Every Model 3100 has been tested and calibrated before shipment.
Setra Systems 3100 pressure transducers sense gauge pressure and convert this
pressure difference to a proportional high level analog output. The following
standard output and excitation versions are offered:
EXCITATIONOUTPUT
10 to 30 VDC4 to 20 mA
5 VDC ±10%0.5 to 4.5 Ratiometric
0 to 10 VDC
2V above Full Scale to 30 VDC max @ 4.5mA0 to 5 VDC
2.0MECHANICAL INSTALLATION
2.1 Media Compatibility
Model 3100 transducers are designed to be used with any gases or liquids
compatible with 17-4 PH Stainless Steel.
2.2 Environment
The operating temperature limits of the 3100 are -40°F to +250°F
(-40°C to +125°C). The compensated temperature range is -40°F to +250°F
(-40°C to +125°C).
Ingress Protection: all transducers/transmitters have a minimum IP rating
of IP65 in accordance with BS EN 60529:1992.
2.2 Electrical (See Diagram A, page 2 for electrical connections)
Cable Connectors: where client cable are used, the cable shield must be
terminated by the client. The shield should not be connected to the
transducer body.
Setra uses a 4-core color coded cable enclosed by a braided shield
terminated within the transducer housing. Conformance of requirement
with relation to the CE Mark, is only valid with Setra’s approved cable.
Frequency
Maximum Current Draw: 2-wire Transmitter = 20mA, Transducer in
voltage mode = 8mA, transducer in millivolt mode = 3.5mA
EMC Data: Meets the requirements of CE.
This product complies with EN61326 Electrical Equipment for Measurement,
Control and Laboratory use – EMC Requirements for Minimum Requirements
and Industrial Locations. Special caution should be taken to meet Standard
EN61000-4-5: 1995 Surge Immunity if any of the following conditions apply to
Response: <1ms for Conditioned Outputs.
0.5 to 4.5 VDC
1 to 6 VDC
1 to 5 VDC
2mV/V (nominal)
3
the installation: The product is installed outside; all or any part of the cable is
exposed to the outside; the cable is greater than 30 meters in length. In order to
meet the Surge Immunity requirements, the following conditions must be
followed during installation:
1. Shielded cable must be used, and the shield must be tied to earth ground (not power supply
ground) on at least one end of the cable shield/drain wire. The shield must be maintained all
the way from sensor to the power supply.
2. If unshielded cable is used, an earth grounded metal conduit fitting can be used to replace
the shielded cable.
3. For a sensor with a metal body or enclosure, the body/enclosure must be grounded to earth.
If a protective metal housing is used, the metal housing should be grounded to earth
4. If a protective plastic housing is used, the housing must be able to withstand at least
2 KV from the housing to earth ground, without damaging the circuit.
2.3 Pressure Ranges
Pressure Range (Psi)Proof PressureBurst Pressure
PSI (Bar)(x Full ScaleX Full Scale
100-300 (10-25)40 x FS
500-1500 (40-100)20 X FS
2000-6000 160-400)10 X FS
7500-15000 (600-1000)4 x FS
20,000 (1,600)2 x FS
25,000 (1,800)1.8 x FS
30,000 (2,200)1.5 x FS
2.20 x FS
1.25 x FS
0.22/6
0.76
19.3
1.45
37
Electrical Connections, Diagram A
(see page 6 for mating connectors)
0.38
9.7
0.72
18.3
1.46
37
2
KEY
M12 x 1P (Code E)
3
1
PinVoltageCurrent
4
M12 x 1P
#ModeMode
V
1
SupplySupply
V
2
out1No
(connect)
3GroundReturn
V
4
out2No
(temp)Connect
3
2
1
Amp Superseal 1.5
(Code 6)
1.02
25.9
Pin Voltage Current
#ModeMode
1Vout1No
(pressure) Connect
2GroundReturn
3VSupplySupply
DIN 9.4mm* (Code B)
2
4
1
3
PinVoltageCurrent
#ModeMode
1
1
(pressure) Connect
2VSupplySupply
3
4GroundReturn
*mating cnnector not supplied
2
Packard Metri Pack
V
out1No
(pressure)
V
out2No
(temp)Connect
(Code 9)
3
Pin Voltage Current
#ModeMode
1Vout1No
(pressure) Connect
2GroundReturn
3VSupplySupply
in.
mm
4
2
3
Deutsch DT04-4P
41
(Code 8)
0.07
1.9
1.5
38.1
0.82
20.83
PinVoltageCurrent
#ModeMode
1GroundReturn
2
3
4
3
V
SupplySupply
V
out2No
(temp)Connect
V
out1No
(pressure) Connect
1.27
32.2
2.4 Pressure Fittings (See Diagram B below)
NPTF (Dryseal & Standard Tapered Threads): “Dryseal” Pipe threads are designed
to seal pressure tight joints without the need of compounds. To accomplish the
seal, the root of both internal and external threads are truncated slightly more
than the crests, i.e. roots have wider flats than crests. Therefore, metal-to-metal
contact occurs when wrenching and crushing the sharper crests of the mating
thread, thus creating the pressure tight joint and preventing spiral leakage.
However, where functionally not objectionable, Setra recommends the use of
an Anaerobic sealing compound to ensure an absolute pressure tight seal and
minimize thread galling. Standard taper threads require the use of a sealing
compound and are not interchangeable with “R” designed threads.
2.5 Installation
Voltage and current units can be installed by either wrench or deep socket. Sizes
22 A/F and 27 A/E. The tightening torque depends upon the material and the
sealing mechanism. The tightening torque should not exceed 30Nm in any case.
Vibration: 50g Sinusoidal 20—200Hz
Operation: Ha ving installed the transducers as instructed, they are ready for use.
