Setra Power Patrol Data sheet

The Setra Power Patrol is every electrical contractor’s dream. The networked 3-phase power meter works with Rogowski Coils and has a small enough form factor to be mounted inside or outside of the panel using either mount­ing tabs or the DINrail clip making it the easiest installation in the industry.
Rogowski and CT Compatible
The Power Patrol works with either Rogowski Coil “ex” CTs or conventional split-core CTs. The ability to have in­terchangeable CTs gives added exibility for last minute changes at the job site. The Power Patrol is embedded with the necessary amplier/integrator circuitry for Rogowski coil CTs—eliminating the need to provide external power.
Power Patrol
Advanced Power Meter
Power Patrol Features:
• Congure & Power Through USB
Easy USB Conguration
Using the Power Patrol HeadStart software, power and con­gure the meter through your computer’s USB port. While other meter’s require conguration in a live enclosure, the Power Patrol can be easily congured outside of the panel, eliminating the risk of arc ash. HeadStart can save me­ter settings, allowing the installer to clone meter proles quickly and easily.
Line Powered from 80-600V
The Power Patrol series instruments are line-powered and do not require external power. Its power supply can accom­modate service voltages ranging from 80-600V (phase-to­phase). The Power Patrol has 3 LED indicators (Red/Green)
which conrm proper CT-to-phase installation.
Field Selectable Communications (4-in-1)
Each Power Patrol comes with a eld selectable Modbus or BACnet communication. Communications interface to the Power Patrol is through either an RS-485 serial connec­tion (BACnet MS/TP / Modbus) or over Ethernet (BACnet IP / Modbus TCP).
• Rogowski Coil and Split Core CT Compatible
• Field Selectable BACnet/Modbus (4-in-1)
• Broadband Power Supply (80-600V)
• ANSI C12.20-2010 Class 0.2
• Bi-Directional
• DIN- Mount
Applications:
• Measurement & Verication
• Demand Response
• Energy Cost Allocation
• Equipment Eciency Tracking
• Preventive Maintenance
• Tenant Sub-Metering
• Net Metering
5 Year Warranty
Phone: 800-257-3872 • Fax: 978-264-0292 www.setra.com ©2013 Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc.
Power Patrol
Advanced Power Meter
SPECIFICATIONS
Technical Communications
Service Type Single Phase, Three Phase-Four Wire (WYE), Three Phase-Three Wire (Delta) Direct BACnet IP, BACnet MS/TP, Modbus TCP, Modbus RTU
Power From L1 Phase to L2 Phase. 80-600VAC CAT III 50/60Hz, 70 mA Max. Non-
user replaceable .5 Amp internal fuse protection
Voltage Channels 80-346 Volts AC Line-to-Neutral, 600V Phase-to-Phase, CAT III Baud Rate 9600 (Modbus default), 19200, 38400, 57600, 76800
Current Channels 3 Channels, 0.67 VAC max, 333 mV CTs, 0-4,700 Amps depending on CT Data Bits 8
Maximum Current Input
Measurement Type
Line Frequency 50/60 Data Formats Modbus or BACnet
Waveform Sampling
Parameter Update Rate
Measurements Volts, Amps, kW, kWh, kVAR, kVARh, kVA, aPF, dPF (Partial List) Humidity 5% to 95% non-condensing
Accuracy 0.2% (<0.1% typical) ANSI C12.20-2010 Class 0.2 Enclosure ABS Plastic, 94-V0 ammability rating
Resolution 0.01 Amp, 0.1 Volt, 0.01 watt, 0.01 VAR, 0.01 VA, 0.01 Power Factor
LED Indicators Bi-color LEDs (red and green): 1 LED to indicate communication, 2 LEDs for
Pulse Output Open Collector, 5mA max current, 30V max open voltage
200% of current transducer rating (mV CTs) Measure up to 5000A Patrol Flex
True RMS using high-speed digital signal processing (DSP) Stop Bit 2,1
12 kHz
.5 seconds Operating Temperature -7o to 60o C (-20o to 140o F)
depending on scalar setting
correct CT-to-phase installation (per meter element), 1 LED for pulse
Max Distance 1200 meters with data rate of 100K bits.second of less
(BACnet default), 11200
Parity None, Even, Odd
Mechanical
Weight 340 g (12 ounces, exclusive of CTs
Dimensions 23.0 x 9.0 x 4.0 cm, (9.0” x 3.5” x 1.5”)
Safety
Power Patrol Serial and Ethernet
UL Listed and CE Mark, Conforms to UL Std 61010-1 Certied to CSA Std C22.2 No. 61010-1
Modbus Register/BACnet Object Descriptions (Partial List)
System True Energy (kWh) Individual Phase to Phase Voltages
Instantaneous Total True Power (kW ) Line Frequency (Hz)
Peak Demand (Adjustable Window) (kW) Individual Phases True Energy (kWh)
Maximum Instantaneous Power (kW) Individual Phases True Power (kW)
System Reactive Energy (kVARh) Individual Phases Reactive Energy (kVARh)
System Apparent Energy (kVAh) Individual Phases Reactive Power (kVAR)
System Apparent Power (kVA) Individual Phases Apparent Energy (kVAh)
System Displacement Power Factor (dPF) Individual Phases Apparent Power (kVA)
System Apparent Power Factor (aPF) Individual Phases Apparent Power Factor (aPF)
Average Current (Amps) Individual Phases Displacement Power Factor (dPF)
Average Line to Line Voltage (Volts) Individual Phases Current (Amps)
Average Line to Neutral Voltage (Volts) Individual Phases Line to Neutral Voltages ( Volts)
Multiple Meters External Data Synchronization Individual Phases Line to Line Voltages (Volts)
Ordering Information
for Setra Power Patrol
Communication
Accessories
(Cable and software required for meter setup)
S P P
SPP - Setra Power Patrol
Setra P/N Description
900900-G USB Communication Cable, Type A to B, Power Patrol
900901-G USB Flash Drive, HeadStart Software, Power Patrol
Communication Port
E - Ethernet & Serial
S - Serial Only (RS-485)
Display
D - Display
N - No Display
©2013 Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc. Phone: 800-257-3872 • Fax: 978-264-0292 • www.setra.com
Loading...