sebaKMT Easyflex Com Instruction Manual

Page 1
Instruction Manual
Kommunikationsnetze
Networks
Elektrizitätsnetze
Pow
er Networks
Rohrleitungsnetze
Water
Networks
Leitungsortung
Line
Location
- Date of release:
2003/34
Mess- und Ortungstechnik Measuring and Locating Techniques
Easyflex Com
Page 2
2 MAN_Easyflex_com_eng_01.doc
Page 3
MAN_Easyflex_com_eng_01.doc 3
Easyflex Com
compact and light-weight
Time-Domain Reflectometer
Page 4
4 MAN_Easyflex_com_eng_01.doc
Page 5
MAN_Easyflex_com_eng_01.doc 5
TABLE OF CONTENTS
1 GENERAL ..................................................................................... 9
1.1 Advice from Hagenuk KMT GmbH.........................................................9
1.2 Terms and conditions of warranty........................................................10
1.3 Safety Instructions................................................................................11
1.4 Indications used in the description.......................................................12
2 TECHNICAL DESCRIPTION....................................................... 13
2.1 General Description..............................................................................13
2.2 Specifications........................................................................................15
2.3 Items Supplied and Optional Extras.....................................................19
3 OPERATION................................................................................ 21
3.1 Measuring Terminals............................................................................21
3.2 Display..................................................................................................22
3.3 Functions of Keys and Rotary Encoder................................................24
3.4 Getting Started (Insert / Replace Accumulator) ...................................27
3.5 Switching On and Off............................................................................27
3.6 Main Menu............................................................................................28
3.7 Compensation of Initial Reflection........................................................28
3.8 How to Locate a Fault...........................................................................29
3.8.1 Fields of Application ..........................................................................30
3.8.1.1 Faults Causing a Negative Reflection.....................................30
3.8.1.2 Faults Causing a Positive Reflection.......................................31
3.8.1.3 Further Fields of Application ...................................................32
3.8.2 Testing a Cable with Known Nominal Velocity of Propagation NVP or
with Known Pulse Propagation Velocity (v/2)..............................................33
3.8.3 How to Determine an Unknown Nominal Velocity of Propagation or
Pulse Propagation Velocity.........................................................................35
3.8.4 Simplification of Fault Location Using Comparative Tests................35
3.8.5 Averaging...........................................................................................36
3.8.6 Mode NEXT.......................................................................................37
3.8.7 How to Use the Marker......................................................................38
3.8.8 Change of Pulse Width......................................................................39
3.8.9 Self Test.............................................................................................40
3.9 Memory Function..................................................................................41
3.10 Serial Interface ...................................................................................43
4 NIMH ACCUMULATOR CHARGER ........................................... 44
4.1 Technical Description...........................................................................44
4.1.1 Specification ......................................................................................44
4.1.2 Start-Up .............................................................................................45
Page 6
6 MAN_Easyflex_com_eng_01.doc
4.1.3 General Instructions on How to Handle a NiMH Accumulator ..........46
4.2 Operation..............................................................................................47
4.2.1 Safety Precautions.............................................................................47
4.2.2 Modes of Operation...........................................................................47
4.2.3 Practical Hints....................................................................................48
4.3 Troubleshooting....................................................................................49
5 CARE UND MAINTENANCE.......................................................49
6 APPENDIX...................................................................................50
6.1 List of Abbreviations Used....................................................................50
6.2 Conversion: NVP v/2.........................................................................51
6.3 Table: NVP and v/2 for Common Types of Cables................................52
6.4 Glossary................................................................................................54
Page 7
MAN_Easyflex_com_eng_01.doc 7
EC - Declaration of Conformity
CE Mark
We, the company Hagenuk KMT Kabelmesstechnik GmbH Roederaue D-01471 Radeburg Germany
declare under sole responsibility that our product
Easyflex Com
is in conformity with the directive of the Council of European Communities for the Harmonization of the Laws of Member States on Electromagnetic Compatibility (EMC Directive 89/336/EEC) and Low Voltage (Directive 73/23/EEC).
This EC Declaration of Conformity is the result of a verification test performed by the department of Quality Assurance of Hagenuk KMT Kabelmesstechnik GmbH.
Conformance with the directive on Electromagnetic Compatibility was verified in accordance with the following standards:
EN 50081 Interference Emission, EN 50082 Interference Immunity EN 55011 Product Standard, EN 61000-4-2 Electrostatic Discharge, and EN 61000-4-4 Fast Interfering Electrical Transients
Conformance with the directive on Low Voltage was verified in accordance with the following standards:
EN 61010-1 Safety Regulations for Electrical Measuring, Control, Regulating, and Laboratory Instruments and EN 60529 Enclosure Protection
Radeburg, 6th of March 2003 Dr. Iann Managing Director
Page 8
8 MAN_Easyflex_com_eng_01.doc
Page 9
MAN_Easyflex_com_eng_01.doc 9
1 GENERAL
1.1 Advice from sebaKMT
This user manual has been conceived as a reference work. It is intended to help you answer questions and solve problems as quickly as possible. Should you have any problems, please first read the user manual with care.
To do this, make use of the index and read the relevant section carefully. Also check all equipment connections.
If questions still remain unanswered, please contact the following addresses:
Hagenuk KMT Seba Dynatronic Kabelmeßtechnik GmbH Meß- und Ortungstechnik GmbH Roederaue 41 Dr.- Herbert- Iann- Str.6 D - 01471 Radeburg / Dresden D - 96148 Baunach
TELEFON: +49 / 35208 / 84 - 0 TELEFON: +49 / 9544 / 68 - 0 TELEFAX: +49 / 35208 / 84 249 TELEFAX: +49 / 9544 / 22 73
SERVICE-HOTLINE : TELEFON: +49 / 35208 / 84 211 TELEFON: +49 / 9544 / 68 - 0
TELEFAX : +49 / 35208 / 84 250 TELEFAX: +49 / 9544 / 22 73
e-mail: sales@sebakmt.com internet: http://www.sebakmt.com
© Hagenuk KMT GmbH All rights reserved. No part of this manual may be photocopied or
reproduced in any other form without the prior written consent of Hagenuk KMT. We reserve the right to alter the contents of this manual without prior notice. Hagenuk KMT shall not be liable for technical or typographical errors or omissions in this manual. Nor shall Hagenuk KMT accept liability for damage or injury which is directly or indirectly attributable to the supply, performance or use of this material.
Page 10
10 MAN_Easyflex_com_eng_01.doc
1.2 Terms and conditions of warranty
Hagenuk KMT Kabelmesstechnik GmbH will accept a warranty claim brought forward by a customer for a product sold by Hagenuk KMT under the terms stated below and the General Terms of Supply of Products and Services of the Electrotechnical Industries, date of issue May 1993.
Hagenuk KMT guarantees that Hagenuk KMT products are at the time of their delivery free from defects in workmanship or materials which substantially reduce their value or serviceableness. This warranty does not cover faults in supplied software. During the warranty term Hagenuk KMT will repair defective parts or replace them with new or as-new parts (with the same operability and service life as new parts) at its option.
Additional warranty claims, in particular claims arising from consequential loss, cannot be asserted. All parts and products replaced under the terms of this warranty become the property of Hagenuk KMT.
Warranty claims on Hagenuk KMT lapse 12 months after the delivery date. Parts supplied by Hagenuk KMT within the framework of the warranty are also covered by this warranty for the remaining warranty term, but for no less than 90 days.
Warranty measures are undertaken exclusively through Hagenuk KMT or a special service shop which is authorized by Hagenuk KMT.
Claims under the terms of this warranty are subject to the buyer notifying Hagenuk KMT of defects without delay and no later than within 10 days of the delivery date in the case of perceptible defects.
This warranty does not cover defects or damage caused by the products being exposed to conditions which are not in accordance with the specifications, being stored, transported or used incorrectly, or being serviced or installed by agencies not approved by Hagenuk KMT. The warranty does not cover damage owing to natural wear and tear, force majeure or connection to external parts.
Hagenuk KMT is only liable for claims for damages arising from the violation of claims for repair or replacement in the event of gross negligence or intent. Any liability for ordinary negligence is ruled out.
Page 11
MAN_Easyflex_com_eng_01.doc 11
1.3 Safety Instructions
All persons involved in the installation, operation, maintenance and repair of the Easyflex Com must have read this manual carefully.
The Easyflex Com and its supplementary equipment are in accordance with the current state of safety technology at the time of delivery. Owing to the work processes involved, however, there may be parts of the unit and its peripherals which cannot be given optimum protection without an unreasonable reduction in function and usability. Good personal safety practice is therefore indispensable in terms of the protection of staff and the unit.
Therefore, please comply with the following safety instructions!
GENERAL INSTRUCTIONS
Work on the Easyflex Com and its peripherals must only be carried out by trained and/or instructed staff. Other persons must be kept away.
This manual must be available for the supervisory, operating and maintenance staff to refer to.
Improper use may endanger life and limb, the Easyflex Com and connected equipment, as well as the efficient functioning of the unit (accident prevention regulations). The Easyflex Com may only be used for the purpose for which it is intended by the manufacturer.
Always use the correct tools in perfect condition for all work. Regular checks must be made to ensure that the relevant safety
regulations are being complied with during operation and maintenance. Never operate the Easyflex Com and its peripherals if they are not in a
technically perfect condition. Only parts specified by Hagenuk KMT as accessories must be used for the
Easyflex Com and its peripherals, as the necessary safety will not otherwise be guaranteed. No mode of working which detracts from the safety of the Easyflex Com must be used.
Replace a accumulator only when the device is switched off and disconnected.
Page 12
12 MAN_Easyflex_com_eng_01.doc
The user is under an obligation to report any changes in the Easyflex Com to the supervisor responsible without delay.
The operator is under an obligation to shut the Easyflex Com down immediately in the event of a malfunction which detracts from the safety of staff. The Easyflex Com must only be put back into operation once the malfunction has been rectified.
ELECTROTECHNICAL INSTRUCTIONS
Connect the Easyflex Com and all its accessories according to instructions and regulations. Make sure the relevant regulations such as EN, DIN, VDE or national standards, respectively, are observed.
Repair and maintenance work must only be carried out when the unit is switched off (dead) and then only by a skilled electrician in accordance with current accident prevention regulations. A skilled electrician in the sense of the accident prevention regulations is a person who can assess the work assigned to him/her and recognise possible dangers on the basis of his/her technical training, knowledge and experience, and of his/her knowledge of the relevant regulations.
1.4 Indications used in the description
Important instructions concerning personal protection, work safety and technical safety are indicated as follows:
CAUTION
Caution indicates work and operating procedures which must be complied with in full to prevent the Easyflex Com and/or its peripherals from being damaged or ruined.
NB
NB indicates special technical requirements to which the user must pay particular attention when using the Easyflex Com.
Equipment protected by double insulation or reinforced insulation.
Page 13
MAN_Easyflex_com_eng_01.doc 13
2 TECHNICAL DESCRIPTION
2.1 General Description
The
Easyflex Com
is a compact, light-weight and easy-to-handle digital time-domain reflectometer for locating faults in balanced telecommunication and control lines. It can be handled easily and so enables even an inexperienced user to locate faults precisely and fast. Experts in testing will find a variety of additional functions at their hands. By its design the
Easyflex Com
is a robust device suitable for field application.
The
Easyflex Com
is double-insulated and equipped with safety terminals
to protect the user. The
Easyflex Com
is similar to radar in that it employs the pulse reflection technique. Suitable test pulses are transmitted into the cable to be tested. The pulses travel along the cable at a propagation velocity that is dependent on the connected test object. In every place where the electric characteristics of the cable have changed, part of the transmission pulse is reflected and caused to travel back to the
Easyflex Com
where it will be displayed on the screen with a time delay corresponding to its propagation time.
A change in the electric characteristics of a cable may be caused either by a possible fault or by local circumstances such as junction boxes, connectors, or the end of the cable. The time delay between the incoming reflection and the moment of pulse transmission is the propagation time to the point of fault and back. The distance from a place of interest can be calculated by taking into account the specific pulse propagation velocity of the cable under test. Shape and size of the reflected signal allow conclusion to be drawn on the nature and size of the fault.
The propagation time of the test pulse which is dependent mainly on the material of cable insulating material is taken into account by specifying a signal propagation velocity.
Page 14
14 MAN_Easyflex_com_eng_01.doc
For measuring the distance to the fault, a movable cursor or a combination of marker and cursor are used. Distance is display in m, ft, or µs as selected by the user. In order for the distance to be indicated in m or ft, the pulse propagation velocity of the cable under test has to be entered before the test is carried out.
The greatest advantage of the pulse reflection method is its ability not only to find out that there is a fault but also to find its location and type.
The
Easyflex Com
allows two cables under test to be connected to L1 and L2 at the same time and to show two reflectograms simultaneously. This can be done using currently taken reflectograms or test results stored in memory.
The most important modes of testing are:
Reflection measurement Pair (physical circuit) versus Built-in balancing
network (dummy line)
Difference measurement of two pairs
Location of crosstalk (NEXT) Pair versus Pair (k1 measurement)
There are two display modes the user can choose between. When you wish to get a revealing overview of the cable under test and, at the same time, have a closer look at a cable section, you can choose the display mode which divides the screen of the
Easyflex Com
into two windows. The upper window shows the full distance range with a movable window marking a section the content of which is displayed zoomed in the lower window. There is yet another display mode with a full-screen display of the selected cable section.
Current device settings are display by the LCD. When a stored reflectogram is uploaded as trace 1, all relevant settings such as gain and NVP are also taken over from memory thus allowing the current test result to be easily compared with a reflectogram taken earlier.
The
Easyflex Com
is powered from a NiMH rechargeable accumulator fitting in a accumulator compartment in the bottom of the unit. The instrument has a Power-Down mode. Moreover, the unit can also be powered from an external source of power.
Page 15
MAN_Easyflex_com_eng_01.doc 15
2.2 Specifications
Modes of testing: L1:
Reflection test of cable connected to socket L1 versus built-in balancing network
L2: Reflection test of cable connected to
socket L2 versus built-in balancing network
Alt: A reflection test is carried out alternately on
cables connected to sockets L1 / L2
Diff: Measurement of difference between
cables connected to sockets L1 and L2
NEXT: Location of crosstalk between cables
connected to sockets L1 and L2 Pairs to be connected: 2 Modes of operation:
Single Cont Average
Single test
Continuous testing
Averaging of up to 256 test results
Measuring ranges at
v
/2 = 100 m/µs
50, 100, 200, 400, 1000, 2000 m
4, 15 km
Zoom factors (X direction) 1, 2, 5, 10 (depending on range of
measurement)
Page 16
16 MAN_Easyflex_com_eng_01.doc
Maximum resolution 1.25 cm for range 50 m at 50 m/µs
2.5 cm for range 50 m at 100 m/µs
2.5 cm for range 100 m 5 cm for range 200 m 10 cm for range 400 m 25 cm for range 1000 m 50 cm for range 2000 m 1 m for range 4000 m
2.5 m for range 7500 m 5 m for range 15 km
Accuracy
± 0.1% of range of measurement ± 1
cursor step Gain 0 … 80 dB in steps of 1 dB Dynamic range 90 dB
Distance reading m, ft, or µs Setting range of signal
propagation velocity NVP
v/2
0.200 … 0.999 in steps of 0.001
30.0 … 149.9 m/µs or
98.4 … 491.8 ft/µs
Pulse amplitude
5 ns 2 V±25 % at 120
10 ns 2 V±25 % at 120
20 ns 2 V±25 % at 120
50 ns 3,5 V25 % at 120
200 ns 5,0 V25 % at 120
750 ns 6,0 V25 % at 120
Page 17
MAN_Easyflex_com_eng_01.doc 17
Pulse width Pulse width is linked to range of
measurement: 5 ns for range 50 m (100 m/µs) 5 ns for range 100 m 10 ns for range 200 m 20 ns for range 400 m 50 ns for range 1 km 200 ns for range 2 km 200 ns for range 4 km 750 ns for range 7,5 km 750 ns for range 15 km
Electrical strength of test inputs
250 V AC/DC 50/60 Hz CAT II (overvoltage category)
Memory locations 16 Measuring rate up to 11 reflectograms per second
(averaging mode, short range)
Display rate up to 4 screen images per second Display 256 x 128 pixels, back-lighted Interface RS 232 for PC / printer Power supply Replaceable NiMH rechargeable
accumulator (7,2 V/1,7 Ah) or Plug-in mains unit (optional extra)
Mean operating time with one accumulator charge
ca. 8 hours
Languages German, English,
other languages as optional extras on request
Page 18
18 MAN_Easyflex_com_eng_01.doc
Environmental conditions Operating temperature -10 °C … +50 °C Storage temperature -20 °C … +60 °C (without accum ulator)
Storage temperature (accumulator)
-20 °C … +50 °C
Dimensions, mm 176 x 260 x 70 (L x W x H)
186 x 260 x 70 incl. measuring terminals Weight approx. 1.5 kg
Interelement protection class
II with accumulator compartment closed
and protective cap on serial interface
terminal Enclosure protection IP54
Subject to changes and alterations without further notice!
Page 19
MAN_Easyflex_com_eng_01.doc 19
2.3 Items Supplied and Optional Extras
Items supplied:
Description
Easyflex Com, consisting of Easyflex Com
(G,E, two languages on request)
- 2 pcs. set of test leads
- Case for Easyflex Com
- Accumulator 7,2 V / 1,7 Ah / NiMH
- Charge case
- Plug-in mains unit, for charger case;
according to country: EURO 230 V / 50 Hz USA 120 V / 60 Hz UK 230 V / 50 Hz
- Instruction manual, according to country:
German English More languages on request
Page 20
20 MAN_Easyflex_com_eng_01.doc
Optional Extras:
Description for use as
Rechargeable accumulator 7,2 V / 1,7 Ah / NiMH
(Energy DC17AA)
replaceable accumulator
Winkis Com PC software for
evaluating and storing reflectograms
Printer set means for the on-site
preparation of test reports
Transportation case for printer set Plug-in mains unit external source of
power
Adapter cable for charging the
accumulator from a vehicle electric mains using the charging management of the charger case
Coax adapter for testing coaxial
cables
Fault Converter for locating moisture-
induced faults
Calibration with manufacturer’s test certificate
Subject to changes and alterations without notice!
Page 21
MAN_Easyflex_com_eng_01.doc 21
3 OPERATION
Fig 1
Easyflex Com
, Front View
3.1 Measuring Terminals
L1
In general, these measuring sockets are used for connecting the faulty line or line to be tested. When using this configuration please make sure that your
Easyflex Com
is set to mode L1. In mode NEXT
this pair of sockets is used for receiving the crosstalk.
L2
In general, these measuring sockets are used for connecting a faultless pair of conductors to be used as a reference for comparison with the test object connected to L1. In mode Diff this facilitates the detection of small fault reflections in the tested line connected to L1 because each reflection caused by a junction or terminal occurs in both lines at the same distance and approximately the same size and will thus almost be cancelled out in the reflectogram due to the applied method of subtraction. In mode L1, a line that is possibly connected to L2 will not have any influence whatsoever on the test.
Mode NEXT: This pair of sockets will carry the transmitted pulse. Mode Alt
: Testing is carried out alternately on L1 and L2.
Mode L2: Reflection measurement of L2
Page 22
22 MAN_Easyflex_com_eng_01.doc
3.2 Display
The LC-Display has 256 x 128 pixels, controls for setting contrast, and switchable back lighting. This enables graphic information to be readable even in difficult lighting conditions.
The activated function is display in representation.
Fig 2 Display 1 Window on display (range/X zoom)
2 Back light 3 Contrast 4 ,M for A loading; -M for D loading 5 Average counter in mode averaging
There are two modes of displaying the reflectograms: Press ”Display” when you want to work with two images of the trace, see
Fig 3. The upper is the
reflectogram of the full range of measurement. There is a black bar below this overview indicating a section the position of which can be moved by means of the cursor. The lower and larger part of the display shows this black section magnified in full detail.
reflectogram from memory
distance marker
- cursor
inverted
accumulator condition
or printing is under way testing single test /
waiting for
start no test
Pulse width Line 4 Cursor...m ❄ 1 X-Zoom Mode 5 ...m
Gain ...db
Comp ...
Propagation velocity 2 3 2nd
distance from begin
Trace
Range
Y-zoom
NVP; v/2
Page 23
MAN_Easyflex_com_eng_01.doc 23
Use the cursor when you want to change the position of the section and change the X zoom factor when you want to change the width of the section.
Fig 3: Reflection by the 2 m Interconnect Cable The LC display will display a warning signal top left when the remaining
charge of the accumulator is insufficient for further operation. Replace the accumulator or charge it in order to restore readiness for operation. Switch the instrument off before replacing the accumulator to retain all data.
Press one of the following keys for ca. 1.5 s to return to the default value.
Function
Key(s)
Default value Cursor Cursor 0.0 m/ft/µs Gain Gain 0 dB Compensation Comp
120
Pulse propagation velocity
v
/2
NVP
99.9 m/µs or 327.9 ft/µs
or
0.667 Horizontal zoom Zoom 1 (full range) Mode of connection Line L1 Mode of operation Mode Single Contrast Light key
(press for 3 sec)
standard contrast
Page 24
24 MAN_Easyflex_com_eng_01.doc
3.3 Functions of Keys and Rotary Encoder
How to proceed:
press key(s) to call function
use rotary encoder for selection
Quick-save operation to memory 1 by 2nd Save and 2nd Recall; with Alt to memories 1 and 2.
When you press the help key (?) the
Easyflex Com
will display informations on one of the following topics : (key ?; select with rotary encoder; press key Mark, key ? for return):
Information on help
Fault location
Operation
Compensation
Averaging
Mode of display
NVP or v/2
Types of cables
Storage
Device set-up
Self test (via 2nd Menu)
Accumulator charging
DC external
2nd keys
On/Off light Save Recall Print Start single test
contrast Stop/Start cont.testing
(hold down key, turn rotary encoder) Stop averagin
Page 25
MAN_Easyflex_com_eng_01.doc 25
Marker: Activate cursor; move cursor to start point of measurement; set marker
Cancel
X-Zoom
Propagation velocity / NVP
Single or Dual Display
Menu Menu/Units Menu/Interface Menu/Printer Menu/System Menu/Power supply
Help
Cursor
Range(Measuring Range)
Gain, dB
Compensation
Modes: Single Continuous Average
Mode of connection: L1, L2, ALT (alternating) Diff (Difference L1-L2) NEXT (cross talk)
Second key functions
Page 26
26 MAN_Easyflex_com_eng_01.doc
Possible settings in Menu:
Menu/Units Units
NVP units
meter feet seconds
NVP
v
/2
Menu/Interface Baud rate
Parity (Parity bit)
300 1200 9600 19200
None Even Odd
Menu/Printer Printer
Layout
HP Deskjet Epson compatib. Epson 9 pin Kodak Diconix
Normal Special
Menu/System Self test
Date & time Language
Software version Serial number
mm.dd.yy / hh:mm:ss / AM/PM
German English 2 x other languages
Menu/Power supply Device switched off
Back light switched off Measurement Rate
Reduction
disabled off; 10 s ... 1200 s
disabled off; 5 s .. 600 s disabled off; 1 s ... 60 s
Page 27
MAN_Easyflex_com_eng_01.doc 27
3.4 Getting Started (Insert / Replace Accumulator)
The accumulator compartment is located in the back of the
Easyflex Com
. Make sure that all test leads have been disconnected before opening the accumulator compartment. Switch the device off in order to retain all data. For inserting or replacing the accumulator open the lid and pull out the accumulator, if there is one. Insert the charged NiMH replacement accumulator with its contacts facing the receptacle of the compartment. Make sure that the accumulator is inserted properly, otherwise you would be unable to close the lid. Now the
Easyflex Com
is ready for operation.
3.5 Switching On and Off
Press key to switch the
Easyflex Com
on. During run-up the
manufacturer’s logo will be shown for about 2 seconds. After run-up has been completed, the
Easyflex Com
can be switched off any time by pressing key . When being switched off the device saves all device settings, so the same operating status is restored when the instrument is switched on next time.
The
Easyflex Com
cuts back its function automatically some time after a key
has been pressed last time in order to save accumulator power:
The device is switched off after 360 sec,
The back light of the display is switched off after 60 sec,
The reduction of measuring rate is disabled
These default values as mentioned above can be changed in menu Power Supply.
Device on/off off 10 sec ... 20 min in steps
of 10 sec
Light on/off off 5 sec ... 10 min in
steps of 5 sec
Meas. rate reduction
off 1 sec ... 1 min in
steps of 1 sec
Key operations: 2nd; Menu; rotary encoder to Supply menu; Mark; rotary encoder for Vertical selection; Mark; use rotary encoder to set Time; Mark; Display
Page 28
28 MAN_Easyflex_com_eng_01.doc
3.6 Main Menu
Main Menu will appear automatically after the
Easyflex Com
has been switched on. In this menu measurements are taken employing the device settings that were in effect when the device was used last time. Most functions of
Easyflex Com
can be started directly from menu Measurement
by means of the keys or rotary encoder as described in section 3.3.
3.7 Compensation of Initial Reflection
Use key Comp and the rotary encoder to adjust compensation such that the initial reflection is suppressed on the display. In principle this adjustment should be made in order to provide for optimum matching of the
Easyflex Com
to the impedance of the respective cable so as to be able to detect and locate a fault at close range, i.e. at a distance of up to 10 meters.
When a faultless pair of conductors of the same type of cable as the faulty one is available and when it is connect to sockets L2, the impedance of the faultless cable is used for reference in mode Diff. In this case compensation is not operational and matching is guaranteed. Use compensation when no faultless pair of conductors is available. Switch to mode L1 or L2 according to the socket pair used and select display mode ”DUAL”. Set cursor to distance zero and adjust compensation such that the upper image of the reflectogram is displayed as a horizontal line, if possible, and the initial reflection shown in the lower window of the display shows as small as possible. For facilitating the setting procedure, first set gain to 0 dB for coarse balancing and then increase it for doing the fine adjustment.
Page 29
MAN_Easyflex_com_eng_01.doc 29
3.8 How to Locate a Fault
When you test a defective cable, always obey by the following basic rules: (1) Observe the safety precautions given in section 0 without fail.
(2) De-energise the cable to be tested, whenever possible. When you
take measurements on a live line, its voltage must not exceed 250 V AC/DC. In this case do not open the accumulator compartment and do not remove the cap of the serial interface.
(3) The
Easyflex Com
is able to measure the length of the cable and the distance to a point of fault. It is not able, however, to find out the route of the cable between the point of measurement and the location of the fault.
(4) The precision of the distance reading by the
Easyflex Com
can only be as good as the precision with which you know the pulse propagation velocity of the connected cable. In a wet cable the pulse travel time is increased, so the distance display is too long when the same settings are used as for a dry cable.
Page 30
30 MAN_Easyflex_com_eng_01.doc
3.8.1 Fields of Application
The
Easyflex Com
allows various type of faults to be detected. These are a
few examples:
3.8.1.1 Faults Causing a Negative Reflection
(1) Short circuit: Direct contact of two conductors of a cable. This will
cause a negative reflection, see Fig 4.
Fig 4 Type of Fault Causing a Negative Reflection (2) Short-circuit to shield: One conductor in a cable is in contact with the
metal shield of the cable. For locating this type of short-circuit, first disconnect earth from the shield. Then connect the test leads to the shield and the conductor which is shorted with it.
(3) Reversed (mixed-up) wires: Reversed wires generate a reflectogram
similar to a short circuit but reflections are smaller in size.
Page 31
MAN_Easyflex_com_eng_01.doc 31
3.8.1.2 Faults Causing a Positive Reflection
(1) Open circuit: Open circuit means that one or both conductors of a pair
of conductors are broken or have become detached. This will cause a positive reflection, see Fig 5.
Fig 5 Type of Fault Causing a Positive Reflection (2) Resistance faults: If a cable is not properly connected in a junction
box, increased contact resistance will occur. This type of fault generates a positive reflection in a size which is dependent on the quality of the connection resp. its resistance.
(3) Shield interrupt means that the metal shield of a cable is broken or has
become detached. To locate such faults and to suppress noise signals on the display, connect the test leads to the shield and to as many conductors of the cable as possible. This type of fault generates a fault reflection the size of which is dependent on the resistance of the interrupt.
(4) Crossed lines (”split pairs”) and restored reversed lines occur when a
telecommunication cable is twisted or untwisted. Usually this may happen at a cable joint. This phenomenon is one of the main causes of crosstalk interference. Reversed wires in an untwisted cable will generate a positive error reflection. If an individual cable is twisted, a negative error reflection appears. As the distance between the points of crossing and crossing is usually very small, both reflections occur almost simultaneously and appear as a single weak reflection.
Page 32
32 MAN_Easyflex_com_eng_01.doc
(5) A humidity-induced fault is brought about by water penetrating into a
defective line. At the beginning of a wet section a negative reflection similar to a short-circuit can be observed, followed at the end of the wet section by a small positive fault reflection typical of an open cable end. In some cases, e.g. if the moisture gradually increases or decreases with distance, these points of reflection spread into a constant up and down in the horizontal traceform. In an old cable which is wet along its entire length it may be difficult to detect a moisture-induced fault because the beginning and the end of the zone of moisture exposure are not clearly marked. It is only in rare cases that the fault reflection becomes apparent as clearly as for a short­circuit or broken line. Moisture in a cable filled with petrolatum may possibly result in very small fault reflections as the volume of moisture is only limited.
3.8.1.3 Further Fields of Application
(1) T-joints (Tapped joints) occur when a conductor pair leading to an
extension is tapped off a pair in the main line. Halving the characteristic impedance at the tap or bridge will result in a fault similar to a short circuit (negative reflection). The trace on display is difficult to assess if a pair of conductors is tapped at many points unless precise information about the structure of the cable network is available.
(2) Some telephone lines are coil-loaded in order to increase the
inductance of the line and thereby improve the transfer characteristic of a trunk line. The
Easyflex Com
will interpret the coils used for the inductive loading of the system as open ends. Connect the instrument to some point behind the coil if you want to locate a fault which is situated beyond the bounds of a coil-loaded section.
Page 33
MAN_Easyflex_com_eng_01.doc 33
3.8.2 Testing a Cable with Known Nominal Velocity of Propagation NVP or with Known Pulse Propagation Velocity (v/2)
In many instances the route and characteristics of the cable are known in which case the nature and position of the fault can located quickly. In such circumstances proceed as follows:
(1) De-energise or disconnect the Faulty pair and, where appropriate, a
good reference, if possible. When a test has to be performed under voltage, make sure that the voltage does not exceed 250 V AC/DC.
(2) Use the test leads supplied with the
Easyflex Com
to connect the
Faulty pair to Line 1 and, when appropriate, the good pair to Line 2.
(3) Press key to switch the
Easyflex Com
on. Menu Measurement will
appear after a few seconds.
(4) Press key (Line) to select the appropriate mode of measurement, e.g.
Diff when a good pair is available or L1 when you test the Faulty pair alone.
Set to the desired unit of measurement (2nd; Menu; Menu Units),
select a measuring range according to the length of the cable to be tested, set the pulse velocity to the desired option (NVP, v/2 in m/µs or ft/µs), set the display mode to ”DUAL ”. The sockets of the instrument are the zero mark of the cursor. Use the marker to subtract the supplied interconnect line.
(5) Use keys (v/2) and the rotary encoder to set the cable-specific
propagation time to the value specific value of the cable to be tested.
(6) Match the
Easyflex Com
to the object under test as described in
section 0.
(7) First of all, try to find the (open) end of the cable.
Page 34
34 MAN_Easyflex_com_eng_01.doc
(8) Look for a fault reflection in the overview trace displayed on top. In
doing so, increase gain or amplitude correction steadily until the point of fault is clearly visible.
Fig 6. Display (9) Use the cursor to move the section marker (black bar between the two
traces) such that the reflection is located above the bar. Then use the rotary encoder to move the cursor in the lower part of the screen to the place where the foot point of the fault is located (see Fig. 6).
(10) The distance to the fault can now be read off directly. This value can
be indicated in meters, feet, or nanoseconds depending on the setting in menu Units. The reflectogram can be saved in a the memory for documentation purposes .
(11) Press to switch the
Easyflex Com
off after the test has been
completed.
Page 35
MAN_Easyflex_com_eng_01.doc 35
3.8.3 How to Determine an Unknown Nominal Velocity of
Propagation or Pulse Propagation Velocity
When the nominal velocity of propagation or pulse propagation velocity of the faulty cable is not known, a test sample of the same type of cable with known length is needed (or the distance to a specific point in the cable must be known).
Set the cursor to the foot point of the known reflection. Then adjust the NVP or pulse velocity setting such that the indicated distance to the fault correlates with the actual length of the sample. After that the distance to a fault reflection in the defective cable can be measured.
3.8.4 Simplification of Fault Location Using Comparative Tests
The reflectogram shown in Fig 6 shows cable and fault in virtually ideal conditions. In reality, however, there are cable junctions and other connections resulting in a trace which is normally similar to that shown in Fig 7 (good pair). In Fig. 8 (Faulty pair), in addition to the fault other cable reflections are visible which are caused commonly by connections with an impedance different from that of the line. These jumps in impedance also appear as reflections and thus render the detection of the reflection caused by the fault almost impossible. When a multi-pair cable is tested, a comparative test (see Fig 9) using a good pair (provided that not all conductors are defective) allows the point of fault to be detected. Connect the good pair to L2, the faulty pair to L1. Then select mode Alt by pressing key (Line). Move the cursor to the points where both trace diverge. In Fig 10 mode Diff was used which means that differences between both reflectograms (fault reflections in the defective cable) occur in places where the difference on display deviates from the horizontal. Use the cursor to measure the distance to the foot point of the deviation.
Page 36
36 MAN_Easyflex_com_eng_01.doc
Fig. 7 Fig. 8
Fig. 9 Fig. 10
3.8.5 Averaging
Interfering noisy signals may make the location of faults very difficult in particular when a fault has to be located in a long cable and when high gain is used. In order to solve this problem, the
Easyflex Com
is equipped with
an averaging mode. Press function key Mode and use the rotary encoder to enable mode Averaging. The display will display the number of measurements taken for averaging (max. N256) top right. You can cancel averaging at any time if the number of measurements taken so far is sufficient for an efficient interference suppression. Pressing key Start one more time to start another averaging run.
Page 37
MAN_Easyflex_com_eng_01.doc 37
3.8.6 Mode NEXT
Mode NEXT (Near End cross (X) Talk) is for measuring the cross-talk coupling k1 between two pairs of conductors. Unwanted crosstalk coupling occurs in particular when wires have been crossed.
The
Easyflex Com
is able to pinpoint the fault precisely, so the fault can subsequently be eliminated to the point. For instance, the device can determine the beginning and the end of a ”split pairs” section in a longer trunk line which is composed of a number of sections.
The point of crosstalk coupling is located as in any normal reflection test. This mode is different, however, in that the pair which shall carry the transmitter pulse is connected to L2 and the pair tested for crosstalk to L1. Press key Line and use the rotary encoder to enable mode NEXT.
Fig. 11
„Split-Pairs“section
Section of line
pair 2
pair 1
L2 L1
Transmission reception Easyflex Com
Reversed wires crosstalk
Page 38
38 MAN_Easyflex_com_eng_01.doc
The direction of the pulse at the beginning of the ”Split Pairs” section may be positive or negative depending on the direction in which the wires have been connected to the device. At the end of the ”Split-Pairs” section the reflection is always inverted as compared with its beginning.
3.8.7 How to Use the Marker
If you use only the cursor you can just determine the distance from the
Easyflex Com
to the point of reflection in the cable. The marker offers you additional means to set a point of reference in the cable and to take measurements in relation to this point by means of the cursor. We recommend to use the marker
when subtracting the laught of the test leads,
when the length of a cable section has to be measured (in particular
when a cable is composed of sections with differing NVP / v/2 values),
for measurements in relation to a known point of reference (this will
increase measuring accuracy), and
for determining the NVP / v/2 value of a cable section of known length. Press key Mark to set or erase the marker. To this end press key Cursor
and move the vertical line by means of the rotary encoder to the desired point of reference. Then press key Mark; the marker will now be displayed as a vertical dotted line. When you subsequently use the rotary encoder to move the cursor away from the marked position, the numerical values on display top right will change. The numerical value behind Cursor indicates the distance between the output of the
Easyflex Com
and the position of the cursor whereas the numerical value behind indicates the distance between the marked point of reference and the cursor position. Pressing key Mark one more time will erase the marker. The marker cannot be set to position 0 m.
Page 39
MAN_Easyflex_com_eng_01.doc 39
3.8.8 Change of Pulse Width
Press keys 2nd Range to change pulse width. Doing so will not change the display range.
Display range
(Range/Zoom at v/2=100
m/µs)
Default pulse width Setting range
5 m 5 ns 5 ns 10 m 5 ns 5, 10 ns 20 m 5 ns 5, 10, 20 ns 50 m 5 ns 5, 10, 20, 50 ns
100 m 5 ns 5, 10, 20, 50 ns 200 m 10 ns 10, 20, 50, 200 ns 400 m 20 ns 20, 50, 200 ns
1 km 50 ns 50, 200, 750 ns 2 km 200 ns 200, 750, 3000 ns 4 km 200 ns 200, 750, 3000 ns
7.5 km 750 ns 750, 3000 ns 15 km 750 ns 750, 3000 ns
The offered combinations of pulse width and display range take into account that not every pulse width is suitable for every display range. Thus short pulses are only suitable for testing at close range. On the one hand, they allow tests to be made with high resolution but they are too heavily attenuated and spread at longer distance, on the other. Long pulses are much less attenuated with distance, so clear echos can be received from distant points. At close range, however, they are inferior to shorter pulses due to their poor resolution.
Page 40
40 MAN_Easyflex_com_eng_01.doc
3.8.9 Self Test
After turn on, the
Easyflex Com
performs an automatic selftest. If error code 1 is display the Lithium accumulator is (almost) discharged (the device will still operate for a short while, but you should submit it to the Customer Service to have the Lithium accumulator replaced).
Error code 2 asks for setting the clock (2nd Menu, Menu/System Mark, go with rotary encoder to Date&Time Mark, select unit of time with rotary encoder Mark, select unit of time with rotary encoder Mark for return). If both errors occur at the same time, error code 3 is display.
Key combination (2nd Menu, Menu/System Mark, Self test Mark) starts a comprehensive self test. Please contact our Customer Service should any error code be display.
Page 41
MAN_Easyflex_com_eng_01.doc 41
3.9 Memory Function
The
Easyflex Com
has 16 memory locations. This is how to save a trace:
Press key Save
Use the rotary encoder to select a free memory location or a location
that will be overwritten. The selected memory location is displayed in inverted mode
Press key Mark The memory window will display location number, date and time of
measurement, and parameter Range of the stored reflectogram. Parameter Range is display according to the value of v/2 or NVP which is currently set. This has the consequence that any change of the v/2 setting will also change this value in the reflectogram. When a trace is loaded, v/2 is re-set to its stored value. In mode ALT two adjacent memory locations are made available for storage. Memory location 1 is for quick saving triggered by key combination 2nd Save. If mode ALT is set, quick saving will use memories 1 and 2. For this reason we suggest not to use memory locations 1 and 2 for any reflectograms which shall be retained in memory for a longer period of time.
This is how a reflectogram is loaded from memory:
Press key Recall
Use rotary encoder to select memory location. The selected location is
display in inverted mode.
Press key Mark
Use rotary encoder to toggle between loading, A loading, and D loading
Press key Mark
Page 42
42 MAN_Easyflex_com_eng_01.doc
Mode of loading
Mode of display Indication
Loading Reflectogram stored in selected memory
location
A loading The reflectogram from memory is shown as a
dotted line, the reflectogram currently taken is shown as a continuous line.
If you wish to erase the display of the trace stored in memory, do so by using the key combination Recall set rotary encoder to Erase 2nd trace  Mark.
,M top right in front of Cursor
D loading Difference between current reflectogram and
reflectogram from memory If you wish to return to the display of the
current reflectogram, do so by using the key combination Recall set rotary encoder to Erase 2nd trace  Mark.
-M top right in front of Cursor
Use key combination 2nd Recall for a quick download of a trace from memory location 1.
The traces stored in memory can later be used for processing or for printing out a hardcopy. It is also possible, however, to upload them to a PC using the PC software program
Winkis Com
which is available as an optional extra. For printing out a reflectogram it is important first to use Recall to load the trace from memory before pressing key Print. Another benefit of the memory mode is that it simplifies fault locating and diagnosis. When a number of test objects with identical cable characteristics are tested, the entire test set-up can be taken over from a reflectogram already stored in a memory location, so fault locating can be started without any delay. The memory mode also allows a current reflectogram to be compared with up to 16 reflectograms stored in memory.
