SecuTech SECU-DATA 1420M, SECU-DATA 1420C, SECU-DATA 1421M, SECU-DATA 1421C, SECU-DATA 1500M User guide

...
Page 1
Operating Instructions
SECU-DATA
Wireless data transmission
Page 2
Page 2 Security & Electronic Technologies GmbH
General
In order to keep this document as short as possible the following abbreviations are used:
SECU-DATA 1xxxx is used generally for: SECU-DATA 1420M, SECU-DATA 1420C, SECU-DATA 1421M,
SECU-DATA 1421C, SECU-DATA 1500M, SECU-DATA 1500C, SECU-DATA 1600M, SECU-DATA 1700M
SECU-DATA 142xx is used instead of: SECU-DATA 1420M, SECU-DATA 1420C, SECU-DATA 1421M, SECU-DATA 1421C
SECU-DATA 142xC is used for: SECU-DATA 1420C, SECUDATA 1421C
SECU-DATA 142xM is used for: SECU-DATA 1420M, SECUDATA 1421M
Dcoument: LI036
Version: Rev. 1.0 Date: 2007-04
Important: The technical specification stated in this document is sub­ject to modification by the manufacturer without any notice.
©SECURITY & ELECTRONIC TECHNOLOGIES GmbH.
Page 3
Page 3 Security & Electronic Technologies GmbH
TOC - Table of Contents
Safety instructions ................................................................. 4
Product description ............................................................... 4
Components ................................................................................. 4
SECU-DATA Instruments ............................................................. 5
Checking the contents of delivery ........................................ 6
Control elements .......................................................................... 8
Commissioning ...................................................................... 9
Installation .................................................................................... 9
Application of SECU-DATA 1420S/1421S (4-20 mA).................. 11
Application of SECU-DATA 1500 (Relay) ................................... 11
Application of SECU-DATA 1600 (NAMUR) ............................... 12
Application of SECU-DATA 1700 (TRbF) .................................... 12
Wiring the connection lines ......................................................... 13
Terminals: ................................................................................... 14
SECU-DATA 1420/1421 (4-20mA) ................................ ............. 14
SECU-DATA 1500 (Relay) ......................................................... 15
SECU-DATA 1600 (NAMUR) ...................................................... 17
SECU-DATA 1700 (TRbF) .......................................................... 18
Putting into service a SECU-DATA 142xx................................... 20
Dismantling .......................................................................... 20
Settings ................................................................................. 21
Selection of the RF-channel block .............................................. 21
Matching two SECU-DATA 1xxxx ............................................... 22
Monitoring the RF-status, alarm generation ................................ 23
SECU-DATA 1500C configuration .............................................. 25
Maintenance ......................................................................... 26
Warranty ............................................................................... 26
Disposal ................................................................................ 26
Troubleshooting ................................................................... 27
Technical specification ........................................................ 28
Index...................................................................................... 31
Page 4
Page 4 Security & Electronic Technologies GmbH
Safety instructions
During installation and operation of this measurement system adhere strict­ly to the operating instructions of the manufacturer, take into account all local applicable safety instructions, standards and technical recommenda­tions. SECU-DATA xxxx shall be used for applications only described in this doc­ument. For improper use or applications it is not designated for and also for the resulting damages the manufacturer cannot overtake any responsibility. Modifications on the product are prohibited. Service, repair, and maintenance can be done by the manufacturer or au­thorised service facilities only. SECU-DATA xxxx instruments shall be installed and operated by persons only who have studied and understood these operating instructions.
Product description
Components
The components of the new SECU-DATA product line make use of latest technologies for the transmission of measurement data via radio frequency connections in the 433 MHz band for various fields of applications: Wireless transmission of 4-20 mA signals from a measurement location to the control centre, typical applications are industrial process automisation, evaluation of all kinds of 4-20 mA sensors for temperature, humidity, filling level etc. in the chemical industry. Wide fields of applications exist for remote transfer of liquid levels of all tank probes in common use to a centralised control station, integration of overfill prevention systems into fuelling systems for automotive fuelling, harbour terminals, railway tankers and aeroplane fuelling systems.
The main advantages are:
Wireless transfer of measurement data to the control centre without
galvanic connections
Protection class IP68 for outdoor applications  no wiring, no ground loops  quick installation without digging  highest reliability of the RF-connection due to high noise rejection
with automatic channel selection
Page 5
Security & Electronic Technologies GmbH Page 5
Applications for SECU-DATA 14xxx: All practical applications where 4-20 mA measurement signals have to be transmitted and where wiring is not feasible. Temporary measurement data transmission for verification of fix installed sensors, for this application the high accuracy of the 16-bit resolution is highly appreciated. Measurement data acquisition on mobile tanks, where wiring is not feasible. Remote monitoring of gauge sensors, limit switches.
SECU-DATA Instruments
SECU-DATA 1420M
RF-module for evaluating and transmitting 4-20 mA signals with 12-bit reso­lution to a receiver module SECU-DATA 1420C. “M“ indicates measure­ment site. 4-20 mA signals are commonly used by sensors in process con­trol; therefore this versatile module is suitable for a wide range of applica­tions.
SECU-DATA 1420C
RF module for the reception and reproduction of the 4-20 mA signals from a SECU-DATA 1420M with 12-bit resolution. “C“ is short for controller, SECU­DATA 420C is installed in the control centre.
SECU-DATA 1421M
Same as SECU-DATA 1420M but with enhanced accuracy, with 16-bit resolution fulfilling highest accuracy requirements.
SECU-DATA 1421C
Same as SECU-DATA 1420C but with enhanced accuracy, with 16-bit reso­lution fulfilling highest accuracy requirements.
SECU-DATA 1500M
RF-module for the transmission of the status of two potential free relay con­tacts (open or closed ) to a receiver module SECU-DATA 1500C. “M“ is for measurement site. Applications are remote monitoring of limit switches, of overfill prevention systems, position of limit switches etc. in the chemical industry, in process automisation, for loading and fuelling systems for liq­uids, liquid gas, and powdery products.
SECU-DATA 1500C
RF-module for the output of the status of two relay contacts sent from a SECU-DATA 1500M. “C“ is for controller, SECU-DATA 1500C is installed in the control centre. In combination with a SECU-DATA 1600M (NAMUR) or
Page 6
Page 6 Security & Electronic Technologies GmbH
SECU-DATA 1700M (TRbF) tank probe conditions from NAMUR-type or TRbF-type probes can be monitored remotely.
SECU-DATA 1600M
RF-module for evaluation and transmission of the output signals of a NA­MUR –type probe (NAMUR is an abbreviation for: Normen Arbeitsgemein­schaft für Mess- und Regeltechnik) as per EN 50277 to a receiver module SECU-DATA 500C. “M“ is for measurement site. The conditions “filling permissible“ or “filling not permissible”, and “Probe FAULT“ are sent to the receiver SECU-DATA 1500C and are indicated by two relay contacts.
SECU-DATA 1700M
RF-module for monitoring a TRbF–type probe (TRbF is an abbreviation for the German Technische Regeln für brennbare Flüssigkeiten) with a re­ceiver module SECU-DATA 500C for explosive areas. “M“ is for measure­ment site. The conditions “ON“ or “OFF“, and “Probe FAULT“ are sent to the receiver SECU-DATA 500C and are indicated by two relay contacts. The limit switch of the probe is mounted inside the tank. The limit switch monitors the filling level. It is supplied from the SECU-DATA 1700M directly.
SECU-TOP1, SECU-TOP3, SECU-TOP6
Sets with 1 m, 3 m, 6 m coax-type extension cables incl. mounting material for the RF antenna. This is recommended if an RF-module of the SECU­DATA product range is used in tank room or in an environment damping the transmission of high frequency signals (like dome compartments etc.)
SECU-TOP150
Spare RF-antenna, 15 cm.
SECU-TOP300
Extra long antenna, 30 cm, for extended effective RF range, for critical RF­propagation conditions.
Checking the contents of delivery
Please, check the contents of delivery immediately after receipt and un­packing. In case of missing components or transport damages contact your local dealer or a SECU-TECH representative.
Hint: Each SECU-DATA 1xxxx is shipped with one RF-antenna and an operating instruction manual. Please keep the original packing material if you have to send the instrument to a service facility. For damages resulting from improper packing the man­ufacturer cannot overtake any liability. Keep these operating instructions in case you hand over the instruments to other persons or if operating personnel has to be trained.
Page 7
Security & Electronic Technologies GmbH Page 7
SECU-DATA 1420 - 4-20 mA, 12-bit
SECU-DATA 1420M for measurement site Order No.: HF061 SECU-DATA 1420C for controller site Order No.: HF062
SECU-DATA 1421 4-20 mA, 16-bit
SECU-DATA 1421M for measurement site Order No.: HF063 SECU-DATA 1421C for the controller site Order No.: HF064
SECU-DATA 1500 - relay
SECU-DATA 1500M for measurement site Order No.: HF065 SECU-DATA 1500C for controller site Order No.: HF066
SECU-DATA 1600 - NAMUR
SECU-DATA 1600M for measurement site Order No.: HF067 SECU-DATA 1500C for the controller site Order No.: HF066
SECU-DATA 1700 - TRbF
SECU-DATA 1700M for measurement site Order No.: HF068 SECU-DATA 1500C for the controller site Order No.: HF066
Optional accessories: SECU-TOP1 Extension cable set 1 m for RF antenna with
mounting angle Order No. HF069 SECU-TOP3 Extension cable set 3 m for RF antenna with mounting angle Order No. HF070 SECU-TOP6 Extension cable set 6 m for RF antenna with mounting angle Order No. HF071
SECU-TOP150 spare RF-antenna, 150 mm (/4) Order No. HF072 SECU-TOP300 extra long RF-antenna, 300 mm (/2) Order No. HF073
Page 8
Page 8 Security & Electronic Technologies GmbH
LED
indicators
Antenna
cable
glands
Control elements
LED indicators with the following functions Green: RF connection:
OFF: no RF connection
Blinking: Searching for partner instrument, ON: RF connection active Yellow: Power supply:
OFF: power failure ON: Power supply in nominal range Blinking with green LED: matching mode Red: Error indication:
OFF: system working properly ON: internal error
RF antenna: app. 150 mm (/4), TNC connector. Extension cables and an extra long antenna (/2) are available as an option.
Cable glands (M16 x 1.5)
Page 9
Security & Electronic Technologies GmbH Page 9
83 mm
96 mm
M4
Distance of drilling holes:
Horizontal: 83 mm Vertical: 96 mm
Commissioning
Installation
Mount the supplied RF-antenna on the connector on the housing of the SECU-DATA 1xxxx. Mount the SECU-DATA 1xxxx strain free to the base using 4 pcs. M4 screws:
In case of metallic base material (chassis of vehicles, machinery) try to maximise the distance between RF-antenna and the base to achieve max­imum effective RF range.
Mount the supplied RF antenna to the TNC connector on the housing of the SECU-DATA xxxx
Page 10
Page 10 Security & Electronic Technologies GmbH
SECU-DATA xxxM and also SECU-DATA xxxC have internal block termi­nals (type: WAGO series 256, ATEX certified) for connection of the corre­sponding external wires.
Important: Only qualified personnel with appropriate training and authorisation by the installation manager is entitled to connect SECU-DATA xxxx to an existing installation. Adhere to all applicable, local safety regulations.
Hint: For SECU-DATA systems using the SECU-DATA 1500C as a receiv­er the function of the relay contacts can be reconfigured from make con-
tacts to break contacts, see section Settings-SECU-DATA 1500C relay configuration on page 25.
Attention: In case of connection problems SECU-DATA maintains the last valid information on the receiver output. This is valid for the cur­rent output of SECU-DATA 142X and also for the relay outputs of SECU-DATA 1500C. For overfill prevention applications with SECU­DATA 1600M/1700M it is important to ensure the turn-off of pumps in case of radio failures. This can be achieved by connection the make contact of Re1 of the SECU-DATA 1500C in series to the “RF-status” relay contact.
Page 11
Security & Electronic Technologies GmbH Page 11
4-20 mA 4-20 mA
11 - 40 V
DC
11 - 40 V
DC
SECU-DATA 1420M SECU-DATA 1421M
SECU-DATA 1420C SECU-DATA 1421C
11 - 40 V
DC
11 - 40 V
DC
SECU-DATA 1500M
SECU-DATA 1500C
Application of SECU-DATA 142xM/142xC (4-20 mA)
SECU-DATA 142xx can be supplied from a standard 24 V DC power supply.
Application of SECU-DATA 1500M/1500C (Relay)
Page 12
Page 12 Security & Electronic Technologies GmbH
11 - 40 V
DC
Probe
NAMUR
SECU-DATA 1500C
SECU-DATA 1600M
Re1: NAMUR Re2: Probe fault
Probe
TrbF probe
11 - 40 V
DC
SECU-DATA 1500C
SECU-DATA 1700M
TRbF: ON-OFF
Re1: TRbF: ON-OFF
Re2: Probe fault
Application of SECU-DATA 1600M (NAMUR)
Application of SECU-DATA 1700M (TRbF)
Page 13
Security & Electronic Technologies GmbH Page 13
Button A
Button B
Wiring the connection lines
Open the housing by removing the fixing screws of the lid.
Important:
Install the wiring only after the power supply of the installation has been turned off. Follow strictly the safety instructions from the manufacturer; adhere to all applicable standards, norms and technical guidelines.
Pass all required wires (using round cables) through the cable glands (M16 x 1.5) and fix them tightly to ensure the water protection of the housing.
Page 14
Page 14 Security & Electronic Technologies GmbH
Terminal
Signal, function
1
Plus-pole of power supply (+11 V … +40 V), reverse polarity protection by two 2 diodes
2
Ground line of power supply (0 V)
3
Measuring signal 4-20 mA, positive pole, SECU-DATA 142xM: input, for connection of the
probe SECU-DATA 142xC: output, for connection of
the evaluation equipment
4
Measuring signal 4-20 mA, negative pole, SECU-DATA 142xM: input, for connection of the
probe SECU-DATA 142xC: output, for connection of
the evaluation equipment
5
Not connected
6, 7, 8
Relay contacts, passive, for monitoring the sta­tus of the RF-connection
7 is the root, for active RF-connection terminals 6-7 are interconnected, during RF-interruptions terminals 7-8 are interconnected.
Rated switching capacity: 30 V / 500 mA
Terminals:
SECU-DATA 142xM/142xC (4-20mA)
Page 15
Security & Electronic Technologies GmbH Page 15
Terminal
Signal, function
1
Plus-pole of power supply (+11 V … +40 V), reverse polarity protection by two 2 diodes
2
Ground line of power supply (0 V)
3
SECU-DATA 1500M: input Re1, for connection of the external contact and to terminal 4
SECU-DATA 1500C: output Re1, make contact, for connection of the evaluation equipment
4
SECU-DATA 1500M: input Re1, for connection of the external contact, connected to terminal 6
SECU-DATA 1500C: output Re1, make contact, for connection of the evaluation equipment
Rated switching capacity: 30 V / 500 mA
5
SECU-DATA 1500M: input Re2, for connection of the external contact and to terminal 6
SECU-DATA 1500C: output Re2, make contact, for connection of the evaluation equipment.
Rated switching capacity: 30 V / 500 mA
6
SECU-DATA 1500M: input Re2, for connection of the external contact, connected to terminal 4
SECU-DATA 1500C: output Re2, make contact, for connection of the evaluation equipment
7, 8
Relay contact, passive, for monitoring the status of the RF-connection.
For active RF-connection terminals 7-8 are in­terconnected.
Rated switching capacity: 30 V, 500 mA
SECU-DATA 1500M/1500C (Relay)
Page 16
Page 16 Security & Electronic Technologies GmbH
1 2 3 4 5 6 7 8
V+
V-
V+
V+
Re1
Re2
Funk
SECU-DATA 1500M
1 2 3 4 5 6 7 8
V-
V+
Re2
Re1
RF status
SECU-DATA 1500C
Re1
Re1
Re2
Re2
Connection diagrams:
Transmitter Receiver:
SECU-DATA 1500M SECU-DATA 1500C
Functionality:
The status of the relay contacts Re1 and Re2 connected to the inputs of the SECU-DATA 1500M, is detected and sent per RF-connection to the receiv­er module SECU-DATA 1500C.
Note: There is a current limited voltage present on the inputs for testing the relay contact status. Therefore the contacts have to be potential free and insulated, terminals 4 and 6 are internally connected within the SECU­DATA 1500M. The contact status (“open“ or “closed“) is reproduced on the relay outputs Re1 and Re2 on the SECU-DATA 1500C. The contact function, make or break, can be configured. The rated switching capacity is 30 V / 500 mA. Important application note: SECU-DATA maintains the last valid value on the receiver output in case of connection problems. To ensure that the con­nected controlled device is turned off (this is very important for overfill pre­vention systems!) the make contact of relay Re1 has to be connected in series to the „RF-status“ contact (blue line in the connection diagram).
Page 17
Security & Electronic Technologies GmbH Page 17
Terminal
Signal, function
1
Plus-pole of power supply (+11 … +40 V), reverse polar­ity protection by two 2 diodes
2
Ground line of power supply (0 V)
3
Positive pole for connection of the NAMUR-probe. SECU-DATA 600M applies 8.2 V DC via
1000 Ohms
4
Negative pole for connection of the NAMUR probe
5
Not connected
6, 7, 8
Relay contacts, passive, for monitoring the status of the RF-connection
7 is the root, for active RF-connection terminals 6-7 are interconnected, during RF-interruptions terminals 7-8 are interconnected.
Rated switching capacity: 30 V / 500 mA
SECU-DATA 1600M (NAMUR)
SECU-DATA 1500C is used as the receiver, for the terminal connections see section SECU-DATA 1500 on page 15 in this chapter.
Functionality:
The connected probe is tested for basic functionality: If the probe current is below 0.4 mA or higher than 6 mA, relay Re2 of the receiver SECU-DATA 1500C is activated per RF-connection, the contact is closed. This can be used to issue an alarm message. The contact is connected to terminals 5, 6 of the SECU-DATA 1500C. During the filling process the contact of relay Re1 SECU-DATA 1500C is also closed via RF-signals (probe current is more than 2 mA); if the tank is full (filling is not permissible, probe current below 1 mA) Re1 opens.
See also the important application hint on page 16.
Page 18
Page 18 Security & Electronic Technologies GmbH
Terminal
Signal, function
1
Plus-pole of power supply (+22 V … +40 V), reverse polarity protection by two 2 diodes, ignition prevention level “ib“
2
Ground line of power supply (0 V)
3
Connection of the positive pole of the TRbF probe
4
Connection of the negative pole of the TRbF probe
5
Not connected
6, 7, 8
Relay contacts, passive, for monitoring the sta­tus of the RF-connection
7 is the root, for active RF-connection terminals 6-7 are interconnected, during RF-interruptions terminals 7-8 are interconnected.
Rated switching capacity: 30 V / 500 mA
SECU-DATA 1700M (TRbF)
SECU-DATA 1500C is used as a receiver, for the connections see section
SECU-DATA 1500M/1500C on page 15. See also the important application hint on page 16.
Page 19
Security & Electronic Technologies GmbH Page 19
Wiring of the SECU-DATA xxxx:
1. For the wiring use round wires of type: 0,08 – 2,5mm2 cross section, AWG 28 – 12, flame propagation characteristics as per IEC 60332­1-2, within a round cable to ensure the water protection
2. Strip the wires off app. 5-6 mm
3. Depress each of the levers of the terminal block (Type WAGO se­ries 256) with a small screw driver
4. Put the stripped wire end into the terminal and release the lever again
5. Close the SECU-DATA xxxx housing again and mount it to the final location with the supplied screws in the provided holes of the hous­ing. Take care for correct positioning of the sealing elements. For metal base planes ensure that there is some space between the RF-antenna and the metal material to maintain the best effective range of the RF connection.
Remark: After delivery one cable gland is sealed waterproof with a cap. This is useful if only one cable gland shall be used.
Page 20
Page 20 Security & Electronic Technologies GmbH
Putting into service a SECU-DATA 142xx
1. Connect the probes and the evaluation equipment to the SECU­DATA 142xx units
2. Turn on the DC power supply in the range of +11 V … +40 V
3. Match one pair of instruments together: Set the same channel block number on both instruments – factory default is block #6 – details se chapter Settings-Selection of the RF-channel block Match the instruments together – detail see chapter Settings-
Matching two SECU-DATA xxxx
4. Both SECU-DATA 142xx modules will establish an RF-inter­connection immediately, the green RF-indicators are blinking. After some seconds they are continuously on – the connection is active.
5. The current on the input of the SECU-DATA 142xM is reproduced precisely on the output of the SECU-DATA 142xC for evaluation with the controller equipment.
6. Check the current values on the evaluation instrument for plausibility.
The commissioning is completed now successfully.
Dismantling
Important: If you detect any damage of the housing, controls, connection wires or other connected devices, immediately disconnect the unit from the power supply. If you cannot ensure the safe operation of the device, immediately shut down the unit and the respective accessories, secure them against inad­vertent switching on, mark them clearly as “defective, out of order” and send them in to an authorized service facility.
Page 21
Security & Electronic Technologies GmbH Page 21
Button B
Button A
Settings
Selection of the RF-channel block
SECU-DATA 1xxxx instruments use one RF-channel out of 64. These are organized in 8 blocks with 8 channels each. The default setting is block #6. Two SECU-DATA 1xxxx instruments are able to communicate only if the same block for RF-channels is set on both instruments.
Procedure for both units:
1. Open the housing of the SECU-DATA 1xxxx. Avoid the intrusion of moisture and pollution while the instrument is open to maintain the reliability
2. Turn on the power supply of the SECU-DATA 1xxxx
3. Press the B-button two times shortly
4. The green “RF“-LED will blink several times, the number of light pulses gives the actual number of the channel block (1 to 8).
5. The light pulses are repeated after a 1 s pause. Each press on but­ton A increments the block number by 1. On the end of the range the block number falls back from 8 to 1 automatically.
6. An interruption of the power supply aborts the procedure, the origi­nal block number remains in memory; the actual one is not stored.
7. The procedure can be finished by pressing the B-button; the actual block number is stored permanently.
8. Repeat this procedure for the second SECU-DATA 1xxxx to set the same block number
If required you may check the block number using steps 1 to 4 as described above.
Page 22
Page 22 Security & Electronic Technologies GmbH
Button B
Button A
Matching two SECU-DATA 1xxxx
After the delivery SECU-DATA 1xxxx instruments are not matched together. This has to be done during setup. Also after replacement of a unit, after service and repair it might be necessary to repeat the tuning procedure.
Procedure for both units:
1. Open the housing of the SECU-DATA 1xxxx. Avoid the intrusion of moisture and pollution while the instrument is open to maintain the long-term reliability
2. Turn on the power supply of the SECU-DATA 1xxxx
3. Press shortly on both instruments the A-button
4. The green “RF”-LED and the yellow “Power“-LED on the SECU­DATA 1xxxx start blinking alternately – the instruments are in the matching mode now
5. After completion both instruments perform automatically a RESET – the red LED flashes shortly. If the tuning process is not success­ful you can abort it by pressing shortly the button A – the original settings remain in memory
6. Now the green “RF”-LED and the yellow “Power”-LED on both in­struments are continuously on – the matching procedure is finished successfully and the RF-connection is established.
Page 23
Security & Electronic Technologies GmbH Page 23
Contact 6-7 is closed as long as the RF­connection is estab­lished. This circuitry provides best reliability: if the RF-connection is lost or a power failure of the SECU-DATA xxxx occurred, the contact opens and the alarm lamp will be turned on immediately. Inverter relays can be used also. Additional­ly the contact function can be configured.
7
6
Monitoring the RF-status, alarm generation
Depending on the application it might be important to monitor the status of the RF-connection and to generate an alarm indication in case of interrup­tions. Important: During interruptions of the RF-connection SECU-DATA 1xxxC instruments freeze the latest transmitted value and keep them on the output. The status of the RF-connection can be tested via relay contacts. SECU-DATA 1xxxx incorporate a relay contact, a make contact, which is closed as long as the connection is active. The rated switching capacity of the contact is 30 V / 500 mA.
Hint
Also the instruments SECU-DATA 1xxxM located on the measurement side are equipped with such a relay contact with the same functionality. Thus an alarm indication can be realised on the measurement site too.
If you want to realise an alarm signal (e.g. by a lamp) on the controller site make use of this contact (principle diagram):
SECU-DATA 142xM, 142xC, 1600M, 1700M
Page 24
Page 24 Security & Electronic Technologies GmbH
Contact 7-8 is closed as long as the RF­connection is estab­lished. During RF­interruptions it is open and the lamp goes on to indicate an alarm condi­tion. The rated switching ca­pacity of the contact is 30 V / 500 mA.
7
6
8
The make contact can be used for variants:
SECU-DATA 1500M, 1500C
Page 25
Security & Electronic Technologies GmbH Page 25
Mode
Relay RF
Re1
Re2
1
normal
make
make
2
inverse
make
make
3
normal
break
make
4
inverse
break
make
5
normal
make
break
6
inverse
make
break
7
normal
break
break
8
inverse
break
break
SECU-DATA 1500C configuration
After delivery the relay contacts are configured as make contacts, which can be changed to break contacts if required.
Procedure:
1. Turn on the power supply of the SECU-DATA 1500C
2. Press and keep depressed the button A and press two times the button B. The green “RF“-LED starts blinking, the number of pulses indicates the relay mode:
make … contact closes if the relay is activated.
break … contact opens if the relay is activated.
3. Pressing of button B saves the settings
Hint: On all the other SECU-DATA 1xxxx instruments this configuration is also provided but for the RF-relay function only, thus mode 1 and 2 are available only.
Page 26
Page 26 Security & Electronic Technologies GmbH
Maintenance
Instruments of the SECU-DATA 1xxxx product range do not need any maintenance, no user serviceable components are inside of the housing.
Important:
Repair and service tasks can be done by qualified service personnel only. This is the only way to maintain the required level of ignition prevention. The service activities carried out are documented and these files are kept in archives for at least 10 years.
Warranty
For the actual services and conditions see the internet home page
www.secu-tech.at, see the GTCS – General Terms and Conditions of Sale.
Disposal
SECU-DATA instruments must not be disposed of via the municipal waste collection system. Security & Electronic Technologies GmbH. takes back used SECU-DATA instruments for appropriate disposal for a small charge. The symbol for disposal via qualified recyclers is attached visibly and per­manently on the instrument.
Page 27
Security & Electronic Technologies GmbH Page 27
Troubleshooting
Problem: The RF-connection cannot be established Solution 1:
Check:
Is the supplied antenna mounted correctly?  Are there obstacles which block the propagation of the RF waves?  Is the distance between transmitter and receiver less than 1 km?
Select an optimal position for the antenna, antenna extension cables are available as an option.
Solution 2:
Interrupt shortly the power supply of both SECU-DATA 1xxxx units and turn them on again. The modules will establish a new connection and they will search for free undistorted RF-channels automatically.
Solution 3:
If this does not solve the problem match together the two instruments again. For the procedure see chapter Settings - Matching two SECU-DATA
1xxxx Solution 4:
If the tuning cannot be carried out successfully check the number of the RF­channel block. Both instruments have to operate within the same block of 8 RF-channels. For the procedure of verification and re-definition of the RF-channel block see chapter Settings - Selection of an RF-channel block
If all measures described in this chapter do not solve your problem then send in the modules with a short description of the problem and with a copy of the delivery note (in case of warranty claims) to the manufacturer or to an authorised service facility.
Page 28
Page 28 Security & Electronic Technologies GmbH
Technical specification
Radio frequency data transfer
Transmitting and receiving frequency in the 433 MHz band, very narrow bandwidth, 64 channels in 8 frequency blocks (selectable on the instru­ment), 25 kHz channel separation, effective range up to 1 km or even more in open areas, best temperature stability, insensitive to distortions, automat­ic selection of an undistorted channel, RF data transmission rate: 4.800 Baud (data bits/s). A potential-free relay contact is used to monitor the sta­tus of the RF connection, e.g. to issue an alert in case of an RF interruption
Technical Specification Display: Fuses:
RF-module: Housing of SECU-DATA 1xxxx
Dimensions (l x w x h): 146 x 97 x 60 mm Weight: app. 650 g incl. antenna Antenna: app. 150 mm (l4), connector: TNC Construction: mouldered with PU 403 – WEVO Protection: IP 68 Material, colour: Deltacom ASA 4501 EC 6, dark green
Rated specification of SECU-DATA 1xxxx
Supply voltage: 11 V ... 40 V DC, Power consumption (without probe): max. 1.2 W Ambient temperature: -30°C ≤ Ta ... +75°C
3 LEDs
Temperature fuses
Conform to ETSI EN 300 220 (5/1999/EG R&TTE directive)
Page 29
Security & Electronic Technologies GmbH Page 29
Probe current
Re1
Re2
Meaning
0 … 0.4 mA
OFF
ON
Probe fault, “interruption”
1 … 2 mA
ON
OFF
Filling is in progress
2 … 6 mA
OFF
OFF
Tank full
> 6 mA
OFF
ON
Probe fault, “short”
Probe current
Re1
Re2
Meaning
0 … 6 mA
OFF
ON
Probe fault, “interruption”
6 … 40 mA
ON
OFF
Filling is permissible
>42 mA
OFF
OFF
Filling not permissible
>105 mA
OFF
ON
Probe fault, “short”
Technical specification of SECU-DATA 142xx Measurement uncertainty SECU-DATA 1421M/1421C- 16-Bit:
Typical at 25°C: ±0.02% of measured value Max. (-30°C … 75°C): ±0.1% of measured value Resolution: 0.4 µA
Measurement uncertainty SECU-DATA 1420M/1420C- 12-Bit:
Typical at 25°C: ±0.1% of measured value Max. (-30°C … 75°C): ±0.3% of measured value Resolution: 6 µA Rise time: < 0.5 s
Technical specification of SECU-DATA 1500M/1500C - Relay
For the transmission of the status of the two relay contacts no further speci­fication is required. Rated switching capacity: 30 V / 500 mA.
Technical specification of SECU-DATA 1600M - NAMUR
Switching threshold depending on the current flow through the NAMUR probe:
Technical specification of SECU-DATA 1700M - TRbF
Threshold for the current flow through the TRbF probe:
Connectors of SECU-DATA 1xxxx
The connecting wires (round cables have to be used) are fed into the hous­ing via cable glands (M16 x 1.5, type SKINTOP) with appropriate strain relief to a terminal block (type WAGO series 256). The number of wires and their functionality depends on the SECU-DATA model, see the appropriate section in this document.
Norms, standards applied:
tive).
ETSI EN 300 220 (5/1999/EG R&TTE direc-
Page 30
Page 30 Security & Electronic Technologies GmbH
Notes:
Page 31
Page 31 Security & Electronic Technologies GmbH
Index
alarms ............................................................................................ 23
antenna extension cable ................................................................... 7
block terminals ............................................................................... 10
channel block ................................................................................. 21
channel separation ......................................................................... 28
Connection configurations ........................................................ 11, 12
connection wires ............................................................................. 13
Connectors ..................................................................................... 29
Control elements .............................................................................. 8
Dimensions .................................................................................... 28
ETSI EN 300 220 ........................................................................... 30
LED indicators .................................................................................. 8
operating temperature .................................................................... 28
power consumption ........................................................................ 28
RF antenna ...................................................................................... 8
RF-LED .......................................................................................... 22
terminal block ................................................................................. 19
terminals ......................................................................................... 14
wire type ......................................................................................... 19
Page 32
Telefon: +43 2256 20177-0 Fax: +43 2256 20177-11 E-Mail: office@secu-tech.at Homepage: www.secu-tech.at
Aumühlweg 3/1 A-2544 Leobersdorf Austria
Security & Electronic Technologies GmbH
Other products:
RF Fuelling and overfill prevention system:
LRC – Level Remote Control
Tank contents instrument LC 100
For heating oil tanks, water tanks, waste oil tanks,…
In the distribution line: Level Control Systems
Optilevel – automatic level control Industrial probes from several manufacturers TWM-Hectour – Tank Truck Management System Signalman, Ultiman, Watchman, See our homepage:
Loading...