Scotsman NW458, NW608, NW1008 Service Manual

Page 1
  
SERVICE MANUAL
NW458 NW608
NW1008
Electronic Modular Cubers
98020303-00 Version A
Page 2
2
TABLE OF CONTENTS
Table of contents
Specifications
2-3 4-9
FOR THE INSTALLER
Introduction 10 Storage bin 10 Standard legs 10 Important operating requirements 10 Select location 11 Storage bin 11 Ice machine 11 Stacking instructions 12
FOR THE PLUMBER
Conform to all applicable codes Water inlet
13
Drains 13
For the electrician
Electrical connections 14
Final check list
15
START-UP
Start-up cycle 16 Freezing cycle 16 Harvest cycle 17
OPERATION
Refrigeration during freeze 18 Water system 19 Refrigeration system during harvest 20 Water system 20 Control sequence 20 Alarm conditions 21 PC Board set up 22
SERVICE SPECIFICATIONS
Component 23 Operating characteristics 23
COMPONENT DESCRIPTION
Component description
24-26
Page 3
3
WIRING DIAGRAM
NW 458/608 27 NW 1008 28
SERVICE DIAGNOSIS
Service diagnosis 29
MAINTENANCE & CLEANING INSTRUCTION
Icemaker 30 Ice storage bin 30 Cabinet exterior 30 Cleaning (Icemaker) 30-31
Page 4
4
SPECIFICATIONS
MODULAR CUBER NW 458
Ice Making Capacity
NOTE. To keep your Modular cuber performing at its maximum capacity, it is necessary to perform periodic maintenance as outlined on page 29 of this manual.
Page 5
5
SPECIFICATIONS
MODULAR CUBER NW 458
Air Cooled
Page 6
6
SPECIFICATIONS
MODULAR CUBER NW 608
Ice Making Capacity
NOTE. To keep your Modular cuber performing at its maximum capacity, it is necessary to perform periodic maintenance as outlined on page 29 of this manual.
Page 7
7
SPECIFICATIONS
MODULAR CUBER NW 608
Air Cooled
Page 8
8
SPECIFICATIONS
MODULAR CUBER NW 1008
Ice Making Capacity
NOTE. To keep your Modular cuber performing at its maximum capacity, it is necessary to perform periodic maintenance as outlined on page 29 of this manual.
Page 9
9
SPECIFICATIONS
MODULAR CUBER NW 1008
Air Cooled
Page 10
10
FOR THE INSTALLER
INTRODUCTION
These instructions provide the specifications and the step-by-step procedures for the installation, start up and operation for the SCOTSMAN Model NW 458-608-1008 Modular Cubers. The Models NW 458-608­1008 Modular Cubers are quality designed, engineering and constructed, and are thoroughly tested ice making systems, providing the utmost in flexibility to fit the needs of a particular user.
STORAGE BIN
NW 458 608 1008 stack onto SCOTSMAN bin model NB 393/530/948.
Refrigerant R 404 A
Charge per nameplate rating. STANDARD LEGS: Furnished with storage
bin. Four legs screw into mounting sockets on cabinet base. Provide 18.5 cm. (7’’) minimum heights including adjustable leveling foot.
IMPORTANT OPERATING REQUIREMENTS
Air Temperature
MINIMUM 10 C (50 F)
MAXIMUM 40 C (100 F)
Water Temperature
5 C
(40 F)
35 C
(90 F)
Water Pressures
1 bar
gauge
5 bar
gauge
Electrical Voltage Variations Voltage rating specified on nameplate
-10% +10%
Extended periods of operation exceeding these limitations constitute misuse under the terms of Manufacturer’s Limited Warranty, resulting in a loss of warranty coverage.
INSTALLATION NOTE: Allow 15 cm minimum space at sides and back for ventilation and utility connections.
Page 11
SE
L
Th
e
sel
e
will sp
o
- i
nexc
limi
- t
h
incl
- t
hmacand
ST
O
Th
e393
Ot
h
var
ybacsup
Sta sm
a
wit
h
IC
E
Th
e
for Re
m
Pla the pa
cuse
sid
e
Se
e
Re
mmasDef
ECT LO
C
first ste
p
ct the lo
c
have a d
e
t to insur
e
doors, in eed the tations for
at the
n
uding the
c
at there
hine for
s
rear for
a
RAGE B
Scotsma
, NB530
a
er bins
m
the stor
a
k, using port it, sc
r
nd the bin
ll tears i
n
food gra
d
MACHIN
use of a lifting the
ove fron
t
ce the uni
t
back of
kage, tak
e
them to
s of the b
illustrati
o
ove all
s
king
lector/eva
ATION
in installi
ation. Th
e
sired spot that it is:
an envir
o
air an
d
the equip
m
ecessary
orrect vo
l
be spac
e
ervice, 15 ir-cooled
m
IN
n bins for
nd NB94
8
ay be av
a
ge capa
c
cardboar
d
ew in the
l
upright, a
the ma
c
e silicone
E
mechani
c
uncrated
, top and
s
directly o
the bin.
out two
secure th
e
in. n below.
hipping
m
tapes
porator co
v
ng the eq
u
purchas
e
in mind,
c
nment t
h
water
ent.
utilities
a
tage elect
r
around cm. mini
m
odels.
these uni
t
.
ilable wit
h
ity. Lay t
h
from t
h
egs.
nd correct
hine mo
u
sealant.
al lift is r
e
icemaker
ides pan
e
nto the bi
n
Locate t
h
mounting
Icemak
e
aterial a
s
from
er.
ipment i
s
r of the
u
heck out t
at does
temperat
u
re availa ical powe
the instal
um left, ri
g
s are the
bin top
s
e bin on
e carton
any possi
nting gas
commen
d
onto the
b
ls.