Page 43
MAN_Easyflex_com_eng_01.doc 43
3.10 Serial Interface
The serial interface of the
Easyflex Com
allows reflectograms to be loaded to an external PC or to connect a printer for printing out a hardcopy. Go to Menu/Printer to choose from HP Deskjet, Epson combatib., Epson 9 pin, and Kodak Diconix. The Print function enables the current content of the display to be printed by the connected printer. Moreover, the trace just loaded can be transferred to a PC for storing and documentation purposes provided the communication software
Winkis Com
which is available as an
optional extra is installed on the PC.
Winkis Com
can also be used for re-
loading a reflectogram including its set-up. Furthermore
Winkis Com
gives you access to all reflectograms stored. Please refer to the software manual if you wish to learn some more details.
The default configuration of the
Easyflex Com
serial interface
is as follows: Baud rate 9600, 8 data bits, no parity, 1 stop bit Part of the set-up can be set in Menu/Interface. Pin assignment of the interface cable:
Easyflex Com Printer/PC
9 pins 25 pins
RX Pin 2 ←→ Pin 2 TX TX Pin 3 ←→ Pin 3 RX GND Pin 5 ←→ Pin 7 GND
ATTENTION
Always cover the 9-pin connector of the
Easyflex Com
with its protective cap when it is not in use. Make absolutely sure that all test cables have been removed when the serial interface is being used!
Page 44
44 MAN_Easyflex_com_eng_01.doc
4 NIMH ACCUMULATOR CHARGER
4.1 Technical Description
4.1.1 Specification Plug-in mains unit (Euro, USA, UK):
Input voltage EURO USA UK
230 VAC , ±10 %, 50 Hz 120 VAC , ±10 %, 60 Hz 230 VAC , ±10 %, 50 Hz
Power consumption EURO and UK USA
13.8 VA
14.5 VA Output voltage 12 V DC Interelement protection class II Operating temperature range 0 … 40 °C Storage temperature range -40 … 70 °C
Charger:
Input voltage 12.,0 V DC Maximum input current 580 mA Interelement protection class III Operating temperature range 0 … 50 °C Storage temperature range -40 … 70 °C Type of accumulator Replaceable NiMH rechargeable
accumulator 7,2 V (Energy DC17AA)
Vehicle adapter cable
ATTENTION
The charger, including the mains unit, is only for use indoor use!
Page 45
MAN_Easyflex_com_eng_01.doc 45
4.1.2 Start-Up
First connect the cable from the plug-in mains unit to the DC-IN 12 V socket of the charger, and only then plug the mains unit into a mains outlet (see Fig 13).
The green LED of the charger case should now be on continuously, while the amber LED should flash up at regular intervals.
Now insert the appropriate NiMH rechargeable accumulator into the charger case until it engages gently.
Please make sure that the accumulator contacts face the direction of the LEDs because this is the only way contact is made to the electronic charger circuit (see enlarged details).
The amber indicator lamp shall light up continuously after the accumulator has been inserted. If it does not, shortly disconnect the charger from the mains.
After charging has been completed (approx. 3.5 hours), the amber LED will flash again. You may now remove the accumulator or leave it in the charger.
Disconnect the charger from the mains whenever you intend not to use it for an extended period of time. To do so, just unplug the mains unit from the mains outlet - you need not disconnect the cable from the mains unit to the DC-IN 12V socket of the charger. We suggest to install the charger close to an easily accessible mains outlet.
Charger case
Plug-in mains unit
DC-IN 12 V
mains
Fig 12 Connection to a Mains Outlet
green and amber LEDs
Page 46
46 MAN_Easyflex_com_eng_01.doc
The accumulator can also be charged from the on-board network of a vehicle. To do this, use the vehicle adapter cable to connect the charger case to the 12 V DC on-board network.
Motorcar adapter cable
Charger case
12 V supply
DC-IN 12 V
Fig 13 Connection to a Vehicle supply
Fig 14 How to Insert the NiMH accumulator into the Charger Case
4.1.3 General Instructions on How to Handle a NiMH Accumulator
ATTENTION
Do not short-circuit a accumulator. Do not dismanntle or modify a accumulator. Do not dispose of in fire. Protect batteries from moisture. Do not expose batteries to strong impacts. Make sure that a damaged accumulator is disposed of
immediately and properly.
NOTE
A NiMH accumulator may heat up when being charged or discharged. This is normal and does not indicate a defect. Dispose of batteries which cannot be used any longer properly or submit it for RECYCLING.
Light-emitting diodes
Page 47
MAN_Easyflex_com_eng_01.doc 47
4.2 Operation
4.2.1 Safety Precautions
Protect the device from moisture. Do not cover the ventilation slots of the plug-in mains unit. Do not insert any items into the ventilation slots. Never expose to direct heat or direct sunlight. Do not open the device as there are no user-maintained components
inside and any warranty might be invalidated. Do not store or use charger and mains unit in the close vicinity of storage
media. Only use the plug-in mains unit supplied.
4.2.2 Modes of Operation
OPERATION
The green LED is alight. Indicates that the charger is ready for use.
STATUS / Waiting mode
The amber LED is flashing regularly.
1.) No accumulator has been inserted: The device is waiting for a accumulator to be inserted for charging.
2.) A accumulator has been inserted: The accumulator is fully charged and waiting for being removed.
STATUS / Charging
The amber LED is permanently alight. A accumulator has been inserted. It is being charged.
Please pay also attention to section 4.3, to extend the service life
of the NiMH accumulator.
Page 48
48 MAN_Easyflex_com_eng_01.doc
4.2.3 Practical Hints
In order not to reduce the service life of a NiMH accumulator unnecessarily, make sure that the accumulator is at room temperature when charging is started.
"Overnight charging" will not cause any trouble since an intact accumulator cannot be overcharged. Once charging has been completed, the device will change over to trickle charging to compensate for natural self-discharge.
The optimum way of operation is to have two accumulators, with one remaining in the charger while the other one is used for powering the
Easyflex Com
.
The charger and the inserted accumulator will heat up during charging (hand hot). This is normal and does not indicate any defect.
When the operating life of a accumulator becomes perceptibly shorter even at full charge, you will need to replace it with a new one.
Page 49
MAN_Easyflex_com_eng_01.doc 49
4.3 Troubleshooting
The green indicator lamp does not light up after the unit has been plugged into a mains outlet.
Check the cable and connector for being firmly in position.
Is the mains outlet live ?
The amber LED does not light up continuously although there is a accumulator in the charger.
Shortly disconnect the charger from the mains or on-board network.
Has the accumulator been inserted properly (refer to Start-Up) ?
Has the accumulator been pushed into the charger down to the stop ?
Is the accumulator out of order ?
In case none of these hints allows you to solve the problem, please submit the device to your service station for inspection or contact the Hagenuk KMT hotline.
5 CARE UND MAINTENANCE
Neither the
Easyflex Com
nor any of its accessories contain components which require regular care and maintenance to keep them operational. Submit the
Easyflex Com
or its accessories to your service shop or to
Hagenuk KMT for repair should any defect occur. Never use any aggressive solvent or detergent for cleaning your
Easyflex
Com
and its accessories. Use a soft, dry cloth for cleaning your
Easyflex
Com
and its accessories. When the device is very dirty, moisten the cloth with some mild soap (do not use any abrasive agents) and clean it. Make sure that all traces of moisture have evaporated before the
Easyflex Com
and its accessories are used again.
