Split Core Performance CT
Current Transformers
DESCRIPTION
The hinged Split Core Performance CTs are small, low cost current transformers
with high accuracy over a wide dynamic range with excellent phase shift. These
CTs are ideal where space is limited such as when metering multiple loads within
a panel board. Use for current measurement, energy metering, load surveys, demand metering, energy research, and sub-metering.
SPECIFICATIONS
20A 50A 100A 200A
Window Size 0.4” (10mm) 0.4” (10mm) 1.0” (25mm) 1.0” (25mm)
Current Range 0.25-40A AC 0.25-80A AC 1-200A AC 1-300A AC
Output 333 mV @ 20A AC, 16.65
Ratio Error* <0.5% from 0.25 to 40A AC
Phase Error <1.5
Electrical
mV/A AC
(typical)
o
from 1A to 80A AC
<2o from 0.25 to 1A AC
Wire Polarity White = Hi, positive (+) Black + Low, negative (-)
Phasing Arrow on Case Points
Orientation Toward Load
Frequency Range 50 to 400 Hz
Mechanical
Case Material White Nylon, UL 94 V-0
Leads 2.4 M (8’), 600V, 20 gage 2.4 M (8’), 600V, 22 gage
Operating Temp. -15 to 60oC (5 to 140oF)
Storage Temp. -20 to 85oC (-4 to 185oF)
Safety
Working Voltage 600 VAC, Category III
Dielectric Strength 3525 VAC for 1 Minute 5200 VAC for 1 Minute
Certications UL STD 61010-1 Certied to: CAN/CSA STD 22.2 NO. 61010-1
333 mV @ 50A AC, 6.66
mV/A AC
<0.5% from 0.25 to 80A AC
(typical)
<1.5o from 1A to 40A AC
<2o from 0.25 to 1A AC
333 mV @ 100A AC, 3.33
mV/A AC
<0.3% from 1.0A to 200A AC
(typical)
<0.5o from 1.0A to 200A AC <0.5o from 1.0A to 300A AC
*IEEE C57.13 Certication available upon request
333 mV @ 200A AC, 1.67
mV/A AC
<1.0% from 1.0A to 300A AC
(typical)
ORDERING INFORMATION
C T
Name Amps
SCP Split Core Performance 020 20 Amps
©2013 Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc. Phone: 800-257-3872 • Fax: 978-264-0292 • www.setra.com
S C P
050 50 Amps
100 100 Amps
200 200 Amps