STOP!Possible damage to propertyDamage to the drive system or its environ-
NOTEUseful information or tip.
Simplifies handling of the drive
system.
1.2Right to claim under warranty
A requirement of fault-free operation and fulfillment of any rights to claim under limited
warranty is that you adhere to the information in the documentation. Therefore, read the
manual before you start operating the device!
Make sure that the manual is available to persons responsible for the plant and its operation, as well as to persons who work independently on the device. You must also
ensure that the documentation is legible.
You must comply with the information contained in the MOVIDRIVE® documentation to
ensure safe operation and to achieve the specified product characteristics and performance requirements. SEW-EURODRIVE assumes no liability for injury to persons or
damage to equipment or property resulting from non-observance of these operating instructions. In such cases, any liability for defects is excluded.
•Only specialists are allowed to perform installation and startup observing relevant accident prevention regulations and the MOVIDRIVE
or MOVIAXIS
•Read through this manual carefully before you commence installation and startup of
the DH.41B option.
•As a prerequisite to fault-free operation and fulfillment of warranty claims, you must
adhere to the information in the documentation.
2.2Safety functions
The MOVIDRIVE® MDX60B/61B drive inverters may not perform safety functions without higher-level safety systems. Use higher-level safety systems to ensure protection of
equipment and personnel. For safety applications, ensure that the information in the following publications is observed: "Safe Disconnection for MOVIDRIVE
2.3Hoist applications
MOVIDRIVE® MDX60B/61B, MOVITRAC® B and MOVIAXIS® are not designed for use
as a safety device in hoist applications.
Use monitoring systems or mechanical protection devices as safety features to avoid
possible damage to property or injury to people.
®
operating instructions!
®
MDX60B/61B, MOVITRAC® B
®
MDX60B/61B".
2.4Disposal
Observe current national regulations.
Dispose of the following materials separately in accordance with the country-specific
regulations in force, as:
•MOVI-PLC® basic DHP11B allows for coordinated single axis movements and integration of external inputs/outputs as well as drive operator panels (DOP). This makes
MOVI-PLC
®
basic DHP11B suitable for the task of module controller and also for that
of stand-alone controller for machines of medium complexity.
•MOVI-PLC
higher performance, which allows complex calculations and, for example, interpolated movements. MOVI-PLC
®
advanced DH.41B is characterized by a greater variety of interfaces and
®
advanced is suitable for automating cells and ma-
chines. The integrated Ethernet interface allows for connecting MOVI-PLC
vanced directly to the control level.
3.2MOVI-PLC® advanced DH.41B controller
CharacteristicsThe MOVI-PLC® advanced DH.41B controller is available in two variants:
®
•As control card MOVI-PLC
and MOVITRAC
•As compact controller MOVI-PLC
a DIN rail. As a compact controller, it is designed for controlling inverters (→ chapter
"Technical Data").
advanced DH.41B is available in 3 variants, which differ in the integrat-
advanced DH.41B as an option for MOVIDRIVE® B
®
advanced DH.41B prepared for installation on
Fieldbus interfaces
®
ad-
EngineeringThe engineering of the MOVI-PLC
activities:
•Configuration
•Parameterization
•Programming
These activities are carried out using the MOVITOOLS
ware. The software has a number of useful features for startup and diagnostics of all
SEW-EURODRIVE units. The connection between the MOVI-PLC
controller and the engineering PC is established via the Ethernet 2 communication interface.
Communication
interfaces
The MOVI-PLC
tion interfaces.
®
advanced controller DH.41B is equipped with numerous communica-
The two system bus interfaces CAN 1 and CAN 2 are used primarily for connection, controlling several inverters and integrating decentralized I/O modules.
This machine module can be operated via the integrated fieldbus interface with a higherlevel controller.
Engineering is performed via the integrated Ethernet 2 communication interface.
An operator terminal (e.g. DOP11B) or a gearmotor with integrated MOVIMOT
frequency inverter are connected to the RS485 interfaces.
advanced DH.41B controller as a control unit for an
entire machine.
If used without a higher-level PLC, the MOVI-PLC
®
advanced DH.41B controller takes
over all control tasks, including controlling drives and other actuators, as well as evaluating decentralized inputs and outputs.
In a stand-alone topology, operator terminals (DOP11B) function as the interface between the operator and machine.
You can connect MOVI-PLC
®
advanced DH.41B directly to the company’s Ethernet net-
work.
ETHERNET
ETHERNET
RS485
RS485
Figure 1: Example of a topology when using MOVI-PLC® advanced DH.41B as the standalone
You can also use the MOVI-PLC
mation of a machine module (→ following figure). In this way, the MOVI-PLC
DH.41B controller coordinates motion sequences in the axis system.
The controller is connected to a higher-level PLC via the PROFIBUS interface or via one
of the integrated fieldbus interfaces.
®
advanced DH.41B controller for decentralized auto-
®
advanced
3
Figure 2: Example of a topology for controlling each machine module using
a MOVI-PLC
®
advanced DH.41B controller
[1] Higher-level PLC
[2] System bus (CAN 1, CAN 2)
[3] MOVIMOT
MOVI-PLC
®
(via fieldbus interface DeviceNet MFD.../connected directly to
You can use the MOVI-PLC® advanced DH.41B controller to control a machine module
by coupling several inverters via the system bus. In this way, MOVI-PLC
®
advanced
DH.41B controls all the drives within the machine module and in doing so takes off load
from the master controller (e.g. machine or system PLC). You can connect a maximum
of 64 of the following units to the MOVI-PLC
®
advanced DH.41B controller via system
buses CAN 1, CAN 2 and Ethernet 1:
•MOVITRAC
•MOVIDRIVE
•MOVIAXIS
•Gearmotor with integrated frequency inverter MOVIMOT
®
B frequency inverter
®
MDX60B/61B drive inverter
®
servo inverter
®
(Fieldbus interface
DeviceNet MFD... required)
The PROFIBUS station address is set using the DIP switches on the front of the
MOVI-PLC
®
advanced DH.41B controller. This manual setting means the MOVI-PLC
advanced DH.41B controller can be integrated into the PROFIBUS environment and
switched on within a very short period of time. The higher-level PROFIBUS master can
set the parameters automatically (parameter download).
This option offers the following advantages:
•Less time required to start up the system
•Simple documentation of the application program as all important parameter data
can be transferred from the program of the higher-level controller.
®
Cyclical and acyclical data exchange
via PROFIBUS DP
Cyclical and acyclical data exchange
via PROFIBUS
DP-V1
PROFIBUS monitoring functions
While process data is usually exchanged cyclically, drive parameters are read or written
acyclically using functions such as Read and Write or via the MOVILINK
®
parameter
channel. This parameter data exchange enables you to implement applications in which
all the important drive parameters are stored in the master programmable controller, so
that there is no need to make parameter settings manually on the inverter itself.
The PROFIBUS DP-V1 specification introduced new acyclical Read/Write services within the context of the PROFIBUS DP-V1 expansions. These acyclical services are inserted in special telegrams during cyclical bus operation to ensure compatibility between
PROFIBUS DP (version 0) and PROFIBUS DP-V1 (version 1).
Using a fieldbus system requires additional monitoring functions for the drive technology, for example, time monitoring of the fieldbus (PROFIBUS timeout). The function module that addresses the PROFIBUS issues a PROFIBUS timeout using the relevant fault
information. This allows the application to respond to the PROFIBUS timeout.
Ethernet 2You can implement the following functions and connections via the communication
Binary inputs and
outputs
DiagnosticsThe LEDs of the MOVI-PLC
Connect one of the following devices each to the RS485 interfaces COM1 or COM2:
•DOP11B operator terminal
•Gearmotor with integrated frequency inverter MOVIMOT
interface Ethernet 2:
•Engineering
•Connection of a DOP11B operator terminal
•For visualization (for example: OPC interface)
•Connection to master level
Binary inputs and outputs enable you to switch actuators (e.g. valves) and evaluate binary input signals (e.g. sensors). You can freely use the binary inputs and outputs in the
PLC Editor of the MOVITOOLS
•Power supply of binary inputs and outputs
•General status of the MOVI-PLC
•Status of the control program
•Status of the PROFIBUS interface
•Status of the DeviceNet interface
•Status of the Ethernet interface
•Status of both CAN interfaces
You can connect operator terminals to perform diagnostics. It is recommended to connect an operator terminal to the communication interface Ethernet 2.
®
MotionStudio software in programming.
®
advanced DH.41B controller indicate the following states:
Mounting options for the MOVI-PLC® advanced DH.41B controller
4Mounting/Installation Instructions
4.1Mounting options for the MOVI-PLC® advanced DH.41B controller
Observe the following mounting instructions:
NOTES
•You can insert the MOVI-PLC® advanced DH.41B controller in the
MOVIDRIVE
•Option cards can only be installed or removed for MOVIDRIVE
drive inverters sizes 1 to 6.
•Only SEW-EURODRIVE engineers may install or remove option cards for
MOVIDRIVE
•Only SEW-EURODRIVE engineers may install or remove MOVI-PLC
advanced DH.41B controllers for MOVIAXIS® as well as install MOVI-PLC
DH.41B/UOH..B compact controllers.
®
MDX61B inverter, but not in the MOVIDRIVE® MDX60B inverter.
®
MDX61B size 0 drive inverters.
®
MDX61B
®
®
4.2Mounting MOVI-PLC® advanced DH.41B in MOVIDRIVE® MDX61B
•The MOVI-PLC® advanced DHE41B controller must be plugged into the fieldbus slot
of the MOVIDRIVE
DHE41B option into the expansion slot.
•The MOVI-PLC
expansion slot of the MOVIDRIVE
MDX61B size 0.
Before you beginObserve the following notes before installing or removing the MOVI-PLC
advanced DH.41B controller:
•Disconnect the drive inverter from power. Switch off the DC 24 V and the line voltage.
•Take appropriate measures to avoid electrostatic charges (use discharge strap, conductive shoes, etc.) before touching the MOVI-PLC
•Before installing the MOVI-PLC
and the front cover.
•After installing the MOVI-PLC
and the front cover.
•Keep the MOVI-PLC
mediately before you are ready to install it.
•Hold the MOVI-PLC
any components.
•Never place the MOVI-PLC
®
MDX61B. If the fieldbus slot is not available, you can plug the
®
advanced DHF41B/DHR41B controller must be plugged into the
®
advanced DH.41B controller in its original packaging until im-
®
advanced DH.41B controller by its edges only. Do not touch
®
MDX61B. It cannot be installed in MOVIDRIVE
®
advanced DH.41B.
®
advanced DH.41B controller, remove the keypad
®
advanced DH.41B controller, replace the keypad
®
advanced DH.41B controller on a conductive surface.
Mounting MOVI-PLC® advanced DH.41B in MOVIDRIVE® MDX61B
Basic procedure for installing and removing an option card in/from MOVIDRIVE® MDX61B
2.
1.
3.
4
4.
53001AXX
1. Remove the retaining screws holding the card retaining bracket. Pull the card retaining bracket out evenly from the slot (do not twist).
2. Remove the retaining screws of the black cover plate on the card retaining bracket.
Remove the black cover plate.
3. Position the option card onto the retaining bracket so that the retaining screws fit into
the corresponding bores on the card retaining bracket.
4. Insert the retaining bracket with installed option card into the slot, pressing slightly so
it is seated properly. Secure the card retaining bracket with the retaining screws.
5. Follow the instructions in reverse order when removing the option card.
Status of CAN 1 system bus
Status of CAN 2 system bus
Status of control program
Status of control firmware
Freely programmable
Status input or output DIO 6/7
Status input or output DIO 4/5
Status input or output DIO 2/3
Status input or output DIO 0/1
Status of voltage supply I/O
Voltage input DC+24 V
Reference potential for binary signals
Binary input or output (DIO 0)
Binary input or output (DIO 1)
Binary input or output (DIO 2)
Binary input or output (DIO 3)
Binary input or output (DIO 4)
Binary input or output (DIO 5)
Binary input or output (DIO 6)
Binary input or output (DIO 7)
Signal RS485+ (COM 1)
Signal RS485+ insulated (COM 2)
Signal RS485– (COM 1)
Signal RS485– insulated (COM 2)
Reference potential (COM 1)
Reference potential (COM 2)
DC 5 V power supply
Signal USB–
Signal USB+
Reference potential
Standard Ethernet assignment
16
Terminal X32:
System bus CAN 2
(electrically isolated)
X32:1
X32:2
X32:3
(plug-in terminals)
Terminal X33:
System bus CAN 1
(plug-in terminals)
Reference potential for system bus
CAN 2
System bus CAN 2 high
System bus CAN 2 low
Reference potential for system bus
CAN 1
System bus CAN 1 high
System bus CAN 1 low
Default IP address (192.168.10.4)
Ethernet 2 connection
Mounting/Installation Instructions
Installing the MOVI-PLC® advanced DHE41B controller
4.3.2Connection of binary inputs and outputs (connector X31)
Connector X31 provides 8 binary inputs or outputs (e.g. for controlling external actuators/sensors).
You can define the binary inputs and outputs in the PLC editor of the MOVITOOLS
MotionStudio software.
2
1
3
4
5
X31
6
7
8
9
10
4
®
Figure 3: 12-pin connector for connecting binary inputs and outputs
61018AXX
Binary inputs•The binary inputs are electrically isolated by optocouplers.
•The permitted input voltages are defined according to IEC 61131.
+13 V ... +30 V = "1" = Contact closed
–3 V ... +5 V = "0" = Contact open
Interrupt inputs•You can use binary inputs X31:6 to X31:10 as interrupt inputs. The response time
until the ISR (interrupt service routine) is processed is less than 100 ms.
Binary outputs•The binary outputs are electrically isolated by optocouplers.
•The binary outputs are short-circuit proof but not interference-voltage-proof.
•The maximum permitted output current is 150 mA per binary output. All eight binary
outputs can be operated simultaneously with this current.
STOP!
The supply voltage must be present on X31:1/2 for using the binary inputs and outputs.
The MOVI-PLC
binary inputs and outputs is no longer ensured.
If the supply voltage is stopped, you must turn off all other current supplies to X31:1 ...
10, e.g. the DC 24 V from switches and sensors at the binary inputs.
®
controller can be damaged. In this case, the specified function of the
•To avoid the danger of maximum voltage peaks, you may not connect inductive loads
to the supply voltage or to the binary inputs or outputs without free-wheeling diodes.
Cable specification•Only connect cables with a minimum core cross section of 0.25 mm
a maximal core cross section of 1 mm
2
(AWG18). IEC 60999 does allow clamping
without conductor end sleeves.
•Choose the type and core cross section of the connected cable in dependency of the
required cable length and the load expected from your application.
For more information on binary inputs or outputs, refer to chapter "Technical Data" on
page 61.
Installing the MOVI-PLC® advanced DHE41B controller
4.3.3Connecting system bus CAN 2 (connector X32) / CAN 1 (connector X33)
Do not connect more than 64 units to the CAN 2 or CAN 1 system bus. The system bus
supports the address range 0 ... 63.
NOTES
•The CAN 2 system bus is electrically isolated. Therefore, it is recommended to use
the CAN 2 (X32) interface for connecting field devices (e.g. CANopen inputs and
outputs).
•The CAN 1 system bus is not electrically isolated. Therefore, it is recommended to
use the CAN 1 (X33) interface to connect inverters via the system bus in the control
cabinet.
•SEW-EURODRIVE recommends connecting a maximum of 64 inputs and 64 outputs via I/O modules to the MOVI-PLC
•No CAN system bus connection is necessary for communication between MOVID-
®
RIVE
MDX61B and its installed controller MOVI-PLC® advanced if you use the
'DPRAM' channel (→ "MOVI-PLC
al). A CAN system bus connection is, however, necessary if modules from the
MPLCMotion_MDX and MPLCprocessdata libraries are employed.
®
basic DHP11B.. controller.
®
Programming in the PLC Editor" system manu-
The CAN system bus supports transmission systems compliant with ISO 11898. The
Serial Communication manual contains detailed information about the CAN system bus.
This manual can be ordered from SEW-EURODRIVE.
Wiring diagram for CAN 2 system bus
MOVITRAC® B
S1
S2
ON
OFF
X44
FSC11B
X46
X45
7
23456HL ⊥
1
Figure 4: CAN 2 system bus connection taking the example of a MOVIDRIVE® MDX60B/61B / MOVITRAC® B inverter
MDX60B/61B
X12
ON OFF
DGND
SC11
SC12
S12
1
2
3
MDX61B
DHE41B
X31X32X33
1
2
3
1
2
3
ON OFF
X12:
DGND
1
2
3
1
2
3
SC11
SC12
S12
1
2
3
60526AXX
Cable specification•Use a 2x2-core twisted and shielded copper cable (data transmission cable with
braided copper shield). IEC 60999 does allow clamping without conductor end
sleeves. The cable must meet the following specifications:
– Core cross section 0.2 ... 1.0 mm
2
(AWG 24 ... AWG 18)
– Line resistance 120 Ω at 1 MHz
– Capacitance per unit length ≤ 40 pF/m at 1 kHz
Suitable cables include CAN bus or DeviceNet cables.
advanced DH.41B controller is, for example, located at the end of
the CAN 2 system bus, you have to connect a terminating resistor of 120 O between
pins X32:2 and X32:3 (for CAN 1: terminating resistor between pins X33:2 and pin
X33:3).
STOP!
•There must not be any potential displacement between the units connected via the
CAN 2 system bus.
•There must not be any potential displacement between the units connected via the
CAN 1 system bus.
•Take suitable measures to avoid potential displacement, such as connecting the
unit ground connectors using a separate cable.
4
4.3.4Connection of the RS485 interface (connector X34)
STOP!
•There must not be any potential displacement between the units connected via the
RS485. Take suitable measures to avoid a potential displacement, e.g. by connecting the unit ground connectors using a separate lead.
•Dynamic terminating resistors are installed. Do not connect any external termi-
nating resistors.
You can connect one of the following devices to the RS485 interfaces COM1/2 (connector X34):
•DOP11A operator terminals
•Gearmotor with integrated frequency inverter MOVIMOT
2
1
3
X34
Figure 5: 6-pole connector for connecting the RS485 interfaces COM1/2
4
5
6
NOTE
For more information on how to connect the DOP11B operator terminal, refer to the
chapters "Installation" and "Pin assignment" in the "DOP11B Operator Terminals" system manual.
Installing the MOVI-PLC® advanced DHE41B controller
4.3.8DIP switch S1 default IP address
With the DIP switch S1, you can set a default IP address for the Ethernet 2 connection.
The set IP address is adopted during the next boot process.
S1 switch settingMeaning
TopDefault IP address 192.168.10.4
BottomAddresses set in the configuration file (see sec. 4.3.1)
4.3.9SD memory card type OMH41B-T.
The SD memory card is required for operation of the MOVI-PLC
controller. It stores the firmware, the IEC program and user data (e. g. recipes). It is used
in connection with a MOVIAXIS
eterization in case an axis is replaced.
The SD memory card OMH41B-T.. is plugged into the DH.41B option. If delivery also
includes a compact controller, a MOVIAXIS
DH.41B option, the SD memory card is already installed in the DH.41B option.
The SD memory card is available in 11 different variants (T0 ... T10). The different variants allow for the execution of different technology functions. The technology level can
be changed by replacing the SD memory card.
Variants
Mounting/Installation Instructions
®
advanced DH.41B
®
master module for data backup and automatic param-
®
master module or an inverter with installed
4
Bootloader
update
SD memory card OMH41B-T.
Technology
level T0-T10
T01821 204 2•Speed control management
T11821 205 0Additional technology functions for T0:
T21821 206 9Additional technology functions for T1:
T31821 967 5
T41821 968 3
T51821 969 1
T61821 970 5
T71821 971 3
T81821 972 1
T91821 974 8
T101821 975 6
Part numberDescription
•Positioning, e.g. with the MPLCMotion_MDX library
•Electronic cam
•Electronic gear unit
•Cam control
•Application modules, e.g. Handling, SyncCrane
Required for path interpolation. Technology level depends on the
required functionality and number of calculated kinematics.
When the LEDs L3 and L4 flash orange at a 1 Hz frequency after power-on, a bootloader
update is required. Proceed as follows:
•Do not switch off the power supply during the entire process.
•Press the reset button T1 on the front of the DH.41B option for 3 seconds. When the
bootloader update starts, only LED 4 is flashing.
•The bootloader update has been successful when L4 flashes green.
Status of CAN 1 system bus
Status of CAN 2 system bus
Status of control program
Status of control firmware
Freely programmable
Status input or output DIO6/7
Status input or output DIO4/5
Status input or output DIO2/3
Status input or output DIO0/1
Status of voltage supply I/O
Reserved
Reserved
The two-color LEDs 13 ... 16 display the current status of the fieldbus interface and the
DeviceNet system
Status of PROFIBUS bus electronics
Status of PROFIBUS communication
Reference potential for PROFIBUS
Signal receive transmit negative
Terminal unassigned
DC+5 V potential for bus terminator
Reference potential for PROFIBUS
PROFIBUS control signal for repeater
Signal receive transmit positive
Terminal unassigned
Terminal unassigned
0 V 24
CAN_L
DRAIN
CAN_H
24 V
Fieldbus interface PROFIBUS (X30P) active
Fieldbus interface DeviceNet (X30D) active
The DIP switches 2
MAC-ID (Media Access Control Identifier).
The MAC-ID represents the node address
(address range 0 ... 63)
Setting the baud rate
Setting the baud rate
Reserved
Reserved
Reserved
Voltage input DC+24 V
Reference potential for binary signals
Binary input or output
Binary input or output
Binary input or output
Binary input or output
Binary input or output
Binary input or output
Binary input or output
Binary input or output
Signal RS485+ (COM 1)
Signal RS485+ insulated (COM 2)
Signal RS485– (COM 1)
Signal RS485– insulated (COM 2)
Reference potential (COM 1)
Reference potential (COM 2)
DC 5 V power supply
Signal USB–
Signal USB+
Reference potential
Connection Ethernet 1
System bus (RJ45
socket)
Connector X37:
X37
Standard Ethernet assignment
Connection Ethernet 2
(RJ45 socket)
Terminal X32:
System bus CAN 2
(electrically isolated)
X32:1
X32:2
X32:3
REF_CAN 2
CAN 2H
CAN 2L
Reference potential for system bus CAN 2
System bus CAN 2 high
System bus CAN 2 low
(plug-in terminals, color:
YE/BK)
Terminal X33:
System bus CAN 1
(plug-in terminals, color:
X33:1
X33:2
X33:3
DGND
CAN 1H
CAN 1L
Reference potential for system bus CAN 1
System bus CAN 1 high
System bus CAN 1 low
Installing the MOVI-PLC® advanced DHF41B controller
4.4.2PROFIBUS connection (connector X30P)
Connection to the PROFIBUS system takes place using a 9-pin sub D plug according to
IEC 61158. The T-bus connection must be made using a plug with the corresponding
configuration. The following figure shows the PROFIBUS connector that is connected to
X30P of the MOVI-PLC
RxD/TxD-P
1
6
9
[1]
Figure 7: Assignment of 9-pin D-sub plug to IEC 61158
RxD/TxD-N
CNTR-P
DGND (M5V)
VP (P5V/100mA)
5
DGND (M5V)
®
advanced DHF41B controller.
[2]
3
8
4
5
6
9
[3]
61766AXX
[1] 9-pin sub D plug
[2] Signal line, twisted
[3] Conductive connection over a large area is necessary between plug housing and
the shield
MOVI-PLC
PROFIBUS
connection
/
As a rule, the MOVI-PLC® advanced DHF41B controller is connected to the PROFIBUS
system using a shielded twisted-pair cable. Observe the maximum supported transmission rate when selecting the bus connector.
®
The twisted-pair cable is connected to the PROFIBUS connector using pins 3
(RxD/TxD-P) and 8 (RxD/TxD-N). Communication is carried out via these two pins. The
RS485 signals RxD/TxD-P and RxD/TxD-N must be connected to the same contacts in
all PROFIBUS stations. Otherwise the bus components cannot communicate via the
bus medium.
The PROFIBUS interface sends a TTL control signal for a repeater or fiber optic adapter
(reference = pin 9) via pin 4 (CNTR-P).
Baud rates
greater than 1.5
The MOVI-PLC
operated with special 12 MBaud PROFIBUS connectors.
®
advanced DHF41B controller with baud rates > 1.5 MBaud can only be
MBaud
Bus terminatorYou do not need to equip the MOVI-PLC
nating resistors. This allows the PROFIBUS system to be put into operation more easily
and reduces the number of possible problems and faults during installation.
If the MOVI-PLC
®
advanced DHF41B controller is located at the start or end of a
PROFIBUS segment and if there is only one PROFIBUS cable connected to the
MOVI-PLC
®
advanced DHF41B controller, you must use a connector with an integrated
bus terminating resistor.
Switch on the bus terminating resistors for this PROFIBUS connector.
Installing the MOVI-PLC® advanced DHF41B controller
4
Setting the
station address
The PROFIBUS station address is set using DIP switches 20 ... 26 on the MOVI-PLC
advanced DHF41B controller.
The MOVI-PLC
DHF41B
®
advanced DHF41B controller supports the address range 0...125.
The default setting for the station address is 4:
0
→ Significance: 1 × 0 = 0
2
1
2
→ Significance: 2 × 0 = 0
0
2
1
2
2
2
ON
3
2
4
2
5
2
6
2
7
2
63210AXX
2
2
→ Significance: 4 × 1 = 4
3
→ Significance: 8 × 0 = 0
2
4
2
→ Significance: 16 × 0 = 0
5
2
→ Significance: 32 × 0 = 0
6
→ Significance: 64 × 0 = 0
2
Any change made to the PROFIBUS station address during ongoing operation does not
take effect immediately. You have to switch the compact controller or the inverter in
which the MOVI-PLC
®
advanced DHF41B controller is installed on and off again for the
changes to take effect (power + 24 V off/on).
4.4.3Connecting DeviceNet (connector X30D)
®
The connection to the DeviceNet fieldbus system is in preparation.
Pin assignmentThe assignment of connecting terminals is described in the DeviceNet specification
(Volume I, Appendix A).
DFD11B
DHF41B
1
2
3
4
5
X30D
61612AXX
The DHF41B option card is opto-decoupled on the driver side in accordance with the
DeviceNet specification (Volume I, Chapter 9). This means the CAN bus driver must be
powered with 24 V voltage via the bus cable. The cable to be used is also described in
the DeviceNet specification (Volume I, Appendix B). The connection must be made according to the color code specified in the following table.
Installing the MOVI-PLC® advanced DHF41B controller
Setting the
station address
Setting the baud
rate
The DeviceNet station address is set using DIP switches 20 ... 25 on the MOVI-PLC
advanced DHF41B controller.
