CONTACTOR
CONTROL
POWER
120 V A
C
FAN OR PUMP
DO
DI
24 V AC/DC
Relay Coil
Troubleshooting
Table 1: Troubleshooting
Symptom Action
CSS solid state output does not function Verify the maximum amperage range has not been exceeded.
Setpoint screw keeps turning The setpoint screw has a slip clutch to prevent damage at either
Motor is turned on and switch does not close Insufficient current to the load leads ( for example, a motor or
Voltages or currents above the rated levels may damage the
CSS.
end. To return the LED to the original setting, turn the setpoint
screw 20 full turns counterclockwise and start the calibration
procedure again.
heater) to reach the setpoint threshold. To turn the switch on,
wrap the cable multiple times through the sensing hole (see
Figure 3.)
Technical Specifications
Model CSSGA2100R1
Amperage Range 1.0 to 135 A
Continuous Operating Current 135 A, 600V AC
Switch Setpoint Adjustable
Output Relay Single Pole, Single Throw (SPST), Normally Open (NO), 10 A @ 260V AC, 5 A @ 30 DC
Actuation Coil 32.5 mA maximum
Switch LED Indication Yes
Relay LED Indication Yes
Current Switching Mode Over/U nder current sensing
Trip Setpoint Value 1.0 to 135 A
Sensor Supply Voltage Induced from power conductor cable.
Status Output Switch normally open
Switch Load Capacity 30V AC/ DC max. 1 A max.
Isolation Voltage 600 V AC rms
Temperature Range -15 to 60°C (5 to 140°F)
Frequency Range 50/60 Hz
Humidity Range 0 to 95% non-condensing
Dimensions 65 x 65 x 40 mm (2.56 x 2.56 x 1.56 in.)
Aperture (Sensing Hole) Size 18 mm Dia. (0.71 in. Dia)
Compliance United States: UL Listed, File E317719 CCN NRNT, Under UL 508, Industrial Control Equip-
For all CE technical questions, contact Setra Systems, USA. EU customers may contact our EU representative Hengstler GmbH, Uhlandstr 49, 78554
Aldingen, Germany (Tel: +49-7424-890; Fax: +49-7424-89500).
The performance specifications are nominal and conform to acceptable industry standards. For application of conditions
beyond these specifications, consult your local Setra representative. Setra Systems, Inc. shall not be liable for damages
from misapplication or misuse of its products.
159 Swanson Road, Boxborough, MA 01719/800-257-3872;
4 CSS Series - Current Switch Solid w/Relay Installation Instructions
Fax: 978-264-0292; Email: sales@setra.com/Web: www. setra.com
ment
Canada: UL Listed. File E317719, CCN NRNT7, Under CAN/CAS C22.2 No. 14-05, Industrial
Control Equipment
Europe: CE Mark LVD 2006/95/EC, EMC Directive 2004/108/EC
Model CSSGA2100R1
Installation Instructions
Introduction
The Current Switch Solid (CSS) Series of digital output switches are noninvasive devices designed to detect low current
flowing through a cable or wire. A cost effective solution for
monitoring on and off status or proof of operation, these units
are ideal for monitoring small current loads on motors driving
fans and blowers, and for sensing the status of heating coils
and lighting.
These units provide a universal solid state output. Excitation is
magnetically induced from current carrying conductor (wire
or cable), making these units completely self-powered.
The factory installed snap-on power relay facilitates the
remote startup and stopping of the motor. It requires a
separate 24 V AC/DC supply.
IMPORTANT: The Current Switch Device (CSS) Series Current
Devices are intended to provide an input to equipment under normal
operating conditions. Where failure or malfunction of the CSS could
lead to personal injury or property damage to the controlled equipment or other property, additional precautions must be designed into
the control system. Incorporate and maintain other devices such as
supervisory or alarm systems or safety or limit controls intended to
warn of, or protect against, failure or malfunction of the CSS.
Installation
!
Dimensions
SSCSS-R REV. C 09/17/09
CSS Series - Current Switch Solid w/Relay
WARNING, Risk of Electric Shock
Disconnect power supply before making electrical
connections. Contact with components carrying
hazardous voltage can cause electric shock and may
result in severe personal injury or death.
65 (2.56)
65 (2.56)
Figure 1: CSS Dimensions mm. (in.)
CSS Series - Current Switch Solid w/Relay Installation Instructions 1
40 (1.56)
Mounting
1. Using the two screws (included), attach the mounti
bracket to the back of the electrical enclosure.
2. Snap the CSS into place on the mounting bracket.
Wiring
1. Disconnect power to the conductor cable from the power
source.
2. Slide the power conductor cable to be monitored through
the sensing hole of the CSS.
3. Wire the CSS/Command Relay as shown in Figure 2.
Note: The switch contacts are solid state and work just like
dry contacts When the switch is closed, less than 1 ohm is
present; when the switch is open, more than 1 megohm is
present.
4. Reconnect the power to the conductor cable (see
Figure 2).
5. Calibrate Model CSSGA2100RI (See the Setup and
Adjustments )
Figure 2: Model CSSGA2100R1
27 (1.08)
+
Status
Status
Open Setpoint
Closed
Relay
+
Status
Status
Open
Closed
Setpoint
Relay
If the measured current is too low to be detected or is higher
+
Status
Status
Open
Closed
Setpoint
Relay
+
Status
Status
Open Setpoint
Closed
Relay
than the maximum current rating of the CSS, use the following methods to increase or decrease current:
If Measured Current is Too Low to be Detected
Wrap the conductor (wire) through the sensing hole and
around the CSS body to produce multiple turns to increase
the measured current
Measured current = actual current times the number of
turns (see Figure 3).
