This document contains the Protocol Implementation Conformance Statement (PICS) and BACnet®
Interoperability Building Blocks (BIBBs) for the Setra FLEX™ as required by the American National Standards
Institute/ American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ANSI/ASHRAE) Standard
135-2012, BACnet protocol. BACnet interoperability building blocks are collections of one or more BACnet
services. This document includes a listing of the BIBBs currently supported by the Monitor.
FLEX is a native BACnet Application Specific Controller with MS/TP and IP capabilities.
2. Product Description as per Annex A PICS (normative)
Setra FLEX in conjunction with a separate Expansion I/O module (not BACnet) provide a complete solution for
monitoring and controlling critical room parameters like pressure, temperature, and humidity in healthcare and
laboratory facilities.
3.2 BACnet Interoperability Building Blocks (BIBBs) (Annex K)
Table below lists all the BIBBs that are required for the BACnet Application Specific Controller (B-ASC)
profile for FLEX. The BIBBS that are not required for B-ASC Profile but supported in FLEX are also listed.
Application Specific Controller (B-ASC) Designation
Required for B-ASC Profile
Data Sharing - Read Property – B
Data Sharing - Write Property – B
Device Management - Dynamic Device Binding – B
Device Management - Dynamic Object Binding – B
Device Management - Device Communication Control – B
Not Required for B-ASC Profile but supported in FLEX
Data Sharing - Write Property Multiple – B
Data Sharing - Read Property Multiple – B
Device Management - Reinitialize Device – B
Device Management - Time Synchronization – B
Device Management-Dynamic Device Binding-A
Device Management – UTC Time Synchronization – B
Data Sharing - Read Property – A
Data Sharing - Write Property – A
Data Sharing-COV-B
DS-RP-B
DS-WP-B
DM-DDB-B
DM-DOB-B
DM-DCC-B
DS-WPM-B
DS-RPM-B
DM-RD-B
DM-TS-B
DM-DDB-A
DM-UTC-B
DS-RP-A
DS-WP-A
DS-COV-B
Page 4 of 13
SS-FLEX-BAC-PICS REV. B 10/17/2017
Page 5
3.3 Standard Object Types Supported
3.3.1 Analog Input
Dynamically Creatable: YES NO
Dynamically Deletable: YES NO
Property Identifier
Writable
Object_Identifier No
Object_Name Yes
Object_Type No
Present_Value Yes*
Description Yes
Device_Type No
Status_Flags No
Event_State No
Out_Of_Service Yes
Units No+
Min_Pres_Value No+
Max_Pres_Value No+
Resolution No+
COV_Increment Yes
*writable only when Out_Of_Service is true
+
writable for instances 13-30
Conformance Code
Required Optional
restrictions
Range
3.3.2 Analog Output
Dynamically Creatable: YES NO
Dynamically Deletable: YES NO
Property Identifier
Object_Identifier No
Object_Name Yes
Object_Type No
Present_Value Yes
Description Yes
Status_Flags No
Event_State No
Out_Of_Service Yes
Units No
COV_Increment Yes
Max_Pres_Value Yes
Min_Pres_Value Yes
Resolution Yes
Priority_Array No
Relinquish_Default Yes
Writable
Conformance Code
Required Optional
Range
restrictions
Page 5 of 13
SS-FLEX-BAC-PICS REV. B 10/17/2017
Page 6
3.3.3 Analog Value
Dynamically Creatable: YES NO
Dynamically Deletable: YES NO
Property Identifier
Object_Identifier No
Object_Name Yes
Object_Type No
Present_Value Yes
Description Yes
Status_Flags No
Event_State No
Out_Of_Service Yes
Units No
COV_Increment Yes
Writable
Conformance Code
Required Optional
Range
restrictions
Page 6 of 13
SS-FLEX-BAC-PICS REV. B 10/17/2017
Page 7
3.3.4 Binary Input
Dynamically Creatable: YES NO
Dynamically Deletable: YES NO
Property Identifier
Object_Identifier No
Object_Name Yes
Object_Type No
Present_Value* Yes
Description Yes
Device_Type No
Status_Flags No
Event_State No
Out_Of_Service Yes
Polarity No
Inactive_Text Yes
Active_Text Yes
*writable only when Out_Of_Service is true
Writable
Conformance Code
Required Optional
Range
restrictions
3.3.5 Binary Output
Dynamically Creatable: YES NO
Dynamically Deletable: YES NO
Property Identifier
Object_Identifier No
Object_Name Yes
Object_Type No
Present_Value Yes
Description Yes
Device_Type No
Status_Flags No
Event_State No
Out_Of_Service Yes
Polarity No
Inactive_Text Yes
Active_Text Yes
Priority_Array No
Relinquish_Default Yes
Writable
Conformance Code
Required Optional
Range
restrictions
Page 7 of 13
SS-FLEX-BAC-PICS REV. B 10/17/2017
Page 8
3.3.6 Binary Value
Dynamically Creatable: YES NO
Dynamically Deletable: YES NO
Property Identifier
Object_Identifier No
Object_Name Yes
Object_Type No
Present_Value Yes
Description Yes
Status_Flags No
Event_State No
Out_Of_Service No
Inactive_Text Yes
Active_Text Yes
Writable
Conformance Code
Required Optional
Range
restrictions
Page 8 of 13
SS-FLEX-BAC-PICS REV. B 10/17/2017
Page 9
3.3.7 Device
Dynamically Creatable: YES NO
Dynamically Deletable: YES NO
Property Identifier
Writable
Conformance Code
Required Optional
Object_Identifier No
Object_Name Yes
Object_Type No
System_Status No
Vendor_Name No
Vendor_Identifier No
Model_Name No
Firmware_Revision No
Application_Software_Version No
Location Yes
Description Yes
Protocol_Version No
Protocol_Revision No
Protocol_Services_Supported No
Protocol_Object_Types_Supported No
Object_List No
Max_APDU_Length_Accepted No
Segmentation_Supported No
Local_Time No
Local_Date No
APDU_Timeout No
Number_Of_APDU_Retries No
Max_Master No
Max_Info_Frames No
Device_Address_Binding No
Database_Revision No