The MOVI-PLC
DHF41B
®
advanced DHF41B controller supports the address range 0..0.63.
The default setting for the station address is 4:
0
→ Significance: 1 × 0 = 0
2
1
2
→ Significance: 2 × 0 = 0
0
2
1
2
2
2
ON
3
2
4
2
5
2
6
2
7
2
63210AXX
2
→ Significance: 4 × 1 = 4
2
3
2
→ Significance: 8 × 0 = 0
4
2
→ Significance: 16 × 0 = 0
5
→ Significance: 32 × 0 = 0
2
Any change made to the DeviceNet station address during ongoing operation does not
take effect immediately. You have to switch the compact controller or the inverter in
®
which the MOVI-PLC
advanced DHF41B controller is installed on and off again for the
changes to take effect (power + 24 V off/on).
6
The baud rate is set with DIP switches 2
DIP switches
6
2
00125 kbaud
10250 kbaud
01500 kbaud
11Invalid
and 27.
7
2
Baud rate
®
4.4.4Connecting SafetyBus (connector X38)
The connection to the SafetyBus bus system is in preparation.
Installing the MOVI-PLC® advanced DHF41B controller
4
LED L17
(Fault Profibus)
LED L18
(Run Profibus)
The LED L17 (Fault Profibus) indicates that communication via the PROFIBUS inter-
face is working properly.
Status of the
LED L17
Off•The MOVI-PLC
Red•Connection to the DP master has failed.
Flashing red
(1 Hz)
DiagnosticsTroubleshooting
®
troller exchanges data with the PROFIBUS-DP master (data exchange status).
•The MOVI-PLC
troller does not recognize the PROFIBUS
baud rate.
•Bus interruption has occurred.
•PROFIBUS-DP master not in operation.
•The MOVI-PLC
troller recognizes the baud rate, but the DP
master does not communicate with
MOVI-PLC
•The MOVI-PLC
troller was either not configured in the DP
master or it was configured incorrectly.
advanced DHF41B con-
®
advanced DHF41B con-
®
advanced DHF41B con-
®
advanced DHF41B.
®
advanced DHF41B con-
-
•Check the PROFIBUS connection on
the unit.
•Check project planning of the
PROFIBUS DP master.
•Check all the cables in the PROFIBUS network.
•Check and correct the PROFIBUS
station address set in the
MOVI-PLC
troller and in the configuration software of the DP master.
•Check and correct the configuration
of the DP master.
•Use the GSD file SEW_6007.GSD
with the designation MOVI-PLC for
configuration.
®
advanced DHF41B con-
LED L18 (Run Profibus) indicates the proper functioning of the PROFIBUS electronics
(hardware).
Status of the
LED L18
Green•PROFIBUS hardware OK. -
Flashing
green
(1 Hz)
DiagnosticsTroubleshooting
•The PROFIBUS station address set on
the DIP switches is more than 125. If the
PROFIBUS station address is set to a
value higher than 125, MOVI-PLC
advanced DHF41B will use PROFIBUS
station address 4.
®
1. Check and correct the PROFIBUS
station address on the DIP switches.
2. Switch on all drive inverters again.
The modified PROFIBUS address
will only take effect after a restart.
Status of CAN 1 system bus
Status of CAN 2 system bus
Status of control program
Status of control firmware
Freely programmable
Status input or output DIO6/7
Status input or output DIO4/5
Status input or output DIO2/3
Status input or output DIO0/1
Status of voltage supply I/O
Reserved
Reserved
Bus status
Bus status
Standard Ethernet assignment
Default IP address (192.168.10.4)
Stored IP address / DHCP
EtherNet/IP / Modbus TCP/IP
PROFINET
Reserved
Reserved
Reserved
Voltage input DC+24 V
Reference potential for binary signals
Binary input or output
Binary input or output
Binary input or output
Binary input or output
Binary input or output
Binary input or output
Binary input or output
Binary input or output
Signal RS485+ (COM 1)
Signal RS485+ insulated (COM 2)
Signal RS485– (COM 1)
Signal RS485– insulated (COM 2)
Reference potential (COM 1)
Reference potential (COM 2)
DC 5 V power supply
Signal USB–
Signal USB+
Reference potential
Installing the MOVI-PLC® advanced DHR41B controller
Use prefabricated, shielded RJ45 plug connectors compliant with IEC 11801, edition
2.0, category 5.
[1]
[2]
[3]
[6]
AB
Figure 8: Pin assignment of an RJ45 plug connector
A = Front view
B = View from back
[1] Pin 1 TX+ Transmit Plus
[2] Pin 2 TX– Transmit Minus
[3] Pin 3 RX+ Receive Plus
[6] Pin 6 RX– Receive Minus
6
3
2
1
54174AXX
MOVIDRIVE
®
B / MOVITRAC® B / Ethernet connection
To connect DHR41B to the Ethernet, connect the Ethernet interface X30-1 or X30-2
(RJ45 plug connector) to the other network stations using a category 5, class D twistedpair cable in accordance with IEC 11801 edition 2.0. The integrated switch provides support for realizing a line topology and offers auto crossing functions.
NOTES
•According to IEC 802.3, the maximum cable length for 10/100 MBaud Ethernet
(10BaseT/100BaseT), e.g. between two network stations, is 100 m.
•We recommend that you do not directly connect end devices to the DHR41B option
in order to minimize the load on the end devices caused by undesired multicast data
traffic. Connect non-SEW devices via a network component that supports the IGMP
snooping functionality (e.g. managed switch).
Installing the MOVI-PLC® advanced DHR41B controller
4.5.3Shielding and routing bus cables
Only use shielded cables and connection elements that also meet the requirements of
category 5, class 2 in compliance with IEC 11801 edition 2.0.
Correct shielding of the bus cable attenuates electrical interference that may occur in
industrial environments. The following measures ensure the best possible shielding:
•Manually tighten the mounting screws on the connectors, modules, and equipotential
bonding conductors.
•Use only connectors with a metal housing or a metallized housing.
•Connect the shielding in the connector over a wide surface area.
•Apply the shielding of the bus line on both ends.
•Route signal and bus cables in separate cable ducts. Do not route them parallel to
power cables (motor leads).
•Use metallic, grounded cable racks in industrial environments.
•Route the signal cable and the corresponding equipotential bonding close to each
other using the shortest possible route.
•Avoid using plug connectors to extend bus cables.
•Route the bus cables closely along existing grounding surfaces.
Mounting/Installation Instructions
4
STOP!
In case of fluctuations in the ground potential, a compensating current may flow via the
bilaterally connected shield that is also connected to the protective earth (PE). Make
sure you supply adequate equipotential bonding in accordance with relevant VDE
regulations in such a case.
4.5.4Setting the DIP switches 2
NOTE
The setting of the "20" DIP switch is only adopted with a power-on reset (switching on
and off line voltage and DC 24 V backup voltage).
DIP switch 2
0
If the "20" switch is set to "1" (= ON), the following default IP address parameters are set
when activating the DC 24 V backup voltage:
•IP address: 192.168.10.4
•Subnetwork mask: 255.255.255.0
•Default gateway: 1.0.0.0 for EtherNet/IP (192.168.10.4 for PROFINET)
•P785 DHCP / Startup Configuration: Saved IP parameters (DHCP is deactivated)
DIP switch "21" is used to set the fieldbus protocol that is currently used.
1
•2
= "1" (= ON) the EtherNet/IP / Modbus TCP/IP fieldbus protocol is active
1
•2
= "0" (= OFF) the PROFINET fieldbus protocol is active.
35
4
Mounting/Installation Instructions
Installing the MOVI-PLC® advanced DHR41B controller
4.5.5TCP / IP addressing and subnetworks
IntroductionThe settings for the address of the IP protocol are made using the following parameters:
•MAC address
•IP address
•Subnetwork mask
•Standard gateway
The addressing mechanisms and subdivision of the IP networks into subnetworks are
explained in this chapter to help you set the parameters correctly.
MAC addressThe MAC address (Media Access Controller) is the basis for all address settings. The
MAC address of an Ethernet device is a worldwide unique 6-byte value (48 bits). SEW
Ethernet devices have the MAC address 00-0F-69-xx-xx-xx. The MAC address is difficult to handle for larger networks. This is why freely assignable IP addresses are used.
IP addressThe IP address is a 32 bit value that uniquely identifies a station in the network. An IP
address is represented by four decimal numbers separated by decimal points.
Example: 192.168.10.4
Each decimal number stands for one byte (= 8 bits) of the address and can also be represented using binary code (see following table).
Byte 1Byte 2Byte 3Byte 4
11000000.10101000.00001010.00000100
The IP address comprises a network address and a station address (see following
table).
Network addressStation address
192.168.104
The part of the IP address that denotes the network and the part that identifies the station is determined by the network class and the subnetwork mask.
Station addresses cannot consist of only zeros or ones (binary) because they represent
the network itself or a broadcast address.
Network classesThe first byte of the IP address determines the network class and as such represents
the division into network addresses and station addresses.