Page 50
50 MAN_Easyflex_com_eng_01.doc
6 APPENDIX
6.1 List of Abbreviations Used
ALT Alternating test DC Direct current EMV Electromagnetic compatibility IEC International Electrotechnical Committee LCD Liquid crystal display LED Light emitting diode NEXT Near end cross (X)-talk NiMH Nickel metal hydrid NVP Nominal velocity of propagation TDR Time domain reflectometer VDE Verein Deutscher Elektrotechniker
(Association of German Electrotechnical Engineers)
Page 51
MAN_Easyflex_com_eng_01.doc 51
6.2 Conversion: NVP ⇔⇔ v/2
Conversion NVP v/2 (m/µs)
2
s
m
299.79NVP
=
2
v
µ
Conversion v/2 ( m/µs) NVP
s
m
299.79
2
v
• 2
= NVP
µ
Page 52
52 MAN_Easyflex_com_eng_01.doc
6.3 Table: NVP and v/2 for Common Types of Cables
Typical propagation time
Insulation
v
/2 ,
m/µs
v
/2 , ft/µs
NVP
Oil­impregnated paper
75-84 246-276
0.50-
0.56
Poly, cross­linked
78-87 256-285
0.52-
0.58
Poly, filled with Petrolat
96.0 314.8 0.64
Polyethylene 100.5 329.6 0.67 PTFE 106.5 349.3 0.71 Paper 108-132 354-433
0.72-
0.88 Poly, foamed 122.9 403.4 0.82 Air 141-147 462-482
0.94-
0.98
Page 53
MAN_Easyflex_com_eng_01.doc 53
From your own measurements:
Propagation time
Insulation or
type of cable
v
/2, m/µs
v
/2, ft/µs
NVP
Page 54
54 MAN_Easyflex_com_eng_01.doc
6.4 Glossary
Resolution
In a TDR device, resolution describes the minimum distance between two successive faults in a cable at which the events are depicted on the screen as individual echoes which can be discriminated and, consequently, can be measured. When the echoes superpose each other, the starting time of the second echo – its so-called foot point – cannot be measured. In this event the resolution is too small. Resolution depends on the duration of the used pulse. Obviously short pulses mean much better resolution than long pulses. The distance range which can be covered, on the other hand, is much shorter for short pulses as compared with long ones.
Pulse
In a TDR device, pulses are used as transmitter signals. A pulse is an electrical signal with high amplitude and short duration. When travelling along the cable, each pulse is more and more deformed (attenuation of amplitude, increase in signal duration). The width (duration) of a pulse is measured between those points at which the pulse has half its maximum amplitude. In locating a fault, its distance is determined by moving the cursor to the foot point of the echo – i.e. to its starting point. As each pulse grows wider and wider when travelling along the cable, the achievable resolution is more and more reduced with growing distance.
(Factor of) Propagation Time
NVP
Balancing Network
The balancing network is for simulating the input resistance of the cable to be tested. It is used for suppressing the display of the transmitter pulse so that reflections can be depicted and measured directly from the output of the Easyflex Com – there is no dead zone as otherwise usual.
Page 55
MAN_Easyflex_com_eng_01.doc 55
NEXT
Near End Cross (X) Talk NEXT (Crosstalk) describes the coupling of signal
components into a neighbouring Pair running in parallel. Crosstalk is undesirable as each component coupled into a neighbouring pair will impair the signal-to-noise ratio in this line. This is why in standards on data communication equipment, certain minimum values are required for crosstalk. Crosstalk attenuation is usually worst at the near end, i.e. when one pair is used for transmission and another pair for reception. Crosstalk may also be introduced by other faults in the cable (e.g. a faulty junction box with improper shielding of individual pairs from one another). The Easyflex Com is able to locate these types of faults.
NVP
(= Nominal Velocity of Propagation) The value of NVP, also called propagation time factor or
”reduction factor” (Verkuerzungsfaktor in German), is a way to describe the propagation velocity of a signal along a line. It specifies the ratio of signal propagation velocity to the velocity of light. If, for instance, the NVP of a cable is specified to be 0.65, the propagation velocity along the cable is:
s
m
194.86 =
s
m
299.790.65 = c • NVP = v
µµ
where c = 299.79 m/µs velocity of light. There may be differences between the information given in data leaflets or the table in the manual and actual propagation times in real objects due to the dependence of NVP on the material used. As a rule, the difference is greater in balanced cables than in coaxial cables. Moreover you have to reckon with the individual pairs having slightly different values of NVP. This has to be attributed to the fact that the shields of different conductors contain different types of dye in order to be able to distinguish individual conductors. As each dye has a different value of ε
r
, signal propagation velocity is
different from pair to pair. In the Easyflex Com, signal propagation velocity can be set
as either NVP or v/2.
Page 56
56 MAN_Easyflex_com_eng_01.doc
Impulse
Pulse
Split Pairs
Improperly connected, twisted two-wire connection. The conductors of the individual pairs are not properly twisted with each other in pairs. New pairs are generated by the fact that at either end of the line one conductor is reversed. Begin (split) and end (resplit) of the revered section show strong crosstalk interference. Split Pairs are the result of erroneous installation.
Pair
Pair of conductors of a balanced (symmetrical) line
STP
(= Shielded Twisted Pair) Line which consists of a number of twisted two-wire pairs.
Each pair is wrapped in a foil shield of its own. By S/STP (Screened Shielded Twisted Pair) a cable is understood the entire body of which is enclosed in a common shield.
Balanced Line
Two-wire line with the voltages of either conductor versus earth being equal in size but opposite in polarity. Usually two-wire line are twisted (twisted pairs) to avoid any interference effects.
TDR
(= Time Domain Reflectometer) The Easyflex Com is a reflectometer operating in what is
known as the time domain. Apart from the amplitude, the Easyflex Com measures exclusively propagation times with the aim of calculating the distance to cable inhomogeneities. In doing so it employs a different operating principle than a frequency-domain instrument (network channel analyser, spectrum analyser).
UTP
(= Unshielded Twisted Pair) Line consisting of a number of twisted two-wire line pairs.
Unlike an STP cable, the individual pairs are not shielded. By S/UTP (Screened Unshielded Twisted Pair) a cable is understood the entire body of which is enclosed in a common shield.
Page 57
MAN_Easyflex_com_eng_01.doc 57
v
/2
In cable testing it is common practice to specify the signal propagation velocity in term of half the actual velocity. When employing the reflection technique, this is a usual way of taking twice the signal travel path into account. To depict a reflection on the screen, the signal has to travel from the meter to the fault and back. If the v/2 values of various cables are listed in a table, these values can directly be used to convert the measured signal propagation time tx into fault distance E.
Reduction Factor
NVP (Nominal Velocity (of) propagation)
Loading...