SENSING LABS SL PUL-LAB-41NS Datasheet

Page 1
SMART BUILDING
SMART METERING
INDOOR
WATER AND ENERGY METERING
(PULSE)
THIS SENLAB™ M SMART WIRELESS DEVICE,
Ref : PUL-LAB-41NS
17 years * (replaceable battery)
15 km *
Local or Public Network compliant
* Depending on the operating conditions
IP30 (Indoor use)
Building Energy Management System
Energy efciency : Regulate energy costs
FEATURING THE LoRaWAN™ CONNECTIVITY PROTOCOL,
IS EQUIPPED WITH TWO INPUTS : DRY CONTACT,
Designed for indoor use, Senlab™ M offers a small casing with a discreet aesthetic that
makes it ideal for housing or ofce. This Senlab offers best in class features such as :
Battery life time up to 17 years
Rich Data Content thanks to datalogging : Up to 24 measures / radio transmission
Radio Performances
Advanced set of functionalities
Dual meters monitoring
TYPICAL APPLICATIONS
Water, gas, and electricity metering
Control and monitor energy consumption
TECHNICAL SPECIFICATIONS
*COMPATIBILITY TO CHECK
Physical
specications
RF
specications
EC Conformity :
Compliant with Directive
2014/53/UE (RED)
Dimensions 50 x 91,5 x 25 mm
Weight 60 gr
Operating temperature 0°C to +55°C
RF sensitivity -137 dBm
RF power +14 dBm (25 mW)
Radio band 868 MHz
EMC
Radio EN 300 220-2 v3.1.1
Magnetic eld exposure EN 62479
Safety EN 60950-1
Final draft EN 301 489-3 v2.1.1
Draft EN 301 489-1 v2.2.0
www.sensing-labs.com
Page 2
TECHNICAL FEATURES FOCUS
DIMENSIONAL DRAWING
91,5 mm
25 mm
50 mm
Plug & Play installation
Product fixing with double
sided tape or screw mounting
Screw terminal for pulse
emitter cable connection
Activation with magnet
(LED feedback)
LED indication of pulse during
few minutes after activation
BATTERY LIFE DURATION ESTIMATION
This following matrix provides the estimated battery lifetime depending on
the average spreading factor used by the Senlab and the transmission period.
High congurability of pulse counting
2 inputs configurable for dry contact
or open collector interfaces
Set/Reset of start index
Wirecut and minimal flowrate
information
Log and transmit mode for battery
lifetime enhancement (up to 24 compressed measures per transmission)
Stream mode (timestamp for each
pulse) for consumption profile analysis
Reconfiguration possible
over the air
Network Conguration
LoRaWAN parameters
(OTAA or ABP activation
mode, initial datarate,...)
Encryption keys
customizable by client
Standard LoRaWAN
retries support
Radio collisions avoidance
by pseudo-randomization of transmissions
Advanced transmission
reliability mechanisms (redundancy of data, recovery of lost messages, …)
Battery life (years) 10 min 15 min 30 min 1 h 2 h 4 h 6 h 8 h 12 h 24 h
SF7 12,4 13,6 15,1 16,0 16,5 16,7 16,8 16,9 16,9 16,9
SF8 10,4 12,0 14,0 15,4 16,1 16,6 16,7 16,8 16,8 16,9
SF9
SF10
SF11
SF12
6 measures per frame. For guidance and information purposes only.
www.sensing-labs.com
7,9 9,6 12,3 14,3 15,5 16,2 16,5 16,6 16,7 16,9
5,4 7,0 9,9 12,5 14,4 15,6 16,0 16,3 16,5 16,7
3,4 4,7 7,3 10,3 12,8 14,6 15,3 15,7 16,1 16,5
2,1 2,9 5,0 7,7 10,6 13,0 14,1 14,7 15,4 16,2
T : +33 (0)4 67 47 55 67