Setra SRH Data sheet

Setra Relative Humidity
Applications
HVAC/R Control
Indoor Air Quality (IAQ)
Laboratories
Antiquities Preservation
Sensor Line
Features
Key part of comprehensive HVAC solution package (i.e. humidity, pressure and current)
Active Temperature with Jumper-Selectable Tspan Ranges of 40°C, 50°C and 60°C
Three levels of RH accuracy: 2%, 3%, and 5%
Excellent reliability via unique, proven, and established ASIC technology
Robust, proven capacitive
sensor technology
Easy fi eld-serviceability
Low cost of ownership
High aesthetic/ low profi le
wall-mount enclosure
Quick-mount, 2-screw install w/ plug-in terminal wiring
5 year warranty on electronics; 2 year warranty on sensor module
CE and RoHS Compliant
Now Features
Active
Temperature
Sensing
When it comes to a product to rely on - choose the SRH. When it comes to a company to
trust - choose Setra.
ISO-9001 Certifi ed
800-257-3872
Visit Setra Online:
http://www.setra.com
etra’s Humidity Sensor (SRH) family consists of a wall mount, duct mount,
S
product l ine is desi gned to complement Setra’s pressure and current products while expanding the solution opportunities for the HVAC/building automation market and other relative hu­midity monitoring applications. All models feature removable sensor tips, NIST traceability, and a durable capacitive sensor capable of full-scale 0 to 100% RH measurement.
The SRH product line offers ac­curate humidity with active or passive temperature sensing available in ±2%, ±3%, or ±5% RH accuracy. Humidity transmitters configured with active tempera­ture option feature jumper- se­lectable Tspan ranges of 40°C, 50°C, and 60°C.
This product suite utilizes field­replaceable sensor tips that al­low the end user to replace the sensors on-site. This essentially eliminates time consuming and costly factory calibration, while reducing downtime during ser­vice intervals. As an example, the duct mount probe is easily accessed by taking off the front cover, pulling out the probe, and replacing the sensor tip. This further contributes to a more user-friendly, lower cost product line that is focused on customer needs and ease of use.
Setra’s humidity sensors are the ultimate product for any HVAC installation and, combined with our pressure and current products, allow us to support a one-stop, single source for any customer. The SRH line is a natu­ral progression that grew out of our high quality line of pressure transducers that also use the same unique ASIC coupled with a highly reliable capacitive sen­sor technology. This product line marks the capstone in fulfilling a complete HVAC solution and boasts the same quality, delivery, and innovation demanded of all Setra products.
and outside air unit. This
Features
Key component of comprehensive HVAC/R solution
The Setra humidity/temperature solution is an important part of our overall HVAC/R solution which also includes pressure and current. This bundle of products has es­tablished Setra as a premiere HVAC manu­facturer and a full-solution player for HVAC customers.
Robust, proven capacitive sensor
The unique pairing of Setra’s proven capacitance measurement technology with its custom ASIC (used in thousands of pressure devices) ensures reliable measure of RH levels from 0 to 100%. As a result, customers will experience better resis­tance to contamination, longer stability, and minimal drift.
Attractive/ low profile enclosures
Design and aesthetics have always been considered an important ingredient in any new Setra product. The humidity family consists of three configurations: wall, duct, and outside air models. Great attention was given to the look of the wall mount, ensuring that it complements the décor of any building. It is a space conscious unit that takes up no more space than an electrical outlet. The duct and outside air models utilize a design that ensures ease of both assembly and probe removal for recalibration.
Three levels of RH accuracy ­2%, 3%, and 5%
There are three levels of accuracy avail­able for Setra humidity sensors: 2%, 3%, and 5%. The sensors should not drift more than 1% annually but it is recommended that the sensor be checked each year to ensure high accuracy and dependability.
Field Serviceability
Replaceable sensor board = no calibration and greater accuracy
Depending on the environment in which it is being used, a transducer may drift over time and need to be either recalibrated or replaced. Costs associated with recalibration are often overlooked when select­ing an RH transmitter. However, these costs can easily outweigh the original purchase price if not considered on the front end.
