via the backplane bus. The power supply unit is protected against damage in the event of reverse polarity or overcurrent.
CAN bus and backplane bus are electrically isolated from each other.
NOTE
Correct polarity of the voltage supply at the X1 plug connector is required to avoid
failure of the bus coupler.
Setting the baud
rate using the
address adjuster
Use the address adjuster to set the CAN baud rate and the module ID.
•Set address 00 on the address adjuster.
•Activate the voltage supply for the CAN bus coupler.
The diagnostic LEDs "ER", "RD" and "BA" flash with 1 Hz. Now you have 5 seconds
time to programm the CAN baud rate using the address adjuster.
Address adjusterCAN baud rateMaximum bus length
001 MBaud25 m
01 500 kBaud (factory setting)100 m
02250 kbaud250 m
03125 kbaud500 m
04100 kbaud600 m
0550 kbaud1000 m
0720 kbaud2500 m
08800 kbaud50 m
The CAN baud rate will be saved after 5 seconds.
20
Manual – MOVI-PLC® I/O System
Page 21
Unit Design and Technical Data of the MOVI-PLC® I/O System
Setting the module ID
Technical data
CAN bus coupler OCC11B
NOTE
•The module ID must be set when you have set the baud rate and before switching
on the bus coupler again.
•Each module ID must only be assigned to the CAN bus once. Do not connect any
inverters to the CAN bus.
•The "ER" and "BA" diagnostics LEDs go out and the green "RD" LED continues to
flash.
•Use the address adjuster to set the module ID in the range from 1 to 63.
•The settings will be accepted after 5 seconds and the bus coupler enters normal
operation ("pre-operational" status).
Electrical data of OCC11B
Voltage supply X1
Current consumptionMax. DC 0.7 A
Output current backplane busMax. DC 3.5 A
Galvanic isolationAC 500 V
Status displayLEDs on the front panel
Connections/interfacesCAN bus: 9-pin sub-D connector
CAN bus interface
Coupling9-pin sub-D connector
Network topologyLinear bus, active bus termination at one end, spur lines are possible
Medium
Transmission rate10 kBaud ... 1 MBaud (factory setting: 500 kBaud)
Maximum total lengthWithout repeater: 1000 M at 50 kBaud
Binary inputs / outputsMax. 32 I/O modules can be combined per bus coupler
Maximum number of stations63 stations
Address setting1 ... 63 (factory setting: 1)
Combination with I/O modules
Maximum number of modules32
Dimensions and weight
Dimensions (W ×H ×D) in mm25.4 ×76 ×78
Weight80 g
X1:1
X1:2
DC+24 V input (20.4 V ... 28.8 V)
Reference 24 V
Shielded, three-wire cable. Depending on the ambient conditions,
shielding is not necessary.
4
Manual – MOVI-PLC® I/O System
21
Page 22
4
Unit Design and Technical Data of the MOVI-PLC® I/O System
OTM21B terminal module
4.2OTM21B terminal module
Part number1821 490 8
DescriptionThe OTM21B terminal module is a complementary module for 2-wire or 3-wire installa-
tion. The module is not connected to the backplane bus.
•2 separate rows with 11 electrically interconnected terminals.
•No connection to the backplane bus
•Maximum terminal current DC 10 A
X1
X2
Wiring diagram
[1]
[2]
[1]First terminal strip
[2]Second terminal strip
1
2
3
4
5
6
7
8
9
10
X1
1
2
3
4
5
6
7
8
9
10
X2
62077AXX
22
11
11
62078AXX
Manual – MOVI-PLC® I/O System
Page 23
Unit Design and Technical Data of the MOVI-PLC® I/O System
Technical data
OTM21B terminal module
Electrical data of OTM12B
Number of rows2
Number of terminals per row11
Maximum terminal currentDC 10 A
Terminal colorGray
Dimensions and weight
Dimensions (W ×H ×D) [mm]25.4 × 76 × 88
Weight50 g
4
Manual – MOVI-PLC® I/O System
23
Page 24
4
Unit Design and Technical Data of the MOVI-PLC® I/O System
ODI81B digital input module
4.3ODI81B digital input module
Part number1821 481 9
DescriptionThe ODI81B digital input module has 8 binary inputs, each one with an LED to indicate
the status.
•8 binary inputs, galvanically isolated from the backplane bus
•DC 24 V rated input voltage
•LED status indicator for binary inputs
[1]
1
[2]
[3]
2
3
4
5
6
7
8
9
I0
Connector
assignment
[1]Label for the bit address with description
[2]LED status indicator for binary inputs
[3]Connector strip
Unit Design and Technical Data of the MOVI-PLC® I/O System
ODI81B digital input module
4
LED status
indicator
Wiring diagram
Technical data
LEDs 0 ... 7 light up green if signal "1" is detected from approx. DC 15 V onwards.
1
2
3
4
5
6
7
8
9
10
M
DC 24V
62061AXX
Electrical data of ODI81B
Number of binary inputs8
Rated input voltageDC 24 V (20.4 ... 28.8 V)
Signal voltage "0"0 ... 5 V
Signal voltage "1"15 ... 28.8 V
Input filter time delay3 ms
Input currenttyp. 7 mA
Current consumption from backplane busDC 25 mA
Galvanic isolation500 V
Status indicatorvia LEDs located on the front
Programming data
Input data1 byte
Output dataDiagnostic data-
Dimensions and weight
Dimensions (W ×H ×D) [mm]25.4 × 76 × 88
Weight50 g
(field voltage to the bus)
rms
Manual – MOVI-PLC® I/O System
25
Page 26
4
Parameter settingMake the following settings in the module parameters (→ section "Parameter setting of
Unit Design and Technical Data of the MOVI-PLC® I/O System
ODI81B digital input module
I/O modules"). The settings refer to up to eight ODI81B digital input modules of the PLC
configuration entry. Default settings are printed in bold.
Module parametersSetting range
Transmit modeAcyclic / cyclic
Inhibit time0 ... 5 ... 500 ms
Event time0 ... 500 ms
•If the module parameter "TransmitMode" is set to "acyclic", process data will be
transmitted between MOVI-PLC
of modification. In this case, the module parameter "Event Time" indicates an additional cyclic transmission rate.
•If the module parameter "TransmitMode" is set to "cyclic", the "Event Time" indicates
the transmission rate for cyclic process data transmission.
•The module parameter "Inhibit Time" indicates in all cases a minimum duration
between process data transmissions.
®
controller and MOVI-PLC® I/O system in the event
26
Manual – MOVI-PLC® I/O System
Page 27
Unit Design and Technical Data of the MOVI-PLC® I/O System
ODO81B digital output module
4.4ODO81B digital output module
Part number1821 482 7
DescriptionThe ODI81B digital output module has 8 binary outputs, each one with an LED to
indicate the status.
•8 binary outputs, galvanically isolated from the backplane bus
•Power supply voltage DC 24 V
•Output current DC 0.5 A
•Status indicated by LED
[1]
1
[2]
[3]
2
3
4
5
6
7
8
9
I0
4
Connector
assignment
[1]Label for the bit address with description
[2]LED status indicator
[3]Connector strip
ODO81BTer mi-
nal/LED
1Power supply voltage DC 24 V
2Binary output 0
3Binary output 1
Green: DC 24 V present
Red: An error occurred
Green: Binary output active
Manual – MOVI-PLC® I/O System
27
Page 28
4
Unit Design and Technical Data of the MOVI-PLC® I/O System
ODO81B digital output module
LED +The "+" LED lights up green if the DC 24 V supply voltage is present.
LED 0 ... 7 Status
LEDs 0 ... 7 light up green if a binary output is active.
display
'F' LEDThe "F" LED lights up red if an error occurs caused by overload, overheating, or short
circuit.
Wiring diagram
1
2
3
4
5
6
7
8
9
10M
L+
DC 24V
62062AXX
Technical data
Electrical data of ODI81B
Number of binary outputs8
Rated load voltageDC 24 V (20.4 ... 28.8 V)
Current consumption
at L+ without load
from backplane bus
Output current per channel0.5 A short-cirucit proof
Total current4 A
Voltage supplyDC 24 V (20.4 V ... 28.8 V)
Galvanic isolation500 V
Status indicatorvia LEDs located on the front
Programming data
Input dataOutput data1 byte
Diagnostic data-
Dimensions and weight
Dimensions (W ×H ×D) [mm]25.4 × 76 × 88
Weight50 g
DC 10 mA
DC 70 mA
rms
(field voltage to the bus)
28
Manual – MOVI-PLC® I/O System
Page 29
Unit Design and Technical Data of the MOVI-PLC® I/O System
ODO81B digital output module
Parameter settingMake the following settings in the module parameters (→ section 5.6). The settings refer
to up to eight ODO81B digital output modules of the PLC configuration entry. Default
settings are printed in bold.
Module parametersSetting range
Transmit modeAcyclic / cyclic
Inhibit time0 ... 5 ... 500 ms
Event time0 ... 500 ms
4
•If the module parameter "TransmitMode" is set to "acyclic", process data will be
transmitted between MOVI-PLC
of a modification. In this case, the module parameter "Event Time" indicates an
additional cyclic transmission rate.
•If the module parameter "TransmitMode" is set to "cyclic", the "Event Time" indicates
the transmission rate for cyclic process data transmission.
•The module parameter "Inhibit Time" indicates in all cases a minimum duration
between process data transmissions.
®
controller and MOVI-PLC® I/O system in the event
Manual – MOVI-PLC® I/O System
29
Page 30
4
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAI41B analog input module (voltage)
4.5OAI41B analog input module (voltage)
Part number1821 483 5
DescriptionThe OAI41B analog input module has 4 inputs, each with an LED to indicate the status.
The OAI41B input module requires a total of 8 bytes of the process image for the input
data (2 bytes per channel). The channels on the OAI41B input module are galvanically
isolated from the backplane bus by means of DC/DC converters.
•4 analog inputs; channels galvanically isolated from the backplane bus
•The different channels can be configured individually and can be deactivated
•Suitable for encoders with ±10 V
•LED status indicator
[1]
1
[2]
[3]
2
3
4
5
6
7
8
9
I0
[1]Label for the bit address with description
[2]LED status indicator
[3]Connector strip
62059AXX
30
Manual – MOVI-PLC® I/O System
Page 31
Connector
assignment
Unit Design and Technical Data of the MOVI-PLC® I/O System
4Positive connection channel 1
5Ground channel 1
6Positive connection channel 2
7Ground channel 2
8Positive connection channel 3
9Ground channel 3
10Not assigned
'SF' LEDLights up red if
Assignment/description
•parameters are set incorrectly
•the upper or lower limit of the control
range is exceeded
4
'SF' LEDThe 'SF' LED lights up red if
•the upper or lower limit of the control range is exceeded
•parameters are set incorrectly
Wiring diagram
1
2
3
4
5
6
7
8
9
10
V
V
V
V
62063AXX
NOTE
Connect temporarily unused inputs with activated channel to the associated ground to
obtain defined values at these channels.
Manual – MOVI-PLC® I/O System
31
Page 32
4
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAI41B analog input module (voltage)
Function
assignment
You set the functions in the PLC Editor in the PLC configuration in the module parameters of the I/O module (→ section "Parameter setting of I/O modules"). Default settings
are printed in bold.
Module parametersSetting rangeDescription/measuring range/representation
Event time0 ... 10 ... 500 msThe "Event time" is used to set the transmission rate for
–10 ... 10 V
(–27648 ... 27648)
Mode channel 1 ... 4
–10 ... 10 V
(–16348 ... 16348)
Not active-
cyclic data transmission between MOVI-PLC
MOVI-PLC
DC ±11. 76 V
DC 11.76 V = Max. value overdrive range (32511)
DC –10 V ... 10 V = Rated range (–27648 ... 27648)
DC –11.76 V = Max. value underdrive range (–32512)
Two’s complement
DC ±12.50 V
DC 12.50 V = Max. value overdrive range (20480)
DC –10 V ... 10 V = Rated range (–16384 ... 16384)
DC –12.50 V = Min. value underdrive range (–20480)
Two’s complement
®
I/O system.
®
and
NOTE
The default setting of the I/O module OAI41B is "–10 ... 10 V (–27648 ... 27648)".
Technical data
Electrical data of OAI41B
Number of analog inputs4
Cable length (shielded)200 m
Voltages, currents, potentials
Galvanic isolation
Channel/backplane bus
between the channels
Permitted potential difference
between inputs
between inputs and M
Insulation tested atDC 500 V
Current consumption from backplane busDC 120 mA
Power loss of the I/O module0.6 W
Interference suppression for f = n × (f1±1 %)
(f1 = interfering frequency; n = 1, 2, ...)
Common-mode interference (U
Interference between inputs> 50 dB
Operational limits (over entire temperature range, referred to input)
Voltage inputMeasuring range ±10 V / tolerance ±0.2 %
(U
internal
)
iso
< 2 V)> 80 dB
CM
Yes
No
DC 2 V
DC 75 V/AC 60 V
n×2ms
13 bit
f = 50 Hz ... 400 Hz
32
Manual – MOVI-PLC® I/O System
Page 33
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAI41B analog input module (voltage)
Electrical data of OAI41B
Basic error limit (operational limit at 25 °C, referred to input)
Voltage inputMeasuring range ±10 V / tolerance ±0.1 %
Temperature error
(referred to input)
Linearity error
(referred to input range)
Repeatability
(under steady-state conditions, at 25 °C,
referred to input range)
DiagnosticsNo
Diagnostics interruptNo
Fault display for group fault'SF' LED (red)
Encoder selection data
VoltageInput range: ±10 V/input resistance: 100 kΩ
Permitted input voltage for voltage input
(destruction limit)
Voltage measurementPossible
Permitted ambient conditions
Operating temperature0 °C ... 60 °C
Transport and storage temperature–25 °C ... 70 °C
Relative humidity95 % without condensation
vibration and shock resistanceAccording to IEC 68000-2/IEC 68000-2-27
EMC resistance
ESD/burst
Programming data
Input data8 bytes (1 word per channel)
Output data-
Dimensions and weight
Dimensions (W ×H ×D) [mm]25.4 × 76 × 88
Weightca. 80 g
±0.005 %/K
±0.02 %
±0.05 %
Max. 30 V
According to IEC 61000-4-2
IEC 61000-4-2/IEC 61000-4-4 (up to level 3)
4
Manual – MOVI-PLC® I/O System
33
Page 34
4
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAI42B analog input module (current)
4.6OAI42B analog input module (current)
Part number1821 484 3
DescriptionThe analog input module OAI42B has 4 inputs. Their functions can be configured
individually. The OAI42B input module requires a total of 8 bytes of the process image
for the input data (2 bytes per channel). The channels on the OAI42B input module are
galvanically isolated from the backplane bus by means of DC/DC converters.
•4 analog inputs; channels galvanically isolated from the backplane bus
•The different channels can be configured individually and can be deactivated.
•Suitable for encoders with 4 ... 20 mA, ±20 mA
•LED status indicator
[1]
1
[2]
[3]
2
3
4
5
6
7
8
9
I0
[1]Label for the bit address with description
[2]LED status indicator
[3]Connector strip
62059AXX
34
Manual – MOVI-PLC® I/O System
Page 35
Connector
assignment
Unit Design and Technical Data of the MOVI-PLC® I/O System
4Positive connection channel 1
5Ground channel 1
6Positive connection channel 2
7Ground channel 2
8Positive connection channel 3
9Ground channel 3
10Not assigned
'SF' LEDLights up red if
•parameters are set incorrectly
•the upper or lower control limit is
exceeded
4
'SF' LEDThe 'SF' LED lights up red if
•the upper or lower control limit is exceeded
•if parameters are set incorrectly
Wiring diagram
1
2
3
4
5
6
7
8
9
10
A
A
A
A
62064AXX
NOTE
Connect temporarily unused inputs with activated channel to the associated ground to
obtain defined values at these channels.
Manual – MOVI-PLC® I/O System
35
Page 36
4
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAI42B analog input module (current)
Function
assignment
You set the functions in the PLC configuration in the PLC Editor in the module parameters of the I/O module (→ section "Parameter setting of I/O modules"). Default settings
are printed in bold.
Module parametersSetting rangeDescription/measuring range/representation
Event time0 ... 10 ... 500 msThe "Event time" is used to set the transmission rate for
4 ... 20 mA
(0 ... 27648)
–20 ... 20 mA
(–27648 ... 27648)
Mode channel 1 ... 4
4 ... 20 mA
(0 ... 16348)
–20 ... 20 mA
(–16384 ... 16384)
Not active-
cyclic data transmission between MOVI-PLC
MOVI-PLC
DC 1.185 ... 22.81 mA
DC 22.81 mA = Max. value overdrive range (32511)
DC 4 ... 20 mA = Rated range (0 ... 27648)
DC 1.185 mA = Minimum value underdrive range
(–4864)
Two’s complement
DC ±23.52 mA
DC 23.52 mA = Max. value overdrive range (32511)
DC –20 mA ... 20 mA = Rated range (–27648 ... 27648)
DC –23.52 V = Min. value underdrive range (–32512)
Two’s complement
DC 0.8 ... 24 mA
DC 24 mA = Max. value overdrive range (32511)
DC 4 .. 20 mA = Rated range (0 ... 16384)
DC 0.8 mA = Min. value underdrive range (–3277)
Two’s complement
DC ±25 mA
DC 25 mA = Max. value overdrive range (20480)
DC –20 mA ... 20 mA = Rated range (–16384 ... 16384)
DC –25 mA = Min. value underdrive range (–20480)
Two’s complement
®
I/O system.
