Operating Instructions – Electronic Motor DRC.-..-SNI
5
1
General Information
Use of this documentation
1General Information
Electronic Motor DRC.-..-SNI
1.1Use of this documentation
The documentation is an integral part of the product and contains important information
on operation and service. The documentation is written for all employees who assemble,
install, start up, and service this product.
The documentation must be accessible and legible. Make sure that persons responsible
for the system and its operation, as well as persons who work independently on the unit,
have read through the documentation carefully and understood it. If you are unclear
about any of the information in this documentation, or if you require further information,
contact SEW-EURODRIVE.
1.2Structure of the safety notes
1.2.1Meaning of the signal words
The following table shows the grading and meaning of the signal words for safety notes,
notes on potential risks of damage to property, and other notes.
Signal wordMeaningConsequences if disregarded
DANGERImminent dangerSevere or fatal injuries
WARNINGPossible dangerous situationSevere or fatal injuries
CAUTIONPossible dangerous situationMinor injuries
NOTICEPossible damage to propertyDamage to the drive system or its
INFORMATIONUseful information or tip:
Simplifies the handling of the
drive system.
environment
1.2.2Structure of the section-related safety notes
Section-related safety notes do not apply to a specific action, but to several actions
pertaining to one subject. The used symbols indicate either a general or a specific
hazard.
This is the formal structure of a section-related safety note:
SIGNAL WORD
Type and source of danger.
Possible consequence(s) if disregarded.
•Measure(s) to prevent the danger.
1.2.3Structure of the embedded safety notes
Embedded safety notes are directly integrated in the instructions just before the description of the dangerous action.
This is the formal structure of an embedded safety note:
• SIGNAL WORD Nature and source of hazard.
Possible consequence(s) if disregarded.
– Measure(s) to prevent the danger.
6
Operating Instructions – Electronic Motor DRC.-..-SNI
Rights to claim under limited warranty
1.3Rights to claim under limited warranty
A requirement of fault-free operation and fulfillment of any rights to claim under limited
warranty is that you adhere to the information in the documentation. Read the documentation before you start working with the unit!
1.4Exclusion of liability
You must comply with the information contained in this documentation to ensure safe
operation and to achieve the specified product characteristics and performance
features. SEW-EURODRIVE assumes no liability for injury to persons or damage to
equipment or property resulting from non-observance of these operating instructions. In
such cases, any liability for defects is excluded.
part of this documentation is strictly prohibited.
General Information
1
1.6Product names and trademarks
All brands and product names in this documentation are trademarks or registered trademarks of their respective titleholders.
Operating Instructions – Electronic Motor DRC.-..-SNI
7
2
Safety Notes
General Information
2Safety Notes
2.1General Information
The following basic safety notes must be read carefully to prevent injury to persons and
damage to property. The operator must ensure that the basic safety notes are read and
adhered to. Ensure that persons responsible for the system and its operation, as well as
persons who work independently on the unit, have read through the operating
instructions carefully and understood them. If you are unclear about any of the information in this documentation, or if you require further information, please contact SEWEURODRIVE.
Never install damaged products or take them into operation. Submit a complaint to the
shipping company immediately in the event of damage.
During operation, DRC drive units can have live, bare and movable or rotating parts as
well as hot surfaces, depending on their degree of protection.
Removing covers without authorization, improper use as well as incorrect installation or
operation may result in severe injuries to persons or damage to property.
Refer to the documentation for additional information.
2.2Target group
Only qualified electricians are authorized to install, start up or service the units or
correct unit faults (observing IEC 60364 or CENELEC HD 384 or DIN VDE 0100 and
IEC 60664 or DIN VDE 0110 as well as national accident prevention guidelines).
Qualified electricians in the context of these basic safety notes are all persons familiar
with installation, assembly, startup and operation of the product who possess the
necessary qualifications.
All persons involved in any other work, such as transportation, storage, operation and
disposal, must be trained appropriately.
8
Operating Instructions – Electronic Motor DRC.-..-SNI
2.3Designated use
DRC drive units are components intended for installation in electrical systems or machines.
In case of installation in machines, taking the DRC drive units into operation (i.e. start of
designated operation) is prohibited until it is determined that the machine meets the requirements stipulated in EC Directive 2006/42/EC (Machinery Directive).
Startup (i.e. the start of designated use) is only permitted under observance of EMC
directive 2004/108/EC (EMC Directive).
DRC drive units comply with the regulations of the Low Voltage Directive 2006/95/EC.
The standards given in the declaration of conformity are applied to the DRC drive units.
You must observe the technical data and information on the connection requirements
as provided on the nameplate and in the documentation.
2.3.1Safety functions
DRC drive units may not
and expressly permitted.
Safety Notes
Designated use
perform safety functions unless these functions are described
2
2.3.2Lifting applications
DRC drive units are not designed for use as safety devices in lifting applications.
2.4Other applicable documentation
Note also the following documentation:
•"DRC Gearmotors" catalog
•Operating instructions for the gear unit (only for DRC gearmotors)
You can download or order these publications on the Internet (http://www.sew-
eurodrive.com under the heading "Documentation").
2.5Transportation, storage
You must observe the notes on transportation, storage and proper handling. Comply
with the requirements for climatic conditions stated in chapter "Technical Data". Tighten
installed eyebolts securely. They are designed for the weight of the DRC drive unit. Do
not attach any additional loads. Use suitable, sufficiently rated handling equipment (e.g.
rope guides) if required.
Operating Instructions – Electronic Motor DRC.-..-SNI
9
2
Safety Notes
Installation
2.6Installation
2.7Electrical connection
The units must be installed and cooled according to the regulations and specifications
in the corresponding documentation.
Protect the DRC drive units from improper strain.
The following applications are prohibited unless explicitly permitted:
•Use in potentially explosive atmospheres.
•Use in areas exposed to harmful oils, acids, gases, vapors, dust, radiation, etc.
•Use in non-stationary applications that are subject to mechanical vibration and shock
loads as stated in the documentation for DRC drive units.
Important: DRC drive units and corresponding mount-on parts must not protrude into
footways.
Working on live parts of DRC drive units is not permitted.
The drive is operated as a generator due to the kinetic energy of the system/machine.
Secure the output shaft against rotation before opening the wiring compartment.
Electrical installation must be carried out in compliance with pertinent regulations (e.g.
cable cross sections, fusing, protective conductor connection). For any additional information, refer to the applicable documentation.
You find notes on EMC-compliant installation, such as shielding, grounding, arrangement of filters and routing of lines, in the documentation of the DRC drive units. The
manufacturer of the system or machine is responsible for maintaining the limits established by EMC legislation.
Protective measures and protection devices must comply with the regulations in force
(e.g. EN 60204-1 or EN 61800-5-1).
2.8Safe disconnection
DRC drive units meet all requirements for safe disconnection of power and electronics
connections in accordance with EN 61800-5-1. All connected circuits must also satisfy
the requirements for safe disconnection to ensure reliable isolation.
10
Operating Instructions – Electronic Motor DRC.-..-SNI
2.9Operation
Safety Notes
Operation
Systems with integrated DRC drive units must be equipped with additional monitoring
and protection devices according to the applicable safety guidelines, such as the law
governing technical equipment, accident prevention regulations, etc. Additional protective measures may be necessary for applications with increased potential risk. Changes
to DRC drive units using the operating software are permitted.
Do not touch live components and power connections immediately after separation of
the DRC drive units from the supply voltage because some capacitors might still be
charged. Wait at least for 10 minutes after the supply voltage has been switched off.
The connection boxes must be closed and screwed on before the supply voltages are
connected to DRC drive units.
The unit may still be live and connected to the power supply even if the operation LEDs
and other display elements are no longer illuminated.
Mechanical blocking or internal safety functions of the unit can cause a motor standstill.
Eliminating the cause of the problem or performing a reset may result in the drive restarting automatically. If, for safety reasons, this is not permitted for the driven machine,
disconnect the unit from the supply system before correcting the error.
Caution: Danger of burns: The surface temperatures of DRC drive units can be more
than 60 °C during operation.
2
Operating Instructions – Electronic Motor DRC.-..-SNI
11
3
3Unit Structure
3.1DRC drive unit
Unit Structure
DRC drive unit
The following figure depicts drive units consisting of DRC1/DRC2 electronic motor and
R gear unit:
R..DRC1-...
[1]
[2]
[3]
[1]
[2]
R..DRC2-...
[3]
12
9007203299592075
[1] Electronics cover
[2] DRC electronic motor with connection unit
[3] Gear unit (in the figure: R gear unit)
Operating Instructions – Electronic Motor DRC.-..-SNI
3.2Cable entry positions
RUN
NET
DRIVE
3
X
2
The DRC electronic motor generally comes equipped with the following cable entries1):
•Position X + 2 + 3
– X: 2 x M25 x 1.5 + 2 x M16 x 1.5
– 2: 2 x M25 x 1.5 + 2 x M16 x 1.5
– 3: 2 x M25 x 1.5 + 2 x M16 x 1.5
Unit Structure
Cable entry positions
3
9007203301611787
1) 1 x M16 x 1.5 reserved for pressure compensation fitting (only in conjunction with ASEPTIC/ASEPTIC
variants as well as brakemotors operated at ambient temperatures of < 20 °C)
Operating Instructions – Electronic Motor DRC.-..-SNI
plus
13
3
[1]
[2]
76646 Bruchsal/Germany
kgAMB1845 494 1.50°C
M
A
M
BR
Ma
pk
Nm
IM
Nm
Nm
i
kW
Iso.Kl.M.L.Hz 50-60 VA
nR
r/minIP
eff%
26.000
85...0.04
TENV
87,1 IE4
1.04
156
-20...40Made in Germany
M1CLP 220 Miner.Öl/0.65 l
1/2000
23.5962
155
0.55 S1
(F)
380...500
65
3~IEC61800
RF47 DRC1-005-SNI-A-ECR/IV
01.1751709009.0001.11
Inverter duty VPWM
Unit Structure
Example nameplate and type designation of drive units
3.3Example nameplate and type designation of drive units
3.3.1Nameplate
The following figure gives an example of a DRC nameplate. For the structure of the type
designation, refer to chapter "Type designation".
