1.0 Introduction
The Setra Lite provides a simple, cost-effective, and accurate way to measure and display
room differential pressure in areas today that require manual verication. For local staff
managing area, Setra Lite has a light ring that is green or red, showing a clear indication of
room conditions. For the facility manager, using the Lite means the frequency of preventative
maintenance walk-by inspections can be reduced because Setra Lite is monitoring the space.
Setra Lite has many features found only in larger, more complex room pressure monitors.
These include a bright light ring that can be seen at an angle or down a hallway, a digital
display of the pressure value that is always-on or momentary an alarm delay for door entry,
and POS or NEG room mode. The Setra Lite sensor has Setra’s accuracy and reliability that
you can trust.
Setra Lite is about the size of a standard light switch and just as simple to install. It ts in
a single-gang US electrical box, international 86-box or international round back-box, and
is powered by 24VAC or 24VDC. The reference side pressure pickup is integral with the Lite
faceplate. An analog output provides the building management system with the pressure
signal for any additional trending or alarming needed.
The Setra Lite also integrates seamlessly with the Setra Flex environmental monitor. Mount
Setra Lite at additional doors that enter the space and use an on-screen badge to display its
value.
1.1 Intended use
Setra Lite is designed to sense and visually indicate the pressurization status of critical
environments, including cleanrooms and sensitive hospital areas (sterile bronchoscopy
rooms, and other USP 800 compliant pressurized spaces). Setra Lite is design provide an
intuitive visual indicator of the status of the room and can also be tied into other devices via
analog output.
1.2 Display and LED light ring
Setra Lite features and LED light ring that will glow red if room pressurization violates the
congured alarm threshold. The design of the light ring allows the room status to be visible
from a distance, even from down a hallway. With a simple press of the front lens of the unit,
the LCD displays the current differential pressure. Conguration of the unit can be performed
on the device via buttons located behind the removable front lens. The unit can be put into and
taken out of “Standby” mode by pressing the front lens 3 times in quick succession.
4
2.0 Rough-in installation
For Setra Lite to be installed correctly, the rough-in phase of the project must be completed
properly. This section will outline the specic considerations the General Contractor must pay
attention to so that the nal wiring and commissioning will go smoothly.
2.1 Intended use
The following is a list of parts required and supplied by installer for Setra Lite:
1. Power (18-22 AWG recommended) and signal wire
2. 1/8 in. ID silicon tubing to run from the room(s) Pressure Pickup Ports to the Setra Lite
monitor or external sensors.
3. 24 VAC or VDC transformer, capacity rated for number of Setra Lite units powered
4. Single-gang electrical box, if opting not to install directly into wall
5. Single-gang electrical box, one per Pressure Pickup Port, if opting not to install directly
into wall
2.2 Parts included with your order
The following parts are included with your order:
1. Setra Lite main unit
2. Pressure Pickup Port (located in master shipping box)
3. Mounting hardware
4. Elbow connectors, if needed
5. 250 ohm resistor, if wiring inputs for 4-20 mA current loops
2.3 Unboxing the unit
When rst opening the Setra Lite box, the faceplate and lens are in a protective bag on top. Set
aside these parts for nal installation.
Located underneath the faceplate and lens is the main sensor body of the Setra Lite.
Attachment hardware is located in the side slot of the packing foam inside the Setra Lite box.
A Pressure Pickup Port is separately packaged and included in the master shipping box that
contained the Setra Lite.
5
3.0 Installation overview
Each Setra Lite unit comes compete per order specications to provide room differential
pressure sensing and an intuitive visual indicator of room pressurization status.
3.1 Prepare wall for mounting
1. Cut hole in wall for Setra Lite or install 1-gang electrical box
2. Install 1-gang electrical box for each Pressure Pickup Port (RPS), either horizontal ceiling
mounted or vertically mounted high on a wall surface
3. Ensure electrical boxes are level and flush to the nished wall surface
3.2 Install Pressure Pickup Port (RPS)
1. Install room-side Pressure Pickup Port, which transmits pressure to be measured by
Setra Lite.
Note: Reference-side pressure pickup is integrated into the main body of Setra Lite no additional Pressure Pickup Port is required for reference side.
2. Run tubing to Setra Lite electrical box, being careful not to crimp tubing in conduit or
within walls
3. Run all wiring to the Setra Lite electrical box.
3.3 Plumbing
Typically, a Pressure Pickup Port (RPS) is installed in the primary monitored room and Setra
Lite is installed in the reference area (typically a hallway). Installing a single gang electrical box
inside the room, typically high on the wall or flush-mounted to the ceiling is appropriate for the
Pressure Pickup Port. 1/8” ID soft platinum-cured silicon tubing is typically used to bring the
pressure signal from the Pressure Pickup Port to the pressure tting on the back of Setra Lite.
Note: Caution should be taken to locate the Pressure Pickup Port and Setra Lite at least
six (6) feet from air turbulence that may originate from air supply diffusers, slot diffusers,
mobile equipment cooling fans, or other devices that may exhaust air in the direction
of the ports. Air velocity blowing directly on these ports can cause inaccurate pressure
measurement.