Model SRIM1
Room Isolation Monitor
The SRIM1 is Setra’s standard non-BACnet product measuring low dierential pressure in critical applications. The
SRIM1 is an ideal solution for anyone who requires cost-effective local monitoring and alarming of a single pressure relationship, but does not require BACnet protocol. The SRIM1
has a two-line LCD display with easy menu navigation and
congurable visual/audible alarm setup. The SRIM1 has eld
selectable output and uses a unique removable faceplate design, allowing the user to fully calibrate the unit without the
hassle of removing plumbing or wiring.
Why Use Anything But the Best?
In the most critical of environments where contamination
can result in nancial loss and even the loss of life, it is no
secret why Setra dierential pressure sensors are the most
trusted in the industry. Setra’s capacitive stainless steel design oers the most stable very low dierential pressure sensor for building automation systems.
n Maximize Patient Safety
n Save on Calibration & Installation
n Low-Cost Reliable Solution
Premium Performance at Affordable Price
The SRIM1 is designed for the facility that needs local alarming on pressure, without paying a premium for the bells and
whistles of higher priced devices. The SRIM1 has a congurable audible/visual alarm for pressure, which is easily congured through the 2-line LCD display.
Save Time and Money on Calibration
With requirements to calibrate pressure sensors anywhere
from 1-3 times annually, the Setra SRIM1 oers a solution to
help you save on calibration time. The SRIM1 allows the end
user to remove the sensor without detaching any wiring or
plumbing, saving time and money by completing the calibration in minutes.
Model SRIM1 Features:
• Dead- Ended On-board Sensor - Industry Best Accuracy
• 2-Line LCD Display for Easy Setup and Room Display
• Congurable Audible & Visual Alarm
• Flush Mount (43mm wall depth) and Surface Mount
Available
• Field Congurable Output (0-5VDC, 0-10VDC, 4-20mA)
• Removable Faceplate for No Hassle Calibration
• True Selectable 2-Wire 4-20mA Output
Where We’re Installed:
• Battelle Laboratories
• Bella Vista Hospital
• Fort Lauderdale Hospital
• Harvard Medical School
• Russell Medical Center
Phone: 800-257-3872 • Fax: 978-264-0292 • setra.com © Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc.
Model SRIM1
74
2.9
144
5.67
[ mm ]
in.
74
2.9
144
5.67
112.8
4.44
157.2
6.19
6.9
0.27
4.7
0.19
43.4
1.71
[ mm ]
in.
Room Isolation Monitor
ORDERING INFORMATION
S R I M
Model Pressure Ranges Type** Output** Mounting/Logo Accuracy Pressure Snubber
SRIM1 = SRIM1
Example: Part No. SRIM2R05WD11WLC1 = Model SRIM2, 0 to 0.05 in. W.C. Pressure Range, Unidirectional, 4 to 20 mA Output, Wall Mount with Logo, ±1.0% FS Accuracy, 1 Snubber
1
(in W.C.) (Pascals)
R05W* 0 to 0.05 ±0.05 Z02L 0 to 12.5 ±12.5
0R1W 0 to 0.1 ±0.1 025L 0 to 25 ±25
R25W 0 to 0.25 ±0.25 050L 0 to 50 ±50
OR5W 0 to 0.5 ±0.5 100L 0 to 100 ±100
001W 0 to 1.0 ±1.0 250L 0 to 250 ±250
2R5W 0 to 2.5 ±2.5 500L 0 to 500 ±500
005W 0 to 5.0 ±5.0 10CL 10CL 10CL
25CL 0 to 2500 ±2500
Dierential
11 4 to 20mA WL Wall Mount w/ Logo
C ±1.0% FS N None
D Unidirectional 2B 0 to 5 VDC DL Duct Mount w/ Logo F ±0.25% FS w/ cal. cer t 1 Quantity 1
B Bidirectional 2C 0 to 10 VDC WN Wall Mount, No Logo H ±.05% FS w/ cal. cert 2 Quantity 2
*available in unidirectional only
**Field Congurable but factory congured for cal certs.
DN Duct Mount, No Logo G ±1.0% FS w/ cal. cert
DIMENSIONS GENERAL SPECIFICATIONS
157.2
112.8
4.44
43.4
1.71
1/2" CONDUIT
KNOCKOUT
6.19
PRESSURE FITTING
FOR 3/16 I.D. / (4.4mm)
TUBING
4.7
0.19
Performance Data Environmental Data
Code F Code H Code C/G Operating Temp. °F (°C) 22 to +140 (-6 to +60)
Accuracy RSS* ±0.25% FS ±0.5% FS ±1.0% FS Operating Humidity 5 to 95% RH (Non-Condensing)
Non-Linearity (BFSL) ±0.22% FS ±0.49% FS ±0.98% FS
Hysteresis ±0.1% FS ±0.1% FS ±0.1% FS
Non-Repeatability ±0.05% FS ±0.05% FS ±0.05% FS Output (eld selectable) 0 to 5 VDC, 0 to 10 VDC, 4 to 20 mA
Zero/Span Setting Tol. ±0.5% FS ±0.5% FS ±1.0% FS Excitation 18 to 32 VDC
Thermal Eects Current Consumption 5 mA (voltage output mode)
Compensated Range
40 to 120 (4.5 to 50)
°F (°C)
Zero/Span Shift
±0.02% FS/deg
C
Typ. Electrical Connection Screw Terminal
%FS**
Overpressure Up to 10 PSI (Range Dependent) Weight 8.9 oz (Duct) 9.8 oz (Wall)
Pressure Media
Air or non-conductive, non-explosive gases. Pressure Fittings Barbed Fittings for 1/4” Tubing
Certications
CE
RoHS
EN61326-1 & EN61326-2-3 BASIC Immunity &
Class B Emission
Electrical Data
Circuit 3-Wire (Exc, Out, Com)
2-Wire (+Exc, Com)
Physical Description
Display Custom 2-Line Character LCD
Case Fire Retardant Plastic UL94V-0
*RSS of Non-Linearity, Non-Repeatability & Hysteresis at constant temp.
**Units calibrated at nominal 21ºC. Max thermal error computed from this datum.
Phone: 800-257-3872 • Fax: 978-264-0292 • setra.com © Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc.
43.4
1.71
SSP-SRCM REV. D 12/13