Installing the MOVI-PLC® advanced DHR41B controller
Subnet maskA subnet mask is used to divide the network classes into even finer sections. The subnet
mask is represented by four decimal numbers separated by decimal points, in the same
way as the IP address.
Example: 255.255.255.128
Each decimal number stands for one byte (= 8 bits) of the subnetwork mask and can
also be represented using binary code (see following table).
Byte 1Byte 2Byte 3Byte 4
11111111.11111111.11111111.10 000000
If you compare the IP addresses with the subnet masks, you see that in the binary representation of the subnet mask all ones determine the network address and all the zeros
determine the station address (see following table).
Byte 1Byte 2Byte 3Byte 4
IP address
Subnetwork mask
Decimal192.168..10.129
Binary11000000.10101000.00001010.10000001
Decimal255.255.255.128
Binary11111111.11111111.11111111.10000000
4
The class C network with the address 192.168.10. is further subdivided into
255.255.255.128 using the subnetwork mask. Two networks are created with the ad-
dress 192.168.10.0 and 192.168.10.128.
The following station addresses are permitted in the two networks:
•192.168.10.1 ... 192.168.10.126
•192.168.10.129 ... 192.168.10.254
The network stations use a logical AND operation for the IP address and the subnetwork
mask to determine whether there is a communication partner in the same network or in
a different network. If the communication partner is in a different network, the standard
gateway is addressed for passing on the data.
Standard gatewayThe standard gateway is also addressed via a 32-bit address. The 32-bit address is rep-
resented by four decimal numbers separated by decimal points.
Example: 192.168.10.1
The standard gateway establishes a connection to other networks. In this way, a network station that wants to address another station can use a logical AND operation with
the IP address and the subnetwork mask to decide whether the desired station is located
in the same network. If this is not the case, the station addresses the standard gateway
(router), which must be part of the actual network. The standard gateway then takes on
the job of transmitting the data packages.
DHCP (Dynamic
Host Configuration Protocol)
Instead of setting the three parameters IP address, subnetwork mask and standard
gateway manually, they can be assigned in an automated manner by a DHCP server in
the Ethernet network.
This means the IP address is assigned from a table, which contains the allocation of
MAC address to IP address.
Parameter P785 indicates whether the DHR41B option expects the IP parameters to be
assigned manually or via DHCP.
Installing the MOVI-PLC® advanced DHR41B controller
4.5.6Operating displays of the MOVI-PLC® advanced DHR41B controller in PROFINET mode
NOTE
The LEDs identical with DHE41B (L1 – L10) are described in section "Operating displays of the MOVI-PLC
There are 4 LEDs (L11, L12, L13, L14) on the DHR41B option card that display the current status of the DHR41B option, the PROFINET system and the safety options.
FS LEDLED L12 (FAILSAFE-STATUS) indicates the failsafe status on PROFINET.
®
advanced DHE41B controller".
LED L13
(BUS-FAULT)
Status of
the "FS"
LED
Green•The safety option is currently perform-
Red•Fault status in the safety part.
Off•The safety option is currently in the
Flashing
red / green
Cause of errorTroubleshooting
ing a cyclical data exchange with the
F-host (data exchange).
•Standard operating state.
•No 24 V_LS supply voltage present.
initialization phase.
A fault occurred in the safety part; cause
of the fault already remedied acknowledgement required.
–
•Read diagnostic in F-Host.
•Eliminate the cause of the fault and
acknowledge in the F-Host.
•Check voltage supply.
•Check configuration of the bus master.
Acknowledge fault in the F-Host (reintegration).
The LED L13 (BUS FAULT) displays the status of the PROFINET.
Status of the
LED L13
Off•PROFINET IO device is currently
Flashing green
Flashing
green/red
Red•Connection to the PROFINET IO
Yellow
Flashing yellow
Cause of errorTroubleshooting
exchanging data with the PROFINET
IO controller (Data Exchange).
•The flashing function in the PROFINET IO controller project planning is
activated to visually localize the stations.
controller has failed.
•PROFINET IO device does not
detect a link
•Bus interruption
•PROFINET IO controller is not in
operation
•The STEP 7 hardware configuration
contains a module that is not permitted.
-
-
•Check the PROFINET connection of
the DHR41B option
•Check the PROFINET IO controller
•Check the cabling of your PROFINET
network
•Switch the STEP 7 hardware configuration to ONLINE and analyze the status of the components of the slots in
the PROFINET IO device.
Installing the MOVI-PLC® advanced DHR41B controller
LED L14 (RUN)LED L14 (RUN) indicates that the bus electronics are operating correctly.
4
LED
Link / Activity
Status of the
LED L14
Green•DHR41B hardware OK.
Off•DHR41B is not ready for opera-
Red•Error in the DHR41B hardware
Flashing
green
Flashing
yellow
Yellow•Switch the unit on again. Consult SEW Ser-
Cause of errorTroubleshooting
•Proper operation
tion.
•Hardware of the DHR41B does
not boot up.
–
•Switch the unit on again. Consult SEW Service if the error occurs again.
•Switch the unit on again. Set default IP
addressparameter via DIP switch "S1". Consult SEW service if the error occurs again.
vice if the error occurs again.
The two LEDs Link (green) and Activity (yellow), integrated in the RJ45 plug connectors (X30-1, X30-2), display the status of the Ethernet connection.
Initial startupFor PROFINET IO, the IP address parameters are determined via the "DCP" protocol
Mounting/Installation Instructions
Installing the MOVI-PLC® advanced DHR41B controller
(Discovery and Configuration Protocol). DCP operates with device names (Device
Name). The device name uniquely identifies a PROFINET IO station in the network. It
is identified with the PROFINET IO controller for the project planning of the station and
also set using the project planning software on the PROFINET IO device. With the aid
of the device name, the controller identifies the device during startup and transfers the
corresponding IP address parameters. Settings directly on the slave are no longer required.
Resetting the IP
address parameters
If you do not know the IP address parameters and cannot access the inverter using the
serial interface or the DBG60B keypad, you can reset the IP address parameters to the
default values using the DIP switch "2
This action resets the DHR41B option to the following default values:
•IP address: 192.168.10.4
•Subnetwork mask: 255.255.255.0
•Default gateway: 1.0.0.0
•PROFINET device name: PNETDeviceName_MACID
Proceed as follows to reset the IP address parameters to the default values:
•Switch off the 24 V DC supply voltage and the mains voltage.
•Set the DIP switch "2
•Switch the DC 24 V supply voltage and the line voltage back on.
•Wait until the DHR41B option has booted up. The "RUN" LED is green when the option is ready.
You can now access the inverter via the IP address 192.168.10.4. Proceed as follows
to set new IP address parameters:
•Start MOVITOOLS
•Select the address parameters you want.
•Set the DIP switch "2
•The new address parameters are adopted after the device is switched off and
switched on again.
Installing the MOVI-PLC® advanced DHR41B controller
LED Link /
Activity
The two LEDs Link (green) and Activity (yellow), integrated in the RJ45 plug connectors (X30-1, X30-2), display the status of the Ethernet connection.
Installing the MOVI-PLC® advanced DHR41B controller
4.5.9Setting the IP address parameters
Initial startupThe "DHCP" protocol (Dynamic Host Configuration Protocol) is activated as the default
setting for the DHR41B option. This means that the DHR41B option card expects its IP
address parameters from a DHCP server.
NOTE
Rockwell Automation provides a DHCP server free-of-charge on their homepage. The
tool is known as "BOOTP Utility" and can be downloaded from the following website:
http://www.ab.com/networks/bootp.html.
Once the DHCP server has been configured and the settings have been made for the
subnetwork screen and the standard gateway, the DHR41B must be inserted in the assignment list of the DHCP server. In doing so, the MAC ID of the DHR41B option is allocated a valid IP address.
NOTE
The configured IP address parameters are permanently adopted into the parameter
set if DHCP is deactivated after the IP address has been assigned.
4
Changing the IP
address parameters after successful initial
startup
If the DHR41B was started using a valid IP address, you can also access the IP address
parameters via the Ethernet interface.
The following options are available for changing the IP address parameters via Ethernet:
•With the MOVITOOLS
•With the EtherNet/IP TCP/IP interface object
You can also use the DBG60B keypad to change the IP address parameters. To do so,
connect the DBG60B keypad to the serial interface (X24) of the UOH21B compact controller.
If the IP address parameters are assigned to the option DHR41B via a DHCP server,
you can only change the parameters by adjusting the settings of the DHCP server.
The options listed above for changing the IP address parameters only come into effect
once the supply voltages (mains and DC 24 V) have been switched off and back on
again.
Installing the MOVI-PLC® advanced DHR41B controller
Deactivating /
activating the
DHCP
Resetting the IP
address parameters
The type of IP address allocation is determined by the setting of the attribute Configuration Control of the EtherNet/IP TCP/IP interface object. The value is displayed or modi-
fied in the parameter P785 DHCP/Startup Configuration.
•Setting "Saved IP parameters"
The saved IP address parameters are used.
•Setting "DHCP"
The IP address parameters are requested by a DHCP server.
