Model SRPM
Room Pressure Monitor
The SRPM is Setra’s standard single room BACnet capable
room pressure monitor for measuring low dierential pressure in critical applications. The SRPM’s backlit touchscreen
LCD provides an intuitive graphic user interface for ease of
setup. The SRPM has a built-in calibration feature and only
requires zeroing when installed, signicantly reducing the
cost of ownership. The SRPM monitors and alarms while providing a digital input for a door alarm. The SRPM is a simple,
cost-eective solution which combines state-of-the-art electronics with Setra’s superior true dierential pressure sensing technology to ensure safety in critical environments. The
SRPM also incorporates two-level password protection.
Monitor & Alarm Critical Rooms
The SRPM is most user friendly room pressure monitor on
the market today. It has an intuitive touchscreen interface
that allows the user to easily congure alarm set points,
passwords and audible alarming conditions. With its bi-directional sensor, the unit can switch between protection and
isolation room modes, or be put into standby mode when
the room is not in use.
On-Board Dead-Ended Pressure Sensor
Protection and isolation rooms are designed to adhere to
strict standards in order to provide a proper barrier between
the room and reference space. Unlike a ow-through design,
the SRPM utilizes an on-board dead-ended low dierential
pressure sensor. This technology provides the user with a
trusted solution & peace of mind that the sensor will prevent
contaminated air from passing through it.
Save Time and Money on Installation & Calibration
The SRPM is designed with both the installer and end user in
mind. The BACnet enabled unit can be installed in an o-theshelf electrical box, improving the ease of installation instead
of having to use a custom electrical box that is not typically
available at the rough stage of the project. The SRPM oers
push button zero and span calibration that is easily performed by any low dierential pressure calibrator and can be
calibrated in minutes.
n Maximize Patient Safety
n Save on Installation Costs
n Low-Cost BACnet Solution
Model SRPM Features:
• On-board Sensor - Industry Best Accuracy
• LCD Touch Screen for Easy Setup and Room Display
• Monitor Single Pressure Relationship and Door Status
• Congurable Audible & Visual Alarms to Avoid Nuisance
• Easy Surface Mounting - Wall Thickness is Irrelevant
• Increased Safety with 2 Layer Password Protection
• Calibration: Only Requires Zeroing Once Installed
Where We’re Installed:
• Brigham and Women’s Hospital
• Emory University Medical Center
• Memorial Sloan Kettering Cancer Center
• Stanford University Medical Center
• Veterans Aairs (VA) Medical Center
Phone: 800-257-3872 • Fax: 978-264-0292 • setra.com © Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc.
Model SRPM
Room Pressure Monitor
ORDERING INFORMATION
S R P M
Model Range Code Excitation/Output Accuracy
SRPM = SRPM
RANGE CODE INCHES W.C.
005WB ±5
2R5WB ±2.5 A2 24 VAC w/ BACnet®
001WB ±1.0 V2 120/240VAC BACnet®
0R5WB ±0.50
R25WB ±0.25
0R1WB ±0.1
Ordering Example: Part No. SRPM005WBA1E for a SRPM, ±5 in. W.C. Range, 24 VAC EXC. with 4 to 20 mA output, and ±0.5% FS Accuracy.*
Please contact factory for versions not shown..
24 VAC/4-20 mA or
A1
0-5 and 0-10 VDC
V1 120/240 VAC/4-20 mA
or 0-5 and 0-10 VDC
E ±0.5% FS
V ±0.25% FS
"BACnet" is a registered
trademark of ASHRAE"
DIMENSIONS GENERAL SPECIFICATIONS
Performance Data Environmental Data
Standard Optional Operating Temp.3 °F (°C) 32 to +120 (0 to +50)
Accuracy RSS
Non-Linearity (BFSL) ±0.49% ±0.24% Operating Humidity 5 to 95% RH
Hysteresis ±0.05% ±0.05%
Non-Repeatability ±0.05% ±0.05% Circuit 3-Wire (Exc, Out, Com)
Span Setting Tol.
Thermal Eects
Compensated Range (oFoC) 40 to 120 (4.5 to 50) Power Consumption 5W
Zero/Span Shift %FS ±0.03% FS (±0.05%FS) Excitation:
Overpressure ±15”W.C.
Physical Description
Case Fire-Retardant Plastic
Dimensions 8”H x 5.1”W x 1.8”D
Electrical Connection Removable Terminal Block Output 4 to 20 mA
Pressure Fittings Barbed Fittings 1/4” O.D.
Weight (approx.) 1.5lbs (680g) Excitation:
1
RSS of Non-Linearity, Hystereis, and Non-Repeatability.
2
Units calibrated at nominal 70oF. Max thermal error computer from this datum.
3
Operating temperature limits of the electronics only.
4
Calibrated into a 50K ohm load, operable into a 5000 ohm load or greater
5
Zero setting tol. negated by zero push button
Specications subject to change.
1
±0.5% ±0.25% Storage Temp. °F (°C) -20 to +160 (-30 to +170)
(Non-Condensing)
Electrical Data (Voltage)
5
2
±0.5% Rdg. ±0.5% Rdg. Output
4
0 to 5 VDC, 0 to 10 VDC
Alarm Output SPDT Relay: 1A @ 24 VDC,
1A @ 120 VDC
Code V1
Code A1
Code V2
Code A2
85-265 VAC, 50-60 Hz
18-32 VAC, 50-60 Hz
85-265 VAC, BACnet®
18-32 VAC, BACnet®
Electrical Data (Current)
(NEMA1, IP20 Rated for
Indoor Applications)
(203 x 130 x 46 mm)
Tubing
Circuit 2-Wire
External Load 0 to 510 ohms
Code Vi:
Code A1
85-265 VAC, 50-60 Hz1
8-32 VAC, 50-60 Hz
8.0
203
5.1
130
2.17
55
4.61
117
1.8
46
mm
in.
Phone: 800-257-3872 • Fax: 978-264-0292 • setra.com © Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc.