Setra SRH200 Manual

Page 1
Model SRH200
Operating Instructions
Setra Systems, Inc.
159 Swanson Road, Boxborough, MA 01719
800.257.3872 • www.setra.com
Page 2
Contents
1.0 General information .......................................................................................................3
2.0 Caution .............................................................................................................................. 3
3.0 Connection diagrams......................................................................................................3
4.0 LED indication...................................................................................................................4
5.0 Scope of supply................................................................................................................4
6.0 BACnet or modbus setup ............................................................................................... 5
6.1 BACnet address using address switch ...........................................................5
6.2 BACnet address using software .......................................................................6
6.3 Modbus address using software .....................................................................8
6.4 Modbus address using address switch ........................................................10
6.5 Modbus setup ....................................................................................................11
7.0 Technical data ...............................................................................................................12
8.0 Setup and adjustment ..................................................................................................13
9.0 Maintenance ..................................................................................................................14
9.1 Humidity calibration and adjustment ............................................................14
9.2 Temperature calibration and adjustment ......................................................14
9.3 When employed in dusty, polluted environment .........................................14
10.0 Accessories ...............................................................................................................15
11.0 Returning products for repair or replacement ......................................................16
11.1 Calibration services ........................................................................................16
12.0 Limited warranty and limitation of repair ...............................................................17
Page 3
1.0 General information
The Setra Systems Model SRH200 transmitter, available for wall or duct mounting, is designed for the measurement of humidity and temperature in HVAC applications.
For use in special applications, please contact Setra Systems.
2.0 Caution
• For accurate measurement, it is essential that the temperature of the sensing probe and the sensing head is same as the temperature of the air to measure. Avoid mounting the SRH200 transmitter in a way which creates temperature gradients along the probe.
• The transmitter and the sensing head should not be exposed to extreme mechanical stress.
The transmitter must be operated with the lter cap on at all times. DO NOT touch the sensors inside the sensing head.
3.0 Connection Diagrams
SRH200 - Analog volts
SRH200 - Analog milliamps
SRH200 - Digital
DO NOT CONNECT!
Bus termination resistor 120 Ω (jumper)
Page 4
4.0 LED indication
Green LED Blue LED
Setra Product Conguration Adapter
On Everything okay
Main board does not recognize the
Flashing
measurement electronics inside the sensing probe
Off No power supply or main board failure PCA not connected to the SRH200
(SETRAPCA1) is powered, no communication in progress
PCA powered, communication in progress
5.0 Scope of supply
SRH200 wall mount
Model
SRH200 Transmitter according to
ordering guide
Cable tting
Mounting kit
Mounting flange
Calibration & inspection certicate
according to DIN EN10204 - 3.1
Quick Guide -
SRH200 RS485 Setup included with all BACnet & Modus units
(Type A)
SRH200 Duct mount
(Type B)
Page 5
6.0 BACnet or Modbus setup
6.1 Setup BACnet address using the address switch
Remove the unit’s faceplate. You will see an address switch (pictured below). If you wish to set
the address of the unit using this switch, you must rst identify and make note of an available
address found on your network.
Before connecting the device to your network, set the address you wish to have on the switch following the above format and table below.
Note: You will see from the table there are 8 positions. For this device, the 8th position (or 8th bit) is ignored. For Example: ID 127=0111111
BACnet PICS for this unit are available for download at www.setra.com. This unit’s ID as well as many other properties are also read/writable from your BACnet console.
SRH200 Default=2 Permitted=0...127 (BACnet)
SRH300 Default=1 Permitted=0...127 (BACnet)
Page 6
6.2 Sitting BACnet address using the software
Remove the unit’s faceplate. You will see an address switch (pictured below). If you wish to
set the address of the unit using the Setra product conguration software, verify all these
switches are set to “0”.
Prior to adding unit to your network, power up the unit according to diagram on page 3. Now
connect the Setra PCA adapter to the unit and to your laptop.
Start the Setra product conguration software. The software should automatically identify
your unit after a few seconds and begin graphing and displaying sensor data.
Page 7
Click on the communication settings found on left menu. The screen below will be displayed. Here you can set band rate, data, parity, and stop bits. In the bus address cell, you can enter the following ranges.
SRH200 Default=2 Permitted=0...127 (BACnet)
SRH300 Default=1 Permitted=0...127 (BACnet)
Note: Regardless of whether you are setting the address in the software or by using the address switch the following settings are recommended.
38400/8/NONE/1
Page 8
6.3 Setting Modbus address using the software
Remove the unit’s faceplate. You will see an address switch (pictured below). If you wish to
set the address of the unit using the Setra product conguration software, verify all these
switches are set to “0”.
Prior to adding unit to your network, power up the unit according to connection diagram on
page 3. Now connect the Setra PCA adapter to the unit and to your laptop. Start the Setra product conguration software. The software should automatically identify
your unit after a few seconds and begin graphing and displaying sensor data.