[1] Unique serial number
[2] The bar code on the nameplate (code 39) according to ISO/IEC 16388 represents the unique
serial number (with a period as separator).
4762054411
3.3.2Type designation
The following table shows the type designation of the DRC drive unit:
The following figure shows the DIP switches S1 to S3 of the GIO13B application option:
18014401245670283
[1] Nameplate
18
Operating Instructions – Electronic Motor DRC.-..-SNI
Unit Structure
[1]
[3]
[2][1]
[3]
[2]
Example nameplate and type designation of electronics
3.6Example nameplate and type designation of electronics
3.6.1Nameplate
The following figure gives an example of a DRC nameplate. For the structure of the type
designation, refer to chapter "Type designation".
[1] Nameplate of connection unit
[2] Nameplate of application option
[3] Nameplate of electronics cover
3
4766392075
3.6.2Type designation electronics cover
The following table shows the type designation of the electronics cover:
D R C 1–5 0 3–SNI–A – 00 – A
Electronics cover variant
0= Without application slot
A= With application slot
Variant
00= Standard
DRC version
DRC installation technology
SNI= S
Connection type
3= 3-phase (AC)
Supply voltage
50= AC 380 – 500 V
Size
1
2
Product line
DRC = Electronic motor
ingle Line Network Installation
==DRC 1
DRC 2
Operating Instructions – Electronic Motor DRC.-..-SNI
19
3
Unit Structure
Example nameplate and type designation of electronics
3.6.3Type designation of connection unit
The following table shows the type designation of the connection unit:
D R C 1–5 0 3–SNI–A
3.6.4Type designation of application options
The following table shows the type designation for the available application options:
DRC version
DRC installation technology
SNI= Single Line Network Installation
Connection type
3= 3-phase (AC)
Supply voltage
50= AC 380 – 500 V
Size
1
==DRC 1
2
Product line
DRC = Electronic motor
DRC 2
G IO 1 2 B
Version
Variant
2= 4 digital inputs + 2 digital outputs
3 = 4 digital inputs
(2 inputs can be used as primary frequency input)
+ 1 digital output
+ 1 analog input
+ 1 analog output
Version
Functionality
IO = Digital inputs/outputs
Product line
G = Option for MOVIGEAR
®
/ DRC
20
Operating Instructions – Electronic Motor DRC.-..-SNI
Unit Structure
MOVIGEAR
®
B
SNI
A
B
[B 2]
[B 1]
Y
X
X
Y
[A3]
[A3]
[A2]
[A1]
[A7]
[A6]
[A5]
DRC drive units in ASEPTIC / ASEPTICplus design
3
3.7DRC drive units in ASEPTIC / ASEPTIC
NOTICE
Loss of degree of protection IP66 and incompatibility with cleaning agents.
Possible damage to property.
•To achieve degree of protection IP66 and compatibility with cleaning agents, you
have to replace the plastic screw plugs delivered as standard by suitable screw
fittings made of stainless steel.
The following picture shows the additional characteristics of DRC drive units in
ASEPTIC / ASEPTIC
plus
design:
plus
design
DRC
NET
RUN
DRIVE
All illustrations with ASEPTIC / ASEPTIC
tion) in this publication
plus
design are displayed with a shading (= HP200 surface protec-
4766218123
Operating Instructions – Electronic Motor DRC.-..-SNI
21
3
Unit Structure
DRC drive units in ASEPTIC / ASEPTICplus design
AScope of delivery
[A1] Mounting screws for cover made of stainless steel
[A2] Surface protection OS2 to OS4 for ASEPTIC design / OS4 for ASEPTIC
plus
design, see chapter
"Technical data and dimension sheets"
[A3] The delivered plastic screw plugs must be replaced by suitable screw plugs made of stainless
steel.
[A5] Pre-installed pressure compensation fitting (M16) with mounting positions M5, M6
[A6] Pre-installed pressure compensation fitting (M16) with mounting position M1, M2, M4, M4
Optional plug connectors (see chapter "Electrical installation") are available in connection with the
ASEPTIC / ASEPTIC
plus
version.
[A7] Features of gear units in ASEPTIC design
– Surface protection finish OS2 to OS4
Features of gear units in ASEPTIC
plus
design
– Available for gear units with solid shaft, hollow shaft with key or TorqLOC for the following gear
unit sizes: R27-87, F27-87, K37-87 and W37
– Gear unit output shaft including all retaining parts on the output shaft, such as screws, keys,
shrink disk, etc., are made of stainless steel
– If technically possible, the oil seals on the output are configured as double oil seals made from
FKM (Viton
®
)
– The breather valve of the gear units is made from stainless steel
– Surface protection finish OS4 for compatibility with common cleaning agents and disinfectants
– All surface recesses sprayed with elastic rubber compound
– All gear unit options can be selected
– All mounting positions M1 to M6 are available
BRequired screw fittings
[B1]Screw plugs made of stainless steel
[B2]Cable glands made of stainless steel
1)
1)
The required screw fittings can be ordered from SEW-EURODRIVE. For an overview, refer to chapter
"Technical Data / Optional metal screw fittings".
1) Make sure to select plug seals that are compatible with the cleaning agents used
22
Operating Instructions – Electronic Motor DRC.-..-SNI
4Mechanical Installation
4.1Installation notes
INFORMATION
Adhere to the safety notes during installation.
WARNING
Improper installation/disassembly of DRC drive units and mount-on components.
Risk of injury.
•Adhere to the notes about installation and disassembly.
•Before releasing shaft connections, make sure that there are no active torsional
moments present (tensions within the system).
WARNING
Risk of injury if the drive starts up unintentionally and danger of electrical voltage.
Mechanical Installation
Installation notes
4
Dangerous voltages may still be present for up to 10 minutes after disconnection from
the power supply.
Severe or fatal injuries.
•Disconnect the DRC drive unit from the power supply before you start working on
the unit and secure it against unintentional reconnection to the power supply.
•Secure the output shaft against rotation.
•Wait for at least 10 minutes before removing the electronics cover.
4.2Required tools and resources
•Set of wrenches
•Torque wrench
•Mounting device
•Compensation elements (shims and spacing rings), if necessary
•Mounting materials for output components
•Lubricant (e.g. NOCO
•Standard parts are not included in the delivery
4.2.1Installation tolerances for shaft ends
The following table shows the permitted tolerances of shaft ends and flanges of the
DRC motor.
®
Fluid)
Shaft endFlanges
Diameter tolerance according to EN 50347
•ISO j6 with Ø ≤ 26 mm
•Center bore in accordance with DIN 332,
shape DR..
Operating Instructions – Electronic Motor DRC.-..-SNI
Centering shoulder tolerance in accordance
with EN 50347
•ISO j6 with Ø ≤ 250 mm
23
4
Mechanical Installation
Installation requirements
4.3Installation requirements
Check that the following conditions have been met:
•The entries on the nameplate of the DRC unit match the voltage supply system.
•The drive is undamaged (no damage caused by transportation or storage)
•Ambient temperature according to the operating instructions, nameplate and
lubricant table in chapter "Technical data and dimension sheets / Lubricants".
•The drive must not be assembled in the following ambient conditions:
– Potentially-explosive atmosphere
– Oils
–Acids
– Gases
– Vapors
– Radiation
•For special designs: The drive is designed in accordance with the actual ambient
conditions.
•You must clean the output shafts and flange surfaces thoroughly to ensure they are
free of anti-corrosion agents, contamination or similar. Use a commercially available
solvent. Do not expose the sealing lips of the oil seals to the solvent – damage to the
material.
•When the drive is installed in abrasive ambient conditions, protect the output end oil
seals against wear.
24
Operating Instructions – Electronic Motor DRC.-..-SNI
4.4Setting up the drive unit
4.4.1Notes
•Only install the DRC drive unit on a level, low-vibration, and torsionally rigid support
structure.
•Observe the mounting position specified on the motor nameplate.
•Thoroughly remove any anti-corrosion agent from the shaft end. Use a commercially
available solvent. Do not allow the solvent to penetrate the bearings and shaft seals
– this could damage the material.
•Align the motor carefully to avoid placing any unacceptable strain on the motor
shafts. Observe the permitted overhung and axial loads specified in the "DRC Gearmotors" catalog.
•Do not jolt or hammer the shaft end.
•Ensure that cooling air supply is unobstructed and that air discharged by other units
does not influence cooling.
•Balance components that were subsequently mounted to the shaft with a half key
(output shafts are balanced with a half key).
•Use suitable cable glands for the supply leads (use reducing adapters if necessary).
•Seal the cable entry properly.
Mechanical Installation
Setting up the drive unit
4
•Thoroughly clean the sealing surfaces of the DRC cover before re-assembly.
