During installation and operation of this measurement system adhere strictly to the operating instructions of the manufacturer, take into account all
local applicable safety instructions, standards and technical recommendations.
SECU-DATA xxxx shall be used for applications only described in this document. For improper use or applications it is not designated for and also for
the resulting damages the manufacturer cannot overtake any responsibility.
Modifications on the product are prohibited.
Service, repair, and maintenance can be done by the manufacturer or authorised service facilities only.
SECU-DATA xxxx instruments shall be installed and operated by persons
only who have studied and understood these operating instructions.
Product description
Components
The components of the new SECU-DATA product line make use of latest
technologies for the transmission of measurement data via radio frequency
connections in the 433 MHz band for various fields of applications:
Wireless transmission of 4-20 mA signals from a measurement location to
the control centre, typical applications are industrial process automisation,
evaluation of all kinds of 4-20 mA sensors for temperature, humidity, filling
level etc. in the chemical industry.
Wide fields of applications exist for remote transfer of liquid levels of all tank
probes in common use to a centralised control station, integration of overfill
prevention systems into fuelling systems for automotive fuelling, harbour
terminals, railway tankers and aeroplane fuelling systems.
The main advantages are:
Wireless transfer of measurement data to the control centre without
galvanic connections
Protection class IP68 for outdoor applications
no wiring, no ground loops
quick installation without digging
highest reliability of the RF-connection due to high noise rejection
with automatic channel selection
Page 5
Security & Electronic Technologies GmbHPage 5
Applications for SECU-DATA 14xxx:
All practical applications where 4-20 mA measurement signals have to be
transmitted and where wiring is not feasible.
Temporary measurement data transmission for verification of fix installed
sensors, for this application the high accuracy of the 16-bit resolution is
highly appreciated.
Measurement data acquisition on mobile tanks, where wiring is not feasible.
Remote monitoring of gauge sensors, limit switches.
SECU-DATA Instruments
SECU-DATA 1420M
RF-module for evaluating and transmitting 4-20 mA signals with 12-bit resolution to a receiver module SECU-DATA 1420C. “M“ indicates measurement site. 4-20 mA signals are commonly used by sensors in process control; therefore this versatile module is suitable for a wide range of applications.
SECU-DATA 1420C
RF module for the reception and reproduction of the 4-20 mA signals from a
SECU-DATA 1420M with 12-bit resolution. “C“ is short for controller, SECUDATA 420C is installed in the control centre.
SECU-DATA 1421M
Same as SECU-DATA 1420M but with enhanced accuracy, with 16-bit
resolution fulfilling highest accuracy requirements.
SECU-DATA 1421C
Same as SECU-DATA 1420C but with enhanced accuracy, with 16-bit resolution fulfilling highest accuracy requirements.
SECU-DATA 1500M
RF-module for the transmission of the status of two potential free relay contacts (open or closed ) to a receiver module SECU-DATA 1500C. “M“ is for measurement site. Applications are remote monitoring of limit switches, of
overfill prevention systems, position of limit switches etc. in the chemical
industry, in process automisation, for loading and fuelling systems for liquids, liquid gas, and powdery products.
SECU-DATA 1500C
RF-module for the output of the status of two relay contacts sent from a
SECU-DATA 1500M. “C“ is for controller, SECU-DATA 1500C is installed in
the control centre. In combination with a SECU-DATA 1600M (NAMUR) or
Page 6
Page 6Security & Electronic Technologies GmbH
SECU-DATA 1700M (TRbF) tank probe conditions from NAMUR-type or
TRbF-type probes can be monitored remotely.
SECU-DATA 1600M
RF-module for evaluation and transmission of the output signals of a NAMUR –type probe (NAMUR is an abbreviation for: Normen Arbeitsgemeinschaft für Mess- und Regeltechnik) as per EN 50277 to a receiver module
SECU-DATA 500C. “M“ is for measurement site. The conditions “filling
permissible“ or “filling not permissible”, and “Probe FAULT“ are sent to the
receiver SECU-DATA 1500C and are indicated by two relay contacts.
SECU-DATA 1700M
RF-module for monitoring a TRbF–type probe (TRbF is an abbreviation for
the German “Technische Regeln für brennbare Flüssigkeiten”) with a receiver module SECU-DATA 500C for explosive areas. “M“ is for measurement site. The conditions “ON“ or “OFF“, and “Probe FAULT“ are sent to
the receiver SECU-DATA 500C and are indicated by two relay contacts.
The limit switch of the probe is mounted inside the tank. The limit switch
monitors the filling level. It is supplied from the SECU-DATA 1700M directly.
SECU-TOP1, SECU-TOP3, SECU-TOP6
Sets with 1 m, 3 m, 6 m coax-type extension cables incl. mounting material
for the RF antenna. This is recommended if an RF-module of the SECUDATA product range is used in tank room or in an environment damping the
transmission of high frequency signals (like dome compartments etc.)
SECU-TOP150
Spare RF-antenna, 15 cm.
SECU-TOP300
Extra long antenna, 30 cm, for extended effective RF range, for critical RFpropagation conditions.
Checking the contents of delivery
Please, check the contents of delivery immediately after receipt and unpacking. In case of missing components or transport damages contact your
local dealer or a SECU-TECH representative.
Hint: Each SECU-DATA 1xxxx is shipped with one RF-antenna and an
operating instruction manual.
Please keep the original packing material if you have to send the instrument
to a service facility. For damages resulting from improper packing the manufacturer cannot overtake any liability.
Keep these operating instructions in case you hand over the instruments to
other persons or if operating personnel has to be trained.
Page 7
Security & Electronic Technologies GmbHPage 7
SECU-DATA 1420 - 4-20 mA, 12-bit
SECU-DATA 1420M for measurement site Order No.: HF061
SECU-DATA 1420C for controller site Order No.: HF062
SECU-DATA 1421 4-20 mA, 16-bit
SECU-DATA 1421M for measurement site Order No.: HF063
SECU-DATA 1421C for the controller site Order No.: HF064
SECU-DATA 1500 - relay
SECU-DATA 1500M for measurement site Order No.: HF065
SECU-DATA 1500C for controller site Order No.: HF066
SECU-DATA 1600 - NAMUR
SECU-DATA 1600M for measurement site Order No.: HF067
SECU-DATA 1500C for the controller site Order No.: HF066
SECU-DATA 1700 - TRbF
SECU-DATA 1700M for measurement site Order No.: HF068
SECU-DATA 1500C for the controller site Order No.: HF066
Optional accessories:
SECU-TOP1 Extension cable set 1 m for RF antenna with
mounting angle Order No. HF069
SECU-TOP3 Extension cable set 3 m for RF antenna with
mounting angle Order No. HF070
SECU-TOP6 Extension cable set 6 m for RF antenna with
mounting angle Order No. HF071
SECU-TOP150 spare RF-antenna, 150 mm (/4) Order No. HF072
SECU-TOP300 extra long RF-antenna, 300 mm (/2) Order No. HF073
Page 8
Page 8Security & Electronic Technologies GmbH
LED
indicators
Antenna
cable
glands
Control elements
LED indicators with the following functions
Green:RF connection:
OFF: no RF connection
Blinking: Searching for partner instrument,
ON: RF connection active
Yellow: Power supply:
OFF: power failure
ON: Power supply in nominal range
Blinking with green LED: matching mode
Red: Error indication:
OFF: system working properly
ON: internal error
RF antenna: app. 150 mm (/4), TNC connector. Extension cables and
an extra long antenna (/2) are available as an option.
Cable glands (M16 x 1.5)
Page 9
Security & Electronic Technologies GmbHPage 9
83 mm
96 mm
M4
Distance of drilling holes:
Horizontal: 83 mm
Vertical: 96 mm
Commissioning
Installation
Mount the supplied RF-antenna on the connector on the housing of the
SECU-DATA 1xxxx.
Mount the SECU-DATA 1xxxx strain free to the base using 4 pcs. M4
screws:
In case of metallic base material (chassis of vehicles, machinery) try to
maximise the distance between RF-antenna and the base to achieve maximum effective RF range.
Mount the supplied RF antenna to the TNC connector on the housing of the
SECU-DATA xxxx
Page 10
Page 10Security & Electronic Technologies GmbH
SECU-DATA xxxM and also SECU-DATA xxxC have internal block terminals (type: WAGO series 256, ATEX certified) for connection of the corresponding external wires.
Important:
Only qualified personnel with appropriate training and authorisation by the
installation manager is entitled to connect SECU-DATA xxxx to an existing
installation. Adhere to all applicable, local safety regulations.
Hint: For SECU-DATA systems using the SECU-DATA 1500C as a receiver the function of the relay contacts can be reconfigured from make con-
tacts to break contacts, see section Settings-SECU-DATA 1500C relay
configuration on page 25.
Attention: In case of connection problems SECU-DATA maintains the
last valid information on the receiver output. This is valid for the current output of SECU-DATA 142X and also for the relay outputs of
SECU-DATA 1500C. For overfill prevention applications with SECUDATA 1600M/1700M it is important to ensure the turn-off of pumps in
case of radio failures. This can be achieved by connection the make
contact of Re1 of the SECU-DATA 1500C in series to the “RF-status”
relay contact.
Page 11
Security & Electronic Technologies GmbHPage 11
4-20 mA4-20 mA
11- 40 V
DC
11-40 V
DC
SECU-DATA 1420M
SECU-DATA 1421M
SECU-DATA 1420C
SECU-DATA 1421C
11-40 V
DC
11 - 40 V
DC
SECU-DATA 1500M
SECU-DATA 1500C
Application of SECU-DATA 142xM/142xC (4-20 mA)
SECU-DATA 142xx can be supplied from a standard 24 V DC power supply.
Application of SECU-DATA 1500M/1500C (Relay)
Page 12
Page 12Security & Electronic Technologies GmbH
11 - 40 V
DC
Probe
NAMUR
SECU-DATA 1500C
SECU-DATA 1600M
Re1: NAMUR
Re2: Probe fault
Probe
TrbF
probe
11 - 40 V
DC
SECU-DATA 1500C
SECU-DATA 1700M
TRbF: ON-OFF
Re1: TRbF: ON-OFF
Re2: Probe fault
Application of SECU-DATA 1600M (NAMUR)
Application of SECU-DATA 1700M (TRbF)
Page 13
Security & Electronic Technologies GmbHPage 13
Button A
Button B
Wiring the connection lines
Open the housing by removing the fixing screws of the lid.
Important:
Install the wiring only after the power supply of the installation has been
turned off.
Follow strictly the safety instructions from the manufacturer; adhere to all
applicable standards, norms and technical guidelines.
Pass all required wires (using round cables) through the cable glands (M16
x 1.5) and fix them tightly to ensure the water protection of the housing.
Page 14
Page 14Security & Electronic Technologies GmbH
Terminal
Signal, function
1
Plus-pole of power supply (+11 V … +40 V),
reverse polarity protection by two 2 diodes
2
Ground line of power supply (0 V)
3
Measuring signal 4-20 mA, positive pole,
SECU-DATA 142xM: input, for connection of the
probe
SECU-DATA 142xC: output, for connection of
the evaluation equipment
4
Measuring signal 4-20 mA, negative pole,
SECU-DATA 142xM: input, for connection of the
probe
SECU-DATA 142xC: output, for connection of
the evaluation equipment
5
Not connected
6, 7, 8
Relay contacts, passive, for monitoring the status of the RF-connection
7 is the root, for active RF-connection terminals
6-7 are interconnected, during RF-interruptions
terminals 7-8 are interconnected.
Rated switching capacity: 30 V / 500 mA
Terminals:
SECU-DATA 142xM/142xC (4-20mA)
Page 15
Security & Electronic Technologies GmbHPage 15
Terminal
Signal, function
1
Plus-pole of power supply (+11 V … +40 V),
reverse polarity protection by two 2 diodes
2
Ground line of power supply (0 V)
3
SECU-DATA 1500M: input Re1, for connection
of the external contact and to terminal 4
SECU-DATA 1500C: output Re1, make contact,
for connection of the evaluation equipment
4
SECU-DATA 1500M: input Re1, for connection
of the external contact, connected to terminal 6
SECU-DATA 1500C: output Re1, make contact,
for connection of the evaluation equipment
Rated switching capacity: 30 V / 500 mA
5
SECU-DATA 1500M: input Re2, for connection
of the external contact and to terminal 6
SECU-DATA 1500C: output Re2, make contact,
for connection of the evaluation equipment.
Rated switching capacity: 30 V / 500 mA
6
SECU-DATA 1500M: input Re2, for connection
of the external contact, connected to terminal 4
SECU-DATA 1500C: output Re2, make contact,
for connection of the evaluation equipment
7, 8
Relay contact, passive, for monitoring the status
of the RF-connection.
For active RF-connection terminals 7-8 are interconnected.
Rated switching capacity: 30 V, 500 mA
SECU-DATA 1500M/1500C (Relay)
Page 16
Page 16Security & Electronic Technologies GmbH
1
2
3
4
5
6
7
8
V+
V-
V+
V+
Re1
Re2
Funk
SECU-DATA
1500M
1
2
3
4
5
6
7
8
V-
V+
Re2
Re1
RF status
SECU-DATA 1500C
Re1
Re1
Re2
Re2
Connection diagrams:
Transmitter Receiver:
SECU-DATA 1500M SECU-DATA 1500C
Functionality:
The status of the relay contacts Re1 and Re2 connected to the inputs of the
SECU-DATA 1500M, is detected and sent per RF-connection to the receiver module SECU-DATA 1500C.
Note: There is a current limited voltage present on the inputs for testing the
relay contact status. Therefore the contacts have to be potential free and
insulated, terminals 4 and 6 are internally connected within the SECUDATA 1500M.
The contact status (“open“ or “closed“) is reproduced on the relay outputs
Re1 and Re2 on the SECU-DATA 1500C. The contact function, make or
break, can be configured. The rated switching capacity is 30 V / 500 mA.
Important application note: SECU-DATA maintains the last valid value on
the receiver output in case of connection problems. To ensure that the connected controlled device is turned off (this is very important for overfill prevention systems!) the make contact of relay Re1 has to be connected in
series to the „RF-status“ contact (blue line in the connection diagram).
Page 17
Security & Electronic Technologies GmbHPage 17
Terminal
Signal, function
1
Plus-pole of power supply (+11 … +40 V), reverse polarity protection by two 2 diodes
2
Ground line of power supply (0 V)
3
Positive pole for connection of the NAMUR-probe.
SECU-DATA 600M applies 8.2 V DC via
1000 Ohms
4
Negative pole for connection of the NAMUR probe
5
Not connected
6, 7, 8
Relay contacts, passive, for monitoring the status of the
RF-connection
7 is the root, for active RF-connection terminals 6-7 are
interconnected, during RF-interruptions terminals 7-8
are interconnected.
Rated switching capacity: 30 V / 500 mA
SECU-DATA 1600M (NAMUR)
SECU-DATA 1500C is used as the receiver, for the terminal connections
see section SECU-DATA 1500 on page 15 in this chapter.
Functionality:
The connected probe is tested for basic functionality: If the probe current is
below 0.4 mA or higher than 6 mA, relay Re2 of the receiver SECU-DATA
1500C is activated per RF-connection, the contact is closed. This can be
used to issue an alarm message. The contact is connected to terminals 5, 6
of the SECU-DATA 1500C.
During the filling process the contact of relay Re1 SECU-DATA 1500C is
also closed via RF-signals (probe current is more than 2 mA); if the tank is
full (filling is not permissible, probe current below 1 mA) Re1 opens.
See also the important application hint on page 16.
Page 18
Page 18Security & Electronic Technologies GmbH
Terminal
Signal, function
1
Plus-pole of power supply (+22 V … +40 V),
reverse polarity protection by two 2 diodes,
ignition prevention level “ib“
2
Ground line of power supply (0 V)
3
Connection of the positive pole of the TRbF
probe
4
Connection of the negative pole of the TRbF
probe
5
Not connected
6, 7, 8
Relay contacts, passive, for monitoring the status of the RF-connection
7 is the root, for active RF-connection terminals
6-7 are interconnected, during RF-interruptions
terminals 7-8 are interconnected.
Rated switching capacity: 30 V / 500 mA
SECU-DATA 1700M (TRbF)
SECU-DATA 1500C is used as a receiver, for the connections see section
SECU-DATA 1500M/1500C on page 15.
See also the important application hint on page 16.
Page 19
Security & Electronic Technologies GmbHPage 19
Wiring of the SECU-DATA xxxx:
1. For the wiring use round wires of type: 0,08 – 2,5mm2 cross section,
AWG 28 – 12, flame propagation characteristics as per IEC 603321-2, within a round cable to ensure the water protection
2. Strip the wires off app. 5-6 mm
3. Depress each of the levers of the terminal block (Type WAGO series 256) with a small screw driver
4. Put the stripped wire end into the terminal and release the lever
again
5. Close the SECU-DATA xxxx housing again and mount it to the final
location with the supplied screws in the provided holes of the housing. Take care for correct positioning of the sealing elements. For
metal base planes ensure that there is some space between the
RF-antenna and the metal material to maintain the best effective
range of the RF connection.
Remark: After delivery one cable gland is sealed waterproof with a cap.
This is useful if only one cable gland shall be used.
Page 20
Page 20Security & Electronic Technologies GmbH
Putting into service a SECU-DATA 142xx
1. Connect the probes and the evaluation equipment to the SECUDATA 142xx units
2. Turn on the DC power supply in the range of +11 V … +40 V
3. Match one pair of instruments together:
Set the same channel block number on both instruments – factory
default is block #6 – details se chapter Settings-Selection of the RF-channel block
Match the instruments together – detail see chapter Settings-
Matching two SECU-DATA xxxx
4. Both SECU-DATA 142xx modules will establish an RF-interconnection immediately, the green RF-indicators are blinking. After
some seconds they are continuously on – the connection is active.
5. The current on the input of the SECU-DATA 142xM is reproduced
precisely on the output of the SECU-DATA 142xC for evaluation
with the controller equipment.
6. Check the current values on the evaluation instrument for
plausibility.
The commissioning is completed now successfully.
Dismantling
Important:
If you detect any damage of the housing, controls, connection wires or other
connected devices, immediately disconnect the unit from the power supply.
If you cannot ensure the safe operation of the device, immediately shut
down the unit and the respective accessories, secure them against inadvertent switching on, mark them clearly as “defective, out of order” and
send them in to an authorized service facility.
Page 21
Security & Electronic Technologies GmbHPage 21
Button B
Button A
Settings
Selection of the RF-channel block
SECU-DATA 1xxxx instruments use one RF-channel out of 64. These are
organized in 8 blocks with 8 channels each. The default setting is block #6.
Two SECU-DATA 1xxxx instruments are able to communicate only if the
same block for RF-channels is set on both instruments.
Procedure for both units:
1. Open the housing of the SECU-DATA 1xxxx. Avoid the intrusion of
moisture and pollution while the instrument is open to maintain the
reliability
2. Turn on the power supply of the SECU-DATA 1xxxx
3. Press the B-button two times shortly
4. The green “RF“-LED will blink several times, the number of light
pulses gives the actual number of the channel block (1 to 8).
5. The light pulses are repeated after a 1 s pause. Each press on button A increments the block number by 1. On the end of the range
the block number falls back from 8 to 1 automatically.
6. An interruption of the power supply aborts the procedure, the original block number remains in memory; the actual one is not stored.
7. The procedure can be finished by pressing the B-button; the actual
block number is stored permanently.
8. Repeat this procedure for the second SECU-DATA 1xxxx to set the
same block number
If required you may check the block number using steps 1 to 4 as described
above.
Page 22
Page 22Security & Electronic Technologies GmbH
Button B
Button A
Matching two SECU-DATA 1xxxx
After the delivery SECU-DATA 1xxxx instruments are not matched together.
This has to be done during setup. Also after replacement of a unit, after
service and repair it might be necessary to repeat the tuning procedure.
Procedure for both units:
1. Open the housing of the SECU-DATA 1xxxx. Avoid the intrusion of
moisture and pollution while the instrument is open to maintain the
long-term reliability
2. Turn on the power supply of the SECU-DATA 1xxxx
3. Press shortly on both instruments the A-button
4. The green “RF”-LED and the yellow “Power“-LED on the SECUDATA 1xxxx start blinking alternately – the instruments are in the
matching mode now
5. After completion both instruments perform automatically a RESET
– the red LED flashes shortly. If the tuning process is not successful you can abort it by pressing shortly the button A – the original
settings remain in memory
6. Now the green “RF”-LED and the yellow “Power”-LED on both instruments are continuously on – the matching procedure is finished
successfully and the RF-connection is established.
Page 23
Security & Electronic Technologies GmbHPage 23
Contact 6-7 is closed
as long as the RFconnection is established.
This circuitry provides
best reliability: if the
RF-connection is lost
or a power failure of
the SECU-DATA xxxx
occurred, the contact
opens and the alarm
lamp will be turned on
immediately.
Inverter relays can be
used also. Additionally the contact function
can be configured.
7
6
Monitoring the RF-status, alarm generation
Depending on the application it might be important to monitor the status of
the RF-connection and to generate an alarm indication in case of interruptions.
Important: During interruptions of the RF-connection SECU-DATA 1xxxC
instruments freeze the latest transmitted value and keep them on the output.
The status of the RF-connection can be tested via relay contacts.
SECU-DATA 1xxxx incorporate a relay contact, a make contact, which is
closed as long as the connection is active. The rated switching capacity of
the contact is 30 V / 500 mA.
Hint
Also the instruments SECU-DATA 1xxxM located on the measurement side
are equipped with such a relay contact with the same functionality. Thus an
alarm indication can be realised on the measurement site too.
If you want to realise an alarm signal (e.g. by a lamp) on the controller site
make use of this contact (principle diagram):
SECU-DATA 142xM, 142xC, 1600M, 1700M
Page 24
Page 24Security & Electronic Technologies GmbH
Contact 7-8 is closed as
long as the RFconnection is established. During RFinterruptions it is open
and the lamp goes on to
indicate an alarm condition.
The rated switching capacity of the contact is
30 V / 500 mA.
7
6
8
The make contact can be used for variants:
SECU-DATA 1500M, 1500C
Page 25
Security & Electronic Technologies GmbHPage 25
Mode
Relay RF
Re1
Re2
1
normal
make
make
2
inverse
make
make
3
normal
break
make
4
inverse
break
make
5
normal
make
break
6
inverse
make
break
7
normal
break
break
8
inverse
break
break
SECU-DATA 1500C configuration
After delivery the relay contacts are configured as make contacts, which
can be changed to break contacts if required.
Procedure:
1. Turn on the power supply of the SECU-DATA 1500C
2. Press and keep depressed the button A and press two times the
button B. The green “RF“-LED starts blinking, the number of pulses
indicates the relay mode:
make… contact closes if the relay is activated.
break… contact opens if the relay is activated.
3. Pressing of button B saves the settings
Hint: On all the other SECU-DATA 1xxxx instruments this configuration
is also provided but for the RF-relay function only, thus mode 1 and 2
are available only.
Page 26
Page 26Security & Electronic Technologies GmbH
Maintenance
Instruments of the SECU-DATA 1xxxx product range do not need any
maintenance, no user serviceable components are inside of the housing.
Important:
Repair and service tasks can be done by qualified service personnel only.
This is the only way to maintain the required level of ignition prevention.
The service activities carried out are documented and these files are kept in
archives for at least 10 years.
Warranty
For the actual services and conditions see the internet home page
www.secu-tech.at, see the GTCS – General Terms and Conditions of Sale.
Disposal
SECU-DATA instruments must not be disposed of via the municipal waste
collection system.
Security & Electronic Technologies GmbH. takes back used SECU-DATA
instruments for appropriate disposal for a small charge.
The symbol for disposal via qualified recyclers is attached visibly and permanently on the instrument.
Page 27
Security & Electronic Technologies GmbHPage 27
Troubleshooting
Problem: The RF-connection cannot be established
Solution 1:
Check:
Is the supplied antenna mounted correctly?
Are there obstacles which block the propagation of the RF waves?
Is the distance between transmitter and receiver less than 1 km?
Select an optimal position for the antenna, antenna extension cables are
available as an option.
Solution 2:
Interrupt shortly the power supply of both SECU-DATA 1xxxx units and turn
them on again. The modules will establish a new connection and they will
search for free undistorted RF-channels automatically.
Solution 3:
If this does not solve the problem match together the two instruments again.
For the procedure see chapter “Settings - Matching two SECU-DATA
1xxxx “
Solution 4:
If the tuning cannot be carried out successfully check the number of the RFchannel block. Both instruments have to operate within the same block of 8
RF-channels.
For the procedure of verification and re-definition of the RF-channel block
see chapter “Settings - Selection of an RF-channel block”
If all measures described in this chapter do not solve your problem then
send in the modules with a short description of the problem and with a copy
of the delivery note (in case of warranty claims) to the manufacturer or to an
authorised service facility.
Page 28
Page 28Security & Electronic Technologies GmbH
Technical specification
Radio frequency data transfer
Transmitting and receiving frequency in the 433 MHz band, very narrow
bandwidth, 64 channels in 8 frequency blocks (selectable on the instrument), 25 kHz channel separation, effective range up to 1 km or even more
in open areas, best temperature stability, insensitive to distortions, automatic selection of an undistorted channel, RF data transmission rate: 4.800
Baud (data bits/s). A potential-free relay contact is used to monitor the status of the RF connection, e.g. to issue an alert in case of an RF interruption
Technical Specification
Display:
Fuses:
RF-module:
Housing of SECU-DATA 1xxxx
Dimensions (l x w x h): 146 x 97 x 60 mm
Weight: app. 650 g incl. antenna
Antenna: app. 150 mm (l4), connector: TNC
Construction: mouldered with PU 403 – WEVO
Protection: IP 68
Material, colour: Deltacom ASA 4501 EC 6, dark green
Rated specification of SECU-DATA 1xxxx
Supply voltage: 11 V ... 40 V DC,
Power consumption (without probe): max. 1.2 W
Ambient temperature: -30°C ≤ Ta ≤... +75°C
3 LEDs
Temperature fuses
Conform to ETSI EN 300 220 (5/1999/EG R&TTE directive)
Page 29
Security & Electronic Technologies GmbHPage 29
Probe current
Re1
Re2
Meaning
0 … 0.4 mA
OFF
ON
Probe fault, “interruption”
1 … 2 mA
ON
OFF
Filling is in progress
2 … 6 mA
OFF
OFF
Tank full
> 6 mA
OFF
ON
Probe fault, “short”
Probe current
Re1
Re2
Meaning
0 … 6 mA
OFF
ON
Probe fault, “interruption”
6 … 40 mA
ON
OFF
Filling is permissible
>42 mA
OFF
OFF
Filling not permissible
>105 mA
OFF
ON
Probe fault, “short”
Technical specification of SECU-DATA 142xx
Measurement uncertainty SECU-DATA 1421M/1421C- 16-Bit:
Typical at 25°C: ±0.02% of measured value
Max. (-30°C … 75°C): ±0.1% of measured value
Resolution: 0.4 µA
Typical at 25°C: ±0.1% of measured value
Max. (-30°C … 75°C): ±0.3% of measured value
Resolution: 6 µA
Rise time: < 0.5 s
Technical specification of SECU-DATA 1500M/1500C - Relay
For the transmission of the status of the two relay contacts no further specification is required. Rated switching capacity: 30 V / 500 mA.
Technical specification of SECU-DATA 1600M - NAMUR
Switching threshold depending on the current flow through the
NAMUR probe:
Technical specification of SECU-DATA 1700M - TRbF
Threshold for the current flow through the TRbF probe:
Connectors of SECU-DATA 1xxxx
The connecting wires (round cables have to be used) are fed into the housing via cable glands (M16 x 1.5, type SKINTOP) with appropriate strain
relief to a terminal block (type WAGO series 256).
The number of wires and their functionality depends on the SECU-DATA
model, see the appropriate section in this document.
For heating oil tanks, water tanks, waste oil tanks,…
In the distribution line:
Level Control Systems
Optilevel – automatic level control
Industrial probes from several manufacturers
TWM-Hectour – Tank Truck Management System
Signalman, Ultiman, Watchman, …
See our homepage:
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.