Setra SRPM Operating Manual

Model SRPM
Room Pressure Monitor
Installation and Operating Manual
1
Setra SRPM Room Pressure Monitor
The Setra SRPM Room Pressure Monitor is designed for critical low
differential pressure applications that require stringent pressure monitoring
and alarming. The SRPM can be congured to monitor positive, negative or neutral pressure in protected environments and hospital isolation rooms
per CDC guidelines. The SRPM is a complete system that includes a backlit
RGB LCD display with a graphic user interface, which enables access to pressure, security, calibration, and alarm setup. The touch-screen displays menus that guide the user through setup, as well as setting up password
protection. Red and green LED’s and a local audible alarm (with time delay feature) alert personnel to system status. The SRPM has a NEMA 1 (IP20)
rated re retardant plastic housing for indoor applications. True differential pressure is displayed with a resolution of .0001”. Setra’s patented very low pressure capacitance sensor is dead ended and avoids the potential for
cross contamination of the room and reference space as well as eliminating
drift that results from fouling of ow based sensors, which by nature have a ow path connecting the protected and reference spaces. Additionally there are 2 levels of password protection available as well as optional BACnet
MSTP communications.
2
Table of Contents
1.0 Intended Use ..................................................................................4
1.1 Specications ............................................................................4
1.2 SRPM Function .........................................................................5
2.0 Parts ..............................................................................................6
2.1 SRPM Included parts.................................................................6
2.2 SRAN Included parts ................................................................. 6
2.3 RPS included parts .................................................................... 6
2.4 Parts required and to be supplied by installer ...........................6
3.0 Installation ......................................................................................7
3.1 Wiring (Rough in).......................................................................7
3.2 Plumbing ...................................................................................9
3.3 Wiring (Finish) ........................................................................10
3.3.1 Alarm Relay ..........................................................................10
3.3.2 Remote Annunciator .............................................................10
3.3.3 Door status input .................................................................. 11
3.3.4 Analog Output ....................................................................... 11
3.3.5 BACnet .................................................................................12
4.0 Startup and Operation ..................................................................13
4.1 Menu Tree ...............................................................................13
4.2 Power Up ................................................................................. 13
4.3 Monitoring Screen ...................................................................13
4.4 Main Menu ............................................................................... 14
4.5 Setup Unit ................................................................................ 15
4.6 Setup Room.............................................................................17
4.7 Setup Alarms ...........................................................................18
4.8 Self Test ...................................................................................19
4.9 Calibration ...............................................................................20
4.10 BACnet Setup Screen ............................................................21
5.0 Remote Annunciator ..................................................................... 23
6.0 Maintenance ................................................................................. 24
7.0 Agency Electrical Standards .........................................................25
8.0 Wiring and Plumbing Overview ....................................................26
9.0 Menu Tree ....................................................................................27
3
1.0 INTENDED USE
The SRPM is designed to monitor critical environments by providing
differential pressure indication. Typically this is between a monitored room and a reference space such as a corridor or ante room. The unit
also provides monitoring, alarm and communications functions.
Installation must be indoors, Polution Degree 2, Installation Category II.
Failure to install per these instructions may impair the safety of the unit.
Typical Applications:
1. Hospitals – patient isolation and protection rooms, operating
suites, intensive care, and emergency rooms.
2. Pharmaceutical, semiconductor, precision manufacturing, and
clean rooms.
3. Laboratories – medical research, BSL (Bio safety labs), radiation,
vivarium, toxic metals and chemicals. Indoor use only.
1.1 SPECIFICATIONS
Service Air or nonconductive, nonexplosive gas
Accuracy ±0.5% F.S., ±0.25% FS optional
Operating Temperature Limits 32 to 120°F (0 to 50°C)
Operating Humidity Limits 5 to 95% Relative humidity (non condensing)
Altitude 2000 meters (max)
Thermal Eects ±0.03% F.S./ °F (± 0.05% F.S./ °C)
Overpressure ±15” W.C.