Setup and Adjustments
Calibration
Model CSSGA2100R1
Position the CSS so that the status output panel faces you.
Confirm that the monitored load (for example a motor or
heater) is running, and then use the following methods to
calibrate the CSS.
Under current Status Condition (Belt Loss, Coupling
Shear, Fan, and Pump Status)
1. Turn the setpoint screw clockwise until the Status Closed
Light-Emitting Diode (LED) turns off and the Status Open
LED turns on.
Figure 3: CSS Shown with Four Turns
IMPORTANT: Failure to derate the current capacity could result in
damage to the CSS when using multiple turns to increase measured
current. Use the following formula to determine the new maximum
current:
New Maximum Current = CSS Current Rating/number of turns
(Example: Model CSSGA2100R1 with 4 turns = 135 A/4 = 33.8 A,
new maximum current.)
To Monitor Currents Exceeding the Maximum Current
Rating of the CSS
For currents> 135 Amps:
Use a 5 A Current Transformer (CT) to reduce the current passing
through the CSS as shown in Figure 4. Run the current transformer secondary wire through the sensing hole. Terminate the
two secondary wires of the 5 A current transformer to each other,
and then install the 5 A current transofrmer in the condutor being
monitored.
Current > 135 A
2. Slowly turn the setpoint screw counterclockwise until the
Status Closed LED turns on and the Status Open LED turns off.
3. Turn the setpoint screw an additional 1/4 turn counterclockwise to create a deadband to prevent hunting.
Figure 5: Status Open, LED On
Figure 6: Status Open, LED Off
The CSS is now calibrated to signal current flows below
normal full load amperes.
Output Status:
● Normal: Output Closed
● Alarm: Output Open
Figure 4: CSS with CT Transformer
2 CSS Series - Current Switch Solid w/Relay Installation Instructions
Over Current Status Condition (Locked Rotor, Seized
Impeller)
1. Turn the setpoint screw counterclockwise until the Status
Open LED turns off and the Status Closed LED turns on.
Note: This is the default factory setting.
Figure 7: Status Closed, LED On
2. Slowly turn the setpoint screw clockwise until the Status
Closed LED turns off and the Status Open LED
turns on.
Figure 8: Status Open, LED On
3. Turn the setpoint screw an additional 1/4 turn clockwise to
create a deadband to prevent hunting.
The CSS is now calibrated to signal current flows below
normal full load amperes.
Output Status:
● Normal: Output Open
● Alarm: Output Closed
CSS Series - Current Switch Solid w/Relay Installation Instructions 3
RETURNING PRODUCTS FOR REPAIR
Please contact a Setra application engineer (800-257-3872, 978263-1400) before returning unit for repair to review information
relative to your application. Many times only minor field adjustments
may be necessary. When returning a product to Setra, the material
should be carefully packaged, and shipped to :
Setra Systems, Inc.
159 Swanson Road
Boxborough, MA 01719-1304
Attn: Repair Department
To assure prompt handling, returned unit(s) must be accompanied
by Setra’s Return Order Form, completely filled out, found on Setra’s
web site
at http://www.setra.com/tra/repairs/cal_rep.htm.
Notes: Please remove any pressure fittings and plumbing that you
have installed and enclose any required mating electrical connectors
and wiring diagrams.
Allow approximately 3 weeks after receipt at Setra for the repair and
return of the unit.
Non-warranty repairs will not be made without customer approval
and a purchase order to cover repair charges.
Setra maintains a complete calibration facility that is traceable to
the National Institute of Standards & Technology (NIST). If you
would like to recalibrate or recertify your Setra pressure transducers
or transmitters, please call our Repair Department at 800-257-3872
(978-263-1400) for scheduling.
WARRANTY AND LIMITATION OF LIABILITY
ETRA warrants its products to be free from defects in materials and workmanship, subject
to the following terms and conditions: Without charge, SETRA will repair or replace
products found to be defective in materials or workmanship within the warranty period;
provided that:
a) the product has not been subjected to abuse, neglect, accident, incorrect
wiring not our own, improper installation or servicing, or use in violation of
instructions furnished by SETRA;
b) the product has not been repaired or altered by anyone except SETRA or its
authorized service agencies;
c) the serial number or date code has not been removed, defaced, or otherwise
changed; and
d) examination discloses, in the judgment of SETRA, the defect in materials or
workmanship developed under normal installation, use and service;
e) SETRA is notified in advance of and the product is returned to SETRA
transportation prepaid.
Unless otherwise specified in a manual or warranty card, or agreed to in writing and signed
by a SETRA officer, SETRA pressure and acceleration products shall be warranted for one year
from date of sale.The foregoing warranty is in lieu of all warranties, express, implied or statutory, including but not limited to, any implied warranty of merchantability for a particular
purpose.SETRA’s liability for breach of warranty is limited to repair or replacement, or if the
goods cannot be repaired or replaced, to a refund of the purchase price. SETRA’s liability for
all other breaches is limited to a refund of the purchase price. In no instance shall SETRA be
liable for incidental or consequential damages arising from a breach of warranty, or from the
use or installation of its products.
No representative or person is authorized to give any warranty other than as set out above or
to assume for SETRA any other liability in connection with the sale of its products.
Calibration Services