®
and
Technical data
NOTE
The default setting of the I/O module OAI42B is "4 ... 20 mA (0 ... 27648)".
Electrical data of OAI42B
Number of analog inputs4
Cable length (shielded)200 m
Voltages, currents, potentials
Galvanic isolation
Channel/backplane bus
between the channels
Permitted potential difference
between inputs
between inputs and M
Insulation tested atDC 500 V
Current consumption from backplane busDC 120 mA
Power loss of the I/O module0.6 W
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAI42B analog input module (current)
Electrical data of OAI42B
Interference suppression, error limits
Interference suppression for f = n × (f1±1 %)
(f1 = interfering frequency; n = 1, 2, ...)
Common-mode interference (U
Interference between inputs> 50 dB
Operational limits (over entire temperature range, referred to input)
Current inputMeasuring range ±20 mA / tolerance ±0.2 %
Basic error limit (operational limit at 25 °C, referred to input)
Current inputMeasuring range ±20 mA / tolerance ±0.1 %
Temperature error
(referred to input range)
Linearity error
(referred to input range)
Repeatability
(under steady-state conditions, at 25 °C,
referred to input range)
DiagnosticsNo
Diagnostics interruptNo
Fault display for group fault'SF' LED (red)
Encoder selection data
CurrentInput range ±20 mA / input resistance 60Ω
Permitted input current for current input
(destruction limit)
Voltage measurement
as 2-wire transducer
as 4-wire transducer
Permitted ambient conditions
Operating temperature0 °C ... 60 °C
Transport and storage temperature–25 °C ... 70 °C
Relative humidity95 % without condensation
Vibration and shock resistanceAccording to IEC 68000-2/IEC 68000-2-27
EMC resistance
ESD/burst
Programming data
Input data8 bytes (1 word per channel)
Output data-
Dimensions and weight
Dimensions (W ×H ×D) [mm]25.4 × 76 × 88
Weightca. 80 g
< 2 V)> 80 dB
CM
f = 50 Hz ... 400 Hz
Measuring range 4 ... 20 mA / tolerance ±0.5 %
Measuring range 4 ... 20 mA / tolerance ±0.2 %
±0.005 %/K
±0.02 %
±0.05 %
Input range 4 ... 20μA / input resistance 60Ω
40 mA
Possible, with external supply
Possible
According to IEC 61000-4-2
IEC 61000-4-2/IEC 61000-4-4 (up to level 3)
4
Manual – MOVI-PLC® I/O System
37
Page 38
4
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAI43B analog input module (multi-input)
4.7OAI43B analog input module (multi-input)
Part number1821 485 1
DescriptionThe OAI43B analog input module has 4 inputs. Their functions can be configured
individually. The OAI43B input module requires a total of 8 bytes of the process image
for the input data (2 bytes per channel). The channels on the OAI43B input module are
galvanically isolated from the backplane bus by means of DC/DC converters.
•The different channels can be configured individually and can be deactivated.
•The common signal inputs of the channels are not isolated from each other; the
permitted potential difference is up to 5 V.
•Diagnostic function
Connector
assignment
[1]
1
[2]
[3]
2
3
4
5
6
7
8
9
I0
[1]Label for the bit address with description
[2]LED status indicator
[3]Connector strip
4Positive connection channel 1
5Ground channel 1
6Positive connection channel 2
7Ground channel 2
8Positive connection channel 3
9Ground channel 3
10Channel 2 with 4-wire connection
LED F0 ... F3Lights up red if
•an error occurs in one of the
channels
•an entry was made in the diagnostic
bytes
62059AXX
38
Manual – MOVI-PLC® I/O System
Page 39
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAI43B analog input module (multi-input)
LEDs F0 ... F3The LEDs F0 ... F3 light up red if
•an error occurs in one of the channels
•an entry was made in the diagnostic bytes
Wiring diagramThe following figure shows the connection options for the various measuring ranges. For
an assignment to the measuring ranges, refer to the "Connection" column in the
"Function assignment" section.
[1][2][3][4]
4
1
2
3
4
5
6
7
8
9
10
1
2
V
A
V
A
V
A
V
A
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
1
2
3
4
5
6
7
8
9
10
U-
I
U+
I
I
U+
I
U-
62065AXX
NOTE
Connect temporarily unused inputs with activated channel to the associated ground to
obtain defined values at these channels.
STOP!
Observe the following points to prevent the I/O module from being damaged:
•The parameterized measuring range must correspond with the connected encoder.
•Do not connect a voltage > DC 15 V to the input.
Manual – MOVI-PLC® I/O System
39
Page 40
4
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAI43B analog input module (multi-input)
Function
assignment
A function number is assigned to a channel by setting the module parameters (→ section "Parameter setting of I/O modules"). The function number 00
means the function
hex
number stored permanently in the parameter setting data is not influenced.
You can disable a channel by specifying FF
Module parameters No.
Event time-0 ... 10 ... 500 msThe "Event time" is used to set the transmission rate for
Module mode--The "Module mode" module parameter is used to set
Setting range / functionDescription / measuring range / representationWiring
hex
cyclic data transmission between MOVI-PLC
®
PLC
I/O system.
whether the OAI43B analog input module is to generate a
diagnostics interrupt or not. In this case, the diagnostic
information will be output at the MPLC_ConnectSEWIOSystem_CAN function module (→ section "IEC pro-
gram"). You find more information in the "MPLCUtilities
Library for MOVI-PLC
Bit 0 ... 5, 7 : Reserved
Bit 6:
•0 = Diagnostic interrupt disabled
•1 = Diagnostic interrupt enabled
.
hex
®
" manual.
®
and MOVI-
diagram
-
-
40
Manual – MOVI-PLC® I/O System
Page 41
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAI43B analog input module (multi-input)
4
Module parameters No.
hex
00The function number in the permanently stored parameter setting data is not changed.
01Pt100 in the 2-wire connec-
02Pt1000 in the 2-wire con-
03NI100 in the 2-wire connec-
04NI1000 in the 2-wire con-
05Resistance measurement
06Resistance measurement
07Resistance measurement
08Resistance measurement
09Pt100 in the 4-wire connec-
0APt1000 in the 4-wire con-
0BNI100 in the 4-wire connec-
0CNI1000 in the 4-wire con-
0DResistance measurement
0EResistance measuring 60 Ω
Mode channel 1 ... 4
0FResistance measuring
10Thermocouple type J
11Thermocouple type K
12Thermocouple type type
13Thermocouple type R
14Thermocouple type T
15Thermocouple type S
16Thermocouple type E
18Thermocouple type J
19Thermocouple type K, inter-
1AThermocouple type N, inter-
1BThermocouple type R, inter-
1CThermocouple type T, inter-
1DThermocouple type S, inter-
Setting range / functionDescription / measuring range / representationWiring
tion
nection
tion
nection
60 Ω two-wire
60 Ω two-wire
3000 Ω two-wire
6000 Ω two-wire
tion
nection
tion
nection
60 Ω four-wire
four-wire
3000 Ω four-wire
1)
externally compensated
externally compensated
1)
N
, externally compen-
sated
externally compensated
1)
externally compensated
1)
externally compensated
1)
externally compensated
2)
internally compensated
nally compensated
nally compensated
nally compensated
nally compensated
nally compensated
1)
1)
–200 °C ... 850 °C
Unit: 1/10 °C; two’s complement
–200 °C ... 850 °C
Unit: 1/10 °C; two’s complement
–60 °C ... 250 °C
Unit: 1/10 °C; two’s complement
–60 °C ... 250 °C
Unit: 1/10 °C; two’s complement
60 Ω = end value (32767)[3]
600 Ω = end value (32767)[3]
3000 Ω = end value (32767)[3]
6000 Ω = end value (32767)[3]
–200 °C ... 850 °C
Unit: 1/10 °C; two’s complement
–200 °C ... 850 °C
Unit: 1/10 °C; two’s complement
–60 °C ... 250 °C
Unit: 1/10 °C; two’s complement
–60 °C ... 250 °C
Unit: 1/10 °C; two’s complement
60 Ω = end value (32767)[4]
600 Ω = end value (32767)[4]
3000 Ω = end value (32767)[4]
,
–210 °C ... 1200 °C
Unit: 1/10 °C, two’s complement
,
–270 °C ... 1372 °C
Unit: 1/10 °C, two’s complement
–270 °C ... 1300 °C
Unit: 1/10 °C, two’s complement
,
–50 °C ... 1769 °C
Unit: 1/10 °C, two’s complement
,
–270 °C ... 400 °C
Unit: 1/10 °C, two’s complement
,
–50 °C ... 1769 °C
Unit: 1/10 °C, two’s complement
,
–270 °C ... 1000 °C
Unit: 1/10 °C, two’s complement
,
–210 °C ... 1200 °C
Unit: 1/10 °C, two’s complement
–270 °C ... 1372 °C
Unit: 1/10 °C, two’s complement
–270 °C ... 1300 °C
Unit: 1/10 °C, two’s complement
–50 °C ... 1769 °C
Unit: 1/10 °C, two’s complement
–270 °C ... 400 °C
Unit: 1/10 °C, two’s complement
–50 °C ... 1769 °C
Unit: 1/10 °C, two’s complement
diagram
[3]
[3]
[3]
[3]
[4]
[4]
[4]
[4]
[2]
[2]
[2]
[2]
[2]
[2]
[2]
[2]
[2]
[2]
[2]
[2]
[2]
Manual – MOVI-PLC® I/O System
41
Page 42
4
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAI43B analog input module (multi-input)
Module parameters No.
hex
1EThermocouple type E, inter-
27Voltage DC±50 mV
28Voltage DC ±10 V
29Voltage DC ±4V
2AVoltage DC ±400 mV
2BVoltage DC ±10 V
2CCurrent DC ±20 mA
Mode channel 1 ... 4
2DCurrent DC 4 ... 20 mA
2ECurrent DC 4 ... 20 mA
2FCurrent DC ±20 mA
32Resistance measuring
33Resistance measuring
35Resistance measuring
36Resistance measuring
37Resistance measuring
38Resistance measuring
Setting range / functionDescription / measuring range / representationWiring
nally compensated
(–27648 ... 27648)
(–27648 ... 27648)
(–27648 ... 27648)
(–27648 ... 27648)
(–16384 ... 16384)
(–27648 ... 27648)
(0 ... 27648)
(0 ... 16384)
(–16384 ... 16384)
6000 Ω four-wire
6000 Ω four-wire
60 Ω two-wire
600 Ω two-wire
3000 Ω two-wire
6000 Ω two-wire
–270 °C ... 1000 °C
Unit: 1/10 °C, two’s complement
DC ±58.79 mV
DC 58.79 mV = Max. value overdrive range (32511)
DC –50 ... 50 mV = Rated voltage (–27648 ... 27648)
DC –58.79 mV = Min. value underdrive range (–32512)
Two’s complement
DC ±11. 76 V
DC 11.76 V = Max. value overdrive range (32511)
DC –10 ... 10 V = Rated range (–27648 ... 27648)
DC –11.76 V = Min. value underdrive range (–32512) Two’s
complement
DC ±4.70 V
DC 4.70 V = Max. value overdrive range (32511)
DC –4 ... 4 V = Rated range (–27648 ... 27648)
DC –4.70 V = Min. value underdrive range (–32511)
Two’s complement
DC ±470 mV
DC 470 mV = Max. value overdrive range (32511)
DC –400 ... 470 mV = Rated range (–27648 ... 27648)
DC –470 mV = Min. value underdrive range (–32512)
Two’s complement
DC ±12.50 V
DC 12.50 V = Max. value overdrive range (20480)
DC –10 ... 10 V = Rated range (–16384 ... 16384)
DC –12.50 V = Min. value underdrive range (–20480)
Value and sign
DC ±23.52 mA
DC 23.52 mA = Max. value overdrive range (32511)
DC –20 ... 20 mA = Rated range (–27648 ... 27648)
DC –23.52 mA = Min. value underdrive range (–32512)
Two’s complement
DC 1.185 ... 22.81 mA
DC 22.81 mA = Max. value overdrive range (32511)
DC 4 ... 20 mA = Rated range (0 ... 27648)
DC 1.185 mA = Min. value underdrive range (–4864)
Two’s complement
DC 0.8 ... 24 mA
DC 24 mA = Max. value overdrive range (20480)
DC 4 ... 20 mA = Rated range (0 ... 16384)
DC 0.8 mA = Min. value underdrive range (–3277)
Value and sign
DC ±25 mA
DC 25 mA = Max. value overdrive range (20480)
DC –20 ... 20 mA = Rated range (–16384 ... 16384)
DC –25 mA = Min. value underdrive range (–20480)
Value and sign
6000 Ω = end value (32767)
6000 Ω = end value (6000)
60 Ω = end value (6000)
600 Ω = end value (6000)
3000 Ω = end value (30000)
6000 Ω = end value (6000)
diagram
[2]
[1]
[1]
[1]
[1]
[1]
[1]
[1]
[1]
[1]
[4]
[4]
[3]
[3]
[3]
[3]
42
Manual – MOVI-PLC® I/O System
Page 43
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAI43B analog input module (multi-input)
4
Module parameters No.
Mode channel 1 ... 4
ModeControl channel 1 ... 4
1) The compensation of the neutralization must be implemented externally.
2) The compensation of the neutralization must be implemented externally. Connect the thermocuple conductors directly to the front connector. Where necessary, extend them using thermocouple extension cables.
Setting range / functionDescription / measuring range / representationWiring
hex
3ACurrent DC ±20 mA
(–16384 ... 16384)
3BVoltage DC ±10 V
(–16384 ... 16384)
3DResistance measuring
60 Ω four-wire
3EResistance measuring
600 Ω four-wire
3FResistance measuring
3000 Ω four-wire
57Voltage DC ±50 mVDC ±50 mV
58Voltage DC ±10 VDC ±11. 76 V
59Voltage DC ±4VDC ±4.7 V
5AVoltage DC ±400 mVDC ±470 mV
5CCurrent DC ±20 mADC ±23.51 mA
5DCurrent DC 4 ... 20 mADC 1.185 ... 22.81 mA
62Cu50 in the 2-wire connec-
tion
6ACu50 in the 4-wire connec-
tion
FFChannel not active (dis-
abled)
DC ±25 mA
DC 25 mA = Max. value overdrive range (20480)
DC –20 ... 20 mA = Rated range (–16384 ... 16384)
DC –25 mA = Min. value underdrive range (–20480)
Two’s complement
DC ±12.50 V
DC 12.50 V = Max. value overdrive range (20480)
DC –10 ... 10 V = Rated range (–16384 ... 16384)
DC –12.50 V = Min. value underdrive range (–20480)
Two’s complement
60 Ω = end value (6000)
600 Ω = end value (6000)
3000 Ω = end value (30000)
DC 58.79 mV = Max. value overdrive range (5879)
DC –50 ... 50 mV = Rated range (–5000 ... 5000)
DC –58.79 mV = Min. value underdrive range (–5879)
Two’s complement
DC 11.76 V = Max. value overdrive range (11760)
DC –10 ... 10 V = Rated range (–10000 ... 10000)
DC –11.76 V = Min. value underdrive range (–11760)
Two’s complement
DC 4.7 V = Max. value overdrive range (4700)
DC –4 ... 4 V = Rated range (–4000 ... 4000)
DC –4.7 V = Min. value underdrive range (–4700)
Two’s complement
DC 470 mV = Max. value overdrive range (4700)
DC –400 ... 400 mV = Rated voltage (–4000 ... 4000)
DC –470 mV = Min. value underdrive range (–4700)
Two’s complement
DC 23.51 mA = Max. value overdrive range (23510)
DC –20 ... 20 mA = Rated range (–20000 ... 20000)
DC –23.51 mA = Min. value underdrive range (–23510)
Two’s complement
DC 22.81 mA = Max. value overdrive range (18810)
DC 4 ... 20 mA = Rated range (0 ... 16000)
DC 1.185 mA = Min. value underdrive range (–2815)
Two’s complement
–50 °C ... 150 °C
Unit: 1/10 °C, two’s complement
–50 °C ... 150 °C
Unit: 1/10 °C, two’s complement
--
The "ModeControl Channel 1 ... 4" module parameter is
used to set the conversion speed as well as averaging and
a Hüllfunktion.
diagram
[1]
[1]
[4]
[4]
[4]
[1]
[1]
[1]
[1]
[1]
[1]
[3]
[4]
-
Manual – MOVI-PLC® I/O System
43
Page 44
4
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAI43B analog input module (multi-input)
NOTE
The default setting of the OAI43B I/O module is "–10 ... 10 V (–27648 ... 27648)".
Module parameter ModeControl
Channel 1 ... 4
Structure
The "ModeControl Channel 1 ... 4" module parameter is used to set the following
parameters:
•Conversion speed
•Mean value calculation
•Envelope function
Bit 0 ... 7Resolution
Bit 3 ... 0: Conversion speed per channel
•0000 = 15 conversions/s
•0001 = 30 conversions/s
•0010 = 60 conversions/s
•0011 = 120 conversions/s
•0100 = 170 conversions/s
•0101 = 200 conversions/s
•0110 = 3.7 conversions/s
•0111 = 7.5 conversions/s
Bit 5 ... 4: Mean value calculation
•00 = disabled
•01 = use 2 of 3 values
•10 = use 4 of 6 values
•11 = disabled
Bit 7 ... 6: Envelope function
•00 = disabled
•01 = envelope ±8
•10 = envelope ±16
•11 = disabled
1) The values refer to single-channel operation. To calculate the conversion speed per channel for
multi-channel operation, divide the specified conversion speeds by the number of active channels.
1)
16
16
15
14
12
10
16
16
Conversion speedUse bit 0 ... 3 to set the conversion speed for each input channel. Note that the resolution
decreases with higher conversion speeds due to the reduced integration time. The data
transmission format remains the same. Only the least significant bits (LSBs) are no
longer relevant for the analog value.
44
Manual – MOVI-PLC® I/O System
Page 45
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAI43B analog input module (multi-input)
4
Mean value
calculation
•Mean value function 2 of 3 values
After every measuring, the OAI43B analog input module calculates the mean value
of the last 3 values. The value most different from the mean value is discarded. The
remaining 2 values are averaged again. This value will then be provided as output
value.
•Mean value function 4 of 6 values
After every measuring, the OAI43B analog input module calculates the mean value
of the last 6 values. The two values most different from the mean value are discarded. The remaining 4 values are averaged again. This value will then be provided as
output value.
Envelope functionThe output value [3] is 'wrapped' with an envelope [A] with a parameterizable value. If
the measured value [1, 2, 4] lies over or under the envelope, the envelope [A] migrates
accordingly. The output value [3] is always the mean value of the envelope (→ following
figure).
[1][2]
+8/+16
[B]
+8/+16
[A]
[3]
[A]
[A]
[4]
62091AXX
[1] Measured value within envelope → no envelope shift. The output value is the
mean value of the current upper and lower limit of the envelope.
[2] Measured value exceeds the envelope upwards → envelope shifts up by the
difference between "old" upper limit of the envelope and measured value. The
output value is the mean value of the "new" upper and lower limits of the
envelope.
[4] Measured value exceeds the envelope downwards → envelope shifts down by
the difference between "old" lower limit of the envelope and measured value. The
output value is the mean value of the "new" upper and lower limits of the
envelope.
[B] Integration time
Manual – MOVI-PLC® I/O System
45
Page 46
4
Technical data
Electrical data of OAI43B
Number of inputs
with 4-wire resistance-based sensor
Cable length (shielded)200 m
Voltages, currents, potentials
Constant current for resistance-based sensor
Galvanic isolation
Permitted potential difference
Insulation tested atDC 500 V
Current consumption from backplane busDC 280 mA
Power loss of the I/O module1.4 W
Analog value generationConversion time/resolution (per channel)
Measuring principleSigma delta
ParameterizableYes
Conversion speed [Hz]2001701206030157.53.7
Integration time [ms]568173367133270
Basic conversion time [ms]7810193569135272
Resolution including overdrive range [Bit]1012141516161616
Interference voltage suppression for interfer-
ence frequency f1 [Hz]
Basic execution time of the I/O module (all
channels enabled) [ms]
Mean value calculation2 of 3
Envelope function±8 or ±16
Interference suppression, error limits
Interference suppression for f = n × (f1±1 %), (f1 = interfering frequency; n = 1, 2, ...)
Common-mode interference (U
Opposed-mode interference (peak value of
interference < rated value of input range)
Interference between inputs> 50 dB
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAI43B analog input module (multi-input)
Channel/backplane bus
between the channels
between inputs (U
between inputs and M
Additional conversion time for wire break
monitoring [ms]
One-time service time per cycle (only with
thermocouple) [ms]
CM
)
internal
(U
)
iso
< 5 V)> 80 dB
CM
4
2
1.25 mA
Yes
No
DC 5 V
DC 75 V / AC 60 V
135
10
No50 Hz and 60 Hz
283240761402765401088
or
4 of 6
>80dB
46
Manual – MOVI-PLC® I/O System
Page 47
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAI43B analog input module (multi-input)
Electrical data of OAI43B
Operational limits (only valid up to 120 W/s)
(over entire temperature range, referred to input range)
Measuring rangeTolerance
Voltage input
Current input
Resistance
Resistance thermometer
ThermocoupleType J, K, N, R, S, E, T± 1.5 %
Basic error limit (operational limit at 25 °C, referred to input)
Voltage input
Current input
Resistance
Resistance thermometer
ThermocoupleType J, K, N, R, S, E, T±1.0 %
Temperature error during current measuring
(referred to input range)
Linearity error
(referred to input range)
Repeatability
(under steady-state conditions, at 25 °C,
referred to input range)
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAI43B analog input module (multi-input)
Electrical data of OAI43B
Signal encoder connection
Voltage measurement
Current measurement
as 2-wire transducer
as 4-wire transducer
Resistance measurement
with 2-wire connection
with 4-wire connection
Linearization of characteristic curves
Parameterizable
for resistance thermometer
Thermocouples
Temperature compensation
Parameterizable
Internal temperature compensation
External temperature compensation
with comparison table (0 °C)
Unit for temperature measurement°C
Programming data
Input data8 bytes (1 word per channel)
Dimensions and weight
Dimensions (W ×H ×D) [mm]25.4 × 76 × 88
Weight80 g
Possible
Possible, with external supply
Possible
Possible
Possible
Yes
Pt100, Pt1000, Ni100, Ni1000, Cu50
Type J, K, N, R, S, E, T
Yes
Possible
Possible
48
Manual – MOVI-PLC® I/O System
Page 49
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAO41B analog output module (voltage)
4.8OAO41B analog output module (voltage)
Part number1821 487 8
DescriptionThe OAO41B analog output module has 4 outputs. Their functions can be configured
individually. The OAO41B analog output module requires a total of 8 bytes of the
process image for the output data (2 bytes per channel). The channels on the OAO41B
output module are galvanically isolated from the backplane bus and power supply
voltage by means of DC/DC converters and optocouplers. The OAO41B analog output
module must be supplied with external DC 24 V.
•4 analog outputs with common ground
•The different channels can be configured individually.
•Suitable for actuators with inputs ±10 V or 0 ... 10 V
•LED status indicator
4
[1]
1
[2]
[3]
2
3
4
5
6
7
8
9
I0
[1]Label for the bit address with description
[2]LED status indicator
[3]Connector strip
62059AXX
Manual – MOVI-PLC® I/O System
49
Page 50
4
V
Connector
assignment
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAO41B analog output module (voltage)
OAO41BTerminal/LED Assignment/description
1Power supply voltage DC 24 V
2Positive connection channel 0
L+
X3
45
AO 4x12Bit Volt
1
2
3
4
5
6
7
8
9
10
OAO41B
62054AXX
3Ground channel 0
4Positive connection channel 1
5Ground channel 1
6Positive connection channel 2
7Ground channel 2
8Positive connection channel 3
9Ground channel 3
10Ground DC 24 V
LED +Green: DC 24 V present
LED L+The L+ LED lights up green if the supply voltage DC 24 V is present.
Wiring diagram
1
2
3
4
5
6
7
8
9
10
L+
DC 24
M
62060AXX
50
Manual – MOVI-PLC® I/O System
Page 51
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAO41B analog output module (voltage)
4
Function
assignment
You set the functions in the PLC configuration in the PLC Editor in the module
parameters of the I/O module (→ section "Parameter setting of I/O modules"). Default
settings are printed in bold.
Module parametersSetting rangeDescription/measuring range/representation
Event time0 ... 10 ... 500 msThe "Event time" is used to set the transmission rate for
–10 ... 10 V
(–27648 ... 27648)
0 ... 10 V
(0 ... 27648)
Mode channel 1 ... 4
–10 V ... 10 V
(–16384 ... 16384)
0 ... 10 V
(0 ... 16384)
Not active-
cyclic data transmission between MOVI-PLC
MOVI-PLC
DC ±11. 76 V
DC 11.76 V = Max. value overdrive range (32511)
DC –10 V ... 10 V = Rated range (–27648 ... 27648)
DC –11.76 V = Min. value underdrive range (–32512)
Two’s complement
DC 0 ... 11.76 V
DC 11.76 V = Max. value overdrive range (32511)
DC 0 V ... 10 V = Rated range (0 ... 27648)
No underdrive range
Two’s complement
DC ±12.5 V
DC 12.5 V = Max. value overdrive range (20480)
DC –10 V ... 10 V = Rated range (–16384 ... 16384)
DC –12.5 V = Min. value underdrive range (–20480)
Two’s complement
DC 0 ... 12.5 V
DC 12.5 V = Max. value overdrive range (20480)
DC 0 V ... 10 V = Rated range (0 ... 16384)
No underdrive range
Two’s complement
®
I/O system.
®
and
NOTE
•The default setting of the OAO41B O/I module is "–10 ... 10 V (–27648 ... 27648)".
•Value "0" is output in all modes when the overdrive range or underdrive range is
exceeded.
Manual – MOVI-PLC® I/O System
51
Page 52
4
Technical data
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAO41B analog output module (voltage)
Electrical data of OAO41B
Number of output channels4
Cable length (shielded)200 m
Supply voltage
Polarity reversal protection
Galvanic isolation
between channel/backplane bus
between channel/supply voltage
between the channels
between channel/load voltage L+
Permitted potential difference
between inputs and M
Insulation tested atDC 500 V
Current consumption
from backplane bus
from load voltage L+ (without load)
Power loss of the I/O module2.7 W
Analog value generation output channels
Resolution
±10 V
0 ... 10 V
Cycle time (all channels)700 μs
Setting time
Resistive load
Capacitive load
Inductive load
Interference suppression, error limits
Interference between outputs> 40 dB
Basic error limit (over entire temperature range,
referred to output range)
Voltage outputMeasuring range ±10 V / tolerance ±0.2 %
Basic error limit (operational limit at 25 °C,
referred to output range)
Voltage outputMeasuring range ±10 V / tolerance ±0.1 %
Temperature error
(referred to output range)
Linearity error
(referred to output range)
Repeatability
(under steady-state conditions at 25 °C,
referred to output range)
Output ripple
Bandwidth 0 to 50 kHz
(referred to output range)
Actuator selection data
VoltageOutput ranges: ±10 V / 0 ... 10 V
Load impedance (in the rated range of the out-
put)
for voltage outputs
Capacitive load
Voltage output
Short-circuit proof
Short-circuit current
Destruction limit against externally applied volt-
ages/currents
Voltage at the output against M
Current
internal
(U
)DC 75 V / AC 60 V
iso
ANA
DC 24 V
Yes
Yes
Yes
No
Yes
DC 60 mA
DC 100 mA
11 bit + sign
11 bit
1.5 ms
3 ms
-
Measuring range 0 ... 10 V / tolerance ±0.4 %
Measuring range 0 ... 10 V / tolerance ±0.2 %
±0.01 %/K
±0.05 %
±0.05 %
±0.05 %
Min. 5 kΩ
Max. 1 μF
Yes
Max. 6 mA
Max. 15 V
Max. 30 mA
52
Manual – MOVI-PLC® I/O System
Page 53
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAO41B analog output module (voltage)
Electrical data of OAO41B
Connection of the actuators
Voltage output2-wire connection
Status, interrupts, diagnostics
Diagnostics interruptDiagnostic functionsFault display for group faultDiagnostic information can be read outSubstitute values can be switched in-
Programming data
Input dataOutput data8 bytes (1 word per channel)
Diagnostic data-
Dimensions and weight
Dimensions (W ×H ×D) [mm]25.4 × 76 × 88
Weight100 g
4
Manual – MOVI-PLC® I/O System
53
Page 54
4
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAO42B analog output module (current)
4.9OAO42B analog output module (current)
Part number1821 488 6
DescriptionThe OAO42B analog output module has 4 outputs. Their functions can be configured
individually. The OAO42B output module requires a total of 8 bytes of the process image
for the output data (2 bytes per channel). The channels on the OAO42B output module
are galvanically isolated from the backplane bus by means of DC/DC converters and
optocouplers. The OAO42B analog output module must be supplied with external
DC 24 V.
•4 analog outputs with common ground
•The outputs can be configured individually.
•Suitable for actuators with inputs 0 ... 20 mA or 4 ... 20 mA
[1]
1
[2]
[3]
2
3
4
5
6
7
8
9
I0
[1]Label for the bit address with description
[2]LED status indicator
[3]Connector strip
62059AXX
54
Manual – MOVI-PLC® I/O System
Page 55
Connector
V
assignment
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAO42B analog output module (current)
OAO42BTer mi-
nal/LED
1Power supply voltage DC 24 V
2Positive connection channel 0
3Ground channel 0
L+
X2
34
OAO42B
AO 4x12Bit Curr
1
2
3
4
5
6
7
8
9
10
62056AXX
4Positive connection channel 1
5Ground channel 1
6Positive connection channel 2
7Ground channel 2
8Positive connection channel 3
9Ground channel 3
10Ground DC 24 V
LED +Green: DC 24 V present
Assignment/description
4
LED L+The L+ LED lights up green if the supply voltage DC 24 V is present.
Wiring diagram
1
2
3
4
5
6
7
8
9
10
L+
DC 24
M
62060AXX
Manual – MOVI-PLC® I/O System
55
Page 56
4
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAO42B analog output module (current)
Function
assignment
You set the functions in the PLC configuration in the PLC Editor in the module parameters of the I/O module (→ section "Parameter setting of I/O modules"). Default settings
are printed in bold.
Module parametersSetting rangeDescription/measuring range/representation
Event time0 ... 10 ... 500 msThe "Event time" is used to set the transmission rate for
4 ... 20 mA
(0 ... 27648)
0 ... 20 mA
(0 ... 27648)
Mode channel 1 ... 4
4 ... 20 mA
(0 ... 16384)
0 ... 20 mA
(0 ... 16384)
Not active-
cyclic data transmission between MOVI-PLC
MOVI-PLC
DC 0 ... 22.81 mA
DC 22.81 mA = Max. value overdrive range (32511)
DC 4 ... 20 mA = Rated range (0 ... 27648)
DC 0 mA = Min. value underdrive range (–6912)
Two’s complement
DC 0 ... 23.52 mA
DC 23.52 mA = Max. value overdrive range (32511)
DC 0 ... 20 mA = Rated range (0 ... 27648)
No underdrive range
Two’s complement
DC 0 ... 24 mA
DC 24 mA = Max. value overdrive range (20480)
DC 4 .. 20 mA = Rated range (0 ... 16384)
DC 0 mA = Min. value underdrive range (–4096)
Two’s complement
DC0 ... 24 mA
DC 24 mA = Max. value overdrive range (20480)
DC 4 ... 20 mA = Rated range (0 ... 16384)
No underdrive range
Two’s complement
®
I/O system.
®
and
Technical data
NOTE
•The default setting of the OAO42B I/O module is "4 ... 20 mA (0 ... 27648)".
•The value "0" is output in all modes when the overdrive range or underdrive range
is exceeded.
Electrical data of OAO42B
Number of output channels4
Cable length (shielded)200 m
Supply voltage
Polarity reversal protection
Galvanic isolation
between channel/backplane bus
between channel/supply voltage
between the channels
between channel/load voltage L+
Permitted potential difference
between inputs and M
Insulation tested atDC 500 V
Current consumption
from backplane bus
from load voltage L+ (without load)
Power loss of the I/O module1.5 W
internal
(U
)DC 75 V / AC 60 V
iso
DC 24 V
Yes
Yes
Yes
No
Yes
DC 60 mA
DC 50 mA
56
Manual – MOVI-PLC® I/O System
Page 57
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAO42B analog output module (current)
Electrical data of OAO42B
Analog value generation output channels
Resolution
0 ... 20 mA
4 ... 20 mA
Cycle time (all channels)700 μs
Setting time
Resistive load
Capacitive load
Inductive load
Interference suppression, error limits
Interference between outputs> 40 dB
Basic error limit (over entire temperature range,
referred to output range)
Current outputMeasuring range 0 ... 20 mA / tolerance ±0.4 %
Basic error limit (operational limit at 25 °C,
referred to output range)
Current outputMeasuring range 0 ... 20 mA / tolerance ±0.2 %
Temperature error
(referred to output range)
Linearity error
(referred to output range)
Repeatability
(under steady-state conditions at 25 °C,
referred to output range)
Output ripple
Bandwidth 0 to 50 kHz
(referred to output range)
Actuator selection data
CurrentOutput ranges: 0 ... 20 mA / 4 ... 20 mA
Load impedance (in the rated range of the out-
put)
for current outputs
Inductive load
Current output
No-load voltageDC 12 V
Destruction limit against externally applied volt-
ages/currents
Voltage at the output against M
Current
Connection of the actuators
Current output2-wire connection
Status, interrupts, diagnostics
Diagnostics interruptDiagnostic functionsFault display for group faultDiagnostic information can be read outSubstitute values can be switched in-
Programming data
Input dataOutput data8 bytes (1 word per channel)
Dimensions and weight
Dimensions (W ×H ×D) [mm]25.4 × 76 × 88
Weight100 g
ANA
12 bit
11 bit
0.03 ms
-
1.5 ms
Measuring range 4 ... 20 mA / tolerance ±0.5 %
Measuring range 4 ... 20 mA / tolerance ±0.3 %
±0.01 %/K
±0.05 %
±0.05 %
±0.05 %
Min. 350 Ω
Max. 10 mH
Max. 12 V
Max. 30 mA
4
Manual – MOVI-PLC® I/O System
57
Page 58
4
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAO43B analog output module (multi-output)
4.10OAO43B analog output module (multi-output)
Part number1821 489 4
DescriptionThe OAO43B analog output module has 4 outputs. Their functions can be configured
individually. The OAO43B output module requires a total of 8 bytes of the process image
for the output data (2 bytes per channel). The values must be specified left-justified in
the two’s complement. The channels on the OAO42B output module are galvanically
isolated from the backplane bus by means of DC/DC converters.