Supply Voltage Code V1 and V2 85-265 VAC, 50-60 Hz
Code A1 and A2 18-32 VAC, 50-60 Hz
Power Consumption (Voltage Output) 5 W.
Output Selectable 4-20 mA (2-wire), 0-5 VDC (3-wire), or
0-10 VDC (3-wire)
Loop Resistance (4-20mA Output) 0-510 OHMS
Electrical Connection Removable terminal block
Pressure Fittings Barbed ttings for 1/4” O.D. tubing
Housing Fire retardant plastic (NEMA 1, IP20 rated for indoor
applications)
Mounting Mounts to customer supplied 4” plaster ring
(mounts to 2-gang electrical box)
Dimensions 8½ H x 5.4½ W x 1.8½ D (20.3 H x 13.7 W x 4.1
Weight (approx.) 1.5 lbs (680 g)
Agency Approval
Communications
CE, CAN/CSA-C22.2 NO. 61010-1-04
BACnet MSTP ASC, optional, see setra.com
for detailed PICS statement
4
1.2 SRPM FUNCTION
The SRPM senses very low differential pressure using high accuracy capacitive sensor technology. The pressure difference for these
applications is the difference in static pressure between a critical
environment room and its surrounding reference area (usually a hallway
or another room). Maintaining and monitoring a static room pressure
difference ensures that the critical environment room is either protected or isolated from a surrounding environment. Protection strategy requires a net positive room static pressure difference, while isolation requires a net negative static pressure difference. The SRPM can be programmed to monitor either positive or negative room static pressure. Low pressure
sensing technology is coupled with multifunctional alarming and simple touch screen user interface with password security protection. The BACnet
communication option allows the device to communicate with other BACnet devices to allow the supervisory system to change conguration
setups and monitor alarms in an open network.
User Interface: LCD Display 128 x 128 COG module, with custom RGB
LED backlight and custom 4-wire resistive touch screen
RGB Backlight. The SRPM indicates the status of the room being
monitored using visual backlight color.
Color Status
Green Room Pressure is within alarm limits
Yellow Door is open. (Door input must be enabled)
Red Room Pressure is outside alarm limits and
alarm delay period has been exceeded and
room is not in “No Isolation” mode.
Visual Feedback: LEDs, green for normal, red for alarm
Audible Feedback: Beeper will sound when pressure is out of range and
alarm delay has timed out. Volume can be adjusted between 1 to 4 in
relative sound levels up to the maximum level specication of the beeper
of 85 dB at 4”. Audible alarm can also be disabled.
Quick Room Mode Change: Sometimes the room needs to be changed quickly from in use (Occupied) to out of use (No Isolation). This is
accomplished by using 2 levels of password protection. The Operator level allows access to change room modes but no other changes. The Supervisor Level allows full access to all menus. In No Isolation mode no alarms are generated even if the pressure is outside limits. To change modes see page 22, Room Mode Change, for directions to change modes.
5
2.0 PARTS
2.1 SRPM (Setra Room Pressure Monitor) INCLUDED
PARTS
Quantity
1 SRPM assembly
2 Barbed Couplings, with Silicone Tubing
4 6-32 x 1/2” Mounting Screws for connecting
the SRPM Base to the plaster ring
2.2 SRAN (Setra Remote Annunciator) INCLUDED PARTS
Quantity
1 Annunciator Assembly
2.3 RPS (Room Pressure Snubber) INCLUDED PARTS
Quantity
1 Room pressure snubber Assembly
2.4 Parts required and to be supplied by installer
MOUNTING AND WIRING
To mount and install properly, the following components are required:
NOT INCLUDED and required for each SRPM
Quantity
1 2-Gang Metal Electrical Box with Grounding Stud
1 4 inch Metal Plaster Ring
1 Door Switch SPDT or SPST, N.O., as needed
NOT INCLUDED and required for each remote annunciator and room pressure snubber
Quantity
1 1-Gang Electrical Box
1/4 “ tubing as required to connect between the RPS
(Room Pressure Snubbers) and the SRPM
6
3.0 INSTALLATION (See Section 8.0 for overview)
For 120/240 VAC Version, only
The SRPM is designed to be mounted on a standard double gang metal
electrical box using a 4 x 4 inch plaster ring adaptor. After the rough in wiring and plumbing is performed remove the cover and mount the baseplate to the plaster ring adaptor using the supplied 6-32 x 1/2” long mounting screws. Note: The plaster ring external mounting face needs to be positioned ush to recessed, relative to the surface of the wall. Also note the orientation of the 4 mounting screws in the plaster ring, as the plaster ring is rotated 90° from conventional mounting.
Note: In the following wiring sections, abbreviations are used (e.g. J1, P3). Please see section 8.0 for complete wiring diagrams with abbreviations.
CAUTION: Do not open or remove SRPM cover (tool required) with input power ap­plied unless performed by a licensed electrician. “Hazardous Live” voltage is present
!
at connector J3 when power is applied. Please observe the warning symbol ( ) near the J3 power connector.
Electrical Box
4 x 4 inch Plaster Ring (Rotated 90°)
SRPM Metal Base
!
SRPM Cover
3.1 WIRING ELECTRICAL BOX (ROUGH IN)
Layout the system in terms of wiring: power, annunciator, analog output, BACnet, relay output and plumbing to connect to the monitored spaces
(pressure taps).
Bring all power, earth ground, signal, communications and analog output wiring into the 4x4 electrical box. Bring 1/4” O.D. tubing for 3/6” Barb tting into box.
In order to conform to the CSA safety standard the electrical installer must comply with the following earth ground instructions:
1. Pre-wire the electrical box with power (24 VAC or 120/240 VAC), and provide earth grounding to the electrical box. The safety ground path consists of four 6-32 x 1/2” metal screws that connect the SRPM metal base to the 4½ x 4½ metal plaster ring. The plaster ring must be ground­ed to the 4½ x 4½ electrical box by 2 metal mounting screws. The 4½ x 4½ electrical box must be connected to the building earth ground. In ad­dition, the marked ground wire included in 120/240 VAC version, should
7
be connected to the electrical box earth ground connection. It is also
highly recommended to use armored cable (Type AC) for all the wiring in
applications where high levels of radio interference may be present.
2. For the 120/240 VAC version only, a switch or circuit-breaker should be included in the building installation. It is advised to indicate the loca­tion of the switch or circuit-breaker by means of a label on or nearby the installed device. The disconnection switch or circuit-breaker should dis­connect all current-carrying con ductors. Any line-connected single-pole
switch should be connected to a terminal intended for connection to the ungrounded conductor of the supply circuit.
Power leads, analog output, door status, and annunciator wiring should be
14 to 22 AWG stranded wire.
BACnet suggested wiring is 22 AWG stranded wire in a shielded cable, a +,-, Gnd (S) and shield should be run. This can be 2 twisted pairs with a separate cable shield. One twisted pair is used for communications,
the second twisted pair can be used for communications ground and the
shield wire can be connected to the other device shield wires. For CE compliance, a properly grounded shielding cable is requried.
8
3.2 PLUMBING (ATTACHING PRESSURE TUBING)
Warning: Always attach tubing to the SRPM header and then place Header onto SRPM. This will prevent overpressure from crimped or collapsed tubes.
Use the following procedure for all room types: positive, negative or
neutral:
Typically a Room Pressure Snubber (RPS) is installed in the monitored room. Often stiff nylon ¼” tubing is used for running pressure signals
from the SRPM to the monitored spaces. To prevent buckling and collapse of this stiff tubing inside the electrical box, use the supplied soft silicone tubing and tubing adaptors to transition from the eld tubing to the pressure ttings on the SRPM.
