Setra SRCM Specifications

Model SRCM
Room Pressure and Condition Monitor
GAUGE PRESSURE
ROOM PRESSURE MONITORS
FEATURES
True Pressure Measurement
• High accuracy Setra low dierential technology
• Dead ended solution —no contamination or clogging
• Standard on-board sensor and optional remote sensor
Display 4 Ambient Parameters
Flush Mount Design
• No visible mounting fasteners
• Snap-in ush bezel
• Face is sealed for cleaning or wipe-down
NOTE: Setra quality standards are based on ANSI-Z540-1. The calibration of this product is NIST traceable.
U.S. Patent nos. 6019002; 6014800
DESCRIPTION
In a hospital, laboratory or animal research facility, the integrity of the ventilation control system is at the heart of a contaminant free environment. Whether a room is to be maintained at a negative pressure to prevent con­taminants from escaping into adjacent areas or positive pressure to protect patients with compromised immune systems, the proper pressurization of the room is es­sential. To assure proper pressurization is maintained in these critical environments, a room pressure monitor is employed to measure and alert sta and personnel of any change in pressure—no matter how small. A fail-safe solution to monitoring these very low pressure changes is Setra’s Model SRCM room pressure monitor, which utilizes highly accurate capacitance sensing technology to mea­sure and display true low pressure dierential.
"BACnet" is a registered
trademark of ASHRAE"
Setra’s “2 in 1” Solution
Full Banner Feature
• Utilize same monitor for room condition
• Clearly display condition with facility specic nomenclature
Clone Feature
Display rotates up for access to USB port
• On-board USB port—cloning of congurations
for multiple unit installation
BACnet® Communications
• Installed or eld upgrade for in-situ installation
• BACnet• MSTP/ASC
• All setups congurable through touch screen display
Alarm Capabilities
• Local Audible and Visual alarming
• Remote annunciator alarming capability
• Alarm delay feature—prevent nuisance alarms
Ease of Installation
• Mounts in o-the-shelf electrical gang box
• 4-screw self leveling mount
1
The Environment is Critical, the Control is Easy
Ambient Parameters
+
Phone: 800-257-3872 • Fax: 978-264-0292 • setra.com ©2013 Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc.
=
SRCM
ROOM PRESSURE MONITORS
Attractive, Intuitive, and Congurable Design
Simultaneously Monitor and Display 4 Parameters Per Room (up to 2 rooms)
Selectable Room Condition Banners
1/3 Screen Banners
Full Sceen Banners
Room Pressure and Condition Monitor
Display 4 Ambient Parameters (slide bar o)
Pressure, Temperature, Humidity, and User-Dened
Parameter
Setup Menu
Password Protected Entry to Menu Structure
Room I.D.
Customer Congurable Feature - Cus­tomize Room Name
Pressure Slide Bar On
Graphic Display of Pressure Reading Relative to Alarm Setpoints
Model SRCM
Room Pressure Mode
Display Positive, Nega­tive, or Neutral Mode of
Room
Room Pressure Status
Visual Indication of Normal, Warning, and Alarm Con-
dition
Displayed Pressure
Displays Room Pressure in User Selectable Units
GAUGE PRESSURE
Setup Display Banner
• User Dened Text: Free form data entry for room name
• Room Status: Change room from Isolation to No Isolation
Fingertip Access for Easy Setup
Setup Display Advanced
• Display Contrast: Change brightness of display
• Display Averaging: Improve display resolution in unstable ambient pressure environments
• Display Ambient Parameters: Display primary
and
secondary rooms or toggle between 2 rooms
• Enable Password: Administrator and Supervisor
Setup Unit Operation
• Setup primary and secondary room
• Change analog output
• Free form data entry for room name
©2013 Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc. Phone: 800-257-3872 • Fax: 978-264-0292 • setra.com
2
Model SRCM
Room Pressure and Condition Monitor
SPECIFICATIONS
Performance Data Environmental Data Electrical Data (Voltage)
3
Operating
Code F Code H
1
(at constant temp) ±0.25% FS ±0.5%
Accuracy RSS
Non-Linearity (BFSL based) ±0.24% ±0.49%
GAUGE PRESSURE
Hysteresis ±0.05% ±0.05%
Non-Repeatability ±0.05% ±0.05%
ROOM PRESSURE MONITORS
Zero/Span Tolerance ±0.05% FS ±0.05% FS
Pressure Media
Air or Non-Conductive, Non-Explosive Gases.
Certications
Electro-Magnetic Compatibility
CE
CSA
1
RSS of Non-Linearity, Hysteresis, and Non-Repeatability.
2
Units calibrated at nominal 70˚F. Maximum thermal error computed from this datum.
3
Operating Temperature limits of the electronics only.