If you use the DHCP server from Rockwell Automation, you can activate or deactivate the DHCP via a button. In this case, an EtherNet/IP telegram is sent to the
TCP/IP interface object of the station that is being addressed.
If you do not know the IP address parameters and there is no serial interface or DGB60B
keypad for reading the IP address, you can reset the IP address parameters to the default values using the DIP switch "2
This action resets the DHR41B option to the following default values:
•IP address: 192.168.10.4
•Subnetwork mask: 255.255.255.0
•Default gateway: 1.0.0.0
•P785 DHCP/Startup Configuration: Saved IP parameters (DHCP is deactivated)
0
".
Proceed as follows to reset the IP address parameters to the default values:
•Switch off the 24 V DC supply voltage and the mains voltage.
•Set the DIP switch "2
•Switch the DC 24 V supply voltage and the line voltage back on.
•Wait until the DHR41B option has booted up. The "MODULE STATUS" LED is green
when the option is ready.
•Set the DIP switch "2
•The following options are available to assign the new IP address:
– With the MOVITOOLS
– With the EtherNet/IP TCP/IP interface object
0
" on the DHR41B option to "1".
0
" on the DHR41B option to "0".
®
MotionStudio software via Ethernet
NOTE
•DHCP remains deactivated when you reset the DIP switch "20" to "0". You can reactivate DHCP via the EtherNet/IP TCP/IP interface object, parameter P785 or the
DHCP server by Rockwell Automation.
•DHCP remains active when resetting the values to the default setting (P802 Factorysetting).
Installing the MOVI-PLC® advanced DHR41B controller
4.5.10 The integrated Ethernet switch
You can use the integrated Ethernet switch to achieve line topologies known from the
fieldbus technology. Other bus topologies, such as star or tree, are also possible. Ring
topologies are not supported.
NOTE
The number of industrial Ethernet switches connected to the line affects the telegram
runtime. If a telegram passes through the units, the telegram runtime is delayed by the
Store & Forward function of the Ethernet switch:
•For a telegram length of 64 Byte by approximately 10 µs (at 100 Mbit/s)
•For a telegram length of 1500 Byte by approximately 130 µs (at 100/Mbit/s)
This means that the more units a telegram has to pass through, the higher the telegram
runtime is.
Autocrossing:The two ports leading out of the Ethernet switch have autocrossing functionality. This
means you can use patch or cross-over cables to connect the next Ethernet node.
4
AutonegotiationThe baud rate and the duplex mode is negotiated by both Ethernet nodes when estab-
lishing the connection. The two Ethernet ports of the EtherNet/IP interface support autonegotiation functionality and operate at a baud rate of 100 Mbit or 10 Mbit in full duplex
or half duplex mode.
Notes on multicast handling
•The integrated Ethernet switch does not provide a filter function for Ethernet multicast telegrams. Multicast telegrams that are usually sent from the adapters
(DHR41B) to the scanners (PLC) are passed on to all switch ports.
•IGMP snooping (managed switch) is not supported.
•SEW-EURODRIVE recommends to connect DHR41B only with network components
that support IGMP Snooping (e. g. managed switch) or in which protective measures
against excessive multicast load are integrated (e. g. units from SEW-EURODRIVE).
When using units that do not possess this function, the high load on the network can
cause faults.
4.6Installing the DH.41B option in MOVIDRIVE® MDX61B
NOTE
The MOVI-PLC® advanced DH.41B controller is installed according to chapter "Mounting options for the MOVI-PLC
vanced DH.41B controller is powered via MOVIDRIVE
supply is only required for the binary inputs and outputs (connector X31).
®
advanced DH.41B controller". The MOVI-PLC® ad-
®
MDX61B. A separate voltage
4.7Installation of the DH.41B option in the MOVIAXIS® MDX61B master module
NOTE
The MOVI-PLC® advanced DH.41B controller is installed according to chapter "Mounting options for the MOVI-PLC
connect connector X33 (CAN1) or X32 (CAN2) of MOVI-PLC
connector X9 (MOVIAXIS
module) or with connector X12 (CAN2 bus of a MOVIAXIS
MOVIAXIS
®
master module also provides further connections as described below.
®
advanced DH.41B controller". To wire the system bus,
®
supply module signalizing bus or of a MOVIAXIS® axis
®
advanced DH.41B with
®
axis module). The
4.7.1Function description of terminals X5a/X5b (MOVIAXIS® master module)
MOVIAXIS® master
module MXM
1
X5b
2
3
4
1
X5a
2
3
4
59233AXX
•The connectors X5a and X5b are connected in parallel. In this way, the voltage supply of the MOVIAXIS
DesignationTermin alFunction
X5b connectorX5b:1
X5a connectorX5a:1
®
master module can be provided from the right to X5b or from
X5b:2
X5b:3
X5b:4
X5a:2
X5a:3
X5a:4
DC 24 V
DGND
DC 24 V
BGND
DC 24 V
DGND
DC 24 V
BGND
Voltage supply for control electronics
E
Reference potential of control electronics
B
Brake voltage supply
Reference potential for brake connection
Voltage supply for control electronics
E
Reference potential of control electronics
B
Brake voltage supply
Reference potential for brake connection
below to X5a. With connection to X5a, further modules can be connected via X5b
(e.g. supply module, axis module). The voltage supply of brake (X5a/b:3, 4) is conducted by the MOVIAXIS
•The MOVI-PLC
®
advanced DH.41B controller can be supplied by the MOVIAXIS
®
master module.
switched mode power supply module (MXS) or from an external voltage supply. For
this purpose, connect X5 between the individual devices.
•If the MOVI-PLC
MOVIAXIS
®
®
advanced DH.41B controller is supplied with DC 24 V by the
switched-mode power supply module, the function of the MOVI-PLC
advanced DH.41B controller is maintained after disconnection from the power supply. This is the case if the DC link voltage is maintained or an external DC 24 V supply
of the MOVIAXIS
Installing the DH.41B option in MOVITRAC® B/compact controller
4.8Installing the DH.41B option in MOVITRAC® B/compact controller
NOTE
The MOVI-PLC® advanced DH.41B controller is installed according to chapter "Mounting options for the MOVI-PLC
tion slot and the compact controller provide additional connections and operating displays for the MOVI-PLC
4.8.1Function description of terminals and LEDs
®
advanced DH.41B controller". The MOVITRAC® B op-
®
advanced DH.41B controller as described below.
Front view
MOVITRAC
compact controller
Lateral view
Compact controller
X26
2345671
®
B/
H1
H2
X2
58905AXX
58906AXX
X26:1
X24:2
X24:3
X24:4
X26:5
X26:6
X26:7
LED
Term inal
H2
X24:4
X24:3
X24:2
X24:1
CAN1H
CAN1L
DGND
Reserved
Reserved
DGND
DC 24 V
Function
System fault
Reserved
DGND
RS–
RS+
5 V
Reference potential COM 1
Signal RS485–
Signal RS485+
Voltage output DC+5 V
System bus CAN 1 high
System bus CAN 1 low
Reference potential controller/CAN1
-
Reference potential controller/CAN1
Voltage supply of controller
Designation
LEDH1
Connector X24:
RS485 COM 1
(RJ10 socket)
DesignationTermin alFunction
Connector X26:
CAN 1 and
voltage supply
(plug-in terminal)
4.8.2Connection of RS485 interface COM 1 (connector X24)
The connectors X24 and X34:1/3/5 are connected in parallel. You can connect a
DOP11B operator terminal at X24. If X24 is unassigned, you can connect an operator
terminal or a gearmotor with integrated MOVIMOT
Installing the DH.41B option in MOVITRAC® B/compact controller
4.8.3Connection of system bus CAN 1/power supply (connector X26)
4
X26:1/2/3 and connector X33 are connected in parallel (see sec. 4.3.3). MOVI-PLC
advanced DH.41B in the compact controller is supplied with power via X26:6/7.
The MOVI-PLC
by MOVITRAC
X12:9/8. If the MOVI-PLC
MOVITRAC
®
advanced DH.41B controller can be supplied with the required voltage
®
B. For this purpose, connect X26:3 (6)/7 with X46:3 (6)/7 or with
®
B, the function of the MOVI-PLC® advanced DHE41B controller is main-
®
advanced DHE41B controller is supplied with DC 24 V by
tained after disconnection from the voltage supply. This requires an external DC 24 V
S2
®
B.
DHE41B
2
1
4
3
6
5
X31
8107
9
2
1
4
3
X34
6
5
X35
T1
342
1
X36
S1
X37
7
1
1
2
2
X32X33
3
3
1
1
2
2
3
3
L1L2L3L5XML6 L7 L8 L9L4L1 0
120Ω
supply to X12:8 / 9 of MOVITRAC
MOVITRAC® B
S1
ON
OFF
X44
FSC11B
X46
X45
23456HL ⊥
1
®
H1
H2
X24
X26
1234567
DC 24V
X12
1
2
3
+
=
-
24V IO
GND
4
5
6
7
8
9
Figure 9: Installation of MOVI-PLC® advanced DHE41B in MOVITRAC® B
Engineering interface of the MOVI-PLC® advanced DH.41B controller
4.9Engineering interface of the MOVI-PLC® advanced DH.41B controller
4
The engineering access to the MOVI-PLC® advanced DH.41B controller is realized via
the Ethernet 2 interface (connector X37). Engineering access to the MOVI-PLC
advanced DHF41B controller is also possible via PROFIBUS (connector X30P) and to
the MOVI-PLC
®
advanced DHR41B controller via Ethernet (connector X30-1/2).
