Setra 231 Operating Manual

Model 231 Multi-Sense®
Wet-to-Wet Pressure Transducer
978-263-1400; 800-257-3872
www.setra.com; sales@setra.com
1
2
Contents
1.0 GENERAL INFORMATION...................................................................... 4
2.0 MECHANICAL INSTALLATION ............................................................. 4
2.2 Environment...................................................................................... 4
2.3 Pressure Fittings............................................................................... 5
2.4 Mounting............................................................................................ 5
2.5 Installation Procedures.................................................................. 5
3.0 OPTIONAL 3-VALVE MANIFOLD PROCEDURE............................... 6
4.0 ELECTRICAL INSTALLATION................................................................. 8
4.1 Electrical Termination
Wiring: 2-Wire , 4 to 20 mA and Remote Zero............................. 8
4.2 Electrical Termination
Wiring: 3-Wire, 0 to 5, 0 to 10, 1-5 VDC and Remote Zero........ 9
5.0 OPERATION..............................................................................................10
6.0 RETURNING PRODUCTS FOR REPAIR..............................................11
7.0 WARRANTY AND LIMITATION OF LIABILITY.................................11
3
Model 231
Installation Guide
Multi-Sense® Model 231 Series
Wet-to-Wet Differential Pressure Transducers
1.0 GENERAL INFORMATION
Every Model 231 has been calibrated and tested before shipment to guarantee performance of all pressure ranges.
The Model 231 has field selectable unidirectional and bidirectional pressure ranges, configurable 0 to 5 VDC, 0 to 10 VDC , and 1 to 5 VDC output, true two-wire 4 to 20 mA output, and auto-zero capability. The Model 231 is factory calibrated to the highest pressure range. The range label on the side of the unit indicates the factory calibrated range.
Setra Systems 231 pressure transducers sense differential pressure and convert this difference in pressure to a proportional high level analog output for unidirec­tional and bidirectional pressure ranges.
Your Model 231 Multi-Sense pressure transducer has been ordered in one of the following versions:
Version Unidirectional Bidirectional
MS1 5, 10, 20, 50 psid ±5, ±10, ±20, ±50 psid MS2 10, 20, 50, 100 psid ±10, ±20, ±50, ±100 psid MS3 25, 50, 125, 250 psid ±25, ±50, ±125, ±250 psid
2.0 MECHANICAL INSTALLATION
2.1 Media compatibility
Model 231 transducers are designed to be used with any gas or liquid compat­ible with 17-4 PH stainless steel, The optional 3-valve manifold assembly is designed to be used with gases or liquids compatible with 360 Brass, Acetal plug valves and Nitrile O-Rings. Never totally submerge the unit in any liquid.
2.2 Environment
The operating temperature limits of the 231 are as follows:
Compensated T emperature Range °F (°C) +32 to +130 (0 to +54) Operating Temperature Range °F (°C) -4 to +185 (-20 to +85) Storage T emperature Range °F (°C) -4 to +185 (-20 to +85)
4