•If the corrosion protection coating is damaged, restore the coating.
•Check whether the degree of protection specified in the operating instructions and
on the nameplate is permitted in the ambient conditions on site.
Operating Instructions – Electronic Motor DRC.-..-SNI
25
4
NETRUNDRIVE
MOVIGEAR
®
B
SNI
NET RUN DRIVE
MOVIGEAR
®
B
SNI
4.4.2Electronics cover
Mechanical Installation
Setting up the drive unit
WARNING
Burns caused by hot surfaces.
Severe injuries.
•Let the units cool down before touching them.
NOTICE
Loss of the guaranteed degree of protection.
Possible damage to property.
•When the DRC electronics cover is removed from the connection box, you have to
protect it from humidity, dust or foreign particles.
•Check to see that the DRC electronics cover was mounted properly.
Installing the
electronics cover
Min. installation
clearance
•Use only electronics covers that match the size.
•Be careful not to tilt the electronics cover when placing it on the connection box.
4813126155
Note the minimum installation clearance (see following figure) required to remove the
DRC electronics cover. For detailed dimension drawings, see chapter "Technical data
and dimension sheets".
100
26
9007201604838411
Operating Instructions – Electronic Motor DRC.-..-SNI
Mechanical Installation
Setting up the drive unit
4
Min. installation
clearance of
application options
4.4.3Installation in damp locations or in the open
4.4.4Painting drive units
Note the minimum installation clearance (see following figure) required to install and
remove the application options.
200
Drives are supplied in corrosion-resistant versions for use in damp areas or in the open.
Repair any damage to the paint work if necessary.
Observe the notes in chapter "Drive units with optional ASEPTIC / ASEPTIC
NOTICE
Breather valves and oil seals may be damaged during painting or re-painting.
9007201604871563
plus
design".
Potential damage to property.
•Clean the surface of the drive unit and make sure it is free from grease.
•Thoroughly cover the breather valves and sealing lip of the oil seals with strips prior
to painting.
•Remove the strips after painting.
Operating Instructions – Electronic Motor DRC.-..-SNI
27
4
4 x
NET
RUN
DRIVE
Mechanical Installation
Application options
4.5Application options
WARNING
Burns caused by hot surfaces.
Severe injuries.
•Let the units cool down before touching them.
4.5.1Removing the application cover
DRC drive units with application slot in the electronics cover are delivered with an application cover as standard.
You have to remove the application cover in order to install an application option:
1. Loosen the 4 retaining screws.
2. Remove the application cover.
18014400859806987
NET
RUN
DRIVE
18014400859827339
28
Operating Instructions – Electronic Motor DRC.-..-SNI
4.5.2Installing the application options
NET
RUN
DRIVE
X4
X3
X2
X1
NOTICE
Loss of the guaranteed degree of protection.
Possible damage to property.
•In disassembled condition, you have to protect the GIO13 application option from
moisture, dust or foreign particles as there are openings for DIP switches.
•Make sure that the application cover is mounted properly.
1. You have to remove the application cover or, depending on the design, the paint
protector in order to install an application option:
2. Insert the option into the application slot.
Mechanical Installation
Application options
4
18014400859846539
3. Secure the option with the 4 retaining screws. The permitted tightening torque for the
retaining screws is 1.4 - 1.6 Nm.
4 x
NET
RUN
X4
DRIVE
X3
X2
X1
18014400859865739
Operating Instructions – Electronic Motor DRC.-..-SNI
29
4
Mechanical Installation
Tightening torques
4.6Tightening torques
4.6.1Blanking plugs
WARNING
Burns caused by hot surfaces.
Severe injuries.
•Let the units cool down before touching them.
Tighten the blanking plugs included in the delivery
Example The following figure shows an example.
with 2.5 Nm:
30
9007203306591371
Operating Instructions – Electronic Motor DRC.-..-SNI
4.6.2Cable glands
Tightening torquesTighten the EMC cable glands optionally
EMC cable glands (stainless steel)1821 636 610 pcsM16 x 1.5 3.5 Nm to 4.5 Nm
1820 478 310 pcsM16 x 1.5 3.5 Nm to 4.5 Nm
1820 480 510 pcsM25 x 1.5 6.0 Nm to 7.5 Nm
1821 638 210 pcsM25 x 1.5 6.0 Nm to 7.5 Nm
The cable retention in the cable gland must withstand the following removal force of the
cable from the cable gland:
•Cable with outer diameter from 4 to 8 mm: Min. 24 N
•Cable with outer diameter from 8 to 11 mm: Min. 34 N
•Cable with outer diameter from 11 to 16 mm: Min. 44 N
Example The following figure shows an example.
Mechanical Installation
Tightening torques
supplied by SEW-EURODRIVE to the following
4
Operating Instructions – Electronic Motor DRC.-..-SNI
9007203306596107
31
4
1
2
4
3
4
2
3
1
Mechanical Installation
Tightening torques
4.6.3DRC electronics cover
Tighten the screws on the DRC cover using 6.0 Nm working diagonally across.
9007203306627211
32
Operating Instructions – Electronic Motor DRC.-..-SNI
Mechanical Installation
Drive units with optional ASEPTIC / ASEPTICplus design
4
4.7Drive units with optional ASEPTIC / ASEPTIC
4.7.1Installation notes
NOTICE
Loss of degree of protection IP66 and incompatibility with cleaning agents.
Possible damage to property.
•To achieve degree of protection IP66 and compatibility with cleaning agents, you
have to replace the plastic screw plugs delivered as standard by suitable screw
fittings made of stainless steel.
Adhere to the following additional notes for DRC drive units in optional ASEPTIC /
ASEPTIC
•Make sure to prevent moisture and dirt from entering the unit during installation.
•After electrical installation, make sure that the sealing and sealing surfaces are clean
•When performing maintenance work, check the condition of the gaskets as well as
•Make sure to install the cables with a drip loop.
•Use only stainless steel cable glands and connection glands offered by SEW-
plus
design:
during assembly.
the tightening torques of the screw fittings. If damaged: Consult SEW-EURODRIVE.
EURODRIVE, see chapter "Technical data and dimension sheets".
plus
design
•You must seal unused cable bushings and plug connectors with suitable screw
plugs, see chapter "Technical data and dimension sheets".
Operating Instructions – Electronic Motor DRC.-..-SNI
33
4
MOVIGEAR
®
B
SNI
[1]
[3]
[2]
Mechanical Installation
Drive units with optional ASEPTIC / ASEPTICplus design
Example The following figure gives an example of a cable entry with drip loop and the replace-
ment of the plastic screw plugs supplied as standard with suitable stainless steel screw
fittings.
4768361227
[1] The delivered plastic screw plugs must be replaced by suitable screw plugs made of stainless steel.
[2] Required stainless steel screw plugs
(see chapter "Technical data and dimension sheets")
[3] Required stainless steel cable glands
(see chapter "Technical data and dimension sheets")
34
Operating Instructions – Electronic Motor DRC.-..-SNI
Mechanical Installation
3
2
NET
RUN
DRIVE
M3
x
3
2
MOVIGEAR
®
B
SNI
NET
RUN
DRIVE
MOVIGEAR
®
B
SNI
M1
M2
M4
M5
M6
2
3
2
3
2
x
2
3
x
3
x
x
x
Drive units with optional ASEPTIC / ASEPTICplus design
4
Mounting positions DRC drive units in optional ASEPTIC / ASEPTIC
plus
design are delivered with pressure
compensation and breather valve installed according to the mounting position.
plus
This is why DRC drive units in optional ASEPTIC / ASEPTIC
design must only be
used in the mounting position specified in the order.
•Mounting position
–M1
–M2
–M3
–M4
–M5
–M6
•Cable entries
– Position 3 (not permitted for M4 mounting position)
– Position 2 (not permitted for M5 mounting position)
– Position X (not permitted for M6 mounting position)
Mounting positionsThe following figure shows the position of the DRC drive unit when installed in mounting
positions M1 to M6:
4768583819
Operating Instructions – Electronic Motor DRC.-..-SNI
35
4
Mechanical Installation
Drive units with optional ASEPTIC / ASEPTICplus design
4.7.2Tightening torques when using optional ASEPTIC
plus
design
WARNING
Burns caused by hot surfaces.
Severe injuries.
•Let the units cool down before touching them.
Blanking plugsTighten the blanking plugs optionally
with 2.5 Nm:
Type of screw fittingContentSizePart number
Screw plugs
hexagon
(made of stainless steel)
Example The following figure shows an example. The number and position of cable entries
depends on the variant you have ordered.
included in the delivery by SEW-EURODRIVE
10 pcsM16 x 1.51 824 734 2
10 pcsM25 x 1.51 824 735 0
B
®
SNI
MOVIGEAR
36
4768590091
Operating Instructions – Electronic Motor DRC.-..-SNI
Mechanical Installation
Drive units with optional ASEPTIC / ASEPTICplus design
4
DRC electronics
cover
Proceed as follows when installing the DRC electronics cover:
B
®
SNI
MOVIGEAR
3
2
4
3
1
4
1
2
4768799755
Steps1. Fix the DRC cover in position on the connection box with a tightening torque of 2 Nm
2. Tighten screws diagonally with 4 Nm.
3. Tighten screws with 6 Nm.
Operating Instructions – Electronic Motor DRC.-..-SNI
37
4
MOVIGEAR
®
B
SNI
Mechanical Installation
Drive units with optional ASEPTIC / ASEPTICplus design
EMC cable glandsTighten the EMC cable glands optionally included in the delivery by SEW-EURODRIVE
EMC cable glands (stainless steel)1821 636 610 pcsM16 x 1.5 3.5 Nm to 4.5 Nm
1820 478 310 pcsM16 x 1.5 3.5 Nm to 4.5 Nm
1820 480 510 pcsM25 x 1.5 6.0 Nm to 7.5 Nm
1821 638 210 pcsM25 x 1.5 6.0 Nm to 7.5 Nm
The cable retention in the cable gland must withstand the following removal force of the
cable from the cable gland:
•Cable with outer diameter > 10 mm: ≥ 160 N
•Cable with outer diameter < 10 mm: = 100 N
Example The following figure shows an example. The number and position of cable entries
depends on the variant you have ordered.
38
4769055499
Operating Instructions – Electronic Motor DRC.-..-SNI
Electrical Installation
Installation planning considering EMC aspects
5Electrical Installation
INFORMATION
Adhere to the safety notes during installation.
5.1Installation planning considering EMC aspects
5.1.1Notes on arranging and routing installation components
Successful installation of decentralized drives depends on selecting the correct cables,
providing correct grounding and a functioning equipotential bonding.
Always apply the relevant standards.
Note the following:
5.1.2EMC-compliant installation
5
INFORMATION
This drive system is not designed for operation on a public low voltage supply system
that supplies residential areas.
This is a product with restricted availability in accordance with IEC 61800-3. This
product may cause EMC interference. In this case, it is recommended for the operator
to take suitable measures.
For detailed information on EMC compliant installation, refer to the publication
"Electromagnetic Compatibility in Drive Engineering" from SEW-EURODRIVE.
With respect to the EMC regulation, frequency inverters cannot be operated as standalone units. Regarding EMC, they can only be evaluated when they are integrated in a
drive system. Conformity is declared for a described, CE-typical drive system. These
operating instructions contain further information.
5.1.3Cable selection, routing and shielding
WARNING
Electric shock caused by faulty installation.
Severe or fatal injuries.
•Take the utmost care when installing the units.
•Observe the connection examples.
For more information on cable selection, routing and shielding, refer to chapter "Cable
routing and shielding".
Operating Instructions – Electronic Motor DRC.-..-SNI
39
5
NET
RUN
DRIVE
[1]
[3] [2]
[4]
Electrical Installation
Installation planning considering EMC aspects
5.1.4Equipotential bonding
Example
Regardless of the protective earth connection, it is essential that low-impedance, HFcapable equipotential bonding is provided (see also EN 60204-1 or DIN VDE 0100-
540):
•Establish a connection over a wide surface area between the DRC drive unit and the
mounting rail.
•To do so, use a ground strap (HF litz wire), for example, to connect the DRC drive
unit and the plant's grounding point.
4867596683
[1] Conductive connection over a large area between drive unit and mounting plate
[2] PE conductor in the supply cable
[3] 2nd PE conductor via separate terminals
[4] EMC-compliant equipotential bonding, for example using a ground strap (HF litz wire)
•Do not use the cable shield of data lines for equipotential bonding.
40
Operating Instructions – Electronic Motor DRC.-..-SNI
5.2Installation instructions
5.2.1Connecting power supply cables
•The rated voltage and rated frequency of the DRC drive unit must correspond with
the data of the power supply system.
Electrical Installation
Installation instructions
5
•Cable cross section: According to input current I
at rated power (see chapter
line
"Technical data and dimension sheets").
•Install line fuses at the beginning of the power supply cable behind the supply bus
junction. Select the fuse size according to the cable cross section.
•Use only copper cables with a minimum temperature range of 85 °C as connection
cable.
•DRC drive units are intended to be operated on voltage supply systems with
grounded star point (TN and TT systems).
5.2.2Permitted cable cross section of terminals
Line terminals Adhere to the permitted cable cross sections for installation:
Line terminals X2without conductor end sleevewith conductor end sleeve (with
2
External braking
resistor terminals
Connection cross section
2
)
(mm
Connection cross section
(AWG)
Stripping length13 mm – 15 mm
Current carrying capacity24 A (max. continuous current)
0.5 mm
AWG20 – AWG10
Adhere to the permitted cable cross sections for installation:
External braking resistor
terminals X5
Connection cross section
2
)
(mm
Connection cross section
(AWG)
Stripping length8 mm – 9 mm
without conductor end sleevewith conductor end sleeve
0.08 mm
2
– 4.0 mm
AWG28 – AWG12AWG 23 – AWG 14
2
– 6 mm
or without insulating shroud)
2
(with or without insulating
shroud)
0.25 mm2 – 2.5 mm
2
Control terminals Adhere to the permitted cable cross sections for installation:
Control terminals X7without conductor
Connection cross section
2
)
(mm
Connection cross section
(AWG)
Stripping length5 mm – 6 mm
Current carrying capacity3.5 A max. continuous current
Operating Instructions – Electronic Motor DRC.-..-SNI
end sleeve
0.08 mm
AWG 28 – AWG 14AWG 23 – AWG 16
with conductor end
sleeve (without
insulating shroud)
2
– 2.5 mm
2
with conductor end
sleeve (with insulat-
ing shroud)
0.25 mm2 – 1.5 mm
2
41
5
1.
2.
2.
1.
5.2.3Terminal activation for the braking resistor
5.2.4Line terminal actuation
Electrical Installation
Installation instructions
Adhere to the following sequence when activating the terminals for the braking resistor:
Terminals for the braking resistor (the following figure shows a schematic illustration)
Adhere to the following sequence when actuating the line terminals:
4055861259
Line terminals (the following figure shows a schematic illustration)
5.2.5Control terminal actuation
Adhere to the following sequence when actuating the control terminals:
Control terminals (the following figure shows a schematic illustration)
9007203310525451
2.
1.
42
3.
9007203462751499
Operating Instructions – Electronic Motor DRC.-..-SNI
Electrical Installation
Installation instructions
5.2.6Line protection and residual current device (RCD or RCM)
WARNING
Electric shock due to incorrect earth-leakage circuit breaker type.
Severe or fatal injuries.
•The connected DRC drive units can cause direct current in the protective earth conductor. In cases where an earth-leakage circuit breaker is used for protection
against direct or indirect contact, only a type B earth-leakage circuit breaker is permitted on the power supply side of DRC drive units.
•Install the fuses at the beginning of the power supply cables behind the supply bus
junction.
•A conventional residual current device is not permitted. Residual current devices
sensitive to universal current (trip current 300 mA) are permitted. During normal
operation of DRC, earth-leakage currents of > 3.5 mA can occur.
•SEW-EURODRIVE recommends to not use residual current devices. However, if a
residual current device is stipulated for direct or indirect protection against contact,
observe the above note in accordance with EN 61800-5-1.
5
5.2.7Line contactor
NOTICE
Damage to the DRC inverter due to jogging of the line contactor.
Damage to the DRC inverter.
•Do not use the line contactor (see wiring diagram) for jog mode but only for
•Observe a minimum switch-off time of 2 s for the line contactor.
•Use only a contactor of utilization category AC3 (EN 60947-4-1) as a line contactor.
switching the inverter on and off. For jog mode, use the control commands.
Operating Instructions – Electronic Motor DRC.-..-SNI
43
5
[1]
M5
2.5 mm²
M5
Electrical Installation
Installation instructions
5.2.8Notes on PE connection
Electric shock due to incorrect connection of PE.
Severe or fatal injuries.
•The permitted tightening torque for the screw is 2.0 – 2.4 Nm (18 – 21 lb.in).
•Observe the following notes regarding PE connection.
WARNING
Prohibited assemblyRecommendation:
Assembly with forked cable lug
Permitted for all cross sections
2377711243
[1] Forked cable lug suitable for M5 PE screws
2377688075
Assembly with solid connecting wire
Permitted for cross sections up to
max. 2.5 mm
2
2377672587
44
Earth-leakage currents ≥ 3.5 mA may occur during normal operation. To meet the
requirements of EN 61800-5-1, observe the following notes:
•The protective earth (PE) connection must meet the requirements for plants with high
earth-leakage currents.
•This usually means
– installing a PE connection cable with a minimum cross section of 10 mm
2
– or installing a second PE connection cable in parallel with the original PE connec-
tion.
Operating Instructions – Electronic Motor DRC.-..-SNI
5.2.9Installation above 1000 m asl
Electrical Installation
Installation instructions
5
You can install DRC drive units at altitudes from 1000 m to a maximum of 4000 m above
sea level
•The nominal continuous power is reduced due to the reduced cooling above 1000 m
(see chapter "Technical data and dimension sheets").
•Above 2000 m above sea level, the air and creeping distances are only sufficient for
overvoltage class 2. If the installation requires overvoltage class 3, you will have to
install additional external overvoltage protection to limit overvoltage peaks to 2.5 kV
phase-to-phase and phase-to-ground.
•If safe electrical disconnection is required, it must be implemented outside the unit
for altitudes of 2000 m above sea level and higher (safe electrical disconnection in
accordance with EN 61800-5-1).
•At installation altitudes between 2000 m and 4000 m above sea level, the permitted
rated power supply voltages are reduced as follows:
– By 6 V per 100 m
5.2.10 Protection devices
•DRC drive units are equipped with integrated protection devices against overload.
•Cable protection must be implemented using external overload devices.
•Observe the relevant standards concerning cable cross section, voltage drop and
installation type.