NOTE
For detailed information, refer to the "MOVI-PLC® advanced Fieldbus Interfaces
PROFIBUS DP-V1, Ethernet TCP/IP, EtherNet/IP, DeviceNet, Modbus TCP/IP"
manual.
4.10Shielding and routing bus cables
Only use shielded cables and connection elements that also meet the requirements of
category 5, class 2 in compliance with IEC 11801 edition 2.0.
Correct shielding of the bus cable attenuates electrical interference that may occur in
industrial environments. The following measures ensure the best possible shielding:
•Manually tighten the mounting screws on the connectors, modules, and equipotential
bonding conductors.
•Use only connectors with a metal housing or a metallized housing.
•Connect the shielding in the connector over a wide surface area.
•Apply the shielding of the bus line on both ends.
•Route signal and bus cables in separate cable ducts. Do not route them parallel to
power cables (motor leads).
•Use metallic, grounded cable racks in industrial environments.
•Route the signal cable and the corresponding equipotential bonding close to each
other using the shortest possible route.
•Avoid using plug connectors to extend bus cables.
•Route the bus cables closely along existing grounding surfaces.
®
STOP!
In case of fluctuations in the earth potential, a compensating current may flow via the
bilaterally connected shield that is also connected to the protective earth (PE). Make
sure you supply adequate equipotential bonding according in accordance with relevant
VDE regulations in such a case.
Configuration with the MOVITOOLS® MotionStudio PC software
I
5
00
Options for engineering access
Address settings
for a point-topoint connection
You have two options to establish engineering access to the MOVI-PLC® advanced
DH.41B controller via the Ethernet 2 interface (connector X37):
•For a point-to-point connection, connect the Ethernet 2 interface (X37) of the
MOVI-PLC
gineering PC. Use an interface of the engineering PC that is not used for connection
of the PC to the Intranet/Internet. In this way, you avoid reconfiguration of the interface.
•Integrate the MOVI-PLC
2 interface (X37). Edit the configuration file NetConfig.cfg in the "System" folder of
the SD memory card to make the necessary address settings. You have the following
options to access the NetConfig.cfg configuration file:
– Take the SD memory card out of the MOVI-PLC
and insert it into a memory card write/read device.
– First, establish a point-to-point connection to the MOVI-PLC
controller. Then access the NetConfig.cfg configuration file via an FTP client.
For older network interfaces, it can be necessary to use a cross cable for the pointto-point connection.
•Setting the default IP address:
– De-energize the MOVI-PLC
– Switch the DIP switch to the upper position.
– Re-energize the MOVI-PLC
192.168.10.4 and the net mask 255.255.255.0 are assigned automatically to the
Ethernet 2 interface of the MOVI-PLC
®
advanced DH.41B controller directly to the Ethernet interface of the en-
®
advanced DH.41B controller in a network via the Ethernet
®
advanced DH.41B controller
®
advanced DH.41B
®
advanced DH.41B controller.
®
advanced DH.41B controller. The IP address
®
advanced DH.41B controller.
•Setting other addresses:
By manually editing the section <Ethernet2...> in the NetConfig.cfg configuration file
in the "System" folder of the SD memory card, you can set other addresses.
Example:
<!-- Ethernet2 is engineering interface -->
<Ethernet2>
<IPAddress>192.168.10.4</IPAddress>
<Netmask>255.255.255.0>/Netmask>
<Gateway>192.168.10.1</Gateway>
<Nameserver>0.0.0.0</Nameserver>
<Hostname>MOVI-PLC_Eth2>/Hostname>
</Ethernet2>
Switch the DIP switch S1 to the lower position. This ensures that the addresses are
adopted during the next boot process of the MOVI-PLC
Configuration with the MOVITOOLS® MotionStudio PC software
00
•Setting the IP address of the PC interface:
– Select the relevant PC interface under [Start] / [Settings] / [Network Connections].
In the context menu, select the properties window of the PC interface.
– Activate the option "Use this IP address" in the property window of the "Internet
protocol (TCP/IP)" entry.
– Enter the net mask which is set in the MOVI-PLC
(e. g. 255.255.255.0, if DIP switch S1 is in the upper position).
– Set the IP address depending on the net mask. The IP addresses of the MOVI-
®
PLC
advanced DH.41B controller (Ethernet 2) and the PC interface must be different except for the areas defined by the net mask. In the area defined by the net
mask, the IP addresses must be the same. The last byte of the IP address may
neither be 0 nor 255.
Example:
Net mask
decimalbinary
255.255.255.011111111.11111111.11111111.00000000
In the example, the last 8 bits of the IP address of the MOVI-PLC
DH..41B controller and the PC interface must be different.
®
advanced DH.41B controller
®
advanced
Address settings
for engineering
access via a
network
Proceed as follows to establish engineering access to the MOVI-PLC
DH.41B controller via an existing network:
•In the section <Ethernet2...> of the NetConfig.cfg configuration file in the "System"
folder of the SD memory card, enter the following according to the specifications of
your network administration:
– IP address
–Net mask
– Gateway address
•Switch the DIP switch S1 to the lower position. This ensures that the new address
settings are adopted during the next boot process of the MOVI-PLC
DH.41B controller.
Configuration with the MOVITOOLS® MotionStudio PC software
I
5
00
Setting the engineering access in
MOVITOOLS
MotionStudio
®
•Open the menu item "Communication plugs" in MOVITOOLS
"Network" menu.
[1]
•Select the entry "Ethernet" [1] from the dropdown menu. Click on the <Edit> button
[2]. Confirm your selection with <OK>.
®
MotionStudio in the
63436AXX
[2]
•Right-click in the empty field "SMLP server IP addresses " and use menu item "Add
IP address" to add the IP address of the Ethernet 2 interface of the MOVI-PLC
advanced DH.41B controller (see following figure). Confirm your entry with <OK>.
Configuration with the MOVITOOLS® MotionStudio PC software
00
•You can also enter the network address (the part of the IP address in which the bits
of the net mask are set) in the "Broadcast IP address" entry field when integrating the
MOVI-PLC
for sending broadcast messages in the specified network. In this case, no entry is required in the field "SMLP server IP addresses".
Example:
– IP address: 10.3.71.38
– Net mask: 255.255.255.0
– Broadcast IP address: 10.3.71.255
®
advanced DH.41B controller in an existing network, filled up with set bits
•Perform a network scan after this. To do so, click on the "Scan" symbol in
MOVITOOLS
Configuration with the MOVITOOLS® MotionStudio PC software
I
5
00
Unit-specific tool
selection
•Click on the <> symbol (Scan) in MOVITOOLS® MotionStudio. The software
now displays all units connected to the engineering PC in a tree structure (see following figure).
11952AXX
•Start the PLC Editor. To do so, right-click on the "MOVI-PLC advanced DH.41B" entry, for example. Select "Programming" from the context menu. You can now create
a new project or open an existing project in the PLC Editor.
•The PLC Editor serves for programming the MOVI-PLC
ler. For further information on programming the MOVI-PLC
troller, refer to the "MOVI-PLC
manuals:
– MPLCMotion_MDX and MPLCMotion_MX libraries for MOVI-PLC
– MPLCMotion_MC07 and MPLCMotion_MM libraries for MOVI-PLC
How to configure and startup drives is described in the following library manuals:
DriveManual
®
MOVIDRIVE
MOVIAXIS
MOVITRAC® 07 / B
MOVIMOT
B
®
®
NOTE
For operation of the MOVI-PLC® advanced DH.41B controller in MOVIDRIVE
MDX61B, the MOVIDRIVE® MDX61B inverter must have at least firmware version
".16" or higher.
This applies regardless of whether the inverter is controlled via the installed
MOVI-PLC
used for installation of the MOVI-PLC
neously used to control other inverters (e.g. MOVITRAC
®
advanced DH.41B controller, or whether the slot of the inverter is only
MPLCMotion_MDX and MPLCMotion_MX libraries for MOVI-PLC
MPLCMotion_MC07 and MPLCMotion_MM libraries for MOVI-PLC
®
advanced DH.41B controller whilst simulta-
®
B).
®
®
®
5.3Configuration and startup in the PLC Editor
NOTE
•For detailed information on configuration and startup of the MOVI-PLC® advanced
DH.41B controller, refer to the MOVI-PLC
manual.
•For information on configuring the master of the different fieldbus systems, refer to
the "MOVI-PLC
When exchanging a MOVI-PLC® advanced DHF41B controller, a compact controller or
a controlled drive, proceed as described in sections 4.2 and 4.3. Plug the SD card of the
old controller into the new controller.