Attach pressure tubing as follows:
1. Connect the 1/4 inch O. D. tubing running from the RPS (or other pressure connection from the monitored space) to the 2-gang electrical box for the SRPM. Install one of the supplied 1/4 inch male
to male barbed tube adaptors onto the end of the tube then push the
4” length silicone tube (supplied) onto the other end. Thread the tubes, with installed adaptor, through the conduit opening at the bottom of the electrical box.
2. Next push the open end of the silicone tubing onto the SRPM
pressure tube header (H1) port labeled “+”. Note: The header is an
Electro-Pneumatic (EP) assembly. “+” indicates (Positive) pressure, and “-” indicates negative or reference pressure.
3. For the most pressure stable operation, an RPS installed in the reference pressure area is also recommended. In this case, install the
RPS in a hallway or reference space. Attach the tube to the SRPM in the
same way as for the + port, except attach the tube to the “-” port on the pressure tube header. Tighten swivel ttings on the SRPM Header H1 assembly if they become loose, 9 in lb. max. Verify that the tubes are not buckled, which could close off pressure signal at end of installation.
Silicone Tubing
SRPM Header H1
Electrical Box
RPS Tubing
RPS Room Pressure SnubberPlumbing inside Electrical Box
9
3.3 WIRING, FINISH
3.3.1 ALARM RELAY OUTPUT
The Single Pole Single Throw (SPST) relay output can be used for remote
signaling of alarm condition. A form “C” contact rated at 1A is available. Connect to J4, P1 and P4 (See Section 8.0 for Diagram of J4). This relay can be used as a dry contact for remote indication or can drive an SRAN
remote annunciator.
3.3.2 OPTIONAL REMOTE ANNUNCIATOR WIRING
Setra SRAN wiring
In the gure below, the SRAN remote annunciator connector is at left, and
the SRPM connector is at right:
On J4 of the SRPM, jumper P1 to P2, this will connect the internal
15V supply to the common of the internal alarm relay. Connect P2 to
A1 (Located on Remote Annunciator), this supplies 15V exc. to the
Annunciator for powering the circuit during normal conditions. Connect P3
of J4 to A2 of SRAN J1, this is the 15V power return. Finally connect P4 of SRPM J4 to A3 terminal of SRAN J1, this is the alarm trigger.
When an alarm occurs and after the programmed alarm delay times out the internal relay will supply 15 V to the Annunciator circuit to actuate the audible beeper and the red LED.
J1: SRAN
+15 VDC Excitation A1
Ground A2
+15 VDC Trigger A3
Jumper
J4: SRPM
P4 (Annunciator Trigger
P3 (Ground)
P2 (+15 VDC Excitation)
P1 (Relay N.O.)
Non-Setra Remote Annunciator
The SRPM can drive other annunciators that are powered by a 15V sup­ply, 50 mA max current draw., and accept a 15V trigger (wire as above).
10
Audible Alarm
Potentiometer
The volume control on the Annunciator is a potentiometer that can be adjusted from 0 to 85 dB. Using a small at bladed screwdriver, rotate
potentiometer (remote annunciator PC board) clockwise to increase
volume and counterclockwise to decrease volume.
3.3.3 DOOR STATUS SWITCH WIRING
Install the door switch into the door jamb. Wire to the normally open (N.O.) side of the door jamb contact switch. The SRPM will indicate the status of door position. A contact closure indicates that the door is closed. This is a
low voltage circuit (5 VDC). Run 2 wires from the door switch to connector J6 on the SRPM (See Section 8.0). The door input status function is enabled in the SETUP ALARMS menu screen, section 4.7
3.3.4 ANALOG OUTPUT
The SRPM can be congured to have either current (4 to 20 mA) or voltage (0 to 5 or 0 to 10 VDC) outputs. Voltage output--pin 1, Current output--pin 2, Common--pin 3. Note: No external excitation is required.
Note1: No external excitation is required.
Note 2: Electro-pneumatic header (page 9) must be connected.
Note 3: For CE compliance a properly grounded shielding cable is required.
Current Output
The SRPM supplies it’s own loop power, do not wire in a separate power
supply.
Voltage Output
1. V Out: 0 to 5, 0 to 10 VDC
2. C Out: 4 to 20 mA
3. Common
+
l
l
Receiver
(mA)
11
1. V Out: 0 to 5, 0 to 10 VDC
2. C Out: 4 to 20 mA
+
l
Receiver
(V)
3. Common
3.3.5 BACnet
BACnet hardware is implemented as isolated RS485. Wire to Connector
J2, labeled RS-485. Connect tx line to +, rx to – and ground wires to S.
Connect Shields together with wire nut.
Hardware conguration is done using a 5 position dip switch (S1) located
in the upper right hand section of the PCBA as well as through the touch
screen interface, see Section 4.4. and 4.9.
Position Function
1 2 3 4 5
Use a small at blade screwdriver or pen to push the switch to the right to turn that function on, otherwise it is off.
There is a BACnet setup screen that is enabled by pushing position 1
switch to the “on” position. After conguration the switch must be moved
to the “off” position.
MAC address enable
N/C Not Connected
Pull Up Resistor
Termination Resistor
Pull Down Resistor
l
12
4.0 STARTUP AND OPERATION
The SRPM is designed with as an easy to use, intuitive, touch screen
interface. In its normal (default) state the Monitoring Screen displays the actual
room static pressure, also a slider bar shows the actual pressure relative
to the alarm limits. The RGB backlight is used to indicate the condition of
the room. The buttons at the bottom of the screen give you access to the
functions that can be performed.
4.1 MENU TREE See section 9.0
4.2 POWER-UP
Apply power and observe the welcome screen and subsequent transition
to the pressure monitor screen. The actual room static pressure is shown
as a number in the center of the LCD and visually as a moving bar indicator operating between the preset alarm units. The vertical bar is an
indicator of the pressure.
4.3 MONITORING SCREEN
BUTTON DESCRIPTION
Silence Menu Reset
Shuts off Alarm Access to Main Menu Functions Resets the unit in “Latched” mode.
13
The following screens are conguration screens, they can be congured
so that Password protection is required to make changes. If no entry is
made to the screen the unit will return to the default screen after approx.
1 minute.
4.4 MAIN MENU SCREEN
BUTTON DESCRIPTION
Unit
Room
Alarm
BACnet Conguration of BACnet Communications
Self Test
Calibration Perform zero and span calibration.
Back Returns to monitoring screen.
Setup Supervisor password, output, engineering units, and display averaging.
Set up high and low pressure limits to monitor
a positive, negative, or neutral room.Operator
password setup.
Setup latch alarm, audible alarm, door alarm input, mute time out, alarm delay, and volume.
Identies product model and software version, and
serial #.
Veries memory and performs alarm test.
14
4.5 SETUP UNIT OPERATION
ENTERING DATA Press (or tap) button to select an output or
engineering unit. Selected button background will change from clear to black.
PASSWORD PROTECTION
Lightly pressing (or tapping) the “Yes” button activates Supervisor password protection. With Supervisor password protection enabled,
operators can not access menu screens to update setup. Pressing “No” disables password protection. Pressing “Change” will open “Password
Setting Screen”. To change the password, enter the present password (numeric value), followed by the new password in the “New Password” and “Conrm New Password” entry boxes, then press save. Be careful to
store password for future reference.
Analog Output
Select : 4-20, 0-5, or 0-10
Eng. Unit
Select: “WC, Pa, cmWC
DISPLAY AVERAGING
Lightly pressing (or tapping) the “Display Averaging” box activates the “Data Entry Screen”). Enter from 0 to 60 seconds. Display averaging affects the analog output. Increase the display averaging time to smooth out the pressure readings, this will also reduce the display update rate.
15
Press Save and Exit.
DATA ENTRY SCREEN
Enter numbers by pressing each key in sequence until the desired
character is displayed in the data entry box above the keypad. (Note:
The cursor will blink for one to two seconds then stop and display the character.) Erase any mistakes by using the “Back Space” key. When
nished entering data, press the “Enter” key to return to SETUP UNIT
screen.
Note: Use the eraser end of a pencil or back-end of a pen to press (or tap) box on screen to increase accuracy of inputs.
16
4.6 SETUP ROOM SCREEN
SETUP ROOM OPERATION
Setup alarm limits for “protective” positive room static pressure, “isolating” negative room static pressure or neutral (where the limits can
be – to +).
ENTERING DATA
Press lightly or tap in the Lower Limit data entry box. Enter the lower limit pressure. Enter the Upper Limit pressure. The Room type box will
change depending on the lower and upper limits. If both entries are
positive, the room will be a Positive Room. If both are negative, the room will be a Negative Room and if the Lower Limit is negative and the Upper Limit is positive the room will be a Neutral Room.
OPERATOR PASSWORD
The operator can only change the room from Occupied to No Isolation
and vice versa.
Lightly pressing (or tapping) the “Yes” button activates Operator password protection. With Operator password protection enabled, room Occupied/No Isolation status can not be changed without entering a valid Operator password. Pressing “No” disables password protection.
Pressing “Change” will open “Password Setting Screen”. To change the
password, enter the present password, followed by the new password in the “New Password” and “Conrm New Password” entry boxes, then press save. Be careful to save the operator password for future
reference.
17
4.7 SETUP ALARMS SCREEN
From this screen the user can access the following:
a. Latched Alarm requires the pressure to return to normal and the alarm to be acknowledged before the alarm can be silenced and reset.
b. Enable the audible alarm by selecting “Yes” or use visual only alarm
by selecting “No”.
c. Provide a “door open” warning visual indication. When a door jamb contact switch is used and this button is activated by pressing “Yes”,
the door status “open” condition is indicated by the touch screen
display turning from green to yellow, and door open indicated on the
monitoring (default) screen.
d. Set the time (in seconds) that the alarm can be silenced in the
latched alarm mode before the alarm resumes. This assumes that the room static pressure is still outside the normal or set operating limits. The Mute Time Out can be set from 0 to 9999 seconds.
e. Set the Alarm Delay (in seconds) from the time that the room
pressure goes out of the preset limits until the alarm activates. The
alarm delay may be set from 0 to 9999 seconds.
f. Set the alarm volume or sound level. Using the Up and Down keys,
the volume can be set at level 1-4. Level 4 alarm volume is the loudest and corresponds to a sound level of 85 dB at a distance of 4
inches.
ALARM SETUP OPERATION
Lightly press (or tap) button to select “Yes” or “No” for Latch Alarm, Audible Alarm, or Door Alarm Inputs. Selected box background will
change from clear to black when selected.
MUTE TIME OUT/ALARM DELAY
Pressing (or tapping) the “Mute Time Out” or “Alarm Delay” box activates
the Data Entry screen to set the time delay duration.
18
4.8 SELF TEST SCREEN
Self Test Operation
This screen identies the Product Model Part Number and Software Version. User can also perform a Self Test of the unit to verify that the
data in protected area of the EEPROM memory hasn’t been corrupted
and also test the alarm to verify the sound level and alarm setup.
Press “Self Test” button to initiate EEPROM memory checksum test sequence.
Press “Alarm Test” to test beeper, visual Red LED Alarm, and relay output. This can be used to verify the system in alarm mode.
Press “Cancel Test” to stop the alarm test.
Press “Exit” to return to Main Menu.
19
4.9 CALIBRATION SCREEN
CALIBRATION
To re-zero the device, disconnect the pneumatic tubing from Header
H1 so that room pressures are not applied to the pressure sensor and
lightly press (or tap) the “Zero” button. If a sufciently accurate Pressure Calibrator is available, apply a steady full-scale pressure signal to the “+” on the header tting and press (or tap) the “Span” button. Reconnect
the room pressure tube and calibration is complete. Calibration must be within ±5% of original calibration for this to occur otherwise an error message will occur.