, align it
w
e hardw
a
screws,
a
r to the
t
well as
t
the
11
to
nit
hat not
re
ble r. led
ht,
NB
to
its
to
ble ket
ed
in.
ith
re
nd
wo
he
ice
R
e
th
e
se
move firs
t
n the ma
nsor.
the ice d
e
sking tap
e
flector/ev
a
from the
porator c
o
ice thick
n
ver
ess
Page 12
12
Page 15
AIR BAFFLE
Install on the back side of the machine the air baffle as per instruction provided with it.
STACKING INSTALLATION
To stack a second NW onto the present one, first remove the top panel from the lower machine. Add a bead of food grade silicone sealant to the top edges of the lower units freezing compartment. Lift the top machine onto the bottom machine, (the use of a mechanical lift is recommended for this step). Align the two machines cabinets, and using the 2 screw from the top units, hardware package, fasten the two units together at the side cabinets. Then make use of the Stacking Kit KSC 450, and KSC 1000, to be mounted as per fitting instructions included in their package, respectively on NW 458, NW608, NW1008 located in the bottom for proper conveying, of the ice cubes made by the top unit, into the storage bin. With food grade silicone perfectly seal the edge between the freezing compartment of the upper machine and of the bottom machine so to avoid any possible leak of water through the clearance in between.
Page 13
13
FOR THE PLUMBER
CONFORM TO ALL APPLICABLE CODES WATER INLET
AIR-COOLED MODELS: The recommended
water supply is cold water connected to the ­3/4'’ gas - male fitting at the back of the cabinet. Install a hand valve near the machine to control the water supply.
1) Plug receptacle
2) Electrical plug
3) Water inlet
4) Shut-off valve
5) Water filter
6) Water inlet line
7) Water outlet line
8) Bin water outlet line
9) Open vented water drain When choosing the water supply for the NW
Cuber, consideration should be given to: A. Length of run. B. Water clarity and purity. C. Adequate water supply pressures.
Since water is the most important single ingredient in producing ice you cannot over emphasize the three items listed above. Low water pressure, below 1 bar may cause malfunction, of the icemaker unit. Water containing excessive minerals will tend to produce cloudy colored ice cubes, plus scale build-up on parts in the water system. Heavily chlorinated water can be controlled using charcoal or carbon filters.
DRAINS AIR-COOLED MODELS: There is one 20 mm.
dia sump drain fitting at the back of the cabinet. Insulations in high humidity areas is recom­mended. The ideal drain receptacle would be a trapped and vented floor drain. STORAGE BIN: A separate gravity type drain needs to be run, similar to the air-cooled sump drain. Insulation of this drain line is recommended.
Page 14
14
FOR THE ELECTRICIAN
ELECTRICAL CONNECTIONS
The unit comes equipped with an electrical cord for power supply. The lead wires must be connected to an electrical plug that corresponds to the local electrical codes and requirements or to a separate two poles disconnect box with opening to the contacts of about 3 millimeters. The disconnect box should be placed close to the selected ice maker location to be easily and prompt reached. Undersized wiring or improperly installed electrical circuit will result in major problems and malfunctions. Voltage variations should not exceed ten percent.
NOTE: All SCOTSMAN Cubers require a neutral wire and a solid earth ground wire to prevent possible severe Electrical Shock Injury to individuals or extensive damage to equipments.
IMPORTANT - All plumbing and electrical connections must be made by licensed plumbers and electricians, this one must follow the electrical specifications printed on the ice maker nameplate.
Page 15
15
FINAL CHECK LIST
1. Is the cabinet/bin level?
2. Is the cuber in a location where ambient temperatures are a minimum of 10 C (50-de­grees F.) all year around and to not exceed a maximum of 40 C. (100 F.)
.3. Is there at least a 15 cm. clearance behind and around the cabinet for all connections and for proper air circulation?
4. Have all electrical and piping connections been made?
5. Has the electrical power supply wiring been properly connected and the voltage tested and checked against the nameplate rating? Has the unit properly grounded?
6. Is the water supply line shutoff valve installed and opened and has the inlet water supply pressure been checked to insure a minimum of 1 bar without exceeding a maximum of 5 bar.
7. Have the compressor hold down bolts been checked to be sure the compressor is snug on the mounting pads.
8. Check all refrigerant lines and conduit lines to gard against vibration and possible failure.
9. Has the cuber and the bin been wiped clean with clean damp cloths?
10. Has the owner/user been given the User Manual and instructed on how to operate the icemaker and the importance of periodic
maintenance?
11. Has the owner/user been given the name and telephone number of the Authorized SCOTSMAN Distributor or Service Agency serving him?
12. Has the Manufacturer’s Registration Card been properly filled out?
Check for correct Model and Serial Numbers from nameplate, then mail the completed card
to the Manufactured.
TYPICAL STACKING INSTALLATION
KIT STACKING KSC 450: TO STACK 2 NW 458 KIT STACKING KSC 450: TO STACK 2 NW 608 KIT STACKING KSC 1000: TO STACK 2 NW 1008
Page 16
16
START-UP
START-UP CYCLE
1. Open the water tap/valve and switch ON the power on the electrical supply line.
2. The models NW 458, 608 enter in the Start Up mode with the PC Board energized as well as the Green LED of the machine under power while the models NW 1008 enter in 90 minutes delay time controlled by a special Start-up Delay PC Board. The Green LED of machine in operation is energized too, blinking fast for 40 seconds.
3. During the Start Up cycle the components in operation are:
• Hot gas valve
• Water Drain Valve
• Water Pump
FREEZING CYCLE
1. After the Start Up cycle the machine enters directly into the Freezing cycle with the following components energized:
• Water Inlet valve
• Compressor
• Fan motor (in continuous operation for the first 3 minutes).
2. The LED energized are:
• Machine under power
• Machine in operation (steady)
3. Water is coming into the water through the Water Inlet Solenoid Valve till the water reservoir if filled up to the maximum level controlled by a Water Level Sensor.
4. 30 seconds later, the Water Pump starts up.
5. After few minutes (3-5) from the start up of the freezing cycle, the Water Inlet Solenoid Valve is activated again for few seconds to re­fill the water reservoir up to the maximum level so to reduce any possibility of slush ice formation.
6. In the meantime the condenser sensor starts to transmit the current to the PC Board keeping in operation the Fan Motor in ON-OFF mode or continuously according to the condenser temperature.
7. The machine remains in the freezing cycle with the ice that become thicker till the two metal plates of the Ice Thickness Sensor are covered by the water cascading through the front surface of the ice plate.
8. When the Power is transmitted back to the PC Board continuously through the metal plates of the Ice Thickness Sensor for more than 6", the machine enters in the Pre-Harvest or directly into the Harvest Cycle mode according to:
• FAN MOTOR IN ON-OFF MODE DURING THE PREVIOUS FREEZING CYCLE
RISE UP THE CUT IN TEMPERATURE OF THE CONDENSER SENSOR TO 38 C (FAN MOTOR OFF) AND EXTEND THE LENGTH OF FREEZING CYCLE BY 30" MORE THEN GO INTO HARVEST CYCLE
• FAN MOTOR ALWAYS IN OPERATION DURING THE PREVIOUS FREEZING CYCLE
GO STRAIGHT TO THE HARVEST CYCLE
9. First freezing time will range between 15 and 20 minutes. Longer time for temperature
NOTE: Do not remove the evaporator deflector cover as it will cause the switching off of the machine at "STORAGE BIN FULL".
NOTE: The models NW 1008 is equipped with a compressor crankcase heater and a Start up Delay PC Board set up at 90 minutes. During the first 90 minutes only the compressor crankcase heater is energized warning up the compressor.
Page 17
17
above 25 and shorter time required when temperature are below 25 ℃ . Average complete cycle time is about 22 min.
HARVEST CYCLE
1. During the harvest cycle the components in operation are:
• Hot Gas valve
• Water Drain/Purge Valve
• Water Pump for the first 40"
• Compressor and both
• Machine Under Power
• Machine in Operation
2. 30 seconds after the beginning of the Harvest Cycle, the Water Inlet Solenoid Valve is energized for 10 seconds only in order to have a short flush of fresh water into the sump while the Water Pump is still in operation.
3. The Fan Motor remains in OFF mode unless the Condenser Sensor probe rise up to more then 38 (same set up as per end of freezing cycle).
4. When the ice plate is falling down from the evaporator, the magnetic switch is activated for a while providing the signal to the PC Board to restart a new freezing cycle.
5. Observe first ice cube harvest and check size of ice cubes; if an adjustment is required thread down or out screw NO.1 as shown on below illustration.
This screw position determines the distance between the sensor reeds and the egg-crate evaporator thus keeping the ice cube at a proper thickness.
6. Observe second and third cube harvest. Check if size and shape combination is correct. In areas where extreme problem water conditions exist, filtering or purifying equipment is recommended.
7. Check operation of magnetic switch controlling it by keeping open the bottom end of plastic deflector for more than 30 seconds. The machine must switch off at storage bin full. Release the plastic deflector. The machine should restart in the freezing cycle mode within few seconds going through a 3' delay time.
8. Place again all cabinet panels and screws previously removed.
9. Thoroughly explain to owner/user the significant specifications of the ice maker start­up, reset and operation, going through the procedures in the operating instructions. Answer all questions about the ice maker by the owner and inform the owner himself of the name and telephone number of the authorized service agency serving him.
NOTE: To assure a correct operation of the machine the water must have a minimum electrical conductivity of 20 us.
NOTE: If water used is too soft, "demineralized" the ice thickness sensor might not be able to sense the water on its reeds, thereby it will not switch the unit on harvest cycle. A safety system built in the P.C. Board switches the unit on harvest cycle whenever the freezing period gets longer than 30' or 40'.
NOTE: This type of machine produce an "ICE PLATE" that breaks when falls down into the storage bin. Setting the ice thickness sensor in order to have single ice cubes may cause malfunction of the machine.
Page 18
O
P
RE
F
Thi
scon
eit
h
A
t
co
m
pre Th
e
the co
o
wit
h
te
m
If
wcon
thr
o
by
t
Afte
givi int
o
thr
o
a t
h
Th
emuc
ERATI
O
RIGERA
T
ice ma
densing
m
er one is
a
the herm
pressed
ssure gas
.
gas mov
e
condens
e
led, the
d
the he
perature.
ater-cool
trolled b
y
ugh the
c
he water
r
r the ga
ng up mu
c
a high p
ugh the li
ermostati
c
thermos
t
h liquid r
e
N
ION DU
R
chine em
edia, the
follows:
etic com
p
into a h
s throug
h
r, air o
r
ischarge
at load ed, the
d
the am
o
ondenser
egulating
v
s is cool
h of its h
e
ressure li
q
quid line
t
expansi
o
atic expa
n
frigerant i
REF
R
ING FRE
E
ploys eit
h
refrigerati
o
ressor,
R
igh temp
e
the disch water-c
o
pressure
and the
ischarge unt of
w
- which i
s
alve.
ed in th
e
at, the g
a
uid. This
o the me
t
n valve.
sion valv
e
s to be all
o
FR
E
IGERATI
O
ZE:
er air a
s
n system
efrigerant
rature, h
arge line i
oled. If
a
will cha
n
ambient
pressure
ater flow
determi
n
conden
s
s conden
s
liquid tra
v
ering devi
meters h
wed into
t
18
EZE CY
C
N SYST
E
a
for
is
igh nto
ir­ge air
is
ing
ed er,
es
els
ce,
ow
he
e
vThTXma
If
tref
(c
o
a
nref
T
h
wi
l
e
v
hi
genthe
su T
hforexref
su hi
g
a
n
LE
M SCHE
M
aporator
s
is is dete
r
V sensin
g
nifold, at
t
he bulb
s
rigerant i
mmon at
d when t
h
rigerant i
s
is is why l decline t
aporator,
t
h pressu
vironment
evapora
ch as wat
e
e low pr
e
ced throu
g
cess liqui
d
rigerant
v
ction tub
e
h pressu
d the cycl
e
ATIC
ection of t
h
mined by bulb, lo
c
he outlet
o
enses a
w
s allowe
d
the begin
n
e temper
a
allowed t
h
the sucti
o
hroughou
t
he liquid
r
re, boils
o
and abs
o
tor surfac
e
r.
ssure re
f
h the he
a
refrigera
n
apor to
, where
i
re, high
t
repeats.
P
e refrige
r
the temp
ated on t
h
f the eva
p
arm suct
into th
e
ing of th
e
ture begi
n
rough.
n side g
a
the freez
e
efrigerant
ff in the
rbs heat
,
and an
y
rigerant
v
t exchan
g
t boils-off
enter th
e
t is reco
m
emperatu
age 19
ation syst
e
erature of
e suction
orator.
ion line,
m
evapor
a
freeze c
y
s to fall,
uge pres
s
cycle. A
t
released
f
low pres
s
thus co
o
thing ne
a
apor the
n
er where
, allowing
o
compre
s
pressed
re gas a
g
m.
the
line
ore tor,
cle)
less
ure
the
rom
ure
ling
r it,
is
any
nly
sor
into
ain
Page 19
19
FREEZE CYCLE
WATER SYSTEM
A combination of a solenoid water inlet valve with a water level sensor is used to control the level of the water into the reservoir/sump. A pump, running continuously, after the first 30" of freezing cycle, forces the water to the top of the evaporator, where it is distributed through a water tube and then cascades down
the evaporator surface by gravity. As it flows across the refrigerated evaporator, some of the water will be chilled enough to change form, turn to ice, and stay frozen onto the evaporator cells. Most of the water returns to the reservoir, to be sucked back into the pump, and re-pumped over the evaporator.
Page 20
20
HARVEST (DEFROST) CYCLE
REFRIGERATION SYSTEM SCHEMATIC
REFRIGERATION SYSTEM DURING HARVEST
The refrigeration system performs the harvest of ice by use of a hot gas bypass valve. When the time comes to de-ice the evaporators, the hot gas valve is energized, and the high temperature, high pressure gas bypasses the condenser, and is allowed directly into the evaporator. The high pressure gas is cooled by the cold evaporator so it condenses into a liquid, giving up its heat as it does so. This heat warms the evaporator and the ice frozen onto the evaporator surface melts, releasing the frozen cubes. Ice then falls by gravity into the storage bin. The liquid refrigerant goes through the suction line into the heat exchanger where it boils-off so that only refrigerant vapor is drawn into the suction tube of the compressor.
WATER SYSTEM
During the harvest cycle, the electric water drain valve is energized thereby opening the drain line.
All water remained in the reservoir at the end of freezing cycle is pumped-out, to the waste, through the water solenoid and drain line during the first 40 seconds of the defrost cycle eliminating any possible build-up and accumulation of minerals concentration and impurities in the water reservoir. The water inlet valve is energized during the last 10" of the operation of the water pump so to rinse the water tank with new fresh water. When the released ice cubes drop into the bin, they open-up for a fraction of a seconds the bottom end of plastic deflector. This deflector swinging motion is enough to reset the contact of the magnetic switch which
- via electronic control board de-energizes the water drain valve allowing the unit to initiate a new freezing cycle. The harvest cycle lasts about 1.5-2 minutes.
CONTROL SEQUENCE
At the start of the freezing cycle, the contacts of the magnetic switch mechanically operated by the actuator plate of the deflector cover are closed, thereby - via electronic control board -
Page 21
21
closing the circuit to the main contactor coil and consequently to the compressor and fan motors and 30" later, to the water pump motors. Then, as the ice thickness reaches the value that corresponds to the full cube size, the film of water that constantly cascades over the slab of ice formed on the evaporator, arrives to establish a contact between the two fingers (energized at low voltage) of the ice sensor control, located on the front upper right side of the evaporator. If the contact between the two fingers of the ice sensor remains established ­by the film of water – for more than 10 seconds, a small relay of the electronic board, get energized, controlling - simultaneously both the hot gas valve and the water drain valve.
At this point, the unit initiates the defrost cycle. The hot gas circulating into the evaporator serpentine causes a slight melting of ice cubes which get released from their molds. Once entirely released the ice cubes drop simultaneously into the ice storage bin below; by doing so they move apart from the evaporator bottom end the plastic deflector. This plastic deflector has on its side a magnetic switch that on account of the deflector swinging motion, caused by the ice while dropping in the bin, opens and closes their contacts. This will, in turn, deactivates the relay contacts that controls the hot gas and water drain valve which get de-energized allowing the unit to start a new freezing cycle. When the ice bin is full of ice, the last batch of ice cubes released from the evaporator accumulates to keep the bottom end of the plastic deflector in open position; with the magnetic switch contacts open for longer than 30'’ the entire unit stops with the glowing of the corresponding LED. The machine will restart when the ice deflector will be back in its normal vertical position provided that 3' are elapsed from unit stop. If not the machine will delay its restart till 3' are elapsed with the blinking of the green LED.
ALARM CONDITIONS
Both the last two Red LED are ON STEADY: Condenser Sensor OUT OF ORDER. Both the last two Red LED are BLINKING SLOW: WATER ERROR Water level inside the water sump too low after 3' from the activation of the Water Inlet Valve. Both the last two Red LED are BLINKING FAST. RESET MODE: Charging water through the Water inlet Solenoid Valve after the tripping OFF on WATER ERROR. The fourth Red LED is ON STEADY: Harvest Cycle longer than 3' 30". The fourth Red LED is BLINKING SLOW: TOO HI CONDENSING TEMPERATURE. The condenser sensor detected a temperature > 65℃. The fourth Red LED is BLINKING FAST. RESET MODE: Condenser Sensor < 50 Fan motor in operation for 3' then back on Start Up Cycle Mode The fifth Red LED is ON STEADY: TOO HI DISCHARGE PRESSURE > 33 bar 460 PSI The fifth Red LED is BLINKING FAST: RESET MODE: FOR THE FIRST 2 TIMES, MACHINE WILL AUTOMATIC RESET, THE MACHINE WILL STOP WHEN HIGH PRESSURE OCCURS THE THIRD TIME.
The PC Board is also checking the maximum time of the freezing cycle that changes according to the operation of the fan motor during the freezing cycle (room temperature):
• Fan motor in: Max. freezing cycle length ON-OFF mode: equal to 30'
• Fan motor ON: Max. freezing cycle length All the time: equal to 40' Whenever the machine remains in the Freezing Cycle for the Maximum time (30 or 40 minutes), the PC Board moves the unit directly into the Harvest Cycle.
NOTE: in case of failure of ice level sensor, the P.C. Board turns - on automatically the unit into the defrost cycle when the freezing cycle reaches 30 or 40 minutes according to the operation of the fan motor during the freezin
g cy
cle.
Page 22
P
C
Th
e
• M for har
v
- J
U
• M a s har
vcyc
- J
U
BOAR
D
PC Boar
d
anual res
e
a short ti
m
est cycle
MP IN J2
anual res
e
hort time
o
est cycle
les - Rec
o
MP IN th
e
SET U
P
can be s
e
t mode a
n
e only a
t
- Sugges
t
t mode a
n
nly at be
plus a ful
l
mmende
d
first TW
O
t up for:
d water
p
beginnin
g
ed for soft
d water p
ginning of
water pu
r
for norma
contacts
urge out
of every water
urge out f
o
every
ge every
s
l /hard wat of J1
22
ix
er
• e
vwa- J
-
Manual r
e
ery harve
s
ter
UMP IN t
h
A
utomati
c
JUMP O
U
set mod
e
t cycle -
e second
reset
T
and full
Recomm
e
TWO con
t
water p
u
nded for
h
acts of J1
rge ard
Page 23
23
SERVICE SPECIFICATION
In servicing a machine, it is often, useful to compare that individual unit operating characteristics to those of a normally operating machine. The data that follows gives those characteristics; however, be aware that these values are for NEW, CLEAN machine operating at 21 ambient and 15 C water.
USE THESE NUMBERS AS A GUIDELINE ONLY.
COMPONENT Reservoir level
NW 458/NW608 ......................... 80~85 mm
NW 1008 ............................. 100~105 mm
Cube Size Control Ice Sensor - distance from evaporator 3~5 mm
High Pressure Safety Switch.
NW 458-608-1008: Cut IN 23 bar - Cut OUT 33 bar
OPERATING CHARACTERISTICS
On air-cooled models during the freezing cycle, the discharge pressure is maintained between two preset values by means of fan control (condenser sensor); and at the same time, the suction pressure will also decline reaching its lowest point just before harvest. Compressor amps experience a similar drop. On water-cooled, the discharge pressure is constantly, maintained during the freeze cycle by the water regulating valve. However, suction pressure and compressor amps, will still decline as the machine freezes ice.
MODEL
Disch.
Pressure
Freeze
max
Disch.
Pressure
Freeze
min
Hi
Pressure
CUT OUT
Suction
Pressure
Beginning
Freeze
Suction
Pressure
end
Freeze
Freezing
time
Amps
Compressor
Beginning
Freeze
Amps
Compressor
end
Freeze
NW 458 A 17,0 bar 15,0 bar 33 bar 3,6 bar 2,3 bar 16' 4,2 3,4 NW 608 A 18,0 bar 16,0 bar 33 bar 2,9 bar 1,7 bar 11' 7,0 5,2
NW 1008 A 18,0 bar 15,5 bar 33 bar 3,2 bar 1,7 bar 11' 30" 4,0 3,1
Refrigerant charge R 404A MODEL NW 458 NW 608 NW1008
Air cooled 50 Hz 700 850 1300
Refrigerant metering device
Thermostatic expansion valve.
NOTE: Always check nameplate on individual ice machine for special refrigerant charge before charging the refrigeration system. Such refrigerant charge is the average charge for the NW Modular Cubers. However it is important to check nameplate for each machine.
Page 24
24
COMPONENT DESCRIPTION
1. Front Console Panel
NW SERIES
2. P.C. Board
Located in the control box, this board is the brain of the system as it governs the ice machine cyclematic through sensors, relays and switches. It consists of two separated printed circuits one at high and the other at low voltage integrated with a fuse, of four connectors for the sensors/switches (condenser sensor - BLACK -, magnetic switch
- GREEN - ice thickness sensor - RED - water level sensor - BLUE), of two jumpers (one J1 for factory use only - and the second J2 for the selection between manual or automatic reset mode), of one outlet connector (front LED display- black) one serial port connector (black)
and of four plug in terminals for input and output power. With J2 closed the P.C. Board is set up for Manual reset mode, when J2 is open on Automatic Reset mode. The P.C. Board is equipped by an electronic safety timer that turns-on automatically the unit to defrost cycle when freezing cycle is longer than 30 or 40 minutes and trips-off completely unit when defrost cycle is longer than 3,5 minutes (2nd Red LED ON). A trimmer, located close to the transformer, can change the current received back from the Ice Thickness Sensor according to the Electrical Conductivity of the water.
BUTTON A Reset/Washing
LED No. 1
A
larm high pressure
LED No. 2
A
larm
LED No. 3
Tank full./Washing
LED No. 4
Operation
LED No. 5
Electrical power supply
A
1
2
3
4
5
Page 25
25
3. Compressor Contactor
Located in the control box, the compressor contactor functions to carry the compressor line current. The contactor is wired to receive power from the P.C. Board.
4. Ice Thickness Sensor
Located in the front upper right side off the evaporator, the sensor is made with two metal reeds in which passes power at low voltage. The two metal reeds, which are individually insulated, are set through a setting screw, to maintain a minimum clearance from the evaporator (3~5 mm). Once ice is formed into each mold and is thick enough to fill-up that minimum clearance existing between the two sensor reeds and the evaporator, the water that cascades over the ice has gradually approached to make contact between the two sensor reeds. It is enough that this contact remains there for about 10 seconds that the P.C. Board receives the signals to put the ice machine on defrost.
5. Magnetic Switch
Located in the front of the evaporator plastic curtain, this switch sends a pulse to the P.C. Board which switches the machine back in the freezing cycle.
6. Hot Gas Solenoid Valve
The Hot Gas Solenoid Valve functions only during the Harvest Cycle, to divert the hot discharge gas from the Compressor, bypassing the Condenser and thermostatic expansion valve, for direct flow to the Evaporator Plate Assembly to release ice cubes from the ice cube molds. The Hot Gas Solenoid Valve is comprised of two parts, the Body & Plunger and the Coil assembles. Installed in the discharge line of the Compressor, the energized solenoid coil lifts the valve stem within the valve body to cause the hot discharge gas to be diverted when the ice Thickness sensor has signaled to the P.C. Board to start the Harvest Cycle.
7. Condenser temperature sensor
The condenser temperature sensor probe (located in contact with the condenser tube coil) detects the condenser temperature variations and signals them by supplying
current, at low voltage, to the P.C. BOARD. In the air cooled versions, in relation to the different current received, the micro processor of the P.C. BOARD supplies, through a TRIAC, the power at high voltage to the fan motor so to cool the condenser and to reduce its temperature. In case the condenser temperature rises and reaches 65 (150 F) the current arriving to the micro processor is such to cause an immediate and total stop of the machine operation with the blinking of the Red LED.
8. High Pressure Control
The high Pressure Control, a safety control, is factory set to cut-out, at 33 bars and cut-in at 22 bars. The high Pressure Control is automatic reset with a monitoring light on the Front Console Panel.
9. Water Regulating Valve
(Water Cooled Models) The Water Regulating Valve functions maintain a constant Compressor head pressure, by regulating the amount of incoming water flow through the Condenser, on water-cooled models. The valve operates through the refrigerant system high side pressure. Rotating the adjusting screw located on top of the valve, can INCREASE or DECREASE the water flow through the water­cooled Condenser, which in turn, will DECREASE or INREASE the Compressor operating head pressure.
10. Water Distribution System
The Water Distribution System functions to even supply water to all cells of the evaporator plate. The water pump pumps water from the sump to the tee. From there water is channeled through the vertical Teflon tube to the water distributors, above the evaporator plate, and from the holes in the distributor tube water flows to the cells on one side of the evaporator plate. Gravity flow returns the unfrozen excess portion of water to the sump reservoir for recirculation.
11. Water Drain Solenoid Valve
The Water Outlet Solenoid Valve functions in conjunction with the water pump to flush-out the sump assembly at the beginning (first 40")
Page 26
26
of every harvest cycle. This action cleans-up and rinses the sump during each harvest cycle preventing dangerous water minerals concentration.
12. Thermostatic Expansion Valve
The Thermostatic Expansion Valve regulates the flow of refrigerant to the evaporator and reduces pressure of liquid refrigerant from condensing pressure to evaporating pressure.
13. Water pump
The water pump primes the water from the sump to the water distributor tube and through the distributing holes it cascades down onto the evaporator cells by gravity so to be frozen into clear ice cubes. The water pump remains off during the first 30" seconds of the freezing cycle (to avoid any cavitation problem) while it's kept running during the first 40" of defrost/harvest cycle to drain out (purge) the remaining water from the sump (reach in mineral salts).
14. Water inlet solenoid valve - 3/4" male fitting
The Water Inlet Solenoid valve is energized by the P.C. Board during the beginning of the freezing cycle till the water reaches the maximum level into the sump (controlled by the Water Level Sensor). After 3 minutes, from the start up of the freezing cycle, the Water Inlet Valve is energized again for a short period to re-fill the sump with water till again to the maximum level so to minimize any possibility of slush ice
formation A flow control, fitted into its outlet port, reduces
the pressure of the water flow.
15. Water level sensor
The Water Level Sensor, located on the upper right side of the water sump, works in conjunction with the P.C. Board in order to control the water level at beginning of the freezing cycle by receiving a low power current passing through the water. When the current reaches the PC Board, the water inlet solenoid valve is de-energized. In case the PC Board doesn’t receive any signal (current) from the Water Level Sensor within the first 3 minutes of the freezing cycle, the PC Board trips OFF the operation of the machine with the switching ON of the Water Error LEDs.
16. Start up delay PC Board
Located in the back side of the unit it delays the start up of the entire machine by 90' so to avoid that compressor can start up w/out be pre-heated.
17. Start up delay PC Board by-pass switch
Located in the back side of the machine allows to by-pass the delay time controlled by the delay PC Board.
WARNING: It is IMPERATIVE to by-pass the delay time only when sure of proper warm up of compressor.
Page 27
27
Page 28
NW 458/608 - WIRING DIAGRAM
220 V. 50 Hz. 1 ph. m = brown bc = light blue
gv = yellow green b = white n = black r = red a = orange
A - Input terminal board B - Compressor contactor C - Compressor D - Ice sensor E - End defrosting switch F - Water level sensor G - Condenser temperature probe H - Led card I - PC Board J - Hi pressure switch
K - Manual/Automatic reset jumper L - Water pump M - Water inlet valve N - Water drain/purge valve O - Hot gas valve P - Fan Motor (only AIR cooled unit) Q - Fan Motor (only WATER cooled unit) RC - Compressor relay CS - Start capacitor CM - Run capacitor
Page 28
28
NW 1008 - WIRING DIAGRAM
400 V. 50 Hz. 3 ph. m = brown
bc = light blue
gv = yellow green b = white n = black r = red a = orange v = purple
A - Input terminal board B - Compressor remote control switch C - Compressor D - Ice sensor E - End defrosting switch F - Water level sensor G - Condenser temperature probe H - Led card I - Electronic card J - Max pressure switch
K - Automatic reset switch L - Water pump M - Water inlet valve N - Water discharge valve O - Hot gas valve P1 - Fan Motor 1 (only AIR cooled unit) P2 - Fan Motor 2 (only AIR cooled unit) R - Crankcase heater S - Delay by pass switch T - Start delay electronic board
Page 29
29
Page 30
SERVICE DIAGNOSIS
The table below is intended as a quick reference to aid the Service Agent in determining the cause of a particular type of malfunction, as well as the recommended repair. It is not intended to be an exclusive list.
Reference to other portions of this manual, including wiring diagrams, installation, and operation are recommended to better determine the cause of a problem.
SYMPTOM POSSIBLE CAUSE CORRECTION
Warning Red LED ON See page 20 See page 20
No warning LED/LIGHT ON P.C. Board inoperative. Remove board and check. No power to unit. Check electrical source.
Bin full Yellow LED ON Bin Full of ice. Nome.
Magnetic switch inoperative.
Check and replace.
Machine runs, compressor does not.
P.C. Board compressor relay open.
Test and replace.
Compressor contactor open.
Test and replace.
Compressor relay open. Test and replace. Compressor winding open. Test and replace.
Machine runs, makes ice, does not try to harvest.
Ice thickness control open. Check sensor fingers if are not
covered with scale sediment.
Too soft water. Water electrical conductivity must be
higher then 20 S. Machine can't run with demineralized water.
Built-in relay on
Check and replace P.C. Board.
P.C. Board open.
Machine runs, makes and harvests ice but very slowly.
Low refrigerant charge. Check system for correct refrigerant
charge. Check for leak weight in charge.
Low ice capacity. High discharge pressure
due to not-condensable or overcharge.
Evacuate and weigh in charge.
Inefficient compressor. Replace. Condenser dirty. Clean. Low water flow
(Water-cooled).
Check and repair.
High air temperature (air-cooled).
Check temperature of air entering condenser.
Machine makes irregular ice. Plugged water distributor. Clean water distributor. TXV superheat wrong. Adjust or replace.
Refrigerant charge low.
Adjust-check for leak. Recharge.
Page 30
30
MAINTENANCE & CLEANING & SANITATION INSTRUCTIONS
A SCOTSMAN Ice System represents a sizable investment of time and money in any company’s business. In order to receive the best return for that investment, in MUST receive periodic maintenance. It is the USER’S RESPONSIBILITY to see that preferable, and less costly in the long run, to avoid possible down time by keeping it clean, adjusting it as needed and by replacing worn parts before they can cause failure. The following is a list of recommended maintenance that will help keep your machine running with a minimum of problems. Maintenance and Cleaning should be scheduled at MINIMUM twice per year while sanitation once per month.
ICEMAKER
THE FOLLOWING MAINTENANCE SHOULD BE SCHEDULED AT LEAST TWO TIMES PER YEAR ON THIS ICEMAKER. CALL YOUR AUTHORIZED SCOTSMAN SERVICE AGENCY.
1. Check and clean or service any optional water treatment devices, if any installed.
2. Clean water strainer.
3. Check that the cabinet is level, in the side­to-side and front-to-back directions.
4. Clean/Sanitise the water system, evaporator plate and sump assembly, using a solution ot Ice Machine Cleaner/Sanitiser. Refer to CLEANING - Icemaker.
5. Check and tighten all bolts and screws.
6. Check for water leaks and make corrections.
7. Check the bin control to test shut-off. Holding the evaporator deflector in open Position for more that 30", should cause the ice maker to shut-off. Once the evaporator deflector is released in its closed position, the ice maker will restart.
8. Check cube size; adjust if required through setting screw of ice thickness control sensor.
9. With unit out of operation, clean the condenser using vacuum, cleaner, wisk broom or brush. Instruct customer to clean condenser frequently DO NOT USE A WIRE BRUSH.
ICE STORAGE BIN
The interior liner of the bin is in contact with a food product, ice, and should be cleaned and sanitised regularly. Once a week sanitise it with a commercial food grade sanitiser complying with the manufacturer dilution.
CABINET EXTERIOR
Wipe clean unit and bin cabinet exterior with a clean cloth or disposable paper wipers, soaked in warm water with mild detergent solution.
CLEANING - Ice maker
1. Empty bin of ice.
2. Remove front panel.
3. Wait till the end of the defrost/harvest cycle then push the RESET BUTTON for 6-8
WARNING - Ice Machine Cleaner contains Phosphoric and Hydroxyacetic acids. These compounds are corrosive and may cause burns. If swallowed, DO NOT induce vomiting. Give large amounts of water or milk. Call physician immediately. In case of external contact, flush with water. KEEP OUT
OF THE REACH OF CHILDREN.
NOTE: Cleaning/Sanitising requirements
vary according to local water conditions and individual user operation. Continuous check of the clarity of ice cubes and visual inspection of the water system parts, evaporator plates and the sump assembly before and after cleaning will indicate frequency and procedure to be followed in local areas.
Page 31
31
Page 32
seconds. The machine should stop with the blinking of the Yellow LED (slow blink).
4. Pour on
- NW 458-600 250 cc
- NW 1008 350 cc of Scotsman Ice Machine Cleaner directly into the reservoir then push again the RESET BUTTON for a while. The water pump starts to operate with the fast blinking of the Yellow LED while the water inlet valve will be energized till the fill up of the water sump.
5. After 15 minutes push the RESET BUTTON for a while. The P.C. Board puts the machine in automatic rinsing mode with the special blinking (blink twice and repeat) of the Yellow LED.
6. At the end of the 7th Rinsing cycle the P.C. Board stops the operation of the machine with the blinking (slow) of the Yellow LED.
7. Pushing the RESET BUTTON for 6-8 seconds the machine restarts in the freezing cycle.
8. Replace the evaporator cover deflector and front panel.
9. Check the next batch of cubes to be sure all the cleaner is gone (no sour taste).
10. Pour hot water into the storage bin melt the cubes, and to also clean the bin drain.
CAUTION - DO NOT use ice cubes produced from the cleaning solution. Be sure none remains in the bin.
NOTE: RINSING mode consists of: a) Energize the water drain valve and the water pump for 40 seconds to empty the reservoir b) De-energize the water drain valve and the water pump for 1 minute c) Energize the water inlet valve till the fill up of the water sump d) Energize the water pump for 1.5 minutes. The above sequence is repeated 7 times so to be sure to have removed any possible trace of Ice Machine Cleaner.
Page 32
32
Scotsman Ice Systems (Shanghai) Co., Ltd.
Room 2505, Building 2, No. 20 Xuhong Middle Rd., Xuhui District,Shanghai, China
Postcode200235 Tel+86 21 61313200 Fax+86 21 61313330
Emailsales@scotsman-china.com
service@scotsman-china.com Hotline+86 400 630 0076 Websitewww.scotsman-china.com
Loading...