4
Calibrated into a 50K ohm load, operable into a 5000 ohm load or greater.
Specications subject to change without notice.
Directive 2004/108/EC Low-Voltage Directive 2006/95/EC RoHS Directive 2011/65/EC
CAN/CSA - C22.2 No. 61010-1-04 ANSI/UL 61010-1, 3rd Edition
Temperature
°F (°C)
Storage Temperature °F (°C) -20 to +160 (-30 to +70) Output
Operating Humidity 5 to 95% RH (non-condensing) Excitation 18-32 VAC, 50-60 HZ
Physical Description
Case Fire Retardant Plastic UL94 V-0 Alarm Output SPDT Relay: 0.6A @ 120 VAC, 2A @ 30 VDC
Dimensions 5.84”H x 7.45”W x 0.38”D (14.84 x 18.92 x 0.95 cm)
Electrical Connection Removable Terminal Block Circuit 2-Wire
Pressure Fittings Barbed Fittings for 1/4” O.D. Tubing Output 4 to 20 mA
Weight (approx.) 1 lb. 3.2 ounces (554 grams) External Load 0 to 510 ohms
Mounting Mounts to a triple gang double-deep electrical box Excitation 18-32 VAC
Communications Option
BACnet® MS/TP ASC Compensated Range °F (°C) ±0.03% FSI (±0.05% FS)
Display Overpressure ±1 PSI (15” W.C. for ≤ 0.10” W.C. F.S.)
LCD 4.3” TFT, 480 x 272, Dimmable
32 to + 120 (0 to +50) Circuit 3-Wire (Exc, Out, Com),
4
Power Consumption 10 W max., 3 W typ.
Electrical Data (Current)
Thermal Eects
0 to 5 VDC, 0 to 10 VDC
2
DIMENSIONS
14.84
5.84
WIRING
18.92
7.45
POWER
Earth Ground
HIGH or room pressure tubing contacts here
L1 24 Vac L2 24 Vac
RELAY
COM COM +15 +15 Vdc NO Normally Open RC Relay COM NC Normally Closed
COM
B (+) A (-) GND
0.95
0.38
5.08
2.00
ANALOG (ANL) OUTPUT
COM COM mA Current Output (4-20 mA) Vdc Voltage Output (0-5 Vdc, 0-10 Vdc)
INPUTS (wired to door N.O. contact)
COM COM Door DI Digital Input
COM COM Analog Input2 IN2 Analog Input2 (0-5, 0-10Vdc) +15 15 Vdc
COM COM Analog Input1 IN1 Analog Input1 (0-5, 0-10Vdc) +15 15 Vdc
LOW or reference pressure tubing connects here
1.49
0.59
7.03
2.77
13.15
5.18
cm
in.
3
REAR VIEW
Phone: 800-257-3872 • Fax: 978-264-0292 • setra.com ©2013 Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc.
ROOM PRESSURE MONITORS
Model SRCM
Room Pressure and Condition Monitor
ORDERING INFORMATION
S R C M
Model Range Code Excitation/Output Accuracy Pressure Snubber* Faceplate
SRCM = SRCM See Table 1 Below A1 24 VAC/4-20 mA or 0-5 and 0-10
VDC
A2 24 VAC w/ BACnet® F ±0.25% FS
Table 1. Range Specication
RANGE
CODE
R05WB 0R1WB R25WB 0R5WB 001WB 2R5WB 005WB
INCHES
W.C. RANGE CODE PASCALS
±0.05 ±0.10 ±0.25 ±0.50 ±1.00 ±2.50 ±5.00
Z02LB 025LB 050LB 100LB 250LB 500LB 10CLB
±12.5 ±25 ±50 ±100 ±250 ±500 ±1000
H ±0.5% FS N
0
1 1
2 2
"BACnet" is a registered
trademark of ASHRAE"
S Setra
B Blank
GAUGE PRESSURE
Logo
Ordering Example: Part No. SRCMR05WBA1HNS for A SRCM, ±0.05”WC Range, 24VAC/4-20 mA, 0.5% Full Scale Accuracy, NO Pressure Snubber
* For other pressure tting congurations, please contact factory.
ACCESSORIES
Model SRAN
Remote Annunciator
Green LED, Normal Indication Red LED, Alarm Indication Buzzer, Audio Alarm, ADJ. from SRPM Acknowl­edge Switch
Order Part Number:
S R A N
Pressure Snubber
Room Pressure Snubber (Wall Mount Pressure Taps)
The RPS is a stainless steel room static pres­sure sensor that has the same footprint (2.75” W X 4.5” H) as your standard electrical wall plate.
©2013 Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc. Phone: 800-257-3872 • Fax: 978-264-0292 • setra.com
SSP-SRCM Rev. D 12/18/13
4
Loading...