1)
provided the following conditions are met:
INFORMATION
It is essential that you adhere to the installation instructions in the documentation of
the controller you use.
1) The maximum altitude is limited by the reduced electric strength due to the lower air density.
Operating Instructions – Electronic Motor DRC.-..-SNI
45
5
5.2.11 UL-compliant installation (in preparation)
Power terminalsObserve the following notes for UL-compliant installation:
Electrical Installation
Installation instructions
•Use only copper cables with a rated thermal value of 75 °C.
•DRC uses cage clamp terminals
Short circuit
current rating
Branch circuit
protection
Motor overload
protection
Ambient
temperature
Wiring diagramsFor wiring diagrams, refer to chapter "Electrical installation".
Suitable for use in current circuits with a maximum short circuit current of 200 000 A
•DRC, the max. voltage is limited to 500 V.
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
The table below list the permitted maximum fusing.
SeriesMax. fuse rating
DRC40 A / 600 V
DRC is provided with motor overload protection with a trip current adjusted to 150% of
the rated motor current.
DRC is suitable for an ambient temperature of 40 °C, max. 60 °C with derated output
current. To determine the output current rating at temperatures above 40 °C, the output
current should be derated by 3.0% per K between 40 °C and 60 °C.
eff
:
46
Operating Instructions – Electronic Motor DRC.-..-SNI
5.3Installation topology (example)
DRC...SNI
Single Line Installation [2]
[1]
DRC...SNI
MOVIGEAR
®
...SNI
Communication
Power
Power
Controller - SNI
Controller / PLC
Control cabinet level
Field level
Line filter
INFORMATION
The following figure shows the basic installation topology with DRC-SNI.
It is essential that you observe the installation instructions in the documentation of the
controller you use.
Electrical Installation
Installation topology (example)
5
[1]
A maximum of 10 SNI actuators in total
[2]
Operating Instructions – Electronic Motor DRC.-..-SNI
Permitted cable length between controller and last actuator max. 100 m
4727073035
47
5
PE
PEPE
PE
12 3
11 1213
1
2
Braking resistor
terminals
Line terminals
X5
X2
12345
11 12 13 14 15
Control terminals
X7
12345
11 12 13 14 15
Electrical Installation
Terminal assignment
5.4Terminal assignment
Electric shock due to regenerative operation when the shaft turns.
Severe or fatal injuries.
•Secure the output shaft against rotation when the electronics cover is removed.
The following figure shows the terminal assignment of DRC-SNI:
WARNING
4729233035
Assignment
Ter min alNo.Name MarkingFunction (permitted tightening torque)
X2 line
terminals
1L1 BrownActuator supply phase L1 with SNI communication – IN
2L2 BlackActuator supply phase L2 with SNI communication – IN
3L3 GrayActuator supply phase L3 with SNI communication – IN
11L 1BrownActuator supply phase L1 with SNI communication – OUT
12L2BlackActuator supply phase L2 with SNI communication – OUT
13L3GrayActuator supply phase L3 with SNI communication – OUT
–PE–Protective earth connection (2.0 to 3.3 Nm )
The communication method requires that you must observe the order of the line
phases L1, L2, L3 between SNI controller and DRC-SNI 1 to 10.
48
Operating Instructions – Electronic Motor DRC.-..-SNI
Electrical Installation
Terminal assignment
Assignment
Ter min alNo. Name MarkingFunction
X7 control
terminals
1STO + YellowInput STO +
2STO −YellowInput STO –
3+24 V_SEN –Input for DC 24 V voltage supply for sensors
The sensor supply voltage is then available at the
optional plug connector
40V24_SEN–Input for 0V24 reference potential for sensors
524V_O–DC 24 V output
11STO +YellowOutput STO + (to loop through)
12STO −YellowOutput STO – (to loop through)
13+24V_SEN–Looping of the DC 24 V voltage supply for sensors
140V24_SEN–Looping of the 0V24 reference potential for sensors
150V24_O–0V24 reference potential output
5
Operating Instructions – Electronic Motor DRC.-..-SNI
49
5
Electrical Installation
Connecting DRC drive units
5.5Connecting DRC drive units
WARNING
No safe disconnection of the DRC drive unit.
Severe or fatal injuries.
•Do not use the 24 V output (terminals 5, 15) for safety-related applications with
DRC drive units.
•You may only jumper the STO input with 24 V when the DRC drive unit need not
fulfill any safety function.
[1] SNI controller connection
[7]
L1 IN1L2 IN
X2
Line terminals [2]
Control
terminals [2]
X7
2 STO IN
1 STO + IN
11 STO + OUT
L3 IN
L1 OUT11L2 OUT12
2
3
[3][4] [5]
5 24V_O
12 STO OUT
L3 OUT
13
15 0V24_O
13 + 24V_SEN
3 + 24V_SEN
BW
BW
1
2
X5
Braking resistor
terminals [2]
[6] Connection the
for sensor inputs
4 0V 24V_SEN
14 0V 24V_SEN
DRC.-...-SNI
optional
plug connector
X5132
4729927435
50
[1] See documentation of the SNI controller
[2] See chapter "Terminal assignment"
[3] DC 24 V output
[4] Sensor supply input, the sensor supply voltage is then available at the optional plug
connector for sensor inputs
[5] Looping of the sensor supply input
[6] See chapter "Optional plug connector assignment"
[7] Braking resistor connection
Operating Instructions – Electronic Motor DRC.-..-SNI
5.6Cable routing and shielding
A1:
A2:
B:
2x
2x
3x
3x
M4x10
(2.0 Nm)
M4x10
(2.0 Nm)
20mm
20mm
3x
2x
5.6.1Installation material kit (part no. 1 824 826 8)
1)
Each DRC drive unit
material for cable shielding:
•A1: Installation material for line and hybrid cables:
2 x shield clamps and screws
(outer shield).
•A2: Conductive film:
2 x pieces of conductive film to wind around the braid shield. Use the conductive film
if required.
•B: Installation material for control cables and data cables:
3 x shield clamp with screw
(STO, CAN, binary signals).
is delivered with an accessory bag that contains installation
2)
Electrical Installation
Cable routing and shielding
2)
to connect the shield of line cables or hybrid cables
to connect the shield of control cables or data cables
5
INFORMATION
For some installation variants, you do not need all the parts of the accessory kit.
1) Exception: Not for plug connector variants
2) Self cutting, which is why the holes in the connection box do not have a thread
Operating Instructions – Electronic Motor DRC.-..-SNI
4071209995
51
5
5.6.2General installation options
Electrical Installation
Cable routing and shielding
The following figure shows the general installation options. The following chapters show
common examples and contain important notes on cable selection and routing.
4071462539
52
Operating Instructions – Electronic Motor DRC.-..-SNI
5.6.3Notes on cable routing and shielding
Note the following when routing and shielding the cables:
•Cable selection
– Only use cable types prescribed by SEW-EURODRIVE.
– It is essential that you observe chapter "Technical data and dimension sheets /
Specification of recommended connection cables for single line installation" in the
operating instructions.
– Always use metal cable glands due to their attenuation properties.
– Use shielded cables for the optional external braking resistor.
– The shield must have good EMC properties (high shield attenuation) and must not
be used for mechanical protection of the cable.
•Cable shielding – Control cables
– Connect the shields of the control cables to the metal housing of the unit using
the shield clamps of the installation material kit. To do so, strip off the cable
sheath around the shield connection surface.
– As an alternative, you can use optionally available EMC cable glands to connect
the shield of control cables, see chapter "EMC cable glands".
Electrical Installation
Cable routing and shielding
5
•Cable shield – external braking resistor
– Connect the cable shield of the cable for an external braking resistor to the metal
housing of the unit using the shield clamps of the installation material kit. To do
so, strip off the cable sheath around the shield connection surface.
•Cable shielding – Supply system cable (single line)
– Wind the conductive film included in the installation material kit around the braid
shield three times, if required.
– Connect the cable shields of the supply system cable (single line) to the metal
housing of the unit using the shield clamps of the installation material kit.
Operating Instructions – Electronic Motor DRC.-..-SNI
53
5
Single Line
(SNI)
STO
STO
External
braking
resistor
20mm
3x
Single Line (SNI)
STO
STO
External
braking resistor
20mm
3x
Recommended cable routing
Electrical Installation
Cable routing and shielding
Alternative cable routing
4731813899
54
Operating Instructions – Electronic Motor DRC.-..-SNI
4732273419
5.7EMC cable glands
5.7.1Cable shielding (alternative) – Control cables
As an alternative to using shield clamps for control cables (STO, binary signals), you can
use EMC cable glands, which are available as an option, to connect the shield.
Electrical Installation
EMC cable glands
5
3388566411
5.7.2Assembly of EMC cable glands
Fit the EMC cable glands supplied by SEW-EURODRIVE according to the following
figure:
[1]
[1] Important: Cut off the insulating foil, do not just fold it back.
Operating Instructions – Electronic Motor DRC.-..-SNI
2661188747
55
5
Electrical Installation
Prescribed power leads
5.8Prescribed power leads
The following table shows the available SNI supply system cables:
SNI supply system cable
Part no. 1 330 330 9 Cable reel 30 m
Cable reel 100 m
Cable reel 200 m
Open cable end
(bulk cable)
Part no. 1 330 550 6 Cable reel 30 m
Cable reel 100 m
Cable reel 200 m
Cable cross
section/cable type
2
2.5 mm
HELUKABEL
®
TOPFLEX
UV-2YSLCYK-J
TOPFLEX
UV-2YSLCYK-J
– EMV-
2
4 mm
HELUKABEL
®
– EMV-
Open cable end
(bulk cable)
56
Operating Instructions – Electronic Motor DRC.-..-SNI
5.9Plug connectors
The wiring diagrams of the plug connectors depict the contact end of the connection.
