Setra SRPM Specifications

Model SRPM
Room Pressure Monitor
The SRPM is Setra’s standard single room BACnet capable room pressure monitor for measuring low dierential pres­sure in critical applications. The SRPM’s backlit touchscreen LCD provides an intuitive graphic user interface for ease of setup. The SRPM has a built-in calibration feature and only requires zeroing when installed, signicantly reducing the cost of ownership. The SRPM monitors and alarms while pro­viding a digital input for a door alarm. The SRPM is a simple, cost-eective solution which combines state-of-the-art elec­tronics with Setra’s superior true dierential pressure sens­ing technology to ensure safety in critical environments. The SRPM also incorporates two-level password protection.
Monitor & Alarm Critical Rooms
The SRPM is most user friendly room pressure monitor on the market today. It has an intuitive touchscreen interface that allows the user to easily congure alarm set points, passwords and audible alarming conditions. With its bi-di­rectional sensor, the unit can switch between protection and isolation room modes, or be put into standby mode when the room is not in use.
On-Board Dead-Ended Pressure Sensor
Protection and isolation rooms are designed to adhere to strict standards in order to provide a proper barrier between the room and reference space. Unlike a ow-through design, the SRPM utilizes an on-board dead-ended low dierential pressure sensor. This technology provides the user with a trusted solution & peace of mind that the sensor will prevent contaminated air from passing through it.
Save Time and Money on Installation & Calibration
The SRPM is designed with both the installer and end user in mind. The BACnet enabled unit can be installed in an o-the­shelf electrical box, improving the ease of installation instead of having to use a custom electrical box that is not typically available at the rough stage of the project. The SRPM oers push button zero and span calibration that is easily per­formed by any low dierential pressure calibrator and can be calibrated in minutes.
n Maximize Patient Safety n Save on Installation Costs n Low-Cost BACnet Solution
Model SRPM Features:
• On-board Sensor - Industry Best Accuracy
• LCD Touch Screen for Easy Setup and Room Display
• Monitor Single Pressure Relationship and Door Status
• Congurable Audible & Visual Alarms to Avoid Nuisance
• Easy Surface Mounting - Wall Thickness is Irrelevant
• Increased Safety with 2 Layer Password Protection
• Calibration: Only Requires Zeroing Once Installed
Where We’re Installed:
• Brigham and Women’s Hospital
• Emory University Medical Center
• Memorial Sloan Kettering Cancer Center
• Stanford University Medical Center
• Veterans Aairs (VA) Medical Center
Phone: 800-257-3872 • Fax: 978-264-0292 • setra.com © Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc.
Model SRPM
Room Pressure Monitor
ORDERING INFORMATION
S R P M
Model Range Code Excitation/Output Accuracy
SRPM = SRPM
RANGE CODE INCHES W.C.
005WB ±5
2R5WB ±2.5 A2 24 VAC w/ BACnet®
001WB ±1.0 V2 120/240VAC BACnet®
0R5WB ±0.50
R25WB ±0.25
0R1WB ±0.1
Ordering Example: Part No. SRPM005WBA1E for a SRPM, ±5 in. W.C. Range, 24 VAC EXC. with 4 to 20 mA output, and ±0.5% FS Accuracy.* Please contact factory for versions not shown..
24 VAC/4-20 mA or
A1
0-5 and 0-10 VDC
V1 120/240 VAC/4-20 mA
or 0-5 and 0-10 VDC
E ±0.5% FS
V ±0.25% FS
"BACnet" is a registered
trademark of ASHRAE"
DIMENSIONS GENERAL SPECIFICATIONS
Performance Data Environmental Data
Standard Optional Operating Temp.3 °F (°C) 32 to +120 (0 to +50)
Accuracy RSS
Non-Linearity (BFSL) ±0.49% ±0.24% Operating Humidity 5 to 95% RH
Hysteresis ±0.05% ±0.05%
Non-Repeatability ±0.05% ±0.05% Circuit 3-Wire (Exc, Out, Com)
Span Setting Tol.
Thermal Eects
Compensated Range (oFoC) 40 to 120 (4.5 to 50) Power Consumption 5W
Zero/Span Shift %FS ±0.03% FS (±0.05%FS) Excitation:
Overpressure ±15”W.C.
Physical Description
Case Fire-Retardant Plastic
Dimensions 8”H x 5.1”W x 1.8”D
Electrical Connection Removable Terminal Block Output 4 to 20 mA
Pressure Fittings Barbed Fittings 1/4” O.D.
Weight (approx.) 1.5lbs (680g) Excitation:
1
RSS of Non-Linearity, Hystereis, and Non-Repeatability.
2
Units calibrated at nominal 70oF. Max thermal error computer from this datum.
3
Operating temperature limits of the electronics only.
4
Calibrated into a 50K ohm load, operable into a 5000 ohm load or greater
5
Zero setting tol. negated by zero push button
Specications subject to change.
1
±0.5% ±0.25% Storage Temp. °F (°C) -20 to +160 (-30 to +170)
(Non-Condensing)
Electrical Data (Voltage)
5
2
±0.5% Rdg. ±0.5% Rdg. Output
4
0 to 5 VDC, 0 to 10 VDC
Alarm Output SPDT Relay: 1A @ 24 VDC,
1A @ 120 VDC
Code V1 Code A1 Code V2 Code A2
85-265 VAC, 50-60 Hz 18-32 VAC, 50-60 Hz 85-265 VAC, BACnet® 18-32 VAC, BACnet®
Electrical Data (Current)
(NEMA1, IP20 Rated for Indoor Applications)
(203 x 130 x 46 mm)
Tubing
Circuit 2-Wire
External Load 0 to 510 ohms
Code Vi: Code A1
85-265 VAC, 50-60 Hz1 8-32 VAC, 50-60 Hz
8.0
203
5.1
130
2.17 55
4.61 117
1.8 46
mm
in.
Phone: 800-257-3872 • Fax: 978-264-0292 • setra.com © Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc.