Installation Instructions for
Prodigy Eclipse Condensing Unit
models ECC0800, ECC1200, ECC1410, ECC1800
TOP VIEW
992.81
39.09
814.22
32.06
FRONT VIEW
32.05
1.26
TYP.
1009.65
39.75
887.73
34.95
.88" ELECTRICAL INLET
1/2" COOL VAPOR LINE
3/4" SUCTION LINE
3/8" LIQUID LINE
83.67
3.29
SIDE VIEW
LINE SET AND ELECTRICAL ATTACHMENT SIDE
330.86
13.03
74.12
2.92
163.02
6.42
248.87
9.80
750.06
29.53
491.69
19.36
INTERFACE HARNESS
ACCESS HOLE
63.50
2.50
17-3456-01
Introduction
A remote low side cuber system consists of two systems: an ice making section and a remote condensing unit.
This instruction manual covers the Condensing Unit.
Unpack
1. Remove the carton.
2. Disconnect condensing unit from skid
3. Remove both side panels.
4. Locate and retain communication wire.
Placement
The footprint of the condensing unit is 39” x 32”. Have roof equipment rails prepared for it. Plan on attaching
the unit per local building codes, including any hurricane requirements.
Location
The condensing unit requires unobstructed air ow to operate efciently. A four foot space between each intake
side and a wall or other cabinet is recommended.
Do not place where it will pick up hot discharged air from an air conditioner or other refrigeration system
condensing unit.
Space must also be reserved for service on the condensing unit.
Roof preparation
Most installations of this system will place the condensing unit on the roof of a building. The roof must be
physically able to accept the load of the equipment and the roong material must be prepared to prevent water
leaks.
Roof Piercing:
The roof (or wall) must have a passage large enough for the three refrigeration tubes and the control wire
to pass through. The minimum recommended size is 4” ID. In most areas the power supply may also pass
through the same passage. If there isn’t a passage one must be created. In most cases this must be done by a
licensed and bonded roofer in order to maintain the roof’s integrity.
Roof Pipe Curb or Pitch Pocket:
To avoid potential kinking of the refrigeration tubing, avoid small, tight radius types of covers on pitch pockets.
Suggestions:
• Orient the assembled unit so that the unit’s refrigeration connections are nearest to the tubing.
• Do NOT place the unit directly onto roof rock.
Position the unit
In most cases a crane will be required to lift the unit to a roof location.
Mount unit to roof rails or curbs and secure with lag screws or similar eld supplied fasteners.
Electrical ConnectIon
Electrical power must be supplied to the condensing unit, it will be separate from the head. Locate condensing
unit dataplate for Voltage, Phase, Miniumum Circuit Ampacity and Maximum Fuse Size.