NOTE
The variable values stored remanently on the MOVI-PLC® advanced DH.41B controller are not stored on the SD card by default. This can be programmed through the application (IEC program), or the data backup must be imported through the project management in MOVITOOLS
You can find important information on changing drives in the manuals of the respective
inverters.
Diagnostic problem: The MOVI-PLC® advanced DHF41B controller is
not working on the PROFIBUS.
Initial status:
•The MOVI-PLC
to the PROFIBUS.
•The MOVI-PLC
DP master and bus communication is active.
The MOVI-PLC
but was either not configured in the DP master or it was configured incorrectly.
Check whether the configured PROFIBUS address is the same as the
address set on the DIP switches.
You may have configured an incorrect unit type or defined the configuration
incorrectly.
Delete the configuration for the MOVI-PLC
from the DP network.
Configure the MOVI-PLC
the unit designation 'MOVI-PLC'.
Use a predefined configuration to simplify the process. Do not change any
of the preset configuration data!
Assign the address range for your control system.
Load the configuration in the DP master and start the bus communication
again.
®
advanced DHF41B controller is physically connected
®
advanced DHF41B controller was configured in the
Is the bus connector plugged in?No →[A]
Response of the LED Fault Profi-
®
advanced DHF41B controller recognizes the baud rate,
PROFIBUS addresses identical?No →[D]
®
↓
Yes
↓
OFF →[B]
bus?
FLASHES
↓
↓
↓
Yes
↓
↓
®
advanced DHF41B controller
↓
advanced DHF41B controller again, choosing
↓
ON →
[C]
60
[A]Check the bus cabling.
[B]The MOVI-PLC® advanced DHF41B controller is currently exchanging data
cyclically with the DP master.
[C]The MOVI-PLC® advanced DHF41B controller does not recognize the
•You will have to supply the binary inputs and outputs with DC 24 V (X31:1/2) separately.
Integrated in MOVIDRIVE
•Power consumption: P
•The MOVI-PLC
connector.
•In the case of disconnection from the line voltage, continued function is guaranteed by DC 24 backup
(external DC 24 V supply to X10:9/10 of /MOVIDRIVE MDX61B required).
Installed in the MOVIAXIS® master module (MXM):
•Power consumption: P
•U = DC 24 V (–15 % / +20 %)
•I
•The MOVI-PLC
power supply module (MXS) or from an external voltage supply. For this purpose, connect X5
between the individual devices.
•If the MOVI-PLC
switched-mode power supply module, the function of the MOVI-PLC
is maintained after disconnection from the line voltage (external DC 24 V supply at X16 of the
MOVIAXIS
•Potential controller/CAN 1/COM1
•Potential COM2
•Potential binary inputs and outputs
•Potential system bus CAN 2
•Data memory: 4 MByte (for IEC application)
•Retain data: 32 kByte
•System variables (retain): 8 kByte
Isolated (optocoupler), PLC-compatible (IEC 61131-2), cycle time 1 ms, available unfiltered and filtered
(filter constant ca. 2 ms)
Can be configured as binary input or output
X31:6...X31:10 are interrupt capable (response time <100 ms)
advanced DHE41B: 1821 160 7
®
max
®
advanced DHE41B controller is supplied by MOVIDRIVE® MDX61B via backplane
max
= 600 mA
max
®
advanced DHE41B.. controller can be supplied by the MOVIAXIS® switched mode
®
advanced DHE41B controller is supplied with DC 24 V by the MOVIAXIS®
®
switched-mode power supply module required).
®
advanced DHE41B controller has the following potential levels:
MDX61B:
= 6.8 W
= 8.5 W
®
®
advanced DHE41B.. controller
Internal resistance
Signal level
Binary outputs
X31:3...X31:10
Signal level
System bus CAN 2
X32:1 ... X32:3
System bus CAN 1
X33:1 ... X33:3
Ethernet 1System bus, reserved
Ethernet 2•TCP/IP
USBUSB 1.0 for connecting an engineering PC (in preparation)
R
≈ 3kΩ, IE ≈ 10 mA
i
DC (+13 V...+30 V) = "1" = contact closed (according to IEC 61131)
DC (–3 V...+5 V) = "0" = contact open (according to IEC 61131)
PLC compatible, (IEC 61131-2) response time 1 ms
Can be configured as binary input or output
Maximum permitted output current I
All 8 binary outputs can be subject to the maximum approved output current I
"0" = 0 V"1" = DC+24 V
•System bus CAN 1 and CAN 2 to CAN specification 2.0, parts A and B, transmission technology to
ISO 11898, max. 64 stations,
•The CAN 2 system bus is electrically isolated
•Max. 64 stations per CAN system bus,
•Max. 64 SCOM transmit objects/256 receive objects per CAN system bus
•Address range 0..0.63
•Baud rate: 125 kBaud...1 MBaud
•If X32 or X33 is the bus terminator, you must connect a terminating resistor (120 Ω) externally.
•You can remove connectors X32 or X33 without interrupting the system bus.
•The system bus can be run in layer 2 (SCOM cyclic, acyclic) or in accordance with the SEWMOVILINK
•Connection options: Engineering PC, other controller, Intranet
Basic procedure for installing and removing an
option card in/from MOVIDRIVE® MDX61B
Baud rate
Bus cables
C
Communication
Configuration
Configuration and startup
Configuration and startup in the PLC Editor
Configuration and startup of the drives
Configuring the PROFIBUS interface
Connecting system bus CAN 2 (connector X32)/
CAN 1 (connector X33) of MOVI-PLC® advanced
DHE41B
Connection MOVIDRIVE® B / MOVITRAC® B Ethernet
Connection of binary inputs and outputs (connector
X31) of MOVI-PLC® advanced DHE41B
Connection of RS485 interface (connector X34) of
MOVI-PLC® advanced DHE41B
Content of this manual
Copyright notice
D
Datenaustausch PROFIBUS
DeviceNet connection (connector X30D) of
MOVI-PLC® advanced DHF41B
Diagnostic LED option of MOVI-PLC® advanced
DH.41B controller
Diagnostic procedure for PROFIBUS-DP
Diagnostic procedure for system bus
CAN 1/CAN 2
Dimension drawings
E
Engineering
Engineering interface of the MOVI-PLC®
advanced DH.41B controller
Error diagnostics
Diagnostic procedure for PROFIBUS-DP
Diagnostic procedure for system bus
CAN 1/CAN 2
......................................8
........................................10
.......15
............................. 35, 51
.........................................58
...........................................52
.......58
...............58
.................12
............17
........................19
..........................................8
...............................12
........................27
...........60
...........................66
............67
...............................51
.....60
..................................59
Exclusion of liability
F
Function description of the terminals, DIP switches
and LEDs of MOVI-PLC® advanced DHE411B
Function description of the terminals, DIP switches
and LEDs of MOVI-PLC® advanced DHF41B
Function description of the terminals, DIP switches
and LEDs of MOVI-PLC® advanced DHR41B
G
General notes
Exclusion of liability
Right to claim under warranty
Structure of the safety notes
I
Installation
Connecting system bus CAN 2 (connector
X32)/CAN 1 (connector X33) of
MOVI-PLC® advanced DHE41B
Installation MOVI-PLC® advanced DH..41B in
MC07B/compact controller
Function descriptions of terminals
and LEDs
Installation of MOVI-PLC® advanced DH.41B in
MC07B/compact controller
Connection for RS485 interface COM 1
(connector X24)
Connection for system bus CAN 1/
power supply (connector X26)
Installation of the MOVI-PLC® advanced
DHR41B controller
Installing MOVI-PLC® advanced DH.41B in
MOVIDRIVE® MDX61B
Introduction
Additional documentation
Content of this manual
IP address
L
LED 24V / I/O OK
LED CAN 1 status
LED CAN 2 status
LED DIO (n/m)
LED Fault Profibus
LED FS (FAILSAFE STATUS)
LED IEC program status
LED PIO
LED PLC status
LED Run Profibus
M
Mounting
Basic procedure for installing and removing
Mounting options for the MOVI-PLC®
MOVI-PLC® advanced DH.41B in
MOVI
MOVI-PLC® advanced DH.41B controller
Binary inputs and outputs
Characteristics
Communication interfaces
Configuring the PROFIBUS interface
Control categories
Diagnostic LEDs
Engineering
PROFIBUS monitoring functions
RS485 interface COM1
Unit types
Operating displays of the MOVI-PLC® advanced
DHR41B controller in EtherNet/IP mode
Operating displays of the MOVI-PLC® advanced
DHR41B controller in PROFINET mode
Operating displays of the MOVI-PLC® advanced
DHR41B in EtherNet/IP mode
Operating displays of the MOVI-PLC® advanced
DHR41B in PROFINET mode
Other applicable documentation
P
Pin assignment of an RJ45 plug connector
PROFIBUS connection (connector X30P) of
MOVI-PLC® advanced DHF41B
PROFIBUS monitoring functions
Project Planning and Startup
R
Replacing the unit
Resetting the IP address parameters
Right to claim under warranty
RS485 interface COM1