Page 9
Click on the communication settings found on left menu. The screen below will be display. Here you can set baud rate, data, parity and stop bits. In the Bus address cell, you can enter the following ranges.
SRH200 Default=245 Permitted=0...247 (modbus)
SRH300 Default=242 Permitted=0...247 (modbus)
Page 10
6.4 Setting Modbus address using the address switch
Remove the unit’s faceplate. You will see an address switch (pictured below). If you wish to set
the address of the unit using this switch, you must rst identify and make note of an available
address found on your network.
Before connecting the device to your network, set the address you wish to have on the switch following the above format and table below.
SRH200 Default=245 Permitted=1...247 (Modbus)
SRH300 Default=242 Permitted=1...247 (Modbus)
10
Page 11
6.5 Modbus setup
The measured values are saved as a 32 bit float value from 0x19 to 0x1B. Additionally, the measured values can be read as 16 bit signed integer from 0x12C to 0x12D.
The factory setting for the Slave-ID is 245 as an integer 16Bit value. This ID can be customized in the register 60001 (0x00) (value margin 1 - 247 permitted).
For Modus outputs the required units (metric or non-metric) must be selected in the “Ordering
guide”, see SRH200 data sheet.
FLOAT (read register):
Register address
30026 0x19 Temperature [°C],[°F]
30028 0x1B Relative humidity [%]
Comm. address
Parameter name
INTEGER (read register):
Register address
30301 0x12C Temperature [°C],[°F]
30302 0x12D Relative humidity [%]
Note: Values are stored with a scaling of 1:100 (e.g.: 2550 is equivalent to 25.5°C)
Protocol setting:
Address, baud rate, parity and stop bits can be set via the congurator software (available on www.setra.com).
Comm. address
Parameter name
INFO (read register):
Register address
30001 0x00 Serial number (as ASCII)
30009 0x08 Firmware version
Comm. address
Parameter name
INTEGER (write register):
Register address
60001 0x00 Slave-ID (Modbus address)
60002 0x01 Modbus protocol settings
Comm. address
Parameter name
11
Page 12
7.0 Technical data
General
Power Supply
for 4-20 mA, 2-wire: 10 V + RL x 20 mA < UV < 35 VDC
for 0-10 V or RS485: 15-35 VDC or 24 VAC ±20%
Current consumption
Analog:
Digital:
Connection Screw terminals, max. 1.5 mm
Housing material Polycarbonate, UL94V-0 approved
Protection class IP65/ NEMA 4
Cable tting PG9 M16 x 1.5
Sensor protection Membrane lter
Electromagnetic compatibility
Temperature ranges
Measured values
Relative humidity (RH) sensor
Working range (RH) 0-100% RH
Accuracy at -40 to 140°F (RH) ±2.5% RH
Temperature dependency typ. ±0.03% RH/°C
Temperature (T) sensor (tolerance class B, DIN EN 60751)
T-accuracy at 20°C ±0.3 °C
w/ DC power supply typ. 5 mA
w/ AC power supply typ. 13 mA
w/ DC power supply typ. 15 mA w/ AC power supply typ. 25 mA
EN61326-1
EN61326-2-3
Operating: -40 to 140°F (-40 to 60°C)
Storage: -40 to 140°F (-40 to 60°C)
2
Outputs
Analog output
0-10 V: -1 mA < IL < 1 mA
4-20 mA (2-wire): RL < 500 Ω
Digital output
RS485 (BACnet MS/TP or Modbus RTU),
max.32 SRH200 units in one bus
12
Page 13
8.0 Setup and adjustment
The SRH200 transmitter is ready to use and does not require any conguration by the user. The
factory setup of SRH200 corresponds to the type number ordered. For ordering guide please see data sheet at www.setra.com. If need, the user can change the factory setup by using the
optional Setra Conguration Adapter and the Setra Product Conguration Software.
SETRAPCA2 for analog outputs SETRAPCA3 for digital outputs
PCA
One can assign other physical quantities to the analogue outputs, change the scaling of the
outputs and perform one or two point adjustment for humidity and temperature.
The Setra Product Conguration Software is free and can be downloaded from www.setra.com.
SRH200
13
Page 14
9.0 Maintenance
9.1 Humidity calibration and adjustment
Depending on the application and the requirements of certain industries, there might arise the need for periodical humidity calibration (comparison with a reference) or adjustment (brining the device in line with a reference).
Calibration and adjustment at Setra
Calibration and/or adjustment can be performed by the Setra calibration laboratory. For
information on the Setra capabilities in ISO or accredited calibration visit www.setra.com.