Before applying power, check that the correct polarity and excitation levels are
being applied.
Pressure Fittings
Diagram B
0.28
0.49
12.5
7
0.43
11
0.28
7
0.55
14
3
0.28
0.5
12.8
2
KEY
1
DIN72585A1-4, 1
4
φ
0.93
φ
23.5
PinVoltage Current
Code 7
#ModeMode
V
1
SupplySupply
2GroundReturn
V
3
out1No
V
4
out2No
(temp)Connect
in.
mm
0.44
11.1
0.28
7
0.57
14.44
7
01 = G 1/4" Ext.
0.28
7
08 and 4D = 1/8"-27 NPT Ext. 05 = G 1/4" A Integral Face Seal
04 = 7/16"-20 UNF w/37° Flare
0.28
7
0.38
9.65
0.49
12.5
1J = 7/16"-20 with O-Ring02 and 4C = 1/4"-18 NPT Ext.
0.28
7
0.43
11
2T = M12 x 1.5 HP Metal Washer Seal
0.65
16.5
0.28
7
Female 7/16 w/Schrader
Notes: The diameter of all cans is 0.748" (19mm). Hex is 0.866" (22mm) across flats for (A/F) for deep socket mounting.
5
1G = 1/4-SAE
0.67
17
3.0 MATING CONNECTORS (OPTIONAL)
For use on
Part NO.Description Elect Code #
557230Mini Din connector, Strain ReliefB
557703-01M0 M12 Cord Set - 1 Meter (Red 1, Green 2, Blue 3, Yellow 4)E
557703-03M0 M12 Cord Set - 3 Meters (Red 1, Green 2, Blue 3, Yellow 4)E
557703-04M0 M12 Cord Set - 4 Meters (Red 1, Green 2, Blue 3, Yellow 4)E
557703-05M0 M12 Cord Set - 5 Meters (Red 1, Green 2, Blue 3, Yellow 4)E
Recommended Mating Parts (AMP p/n: Housing 282087-1;
Contacts 3X 183025-1; Seal 281934-1; Boot 880811-26
557701AMP Superseal Mate Kit6
210729AMP 3.5’ Cable Cord Set - Clear Pos 1, Black Pos 2, Red Pos 36
210730AMP 12” Flying Leads Cord Set - White Pos 1, Black, Red Post 36
Recommended Mating Parts (AMP p/n: Socket Conn. 1-967325-1,
Consult AMP for Contacts, Wire Seal and Strain Relief options)7
557702Din 72585 Twist Lock Mate Kit7
Recommended Mating Parts (Deutsch p/n: Houisng Plug
Recommended Mating Parts (Delphi Packard MetriPack
p/n Body 12065286; Seal 12052893. Consult Delphi for Contacts)9
218760Packard Mate Kit9
581Packard Cord Set 3’ Long
582Packard Cord Set 6’ Long
(18 AWG PVC Cable - White 1, Black 2, Red 3)9
(18 AWG PVC Cable - White 1, Black 2, Red 3)9
6
7
4.0RETURNING PRODUCTS FOR REPAIR
tified
Please contact a Setra application engineer (800-257-3872, 978-263-1400) before
returning unit for repair to review information relative to your application. Many times
only minor field adjustments may be necessary. When returning a product to Setra, the
material should be carefully packaged and shipped prepaid to:
Setra Systems, Inc.
159 Swanson Road
Boxborough, MA 01719-1304
Attn: Repair Department
To assure prompt handling, please supply the following information and include it
inside the package or returned material:
1.Name and phone number of person to contact.
2.Shipping and billing instructions.
3.Full description of the malfunction.
4.Identify any hazardous material used with product. Service order
return form must accompany product. Form is available at
www.setra.com/tra/repairs/cal_rep.htm. Form must be filled out
completely. Returns that arrive without the form or properpaperwork will be rejected.
Notes: Please remove any pressure fittings and plumbing that you have installed and
enclose any required mating electrical connectors and wiring diagrams.
Non-warranty repairs will not be made without customer approval and a purchase
order to cover repair charges.
5.0 LIMITED WARRANTY AND LIMITATION OF LIABILITY
SETRA warrants its products to be free from defects in materials and workmanship, subject to the following
terms and conditions: Without charge, SETRA will repair or replace products found to be defective in
materials or workmanship within the warranty period; provided that:
a) the product has not been subjected to abuse, neglect, accident, incorrect wiring not our own,
improper installation or servicing, or use in violation of instructions furnished by SETRA;
b) the product has not been repaired or altered by anyone except SETRA or its authorized service
agencies;
c)the serial number or date code has not been removed, defaced, or otherwise changed; and
d) examination discloses, in the judgment of SETRA, the defect in materials or workmanship developed
under normal installation, use and service;
e) SETRA is notified in advance of and the product is returned to SETRA transportation prepaid.
Unless otherwise specified in a manual or warranty card, or agreed to in writing and signed by a SETRA
officer, SETRA pressure and acceleration products shall be warranted for one year from date of delivery.
The foregoing warranty is in lieu of all warranties, express, implied or statutory, including but not limited to,
any implied warranty of merchantability for a particular purpose.
SETRA’s liability for breach of warranty is limited to repair or replacement. In no instance shall SETRA be
liable for incidental or consequential damages arising from a breach of warranty, or from the use or
installation of its products. No representative or person is authorized to give any warranty other than as set
out above or to assume for SETRA any other liability in connection with the sale of its products.
OP3100 Rev.B 08/04/06
159 Swanson Road, Boxborough, MA 01719-1304
Tel: 800-257-3872/978-263-1400; Fax: 978-264-0292
Email: sales@setra.com; web: www.setra.com
8
ISO
9001:
2000
Certified
✓
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.