The original factory pressure calibration can be restored, if desired, by
pushing the “Restore Factory Setting” button.
20
4.10 BACnet Setup Screen
BACnet Setup
To setup up BACnet communications, the MAC address enable switch
(S1 [See Section 8]) on the dip switch must be enabled by pushing it to the right.
Set MAC address, input the address of the device.
Select Device Instance by inputting the device instance into the data entry box.
Select baud rate by pressing the correct baud rate button, 9600 to
76800.
Save and Exit to save settings or Cancel to cancel setting changes. Once complete disable the BACnet setup by moving the dip switch
position 1 to “off” (left) position.
If the unit will be at the end of the line, the pull up resistor can be enabled
by pushing position 3 to “on”.
The termination resistor can be inserted by pushing position 4 switch “on”. The pull down resistor can be enabled by turning position 5 to “on”.
Save and Exit. After the unit returns to the main menu screen disconnect the power to the unit, then re-connect to boot up with the proper MAC address and Device Instance.
Position Function
1 MAC address enable 2 Not Used 3 Pull Up Resistor 4 Termination Resistor 5 Pull Down Resistor
See Setra website for information on Points list and PICS and BIBBS statements.
21
Click here to access ROOM MODE Screen
PRESSURE MONITORING SCREENS
At completion of setup, the main display will be the pressure monitoring screen, which displays the actual room static pressure.The room static pressure is shown as a number on the LCD as well as a “Moving Bar”
indicator operating between the preset pressure limits. Normal room
pressure conditions within the preset pressure limits are veried by
a green colored screen. When the door is opened under conditions
within the preset pressure limits, the screen turns to yellow. Room static
pressure outside of the preset limits is indicated by a Red screen after
the alarm’s time delay expires.
CHANGING ROOM MODES
The SRPM can quickly be changed from active monitor and alarming to
No Isolation (or unoccuped). To do this touch the room mode indicator at
the top of the pressure monitoring screen (see above).
OCCUPIED/NO ISOLATION
Use these buttons to quickly change the room to Occupied (Standby) or No Isolation status. If No Isolation is used there will be no alarms generated if the room is outside pressure limits.
Press Save and Exit.
22
5.0 REMOTE ANNUNCIATOR
The Remote Annunciator provides remote indication of room status.
Audible Alarm
Green LED
Red LED
Audible Alarm
Acknowledge Switch
Green LED
Red LED
Acknowledge Switch
Visual indication of normal room condition. Visual indication of a breach in room pressure protection. Beeper sounds to indicate breach in room pressure protection.
Press to silence beeper.
OPERATION
Under normal conditions, the green LED remains on. When an alarmed condition occurs (i.e., room pressure falls outside preset range), a signal is triggered by the SRPM, the green LED shuts off, the red LED ashes,
and the audible alarm sounds. The acknowledge button can be pressed
to momentarily turn-off the audible alarm and the red LED will continue to ash until the alarmed condition is corrected. When the alarmed
condition is corrected the annunciator will reset itself. The green LED
will turn on, and the red LED and audible alarm will shut-off. If the SRPM reaches the mute time out limit it will re-sound the alarm.
23
6.0 MAINTENANCE
The SRPM is designed to operate in an indoor environment, monitoring clean, dry air.
Upon nal installation of the SRPM Room Pressure Monitor, no routine
maintenance is required. A periodic check of system calibration is
recommended. The SRPM is not eld serviceable and should be returned if repair is needed (eld repair should not be attempted and may void warranty). Be sure to include a brief description of the problem plus any relevant application notes. Contact customer service to receive a
return goods authorization number before shipping.
CLEANING Important
Do not blow into the pressure tubing or ttings with mouth, compressed air, or canned air. Such actions may permanently damage the pressure sensor. Do not clean or wash-down the SRPM with industrial cleaners or solvents. The housing may be wiped down with soap and water or
isopropyl alcohol. The LCD may only be cleaned with isopropyl alcohol. Do not immerse unit.