The Setra SRH series uses a highly accurate, reliable, and durable sensor. However, if replacement is needed, the interchangeable RH sensor module can be easily re­moved. These computer-calibrated sensor assemblies are cost effective and do not require skilled techni­cians to perform field servicing. No calibration is needed because each new sensor module is factory-cali­brated before shipping. Another benefit for duct and outside air applications is the sensor module can be replaced without having to remove the unit and disconnect the wiring conduit.
Simple Installation
Easy as 1-2-3
1) Mount the wall plate in desired position on wall (two screws).
2) Connect circuit board to wall plate.
3) Snap cover over assembly .
Applications
HVAC/R Control
Indoor Air Quality (IAQ)
Laboratories
Antiquities Preservation
Features
Key part of comprehensive HVAC solution package (i.e. humidity, pressure and current)
Active Temperature with Jumper-Selectable Tspan Ranges of 40°C, 50°C and 60°C
Three levels of RH accuracy: 2%, 3%, and 5%
Excellent reliability via unique, proven, and established ASIC technology
Robust, proven capacitive
sensor technology
Easy field-serviceability
Low cost of ownership
High aesthetic/ low profile
wall-mount enclosure
Quick-mount, 2-screw install w/ plug-in terminal wiring
5 year warranty on electronics; 2 year warranty on sensor module
CE and RoHS Compliant
Low cost of ownership
As mentioned above, the replace­able sensor assembly eliminates high labor costs associated with field calibration. These products were designed with the customer in mind by combining accuracy, dependability and accessibility into an overall cost effective solution.
Patent No. 7,658,096
The assembly for the duct and out­side air mounts is similar and out­lined in easy-to-follow steps in the installation instructions.
Now Features
Active
Temperature
Sensing
When it comes to a product to rely on - choose the SRH. When it comes to a company to
trust - choose Setra.
ISO-9001 Certified
800-257-3872
Visit Setra Online:
http://www.setra.com
Specifications
12.52
318
MOUNTING FLANGE
WALL/PIPE
UNIVERSAL
POROUS WEATHER SHIELD
60.4
2.38
114.4
4.50
6.10
154.9
4.05
102.7
2.68
68
4.04
102.6
5.10
129.5
142.2
5.60
2.68
68.1
4.69
[119]
2.81
[71.5]
SECURITY LOCK
SECURITY LATCH
.98
[24.7]
RH Performance Data
Sensing Element Capacitive Polymer Humidity Operating Range 0 to 99% RH (Non-condensing) Accuracy @ 68*F (20°C) 2%, 3%, 5%† Hysteresis <1.5% Repeatability <0.5% Long Term Stability <1% /Year @ 68°F (20°C), 50%RH
†5% units available only with passive temperature option.
Electrical Data
Signal Outputs Current (2-Wire ) 4 to 20 mA Field-Selectable Voltage (3-Wire ) 0 to 5 VDC, 0 to 10 VDC, Excitation 13.5 to 30 VDC (10VDC Output) 12 to 30 VDC (4-20mA, 5VDC Output) Maximum Load (Current Only) Ω = (Supply - 10) ÷ 0.02 Electrical Terminations Pluggable Terminal Block (5mm Pitch) Wiring Protection Reverse Excitation
CE Compliance EMC Directive 2004/108/EC
Dimension Drawings
Wall Mount
[71.50]
2.81
[119]
4.69
[60.4]
2.38
Security Lock
[221]
[24.7]
0.98
Security Latch
S R H 1
Model SRH1 = SRH
Replacement Sensor Assembly:
Example: Part No. SRH3-2P-T0 = 2% accuracy, RH only
While we provide application assistance on all Setra products, both personally and through our literature, it is the customer's responsibility to determine the suitability of the product in the application.
Measurements are in [mm] & inches.