5.9.1Designation key
The designation of plug connectors is specified according to the following key:
X2012_
Electrical Installation
Plug connectors
Sequence number (optional)
In case of several plug connectors in one group
Group number (optional)
For several plug connectors with the same function
Typ e
Connection diagram of the plug connector within a function
Function
Function of a plug connector within a group
Group
1 = Power input
2 = Power output
3 = Encoder
4 = Bus
5 = Inputs and outputs
5
5.9.2Connection cables
Connection cables are not included in the scope of delivery.
You can order prefabricated cables from SEW-EURODRIVE. They are described in the
following sections. Specify the part number and length of the required cable in your
order.
The number and type of required connection cables depend on the design of the units
and the components to be connected. This is why not all cables in the list are actually
required.
The following figures show the various cable types:
CableLengthInstallation type
Ter minal
Fixed length
Variable length
Suitable for cable
carrier installation
Not suitable for
cable carrier
installation
INFORMATION
For detailed information about cable types, see chapter "Technical data and
dimension sheets".
Operating Instructions – Electronic Motor DRC.-..-SNI
57
5
[1]
X5502
X1241_1
X1241_1X1241_1
X1241_2
X1241_2
X1241_2
X5503
X5131X5131
X5131
[1]
X
2
3
Electrical Installation
Plug connectors
5.9.3Plug connector positions
The following figure shows possible plug connector positions. A difference is made
between plug connectors with selectable position and plug connectors with fixed
position:
Plug connectorColor Position Location
X5131: Digital inputs/outputs–As
X5502: STO – INOrangeFixed3 (left)
X5503: STO – OUTOrangeFixed3 (right)
X1241_1: AC 400 V connection with SNI
1)
X1241_2: AC 400 V connection with SNIRedAs
2)
[1] Pressure compensation
1) Plug connector X1241_1 is also available separately (i.e. without plug connector X1241_2).
2) Only in conjunction with the optional design for use in wet areas (with MOVIGEAR
(with DRC).
RedAs
–FixedDepends on mounting position
required
required
required
X, 2 or 3,
not together with X1241_1, X1241_2
X, 2 or 3, not together with X5131
X, 2 or 3, not together with X5131
®
) / ASEPTIC design
58
9007201923558283
Operating Instructions – Electronic Motor DRC.-..-SNI
Electrical Installation
[1]
5.9.4Restrictions in conjunction with pressure compensation
The position for STO plug connectors is occupied by the pressure compensation fitting
[1] when using the optional design for use in wet areas (with
MOVIGEAR
case, plug connectors for STO are not possible:
®
)/ASEPTIC
plus
design (with DRC) and M5, M6 mounting position. In this
Plug connectors
5
9007201700846347
Operating Instructions – Electronic Motor DRC.-..-SNI
59
5
5.9.5Plug connector variant
Electrical Installation
Plug connectors
NOTICE
Possible damage of the right-angle connector in case of rotation without mating
connector.
Irreparable damage to the thread, damage to the sealing surface.
•Do not use pliers to adjust the right-angle connector before connecting it.
NOTICE
Adjusting the right-angle connector too often can damage it.
Potential damage to property
•Adjust the plug connector only when installing and connecting the drive unit.
•Do not turn the plug connector regularly once it has been installed.
M23 plug connectors are available in the following variants:
•[1] "Straight" plug connector variant
•[2] "Right-angle" plug connector variant
Once the mating connector has been plugged in, the "right-angle" connector can be
adjusted without using additional tools.
60
Operating Instructions – Electronic Motor DRC.-..-SNI
Example
[2]
[1]
90 °
Electrical Installation
Plug connectors
5
9007203327550219
INFORMATION
Only cable outlet on the side is possible with plug connector position 3 and "rightangle" plug connector variant.
Operating Instructions – Electronic Motor DRC.-..-SNI
61
5
A
6
4
5
PE
B
C
D
SHLD
1
2
3
Electrical Installation
Assignment of optional plug connectors
5.10Assignment of optional plug connectors
WARNING
Electric shock when disconnecting or connecting voltage-carrying plug connectors.
Severe or fatal injuries
•Switch off the power supply voltage.
•Never plug or unplug plug connectors while they are energized.
5.10.1 X1241_1 and X1241_2: AC 400 V connection with SNI
The following table informs about this connection:
Function
AC 400 V connection for supplying the unit/for looping through
with Single Line Network Installation (SNI)
Connection type
M23, SEW insert, SpeedTec-capable, company: Intercontec, female, coding ring: Red, protected against
contact
Wiring diagram
2497125387
Assignment
No.NameFunction
AL1_SNIActuator supply phase L1 with SNI communication
BL2_SNIActuator supply phase L2 with SNI communication
CL3_SNIActuator supply phase L3 with SNI communication
Dn.c.Not connected
PEPEPE connection
1n.c.Not connected
2n.c.Not connected
3n.c.Not connected
4n.c.Not connected
5n.c.Not connected
6n.c.Not connected
7n.c.Not connected
8n.c.Not connected
9n.c.Not connected
10n.c.Not connected
SHLDn.c.Not connected
INFORMATION
The communication method requires that you must observe the order of the line
phases L1, L2, L3 between SNI controller and DRC SNI drive units 1 to 10.
62
Operating Instructions – Electronic Motor DRC.-..-SNI
Electrical Installation
Assignment of optional plug connectors
Connection cables The following table provides an overview of the cables available for this connection:
5
Connection cable
Part number 1 812 750 9
M23, coding ring:
Red
Part number 1 812 751 7
OpenM23, coding ring:
Part number 1 812 752 5
M23, coding ring:
Red
Part number 1 812 753 3
M23, coding ring:
M23, coding ring:
Red
Red
Red
Length/
installa-
tion type
Variable
Variable
Variable
Cable cross-
section/
cable type
2
2.5 mm
HELUKA-
BEL
EMV-UV-
2.5 mm
HELUKA-
BEL
EMV-UV-
2
4 mm
HELUKA-
BEL
EMV-UV-
®
2
®
®
TOPFLEX
2YSLCYK-J
TOPFLEX
2YSLCYK-J
TOPFLEX
2YSLCYK-J
Operat-
ing
voltage
AC 500 V
–
AC 500 V
–
AC 500 V
–
Connection of
cables with open
end
2
4 mm
Variable
OpenM23, coding ring:
Red
HELUKA-
BEL
TOPFLEX
EMV-UV-
2YSLCYK-J
®
–
AC 500 V
The following table shows the conductor assignment of the cable with the following part
number:
1 812 751 7 and 1 812 753 3
Signal nameColor coding
L1_SNIBrown
L2_SNIBlack
L3_SNIGray
PEGreen/yellow
Operating Instructions – Electronic Motor DRC.-..-SNI
63
5
9
1
2
7
6
5
11
12
3
4
8
10
Electrical Installation
Assignment of optional plug connectors
5.10.2 X5131: Digital inputs/outputs
The following table informs about this connection:
Function
Digital inputs/outputs for DRC MotionControl
Connection type
M23, P insert 12-pole, SpeedTec-capable, Intercontec, female, 0°-coded
Operating Instructions – Electronic Motor DRC.-..-SNI
65
5
5.10.3 X5502: STO – IN
Electrical Installation
Assignment of optional plug connectors
WARNING
No safe disconnection of the DRC drive unit.
Severe or fatal injuries.
•Do not use the 24 V output (pins 1 and 3) for safety-related applications with DRC
drive units.
•You may only jumper the STO input with 24 V when the DRC drive unit need not
fulfill any safety function.
The following table informs about this connection:
Function
Input for safe torque off (STO)
Connection type
M12, 5-pole, female, A-coded
Connection cables
Wiring diagram
1
4
Assignment
No.NameFunction
1+24V_ODC 24 V output
2STO −Input STO –
30V24_O0V24 reference potential
4STO +Input STO +
5res.Reserved
2
3
5
2264816267
INFORMATION
Use only shielded cables for this connection and only suitable plug connectors that
connect the shield with the unit in an HF-capable manner.
66
Operating Instructions – Electronic Motor DRC.-..-SNI
Electrical Installation
Assignment of optional plug connectors
The following table provides an overview of the cables available for this connection:
5
Connection cable
Part number 1 812 496 8
M12, 5-pole, A-codedM12, 5-pole,
A-coded
Part number 1 812 497 6
OpenM12, 5-pole,
A-coded
Part number 1 812 740 1
Length/
Installation
type
Variable
Variable
Operating
voltage
DC 60 V
DC 60 V
Connection of
cables with open
end
Variable
DC 60 V
M12, 5-pole, A-codedM12, 5-pole,
A-coded
Part number 1 812 739 8
Variable
DC 60 V
OpenM12, 5-pole,
A-coded
The following table shows the conductor assignment of the cable with the following part
number:
1 812 497 6 and 1 812 739 8
Signal nameCore color/designation
STO −Black / 1
STO +Black / 2
Operating Instructions – Electronic Motor DRC.-..-SNI
67
5
2
1
5
4
3
5.10.4 X5503: STO – OUT
Electrical Installation
Assignment of optional plug connectors
The following table informs about this connection:
Function
Connection for safe torque off (STO) for looping through
Connection type
M12, 5-pole, male, A-coded
Wiring diagram
2264818187
Assignment
No.NameFunction
1res.Reserved
2STO −Output STO – (to loop through)
3res.Reserved
4STO +Output STO + (to loop through)
5res.Reserved
68
Operating Instructions – Electronic Motor DRC.-..-SNI
Connection cables
Electrical Installation
Assignment of optional plug connectors
INFORMATION
Use only shielded cables for this connection and only suitable plug connectors that
connect the shield with the unit in an HF-capable manner.
