Setra CTC Specifications

Model CTC Series
Current Transducers Clamped
Amperage
30, 60, 120 and 20, 100, 150
Applications
HVAC
Refrigeration
Pumps
Small Industrial Motors
Lighting
CTC Series
Features
Clamped/Split Core
Design
Slide Switch, Selectable
Amperage Ranges
Snap on Power Relay
etra’s CTC Series Split Core Current Transducers combine
S
accurate magnetic current sensing with signal conditioning elec­tronics. They are available in either
24 VDC loop power or self-powered, which means they are easy to install
and put into operation. Their self­gripping, compact split core design makes it easy to retrofit into existing equipment
Each unit has a three position
slide switch to select the most suit-
able range for the application. The 0 to
5V and 4 to 20 mA output units have
30/60/120 Amp sensing ranges. The 0 to 10 V output units have a 20/100/150 Amp sensing range.
In addition, when used with the optional CCR-24 or CCR-12 power relay module w/LED indicator, the CTC can be used for remote motor startup.
These units are ideal for monitoring cur rent in PLCs (power line carrier commu­nications) & AMR systems or in remote control system of SCADA software for automation & supervision, security, con­dition monitoring in protection systems and for predictive maintenance of con­veyers, pumps or HVAC motors.
Relay LED Indication
on CTC when Used
with Optional CCR-24 or CCR-12 Command Relay
Benefits
Low Cost Solution
24 VDC Loop Power or
Self Powered
-
Simple Installation
CTCGV05NN Linear Output
5 VDC
0 VDC
0 A
30/60/120 A
CTCGV10NN Linear Output
10 VDC
0 VDC
0 A
20/100/150 A
CTCG420NN Linear Output
20 mA
4 mA
0 A
30/60/120 A
ISO-9001 Certified
800-257-3872
Visit Setra Online:
http://www.setra.com
CTC Series
(Current Transducers Clamped)
Specifications
MODEL
Multi-Range 30/60/120 A 30/60/120 A 20/100/150 A
Continuous Operating Current 120 A Max. 120 A Max. 150 A Max.
Output 4-20 mA 0-5 VDC 0-10 VDC
Accuracy ( 10% FS) ±2% of Selected Ranges
Response Time 2 Seconds
Output Relay No No No
Actuation Coil Use optional CCR-24 or CCR-12 Command Relay
Dimensions 2.7 x 2.56 x 1.08 in. (68.6 x 65 x 27.4 mm) 2.7 x 2.56 x 1.08 in. (68.6 x 65 x 27.4 mm) 2.7 x 2.56 x 1.08 in. (68.6 x 65 x 27.4 mm)
Aperture Size 0.72 x 0.78 in. (18 x 20 mm)
Sensor Supply Voltage 24 VDC Loop Power Self-Powered
Isolation Voltage 600 V AC rms.
Temperature Range 5 to 140 °F (-15 to 60 °C)
Frequency Range 50/60 Hz
Humidity Range 0 to 95% non-condensing
CTCG420NN CTCGV05NN CTCGV10NN
Module ( sold separately)
Use optional CCR-24 or CCR-12 Command Relay Module ( sold separately)
Use optional CCR-24 or CCR-12 Command Relay Module ( sold separately)
Outline Drawings
2.56 65
2.70
68.6
Models
CTCG420NN, CTCGV05NN,
CTCGV10NN
(Current Transducer Clamped)
1.08
27.4
2.70
68.6
in.
mm
CCR-24 /CCR-12 Command Relay
CTC Series
Model CTC Series (Current Transducer Clamped)
ORDERING INFORMATION
Model No. Description
CTCG420NN Model CTC, Output 4 to 20 mA
CTCGV05NN Model CTC, Output 0 to 5 VDC
CTCGV10NN Model CTC, Output 0 to 10 VDC
† Contact factory to order power relay separately.
2.56 65
Models
CTC Models w/Optional
1.73 44
01/26/11
SSP-CSS-CSC Rev A
While we provide application assistance on all Setra products, both personally and through our literature, it is up to the customer to determine the suitability of the product in the application.
159 Swanson Road, Boxborough, Massachusetts 01719/Tel: 800-257-3872;
Fax: 978-264-0292; Email: sales@setra.com; Web: www.setra.com
Loading...