24
7.0 AGENCY ELECTRICAL STANDARDS
This device falls into CSA “Pollution Degree 2” for PCB insulation and
CSA “Installation Category 2”.
The SRPM meets the following requirements:
CSA Standard C22.2 No 0-M 91: General Requirements - Canadian electrical code, Part 1
CAN/CSA C22.2 No. 0.4-04: Bonding of Electrical Equipment
CAN/CSA-C22.2 No. 61010-1-04: Safety requirements for electrical
equipment for measurement, control and laboratory Use Part-1: General
Requirements
ANSI/UL61010-1 (Third Edition): Safety requirements for electrical
equipment for measurement, control and laboratory use Part 1: General
Requirements.
25
8.0 LOCATION OF COMPONENTS AND ACCESSORIES
26
9.0 MENU TREE
27
10.0 RETURNING PRODUCTS FOR REPAIR
Before returning the unit for repair, please contact a Setra application engineer (800-257-3872, 978-263-1400) to review information relative to your application . Many times only minor eld adjustments may be necessary. When returning a product to Setra, the unit should be carefully packaged and shipped prepaid to: Setra Systems, Inc.
159 Swanson Road Boxborough, MA 01719-1304 Attn: Repair Department
To assure prompt handling, please refer to return instructions on our Web site at: http://www.setra. com/tra/repairs/cal_rep.htm.
Allow approximately 3 weeks after receipt at Setra for the repair and return of the unit. Non-warranty repairs will not be made without customer approval and a purchase order to cover repair charges.
Calibration Services
Setra maintains a complete calibration facility that is traceable to the National Institute of Standards & Technology (NIST). If you would like to recalibrate or recertify your Setra pressure transducers or transmitters, please call our Repair Department at 800-257-3872 (978-263-1400) for scheduling.
11.0 WARRANTY AND LIMITATIONS OF LIABILITY
Setra warrants its products to be free from defects in materials and workmanship, subject to the following terms and conditions:
Without charge, Setra will repair or replace products to be found to be defective in materials or workmanship within the warranty period; provided that: a.) the product has not been subjected to abuse, neglect, accident, incorrect wiring not our own, improper installation or servicing, or use in violation of instructions furnished by Setra; b.) the product has not been repaired or altered by anyone except SETRA or its authorized service agencies; c) the serial number or product code has not been removed, defaced, or otherwise changed; and
d) examination discloses, in the judgement of SETRA, the defect in materials or workmanship developed under normal installation, use and service; e) SETRA is notied in advance of and the product is returned to SETRA transportation prepaid. Unless otherwise specied in a manual or warranty card, or agreed to in a writing signed by a SETRA ocer, SETRA pressure and acceleration products shall be warranted for one year from date of sale. The foregoing warranty is in lieu of all warranties, express, implied or statutory, including but not limited to, any implied warranty of merchantability for a particular purpose. SETRA’s liability for breach of warranty is limited to repair or replacement, or if the goods cannot be repaired or replaced, to a refund of the purchase price. SETRA’s liability for all other breaches is limited to a refund of the purchase price. In no instance shall SETRA be liable for incidental or consequential damages arising from a breach of warranty, or from the use or installation of its products. No representative or person is authorized to give any warranty other than as set out above or to assume for SETRA any other liability in connection with the sale of its products.
For all CE technical questions, contact Setra Systems, USA. EU customers may contact our EU representative Hengstler GmbH, Uhlandstr 49, 78554 Aldingen, Germany (Tel: +49-7424-890; Fax: +49-7424-89500).
159 Swanson Road, Boxborough, MA 01719
Tel: 800-257-3872 Fax: 978-264-0292
Email: sales@setra.com Web: www.setra.com
SS-SRPM351 Rev F 12/13/13
28
Loading...