The following table provides an overview of the cables available for this connection:
5
Connection cable
Part number 1 812 496 8
M12, 5-pole, A-codedM12, 5-pole, A-coded
Part number 1 812 740 1
M12, 5-pole, A-codedM12, 5-pole, A-coded
Length/
Installation
type
Variable
Variable
Operating
voltage
DC 60 V
DC 60 V
Operating Instructions – Electronic Motor DRC.-..-SNI
69
5
5.10.5 STO jumper plug
Electrical Installation
Assignment of optional plug connectors
WARNING
Safe disconnection of the DRC drive unit is not possible when the STO jumper plug is
used.
Severe or fatal injuries.
•You may only jumper the STO input with 24 V when the DRC drive unit need not
fulfill any safety function.
The STO jumper plug can be connected to the STO plug connector of the DRC drive
unit. The STO jumper plug deactivates the safety functions of the DRC drive unit.
The following figure shows the STO jumper plug, part number 1 174 709 9:
18014399658394891
70
Operating Instructions – Electronic Motor DRC.-..-SNI
5.11Application options
5.11.1 GIO12B
The following figure shows the M12 plug connectors of the GIO12B option:
Electrical Installation
Application options
RUN
NET
X3X2X1X4
5
DRIVE
9007201701475211
Function
Connection of I/Os
Connection type
M12, 5-pole, female, A-coded
Wiring diagram
1
4
Assignment
No.NameFunction
X31+24VDC 24 V sensor supply
2DO10_A3Relay contact (NC contact)
30V240V24 reference potential for actuators
4DO10_A2Relay contact (NO contact)
5res.Reserved
3
5
2264816267
72
Operating Instructions – Electronic Motor DRC.-..-SNI
6Startup
00
I
6.1Startup notes
INFORMATION
It is essential to adhere to the safety notes during startup.
Risk of crushing due to missing or defective protective covers.
Severe or fatal injuries.
•Install the protective covers of the system according to the instructions.
•Never start up the DRC drive unit without protective covers.
Electric shock caused by dangerous voltages in the connection box. Dangerous
voltages may still be present for up to 10 minutes after disconnection from the power
supply system.
WARNING
WARNING
Startup
Startup notes
6
Severe or fatal injuries.
•Before removing the electronics cover, switch off the power to the DRC drive units
using a suitable external disconnecting device.
•Secure the drive unit against unintended re-connection to the voltage supply.
•Secure the output shaft against rotation.
•Wait for at least 10 minutes before removing the electronics cover.
WARNING
Burns caused by hot surfaces.
Severe injuries
•Let the units cool down before touching them.
WARNING
Unit malfunction due to incorrect unit setting.
Severe or fatal injuries.
•Observe the startup notes.
•The installation must only be carried out by qualified personnel.
•Use only settings that are consistent with the function.
INFORMATION
•Before startup, remove the paint protection cap from the LED displays.
•Before startup, remove paint protection film from the nameplates.
•Observe a minimum switch-off time of 2 seconds for the line contactor.
Operating Instructions – Electronic Motor DRC.-..-SNI
73
6
00
I
Startup
Lifting applications
6.2Lifting applications
INFORMATION
•To ensure fault-free operation, do not disconnect or connect signal cables during
operation.
WARNING
Risk of fatal injury if the hoist falls.
Severe or fatal injuries.
•The DRC drive unit is not designed for use as a safety device in lifting applications.
•Use monitoring systems and mechanical protection devices to ensure safety.
6.3Prerequisties for startup
The following conditions apply to startup:
•Correct project planning for the DRC drive unit. For project planning notes, refer to
the catalog.
•The DRC drive unit must be installed correctly both mechanically and electrically.
•Appropriate safety measures prevent the drives from starting up unintentionally.
•Appropriate safety measures must be taken to prevent risk of injury or damage to the
machine.
74
Operating Instructions – Electronic Motor DRC.-..-SNI
6.4Description of DIP switches
ON DIP
1234
S2
ON DIP
1234
S1
00
I
6.4.1Overview
NOTICE
Damage to the DIP switches caused by unsuitable tools.
Possible damage to property.
•To set the DIP switches, use only suitable tools, such as a slotted screwdriver with
a blade width of no more than 3 mm.
•The force used for setting the DIP switches must not exceed 5 N.
The following figure shows the DIP switches S1 and S2:
Startup
Description of DIP switches
6
9007201622737931
DIP switch S1 The following table shows the functions of DIP switch S1:
DIP switchS1
1234
Binary coding SNI unit address
0
Bit 2
ON1111
OFF0000
Bit 2
1
Bit 2
2
Bit 2
3
DIP switch S2 The following table shows the functions of DIP switch S2:
DIP switchS2
1234
Binary coding operating modeUse of the
Bit 2
ON11Local moderes.
OFF00Sensorsres.
0
Bit 2
1
motion control
inputs
Reserved
Operating Instructions – Electronic Motor DRC.-..-SNI
75
6
00
I
Startup
Description of DIP switches
6.4.2Description of DIP switches
DIP switches S1/1
to S1/4
Setting the SNI address
These DIP switches are used to set the SNI addresses of DRC drive units. You can set
addresses from 0 to 9. Other settings are not permitted.
SNI, the operating mode must be set to "SNI-SEWOS", when
FDC SNI, it must be set to "VARIABLE".
DIP switch S2/3 Use of the motion control inputs
Use this DIP switch to determine the function of the motion control inputs (accessible
only via optional M23 plug connector).
•When DIP switch S2/3 is set to "OFF", the motion control inputs are used for
connecting and evaluating sensors. It is not possible to control the actuator via the
motion control inputs.
•When DIP switch S2/3 is set to "ON", the motion control inputs can be used for local
mode:
Motion control inputs Functionality with DIP switch S2/3 = ON
Motion control input 1CW/stop
Motion control input 2CCW/stop
Motion control input 3Setpoint selection n_f1 / n_f2
Motion control input 4Local/automatic
76
Operating Instructions – Electronic Motor DRC.-..-SNI
6.5Startup procedure
00
I
1. It is essential that you observe the startup instructions.
2. Disconnect all components from the voltage supply and use an external disconnecting device to avoid unintentional re-connection.
3. Check the correct connection of all connected DRC drive units and, if installed, of the
options. Observe chapter "Electrical Installation".
4. Set the DRC unit address:
WARNING Uncontrolled drive enable due to incorrect address setting.
Severe or fatal injuries.
•Assign each device address only once.
•Check the address settings before you enable the drive for the first time.
The following figure shows an example of the DIP switch setting for address 9:
S1
ONDIP
Startup
Startup procedure
6
1234
3
2 x 1 = 8
2
2 x 0 = 0
1
2 x 0 = 0
0
2 x 1 = 1
9
2441445259
The following table shows how to set the DIP switches for unit addresses 0 to 9.
Other settings are not permitted.
SNI, the operating mode must be set to "SNI-SEWOS", when
FDC SNI, it must be set to "VARIABLE".
NOTICE Damage to the DIP switches caused by using unsuitable tools.
Possible damage to property.
•To set the DIP switches, use only suitable tools, such as a slotted screwdriver with
a blade width of no more than 3 mm.
•The force used for setting the DIP switches must not exceed 5 N.
6. Secure the DRC electronics covers on the connection boxes.
7. Start up the assigned SNI controller, observing the instructions in the documentation
of the controller you use.
78
Operating Instructions – Electronic Motor DRC.-..-SNI
Starting up the GIO13B application option
00
I
6.6Starting up the GIO13B application option
WARNING
Burns caused by hot surfaces.
Severe injuries
•Let the units cool down before touching them.
6.6.1Overview of DIP switches
NOTICE
Loss of the guaranteed degree of protection.
Possible damage to property.
•In disassembled condition, you have to protect the GIO13B application option from
moisture, dust or foreign particles as there are openings for DIP switches.
•Make sure that the application cover is mounted properly.