8.7
Example: Part No. SRH1-2P-W-11-T0-N-C = Wall-mount, 2% RH accuracy, 4-20 mA output, RH only, NIST Calibration Certificate
Accuracy
2P = 2% 3P = 3%
6
5P = 5%
S R H 3
Model
SRH3 = SRH6
Temperature Sensing Options (Passive)
T1: Thermistor NTC 10K Ω @ 77°F/25°C (Direct Connect)Type II
T2: RTD Output 1000 Ω @ 32°F/0°C(Direct Connect) 385 Platinum Curve
Temperature Sensing Options (Active)
T3: Ranges °F (°C) -58 to 140 (-50 to 60)
Accuracy @ 68°F (20°C) Typ. @ 50% ±1.1 (±0.6) *
T5: °F (°C) +14 to 140 (-10 to 60)
Physical Description
Enclosure Materials: Wall Mount ABS 94-VO Duct & Outside Air Polycarbonate 94-VO Probe (Duct & Outside Air) Aluminum Weather Shield Porous Polyethylene Sensor Tip Filter 70 Micron Polypropylene
Dimensions See Dimension Drawings
3
3
Specifications subject to change without notice.
Accuracy @ 68°F (20°C) Typ. @ 50% ±0.7 (±0.4) * Signal Output Options (includes humidity output) Current 4 to 20 mA, Field-Selectable Voltage 0 to 5 VDC, 0 to 10 VDC
* Excitation: 24 VDC ± 10% Environmental Data
Operating Temperature °F (°C) -40 to 140 (-40 to 60 ) Storage Temperature °F (°C) -40 to 158 (-40 to 70) Moisture Resistance IP65, NEMA-4 (Duct & Outside Air) Solar UV Resistant (Outside Air) Flammability Rating 94-V0
Compliance RoHS Compliant, CE Compliant
[318]
12.52
[57.15]
2.25
[28.58]
1.125
Duct Mount
[142.2]/5.60
[129.5]/5.10
[68.1]
2.68
CONDUIT KNOCKOUTS BOTH SIDES
DUCT PROBE (5/8” DIA.)
DUCT MOUNT SHOWN WITH OPTIONAL DUCT FLANGE
Ordering Information (Code all blocks in table)
Configuration
W = Wall
D = Duct
O = Outside Air
Outputs
1
11 = 4 - 20 mA
2C = 0 - 5 or 0 - 10 VDC (user-selectable)
Accuracy
2P = 2% 3P = 3%
5P = 5%
Temperature Outputs T0 = None (RH only)
2
T1 = 10KΩ Thermistor (Passive) T2 = 1000Ω RTD (Passive) T3 = -58 to 140°F (-50 to 60°C [Active]) T5 = +14 to 140°F (-10 to 60°C [Active])
Temperature Outputs T0 = None (RH only)
T1 = 10KΩ Thermistor (Passive)
6
T2 = 1000Ω RTD (Passive) T3 = -58 to 140°F (-50 to 60°C [Active]) T5 = +14 to 140°F (-10 to 60°C [Active])
159 Swanson Road, Boxborough, MA 01719/Tel: 978-263-1400;
Toll Free: 800-257-3872; Fax: 978-264-0292; email: sales@setra.com
Outside Air
[154.9]
6.10
[60.4]
2.38
[114.4]
4.50
[102.7]
4.05
UNIVERSAL WALL/PIPE MOUNTING FLANGE
POROUS WEATHER SHIELD
[41.25]
[17.27]
[38.10]
1.50
[57.15]
2.25
3, 5, 6
NOTES:
3. 5, 6
1 Wall (w) configuration not available with T3 Temperature option.
2. Voltage outputs (2C) are factory configured for 0 to 5 VDC opera-
tion. User -selectable jumper for 0 to 10 VDC operation.
3. Tspan jumper factory configured for 60°C. User-selectable Tspan
for 40°C and 50°C option provided
4. Display option available ONLY in Wall mount configuration
5. SRH1 units originally ordered with either a T3 or T5 temperature
5
option MUST be replaced with the same T(x) version.
5
6. 5% accuracy units not available with active temperature option.
1.62
0.68
[76.20]
3.00
Display
N = None
Optional
Duct Flange
(Side View)
4 x (4.57) Ø.180
[44.45]
1.75
Order Duct Flange Separately (P/N 888415)
4
[68]
2.68
Optional
Duct Flange
(Top View)
Options
C = NIST Certificate of Conformance
[102.6]
4.04
SSP-SRH Rev. C 10/19/10