Setra 3550 Manual

Page 1
Operating & Installation Instructions
Series 355X
Please read carefully before installing
INTRODUCTION
Series 355X high output pressure transducers and transmitters are tted with an Asic providing various op­tional (at time of order) voltage outputs, and a 4-20mA current output capable of being used in control and indicating loops without further amplication.
Series 355X with the CE Mark conform with the essential protection requirements of the EMC Directive 2004/108/EC by certied type testing to BS EN61326-1:2006 and EN61326-2-3:2006.
Series 355X with the CE0086 mark also complies with the requirements of the Pressure Equipment Regu­lations 1999 and is classed as a safety accessory and can be used as a safety-related device on Category IV pressure equipment. No other product should be used as “Safety Accessories” as dened by the PED Article
1, Paragraph 2.1.3.
HAZARDOUS PRODUCTS
The Consumer Protection Act of 1987, Section 6 of the Health and Safety at Work Act 1974 and the Control of Substances Hazardous to Health Regulations 1988 require that we advice recipients and users of our prod­ucts of any potential hazards associated with their storage, handling or use.
The products which our Company supplies may be classied as Electrical, Electro-Mechanical and Electronic equipment.
These products are tested and supplied in accordance with our published specications or individual special requirements that are agreed in writing at time of order. They are constructed so as not to aect adversely the safety of persons and property when properly installed, maintained and used by qualied personnel, in the applications for which they were designed and manufactured.
Conformity with the requirements of the CE mark only applies when the installation conditions de­scribed in these instructions have been met. For units supplied without a cable assembly connection to the transducer must be accomplished using Setra’s approved cable. See APPROVED CABLE section.
Phone: 800-257-3872 • Fax: 978-264-0292 www.setra.com ©2013 Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc.
1
Page 2
GENERAL
• Transducer should not be subjected to greater than the maximum allowable pressure (P.S.)/Temperature
(T.S.) as dened on the transducer label.
• Transducer should not be subjected to mechanical impact.
• In the event of re the end user must ensure that the system pressure is vented to a safe area.
• The eects of decomposition of unstable uids should be considered by the user when placing this device
in service.
• The pressure transducer has no means of draining or venting, this must be performed by another compo­nenty in the end users system.
• Pressure range must be compatible with the maximum pressure being measured.
• Pressure media must be compatible with the transducer/transmitter wetted parts listed in these instruc-
tions.
• Liquids must not be allowed to freeze in the pressure port.
• The gasket must be tted under the electrical connector (mini-din only).
• Supply voltage must not exceed the value stated on the unit label.
MECHANICAL INSTALLATION
Mountaing: Pressure Transducer is designed to be attached by the coupling thread only. Omnidirectional,
self supported directly into the pipework. Use a 22mm spanner on the hexagon provided to apply a maxi­mum torque of 15Nm. The customer must ensure that the pressure seal is suitable for the application. If in doubt, please contact Setra Systems, Inc.
ELECTRICAL INSTALLATION
All types with the CE Mark include suppression devices providing EMC protection to EN61000-4-2, EM 6100­4-3, EN 61000-4-4 and EN 61000-4-6. Conformity with the requirements of the CE Mark only applies when connection is made with Setra’s approved cable. See Approved Cable section, and it connected as shown
below.
APPROVED CABLE
Setra Systems, Inc uses cables comprosing 2, 3 or 4 colour-coded cores, enclosed by an aluminised polyester screen where the screen is in intimate contact with a seperate drain wire. The outer sheath is chrome PVC
and overall diameter is approximately 4mm.
2
Phone: 800-257-3872 • Fax: 978-264-0292 www.setra.com ©2013 Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc.
Page 3
OPERATION
Having installed the transducers as instructed, they are ready for use. The transducer should not be removed
whilst the system is at pressure. Before applying power, check the correct polarity and excitation levels are
being applied. See Table 1 for electrical connections.
CALIBRATION
Transducers are calibrated to the datum requested at time of order; this can be identied by the sixth letter
of the identication code as follows:
A - Absolute datum G - Gauge datum vented to atmostphere via the electrical connector or cable
LOAD CHARACTERISTICS (4-20mA Current Output)
The total resistive load in the loop (to include all the cable resistance) can be ‘zero to 50 x (supply volts -7.5)
ohms1 e.g. with a 24 VDC supply the permissible load is from zero up to 825 ohms.