Startup
6
The following figure shows the position of the DIP switches in the GIO13B application
option:
ON
ON
1234ON1234ON1234
1234ON1234ON1234
S1S2
S3
9007201137627403
Operating Instructions – Electronic Motor DRC.-..-SNI
79
6
00
I
Startup
Starting up the GIO13B application option
6.6.2Setting the DIP switches
DIP switch S1The following figure shows the possible settings for DIP switch S1:
ONDIP
S1
1234
S1/4: Binary output
ON = Binary output ON
OFF = Binary output OFF
S1/3: Analog output
ON = Analog output ON
OFF = Analog output OFF
S1/2: Binary inputs
ON = Binary inputs ON
OFF = Binary output OFF
S1/1: Analog input
ON = Analog input ON
OFF = Analog input OFF
9007201137841035
DIP switch S2The following figure shows the possible settings for DIP switch S2:
ONDIP
S2
1234
S2/2 to S2/4:
Configuration of primary frequency input
S2/1: Primary frequency input
ON = Primary frequency input ON
OFF = Primary frequency input OFF
The DIP switches S2/1 to S2/3 are used to configure the primary frequency input. The
following table shows the corresponding configuration options:
DIP switchConfiguration
S2/2S2/3S2/4Primary frequency input, maximum frequency
OFFOFFOFFf = 1 kHz
ONOFFOFFf = 2 kHz
OFF
ONONOFFf = 10 kHz
OFFOFF
ONOFFONf = 40 kHz
OFF
ONONONf = 120 kHz
ONOFFf = 5 kHz
ONf = 20 kHz
ONONf = 80 kHz
9007201137842955
80
Operating Instructions – Electronic Motor DRC.-..-SNI
Startup
ONDIP
1234
S3
S3/4: Analog input current resistor
ON = Enabled
OFF = Disabled
S3/3: Analog input mode
ON = Current input
OFF = Voltage input
S3/2: IPOS download
ON = Download of IPOS program to the command pcb
and start of IPOS program
OFF = No action
S3/1: Primary frequency input mode
ON = Track A/B
OFF = Track A
00
I
Starting up the GIO13B application option
DIP switch S3The following figure shows the possible settings for DIP switch S3:
INFORMATION
If the current input mode is set with DIP switch "S3/3 = ON", the current resistor must
be activated with DIP switch "S3/4 = ON".
INFORMATION
Important: Setting DIP switch S3/2 to "ON" will overwrite any IPOS program on the
command pcb.
6
Operating Instructions – Electronic Motor DRC.-..-SNI
9007201137839115
81
7
00
I
Operation of MOVITOOLS® MotionStudio
About MOVITOOLS® MotionStudio
7Operation of MOVITOOLS® MotionStudio
7.1About MOVITOOLS® MotionStudio
7.1.1Tasks
The software package enables you to perform the following tasks:
•Establish communication with units
•Execute functions of the units
7.1.2Establishing communication with the units
The SEW Communication Server is integrated into the MOVITOOLS
software package for establishing communication with the units.
The SEW Communication Server allows you to create communication channels.
Once the channels are established, the units communicate via these communication
channels using their communication options. You can operate up to four communication
channels at the same time.
®
MOVITOOLS
MotionStudio supports the following types of communication channels:
®
MotionStudio
•Serial (RS-485) via interface adapters
•System bus (SBus) via interface adapters
•Ethernet
•EtherCAT
•Fieldbus (PROFIBUS DP/DP-V1)
•Tool Calling Interface
The available channels can vary depending on the units and its communication options.
7.1.3Executing functions with the units
The software package offers uniformity in executing the following functions:
•Parameterization (e. g. in the parameter tree of the unit)
•Startup
•Visualization and diagnostics
•Programming
The following basic components are integrated into the MOVITOOLS
software package, allowing you to use the units to execute functions:
•MotionStudio
•MOVITOOLS
All functions communicate using tools. MOVITOOLS® MotionStudio provides the right
tools for every unit type.
®
®
MotionStudio
82
Operating Instructions – Electronic Motor DRC.-..-SNI
7.2.2Establishing communication and scanning the network
Proceed as follows to establish a communication with MOVITOOLS
scan your network:
1. Set up a communication channel to communicate with your units.
2. Scan your network (unit scan). Press the [Start network scan] button [1] in the toolbar.
MotionStudio from the Windows start menu via:
MotionStudio and create a project:
First steps
®
7
MotionStudio and
7.2.3Additional information
INFORMATION
The PC is connected to the DRC inverter via the employed controller or gateway. For
detailed information on how to configure a communication channel, refer to the documentation of the controller used.
[1]
9007200387461515
Operating Instructions – Electronic Motor DRC.-..-SNI
83
7
[1]
[2]
00
I
7.2.4Configuring units
Operation of MOVITOOLS® MotionStudio
First steps
Proceed as follows to configure a unit:
1. Select the unit in the network view.
2. Right-click to open the context menu and display the tools for configuring the unit.
9007201974142091
[1]Command PCB
[2]Power section
The example shows the context menu with the tools for a DRC power section [2]. The
communication mode is set to "online" and the unit is scanned in the network view.
3. Select a tool (e.g. "Parameter tree") to configure the unit.
9007202012758411
84
Operating Instructions – Electronic Motor DRC.-..-SNI
7.3Connection mode
00
I
7.3.1Overview
MOVITOOLS
mode. You determine the connection mode yourself. Depending on the selected
connection mode, you can choose offline or online tools specific to your unit.
Operation of MOVITOOLS® MotionStudio
Connection mode
®
MotionStudio differentiates between "online" and "offline" connection
7
Offline tools /
online tools
overview
The following figure illustrates the two types of tools:
[1]
HDD
[2]
RAM
Offline-Tool
Online-Tool
[3]
[1] Hard drive of the engineering PC
[2] RAM of the engineering PC
[3] Engineering PC
[4] Unit
Offline tools /
online tools
description
The following figure illustrates the two types of tools:
Too lsDescription
Offline
tools
Online
tools
Changes made using offline tools affect "ONLY" the RAM [2] at first.
•Save your project so that the changes can be stored on the hard disk [1] of your
engineering PC [3].
•Execute the "Download (PC->unit)" function if you want to transfer the changes to your
unit [4] as well.
Changes made using online tools affect "ONLY" the unit [4] at first.
•Execute the "Upload (unit->PC)" function if you want to transfer the changes to your RAM
[2].
•Save your project so that the changes can be stored on the hard disk [1] of your
engineering PC [3].
Operating Instructions – Electronic Motor DRC.-..-SNI
[4]
4710632331
85
7
00
I
Operation of MOVITOOLS® MotionStudio
Connection mode
INFORMATION
•The "online" connection status is NOT a response message which informs you that
you are currently connected to the unit or that your unit is ready for communication.
Should you require this feedback, observe chapter "Setting the cyclical accessibility test" in the online help (or the manual) of MOVITOOLS
•Project management commands (such as "download" and "upload"), the online
unit status, and the "unit scan" work independently of the set connection mode.
•MOVITOOLS
the program was closed.
7.3.2Selecting the connection mode (online or offline)
Proceed as follows to set the connection mode:
1. Select the connection mode:
•"Switch to online mode" [1] for functions (online tools) that should directly
influence the unit.
®
MotionStudio starts up in the connection mode that was set before
®
MotionStudio.
•"Switch to offline mode" [2] for functions (offline tools) that should influence your
project.
[1] [2]
9007200389198219
[1] "Switch to online mode" icon
[2] "Switch to offline mode" icon
2. Select the unit node.
3. Right-click to open the context menu and display the tools for configuring the unit.
86
Operating Instructions – Electronic Motor DRC.-..-SNI
Operation of MOVITOOLS® MotionStudio
00
I
7.4Executing functions of the units
7.4.1Parameterizing a unit
Units are parameterized in the parameter tree. The parameter tree displays all unit
parameters, grouped into folders.
You can manage the unit parameters using the context menu and the toolbar. The
following steps illustrate how to read or edit the unit parameters.
7.4.2Reading or changing unit parameters
Proceed as follows to read or change unit parameters:
1. Switch to the required view (project view or network view).
2. Select the connection mode:
•Click the "Switch to online mode" button [1] if you want to read or change
parameters directly in the unit.
•Click the "Switch to offline mode" button [2] if you want to read or change
parameters in the project.
Executing functions of the units
7
[1] [2]
[1] "Switch to online mode" icon
[2] "Switch to offline mode" icon
3. Select the unit you want to parameterize.
4. Open the context menu and select the [Parameter tree] command.
This opens the "Parameter tree" view on the right.
5. Expand the "Parameter tree" to the node you require.
9007200389198219
Operating Instructions – Electronic Motor DRC.-..-SNI
4718989195
87
7
00
I
Operation of MOVITOOLS® MotionStudio
Executing functions of the units
6. Double-click to display a particular group of unit parameters.
7. Press the enter key to finalize any changes you make to numerical values in the input
INFORMATION
For detailed information about the unit parameters, refer to chapter "Parameters".
7.4.3Starting up the units (online)
Do the following to start up the units (online):
1. Switch to the network view.
2. In the toolbar, click on "Switch to online mode" [1].
fields.
[1]
9007200438771211
[1] "Switch to online mode" icon
3. Select the unit you want to start up.
4. Open the context menu and select the [Startup] / [Startup] command.
The Startup wizard opens.
5. Follow the instructions of the startup wizard. Then load the startup data into your unit.
88
Operating Instructions – Electronic Motor DRC.-..-SNI
Overview of parameters of the command PCB
00
I
8Parameters
8.1Overview of parameters of the command PCB
8.1.1Display values
Parameters
8
IndexParameter nameMOVITOOLS®MotionStudio
Display
(Range / factory setting)
Command PCB parameters \ display values \ unit status
Unit status
8310.0Operating state[Text]
DIP switch
9621.10, bit 0Setting of DIP switch S1/1[Bit field]
9621.10, bit 1Setting of DIP switch S1/2[Bit field]
9621.10, bit 2Setting of DIP switch S1/3[Bit field]
9621.10, bit 3Setting of DIP switch S1/4[Bit field]
9621.10, bit 4Setting of DIP switch S2/1[Bit field]
9621.10, bit 5Setting of DIP switch S2/2[Bit field]
9621.10, bit 6Setting of DIP switch S2/3[Bit field]
9621.10, bit 7Setting of DIP switch S2/4[Bit field]