Calibration and adjustment by the user
Depending on the level on accuracy required, the humidity reference can be:
• Humidity calibrator - Purchased separately (not currently sold by Setra)
• Hand held device - Purchased separately (not currently sold by Setra)
• Calibrated salt solutions - most economical
9.2 Temperature calibration and adjustment
Due to the outstanding protection of the temperature sensing element integrated in the Setra sensor, a drift of the T measurement is rather unlikely. If adjustment seems necessary, the user can perform a one or two point T adjustment with PCA and PCS against a reference of choice, it is highly recommended to return the device to the manufacturer for this. The
reasons rest on the difculty of an accurate T calibration in the air. Out calibration shall take
into account the self-heating of 8RH200 with closed enclosure, in its real mounting position and in continuous operation. The impact of the output current and of the probe orientation to the self-heating, as well as the cooling effect of the air circulation in the climate chamber used for calibration.
9.3 When employed in dusty, polluted environment
The lter cap shall be replaced once in a while with a Setra original. A polluted lter cap causes
longer response time of the device. If needed, the sensing head can be cleaned. For cleaning instructions please see www.setra.com.
14
Page 15
10.0 Accessories
Category Setra Accessory P/N Description
Filters SRHMF Membrane lter
Filters SRHSS Stainless steel sintered lter
Filters SRHPG Plastic grid lter
Filters SRHPF PTFE - lter Ø12mm
Filters SRHMG Metal grid lter
Filters SRHHP H2O2 - lter
Flanges SRHPMFG Plastic mounting flange 12mm; grey
Flanges SRHMFB Plastic mounting flange 12mm;
black
Part conguration adapter SETRAPCA1 Conguration adapter transmitter to
RS23 and USB
Part conguration adapter SETRAPCA2 Conguration cable for SRH200
analog
Part conguration adapter SETRAPCA3 conguration cable for SRH200
digital & SRH300
Calibration SRH200SCAL SRH200 calibration (ISO)
Calibration SRH200NCAL SRH200 calibration (NIST)
15
Page 16
11.0 Returning products for repair or replacement
Please contact a Setra application engineer (800-257-3872, 978-263-1400) before returning
unit for repair to review information relative to your application. Many times only minor eld
adjustments may be necessary. If a return is required please call 1-800-257-3872 or email
orders@setra.com to obtain an RMA number before sending unit(s) back to us. Once an RMA
number has been assigned to you, please send the package back to the below address.
Setra Systems, Inc. 159 Swanson Road Boxborough, MA 01719-1304
Attn: RMA #
To download return form, please visit Setra’s service page.
To assure prompt handling, please make sure the RMA number is on the outside of the box and a copy of the service request from is included in the shipment. If applicable, include a copy of
the PO for return in the shipment.
NOTES:
Please remove any pressure ttings and plumbing that you have installed and enclose any
required mating electrical connectors and wiring diagrams.
Allow approximately 3 weeks after receipt at Setra for the repair and return of the unit. Non-
warranty repairs will not be made without customer approval and a purchase order to cover repair chargers.
11.1 Calibration Services
Setra maintains a complete calibrations facility that is traceable to the National Institute of Standards and Technology (NIST). If you would like to recalibrate or recertify your Setra product,
please call our Customer Service Department at 800-257-3872 (978-263-1400) for scheduling.
16
Page 17
12.0 Limited warranty & limitation of repair
SETRA warrants its products to be free from defects in materials and workmanship, subject
to the following terms and conditions: Without charge, SETRA will repair or replace products
found to be defective in materials or workmanship within the warranty period; provided that:
a) the product has not been subjected to abuse, neglect, accident,
incorrect wiring not our own, improper installation or servicing, or
use in violation of instructions furnished by SETRA;
b) the product has not been repaired or altered by anyone except
SETRA or its authorized service agencies;
c) the serial number or date code has not been removed, defaced, or
otherwise changed; and
d) examination discloses, in the judgment of SETRA, the defect in
materials or workmanship developed under normal installation, use
and service;
e) SETRA is notied in advance of and the product is returned to
SETRA transportation prepaid.
Unless otherwise specied in a manual or warranty card, or agreed to in writing and signed by
a SETRA ofcer, SETRA pressure, humidity, and acceleration products shall be warranted for
one year from date of sale.
The foregoing warranty is in lieu of all warranties, express, implied or statutory, including but
not limited to, any implied warranty of merchantability for a particular purpose.
SETRA’s liability for breach of warranty is limited to repair or replacement, or if the goods
cannot be repaired or replaced, to a refund of the purchase price. In no instance shall SETRA
be liable for incidental or consequential damages arising from a breach of warranty, or from
the use or installation of its products.
No representative or person is authorized to give any warranty other than as set out above or
to assume for SETRA any other liability in connection with the sale of its products.
For all CE technical questions, contact Setra Systems, USA. EU customers may contact our
EU representative Hengstler GmbH, Uhlandstr 49, 78554 Aldingen, Germany
(Tel: +49-7424-890; Fax: +49-7424-89500).
17
Page 18
Setra Systems, Inc.
159 Swanson Road, Boxborough, MA 01719
800.257.3872 • www.setra.com
SS-SRH200 Rev. B 10/2018