•The outputs can be configured individually.
•Four outputs with common ground
•Suitable for actuators with inputs ±10 V, 1 ... 5 V, 0 ... 10 V, ±20 mA, 4 ... 20 mA or 0
... 20 mA
•Diagnostic LED and diagnostic function
[1]
1
[2]
[3]
2
3
4
5
6
7
8
9
I0
[1]Label for the bit address with description
[2]LED status indicator
[3]Connector strip
62059AXX
58
Manual – MOVI-PLC® I/O System
Page 59
Connector
V
assignment
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAO43B analog output module (multi-output)
OAO43BTer mi-
nal/LED
1Power supply voltage DC 24 V
2Positive connection channel 0
3Ground channel 0
SF
X2
34
AO 4x12Bit Mult
1
2
3
4
5
6
7
8
9
10
OAO43B
62058AXX
4Positive connection channel 1
5Ground channel 1
6Positive connection channel 2
7Ground channel 2
8Positive connection channel 3
9Ground channel 3
10Ground DC 24 V
'SF' LEDLights up red if
Assignment/description
•the OAO43B output module is not
supplied with voltage
•a short-circuit occurs in the voltage
output
•a wire break occurs in the current
output
•the module contains an incorrect
parameter
4
'SF' LEDThe 'SF' LED lights up red if
•the OAO43B output module is not supplied with voltage
•a short-circuit occurs in the voltage output
•a wire break occurs in the current output
•a parameter in the module was set incorrectly
Wiring diagram
1
2
3
4
5
6
7
8
9
L+
DC 24
10
Manual – MOVI-PLC® I/O System
M
62060AXX
59
Page 60
4
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAO43B analog output module (multi-output)
Function
assignment
A function number is assigned to a channel by setting the module parameters (→ section "Parameter setting of I/O modules"). The function number 00
means the function
hex
number stored permanently in the parameter setting data is not influenced.
You can disable a channel by specifying FF
Module parameters No.
Event time-0 ... 10 ... 500 msThe "Event time" is used to set the transmission rate for cyclic data
Module mode--The "Module mode" module parameter is used to set whether the OAO43B
analog output module is to generate a diagnostics interrupt or not. In this
case, the diagnostic information will be output at the MPLC_ConnectSEWIOSystem_CAN function module (→ section "IEC program"). You find more
information in the "MPLCUtilities Library for MOVI-PLC
Bit 0 ... 5, 7 : Reserved
Bit 6:
•0 = Diagnostic interrupt disabled
•1 = Diagnostic interrupt enabled
hex
.
®
and MOVI-PLC® I/O system.
®
" manual.
60
Manual – MOVI-PLC® I/O System
Page 61
Unit Design and Technical Data of the MOVI-PLC® I/O System
DC ±12.5 V
DC 12.5 V = Max. value overdrive range (20480)
DC –10 ... 10 V = Rated range (–16384 ... 16384)
DC –12.5 V = Min. value underdrive range (–20480)
DC 0 ... 6 V
DC 6 V = Max. value overdrive range (20480)
DC 1 ... 5 V = Rated range (0 ... 16384)
DC 0 V = Min. value underdrive range (–4096)
DC 0 ... 12.5 V
DC 12.5 V = Max. value overdrive range (20480)
DC 0 ... 10 V = Rated range (0 ... 16384)
No underdrive range
DC ±11.7 6 V
DC 11.76 V = Max. value overdrive range (32511)
DC –10 ... 10 V = Rated range (–27648 ... 27648)
DC –11.76 V = Min. value underdrive range (–32512)
DC 0 ... 5.704 V
DC 5.704 V = Max. value overdrive range (32511)
DC 1 ... 5 V = Rated range (0 ... 27648)
DC 0 V = Min. value underdrive range (–6912)
DC 0 ... 11.76 V
DC 11.76 V = Max. value overdrive range (32511)
DC 0 ... 10 V = Rated range (0 ... 27648)
No underdrive range
DC ±25 mA
DC 25 mA = Max. value overdrive range (20480)
DC –20 ... 20 mA = Rated range (–16384 ... 16384)
DC 25 mA = Min. value underdrive range (–20480)
DC 0 ... 24 mA
DC 24 mA = Max. value overdrive range (20480)
DC 4 ... 20 mA = Rated range (0 ... 16384)
DC 0 mA = No underdrive range (–4096)
DC 0 ... 25 mA
DC 25 mA = Max. value overdrive range (20480)
DC 0 ... 20 mA = Rated range (0 ... 16384)
No underdrive range
DC ±23.52 mA
DC 23.52 mA = Max. value overdrive range (32511)
DC –20 ... 20 mA = Rated range (–27648 ... 27648)
DC –23.52 mA = Min. value underdrive range (–32512)
DC 0 ... 22.81 mA
DC 22.81 mA = Max. value overdrive range (32511)
DC 4 ... 20 mA = Rated range (0 ... 27648)
DC 0 mA = Min. value underdrive range (–6912)
DC 0 ... 23.52 mA
DC 23.52 mA = Max. value overdrive range (32511)
DC 0 ... 20 mA = Rated range (0 ... 27648)
No underdrive range
NOTES
•The default setting of the OAI43B I/O module is "–10 ... 10 V (–27648 ... 27648)".
•The value "0" is output in all modes when the overdrive range or underdrive range
is exceeded.
Manual – MOVI-PLC® I/O System
61
Page 62
4
Technical data
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAO43B analog output module (multi-output)
Electrical data of OAO43B
Number of output channels4
Cable length (shielded)200 m
Supply voltage
Polarity reversal protection
Galvanic isolation
between channel/backplane bus
between channel/supply voltage
between the channels
between channel/load voltage L+
Insulation tested atDC 500 V
Current consumption
from backplane bus
from load voltage L+ (without load)
Power loss of the I/O module1.8 W
Analog value generation output channels
Resolution (incl. overdrive range)
±10 V, ±20 mA
4 ... 20 mA, 1 ... 5 V
0 ... 10 V, 0 ... 20 mA
Cycle time (all channels)700 μs
Conversion time (per channel)450 μs
Setting time
Resistive load
Capacitive load
Inductive load
Interference suppression, error limits
Interference between outputs> 40 dB
Operational limits (over entire temperature range, referred to output range)
Voltage output
Current output
Basic error limit (operational limit at 25 °C, referred to output range)
Voltage output
Current output
Temperature error
(referred to output range)
Linearity error
(referred to output range)
Repeatability
(under steady-state conditions at 25 °C,
referred to output range)
Output ripple
Bandwidth 0 to 50 kHz
(referred to output range)
Actuator selection data
Output ranges (rated values)
Voltage
Current
DC 24 V
Yes
Yes
Yes
No
Yes
DC 75 mA
DC 60 mA
11 bit + sign
10 bit
11 bit
0.05 ms
0.5 ms
0.1 ms
Measuring range 1 ... 5 V / tolerance 0.8 %
Measuring range 0 ... 10 V / tolerance 0.6 %
Measuring range ±10 V / tolerance 0.4 %
Measuring range 4 ... 20 mA / tolerance ±0.8 %
Measuring range 0 ... 20 mA / tolerance ±0.6 %
Measuring range ±20 mA / tolerance ±0.3 %
Measuring range 1 ... 5 V / tolerance 0.4 %
Measuring range 0 ... 10 V / tolerance 0.3 %
Measuring range ±10 V / tolerance 0.2 %
Measuring range 4 ... 20 mA / tolerance ±0.5 %
Measuring range 0 ... 20 mA / tolerance ±0.4 %
Measuring range ±20 mA / tolerance ±0.2 %
±0.01 %/K
±0.05 %
±0.05 %
±0.05 %
1 ... 5 V, 0 ... 10 V, ±10 V
4 ... 20 mA, 0 ... 20 mA, ±20 mA
1)
1)
1)
2)
2)
2)
1)
1)
1)
2)
2)
2)
62
Manual – MOVI-PLC® I/O System
Page 63
Unit Design and Technical Data of the MOVI-PLC® I/O System
OAO43B analog output module (multi-output)
Electrical data of OAO43B
Load impedance (in the rated range of the output)
for voltage outputs
Capacitive load
for current outputs
Inductive load
Voltage output
Short-circuit proof
Short-circuit current
Current output
No-load voltageMax. DC 13 V
Destruction limit against externally applied volt-
ages/currents
Voltage at the output against M
Current
Connection of the actuators
Voltage output
Current output
Status, interrupts, diagnostics
Diagnostics interruptParameterizable
Diagnostic functionsParameterizable
Fault display for group fault'SF' LED
Diagnostic information can be read outPossible
Substitute values can be switched inNo
Programming data
Input dataOutput data8 bytes (1 word per channel)
Dimensions and weight
Dimensions (W ×H ×D) [mm]25.4 × 76 × 88
Weight100 g
1) The error limits were determined with a load R = 1 GΩ. When voltage is output, the output resistance of
the I/O module is 30 Ω.
2) The error limits were determined with a load R = 10 Ω.
ANA
Min. 1 kΩ
Max. 1 μF
Max. 500Ω
Max. 10 mH
Yes
Max. 31 mA
Max. 15 V
Max. 30 mA
2-wire connection
2-wire connection
4
Manual – MOVI-PLC® I/O System
63
Page 64
5
Project Planning with MOVITOOLS® MotionStudio
PLC Editor project planning tool
5Project Planning with MOVITOOLS® MotionStudio
This chapter describes the project planning for the MOVI-PLC® I/O system with the
MOVITOOLS
®
MotionStudio.
5.1PLC Editor project planning tool
•Start MOVITOOLS® MotionStudio and the PLC Editor.
You find more detailed information in the "Project Planning with MOVITOOLS
MotionStudio" section in the manuals "MOVI-PLC® basic controller DHP11B" and
MOVI-PLC
•For basic information on the PLC Editor and PLC configuration, refer to the "MOVIPLC
®
advanced controller DH.41B"
®
Programming in the PLC Editor" system manual.
5.2Adding a MOVI-PLC® I/O system
•In the PLC configuration, activate the interface to be used for connecting the
OCC11B CAN bus coupler of the MOVI-PLC
controller. Replace the relevant entry with "... enabled" (e.g. "CAN 1 enabled" →
following figure)
The baud rate set in the module parameters of the interface must correspond with
the baud rate set on the OCC1B CAN bus coupler (→ section "OCC11B CAN bus
coupler").
•Select the required entry (e.g. "CAN 1 enabled") and choose the menu items
[Append Subelement] / [MOVI-PLC I/O system] from the context menu (→ following
figure).
•In the module parameters of the MOVI-PLC
that was set at the CAN bus coupler of the MOVI-PLC
"OCC11B CAN bus coupler").
®
I/O system to the MOVI-PLC
®
I/O system, set the same bus address
®
I/O system (→ section
®
®
64
11675AEN
Manual – MOVI-PLC® I/O System
Page 65
Project Planning with MOVITOOLS® MotionStudio
5.3Configuring I/O modules
Configuring I/O modules
5
•In the PLC configuration (→ following figure), the entries "Inputs" and "Outputs"
appear underneath the MOVI-P LC
®
PLC
I/O system to these entries. To do so, choose the required module designa-
tions from the context menu.
•Choosing an "Analog ... OA.." analog module will add the relevant module. Choosing
the entry "Digital ... 8x OD.." will guide you in one step to the configuration of 8 digital
modules even if less than 8 modules are installed.
®
I/O system. Add the I/O modules of your MOVI-
11676AEN
In the event of multiple configuration of I/O modules of the same type, the sequence
displayed in the PLC configuration window will correspond with the physical
sequence in the MOVI-PLC
arrangement and combination of various I/O module types need not be reflected in
the PLC configuration. Terminal modules are not displayed in the PLC configuration.
Example: The physical arrangement of the MOVI-PLC
ODI81B digital input modules followed by one ODO81B digital output module and
five ODI81B digital input modules. However, the PLC configuration still displays all 8
digital input modules in the "Digital IN 8x ODI81B.." entry.
®
I/O system from left to right. However, the physical
®
I/O system consists of three
NOTES
•The following scaling applies in conjunction with a MOVI-PLC® basic DHP11B
controller:
– You can arrange a maximum of one analog input module and one analog output
module each to the bus coupler per MOVI-PLC
– Additonally, you can install a maximum number of 8 digital input modules and 8
digital output modules and terminal modules.
Configurations other than this scaling (e.g. two entries "Digital 8x ODI81B..") are not
supported physically.
•Please also refer to the information in the "Backplane bus" and "step-by-step
installation of the I/O system" section in the "Mechanical Installation" chapter.
®
I/O system.
Manual – MOVI-PLC® I/O System
65
Page 66
5
Project Planning with MOVITOOLS® MotionStudio
Configuring I/O modules
5.4Configuring I/O modules
In the module parameters of the I/O modules (→ following figure), set the required
functionality according to the module descriptions (→ section "Unit design and technical
data of I/O modules").
5.5IEC program
•In the library manager, add the MPLCUtilities library to your project. Have the
•The process image of the relevant I/O system is refreshed while the function module
11677AEN
MPLC_ConnectSEWIOSystem_CAN function module execute an instance in a
cyclic task per MOVI-PLC
is being executed.
®
I/O system.
NOTE
For a detailed description of the MPLC_ConnectSEWIOSystem_CAN function module
and the output diagnostic information, refer to the "MPLCUtilities Library for MOVI-
®
PLC
" manual.
66
Manual – MOVI-PLC® I/O System
Page 67
UWU52A switched-mode power supply
6Appendix
6.1UWU52A switched-mode power supply
Technical data
Switched-mode power supplyUWU52A
Part number188 181 7
Input voltageAC 1 × 110 ... 240 V
Voltage rangeAC 95 ... 265 V, AC 110 ... 300 V
Frequency50/60 Hz
Max. no-load currentAC 40 mA
Rated input current
at AC 1 × 110 V
at AC 1 × 230 V
Output voltageDC 24 V (-1% / +3%)
Rated output current
at 40 °C
at 55 °C
Residual ripple< 50 mV
Interference voltage< 120 mV
Power loss< 5.5 W
Weight0.23 kg
Operating temperature0 ... +55 °C (condensation not permitted)
Degree of protectionIP20 (EN 60529)
Protection classI
ConnectionScrew terminals for cable cross sections 0.20 ... 2.5 mm
Appendix
1.04 AAC
AC 0.63 A
DC 2.5 A
DC 2.0 A
eff
SS
6
2
Dimension
drawing
The power supply is short-circuit proof and protected against overload. Input and output
are galvanically isolated.
38
76
4EN 60715TM35
109
101
62140AXX
Leave a clearance of at least 50mm at top and bottom of venting slots!
EMC-compliant installation
Procedure for wiring plug connectors
Shielding of lines
Wiring plug connectors
..........................................15
...........................15
.................................16
.................................15
...............................................4
..............................................4
Exclusion of liability
General safety notes for bus systems
Rights to claim under limited warranty
Structure of the safety notes
Hoist applications
Electrical installation
Mechanical installation
........................................4
..........................4
...........................................5
.....................................15
...................................9
..........................................11
Backplane bus connector
Dimension drawing mounting rail
Installation clearance
Mounting position
Notes on installation of I/O modules
Step-by-step installation of the I/O system
Step-by-step removal of the I/O system
Additional addresses for service in China provided on request!
BogotáSEW-EURODRIVE COLOMBIA LTDA.
SEW-EURODRIVE CHILE LTDA.
Las Encinas 1295
Parque Industrial Valle Grande
LAMPA
RCH-Santiago de Chile
P.O . Bo x
Casilla 23 Correo Quilicura - Santiago - Chile
No. 78, 13th Avenue, TEDA
Tianjin 300457
333, Suhong Middle Road
Suzhou Industrial Park
Jiangsu Province, 215021
P. R . Ch in a
Calle 22 No. 132-60
Bodega 6, Manzana B
Santafé de Bogotá