SMART BUILDING
SMART METERING
INDOOR
WATER AND ENERGY METERING
(PULSE)
THIS SENLAB™ M SMART WIRELESS DEVICE,
Ref : PUL-LAB-41NS
17 years *
(replaceable battery)
15 km *
Local or Public
Network compliant
* Depending on the
operating conditions
IP30
(Indoor use)
• Building Energy Management System
• Energy efciency : Regulate energy costs
FEATURING THE LoRaWAN™ CONNECTIVITY PROTOCOL,
IS EQUIPPED WITH TWO INPUTS : DRY CONTACT,
ELEC. SWITCHING, S0 OUTPUT*.
Designed for indoor use, Senlab™ M offers a small casing with a discreet aesthetic that
makes it ideal for housing or ofce. This Senlab offers best in class features such as :
• Battery life time up to 17 years
• Rich Data Content thanks to datalogging : Up to 24 measures / radio transmission
• Radio Performances
• Advanced set of functionalities
• Dual meters monitoring
TYPICAL APPLICATIONS
• Water, gas, and electricity metering
• Control and monitor energy consumption
TECHNICAL SPECIFICATIONS
*COMPATIBILITY TO CHECK
Physical
specications
RF
specications
EC Conformity :
Compliant with Directive
2014/53/UE (RED)
Dimensions 50 x 91,5 x 25 mm
Weight 60 gr
Operating temperature 0°C to +55°C
RF sensitivity -137 dBm
RF power +14 dBm (25 mW)
Radio band 868 MHz
EMC
Radio EN 300 220-2 v3.1.1
Magnetic eld exposure EN 62479
Safety EN 60950-1
Final draft EN 301 489-3 v2.1.1
Draft EN 301 489-1 v2.2.0
www.sensing-labs.com

TECHNICAL FEATURES FOCUS
DIMENSIONAL DRAWING
91,5 mm
25 mm
50 mm
Plug & Play installation
• Product fixing with double
sided tape or screw mounting
• Screw terminal for pulse
emitter cable connection
• Activation with magnet
(LED feedback)
• LED indication of pulse during
few minutes after activation
BATTERY LIFE DURATION ESTIMATION
This following matrix provides the estimated battery lifetime depending on
the average spreading factor used by the Senlab and the transmission period.
High congurability
of pulse counting
• 2 inputs configurable for dry contact
or open collector interfaces
• Set/Reset of start index
• Wirecut and minimal flowrate
information
• Log and transmit mode for battery
lifetime enhancement
(up to 24 compressed measures
per transmission)
• Stream mode (timestamp for each
pulse) for consumption profile analysis
• Reconfiguration possible
over the air
Network Conguration
• LoRaWAN parameters
(OTAA or ABP activation
mode, initial datarate,...)
• Encryption keys
customizable by client
• Standard LoRaWAN
retries support
• Radio collisions avoidance
by pseudo-randomization of
transmissions
• Advanced transmission
reliability mechanisms
(redundancy of data, recovery
of lost messages, …)
Battery life (years) 10 min 15 min 30 min 1 h 2 h 4 h 6 h 8 h 12 h 24 h
SF7 12,4 13,6 15,1 16,0 16,5 16,7 16,8 16,9 16,9 16,9
SF8 10,4 12,0 14,0 15,4 16,1 16,6 16,7 16,8 16,8 16,9
SF9
SF10
SF11
SF12
6 measures per frame. For guidance and information purposes only.
www.sensing-labs.com
7,9 9,6 12,3 14,3 15,5 16,2 16,5 16,6 16,7 16,9
5,4 7,0 9,9 12,5 14,4 15,6 16,0 16,3 16,5 16,7
3,4 4,7 7,3 10,3 12,8 14,6 15,3 15,7 16,1 16,5
2,1 2,9 5,0 7,7 10,6 13,0 14,1 14,7 15,4 16,2
T : +33 (0)4 67 47 55 67
contact@sensing-labs.com
Sensing Labs - 187 rue Hélène Boucher
34170 Castelnau-le-Lez