OPERATIONAL LIFE
Limited to 100M cycles to maximum allowable pressure.
WARRANTY
We guarantee this instrument against fault workmanship and material for a period of two years from date of
delivery. The company undertake to repair, free of charge, ex-works any instrument found to be defective
within the specied period providing the instrument has been used within the specication in accordance with these instructions and has not been misused in any way.
Detailed notice of such defects and satisfactory proof thereof must be given to the company immediately after the discovery and the goods are to be returned free of charge to the company, carefully packaged and accompanied by a detailed failure report. See RETURN TO FACTORY.
WETTED PARTS
316 Stainless Steel.
Phone: 800-257-3872 • Fax: 978-264-0292 www.setra.com ©2013 Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc.
3
Page 4
SERVICING
The transducer cannot be repaired locally and if damaged should be returned to Setra Systems, Inc at the address shown below or to accredited dealers when a replacement/repair is required:
Setra Systems, Inc. 159 Swanson Rd
Boxborough, MA 01719
U.S.A
RETURN TO FACTORY
Please Note: To comply with Health and Safety requirements, the instrument must be clean and safe to handle and accompanied by a formal statement to that eect duly signed by an authorized ocer of the company.
Any instrument returned without certication will be quarantined and no action will occur until cleared. It
may ultimately be returned to you and subject to a transportation charge.
MAINTENANCE
Routine Inspections: Not required except for periodic inspection of the cable and connector to ensure that
these are neither damaged nor softened by incompatible liquid.
For all CE technical questions, contact Setra Systems, USA. EU customers may contact our EU representative
Hengstler GmbH, Uhlandstr. 49, 78554 Aldingen, Germany (TEl: +49-7424-890, Fax: +49-7424-89500)
4
Phone: 800-257-3872 • Fax: 978-264-0292 www.setra.com ©2013 Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc.
Page 5
TABLE 1
CONNECTION 355X SERIES
M12 CONNECTOR - CODE E
OUTPUT IDENTIFICATION CURRENT OUTPUT 4-20 mA VOLTAGE OUTPUT RATIOMETRIC OUTPUT
1 POSITIVE SUPPLY POSITIVE
2 DO NOT CONNECT PRESSURE OUTPUT
3 NEGATIVE COMMON
4 DO NOT CONNECT DO NOT CONNECT
GDS 207 CONNECTOR - CODE B
OUTPUT IDENTIFICATION CURRENT OUTPUT 4-20 mA VOLTAGE OUTPUT RATIOMETRIC OUTPUT
1 DO NOT CONNECT PRESSURE OUTPUT
2 POSITIVE SUPPLY POSITIVE
3 DO NOT CONNECT DO NOT CONNECT
4 NEGATIVE COMMON
DEUTSCH DT04-4P CONNECTOR - CODE 8
OUTPUT IDENTIFICATION CURRENT OUTPUT 4-20 mA VOLTAGE OUTPUT RATIOMETRIC OUTPUT
1 NEGATIVE COMMON
2 POSITIVE SUPPLY POSITIVE
3 DO NOT CONNECT DO NOT CONNECT
4 DO NOT CONNECT PRESSURE OUTPUT
PACKARD METRIPAK CONNECTOR - CODE 9
OUTPUT IDENTIFICATION CURRENT OUTPUT 4-20 mA VOLTAGE OUTPUT RATIOMETRIC OUTPUT
A NEGATIVE NOT
B POSITIVE SUPPLY POSITIVE
C DO NOT CONNECT PRESSURE
AVAILABLE
COMMON
OUTPUT
159 Swanson Rd Boxborough, MA 01719
800-257-3872 || www.setra.com
Phone: 800-257-3872 Fax: 978-264-0292 www.setra.com ©2013 Setra Systems, Inc. All rights reserved. The Setra Systems name and logo are registered trademarks of Setra Systems, Inc.
SS3550 Rev. A 3/7/14