SEZ7000 Series
BACnet Commercial Zoning
System
A cost-effective, scalable zoning system for the commercial
market that delivers unparalleled flexibility via the open BACnet® communication protocol.

Schneider Electric | SDS-SE Z7000BZONE- EN.A4.08.2015.v2 August 2015
SEZ7000 BACnet Commercial Zoning System Features
Introduction
The SEZ7000 BACnet® commercial zoning system is specifically
designed to bring a simple scalable BACnet zoning system solution to the
commercial mid-market without the cost associated with a typical DDC
zoning system.
Our zoning system provides even more flexibility by offering additional
functionality and new models covering more applications while still
achieving excellent energy savings. The new central models include
rooftop and heat pump units controlling analogue heat, CO
and indoor air quality in conjunction with zoning controllers that provide
floating and analogue damper control. The most unique feature of the
zoning system is its scalability; a single central controller unit can support
up to 63 individual zone controllers.
Zoning System
All zone controllers can be ordered with an on-board passive infrared
(PIR) occupancy sensor cover that allows for advanced occupancy
AT A GLANCE
Custom design
• Best in class system scalability
• Provides DDC type control functionality and
accuracy
• No external software tools required for
installation, commissioning or servicing with
embedded local HMI utility
• ZigBee® communication protocol
• Full line of models offer solutions for a wide
range of application
• Control IAQ with any typical third-party wall
mounted C02 sensor
• Controls and measures fresh air with any
third-party fresh air measurement station
• Provides embedded free cooling economizer
loop
• Built in Network-ready functionality
Options and accessories
• PIR occupancy sensor
strategies. This enables the zone controllers to be able to provide even
greater energy savings to zones during scheduled occupied events when
no occupants are present. This automatic energy-saving feature reduces
overall operating costs and accelerates return on investment.
With exceptional system performance rivalling more costly and complex
programmable automation systems, the SEZ7000 can be installed at a
fraction of the total cost of a comparable system. System installation,
setup, and commissioning have been simplified by eliminating the need
for additional external commissioning equipment or tools. All required
testing and configuration including addressing and zone-weighting is
accomplished using the easy-to-read LCD interface provided on
all controllers.
Moreover, since no other programming tools are required, mechanical
service technicians can quickly and easily install and service the system
without costly support.
The SEZ7000 offers unparalleled flexibility through the use of the open
BACnet communication protocol. The system can also be complemented
with your choice of BACnet controllers or graphical workstation software.
BACnet object mapping can also be accomplished seamlessly without the
need for any complex programming tools.
levels,
2
2

Schneider Electric | SDS-SE Z7000BZONE- EN.A4.08.2015.v2 August 2015
SEZ7000 BACnet Zoning System
Typical application
Fresh air
measurement station
3
Outdoor
air sensor
SEZ7656E1000B
ZigBee® Wireless
Optional wireless communication
BACnet MS/TP
Wired communication protocol
Return air sensor
Optional
supervisory
system
Control Board
Bypass
damper
Static pressure
sensor
Supply air sensor
SEZ7260F5000B
CO2
sensor
CO2
sensor
Damper control
(All Zones)
PI modulating
0-10Vdc actuator
TYPICAL INTERNAL ZONE
Reheat control
PI time proportioning
or 0-10Vdc hydronic
or electric reheat
1
TYPICAL DUCT REHEAT ZONE
2
SEZ7260F5000B
Reheat control
PI time proportioning
or 0-10Vdc hydronic
or electric reheat
TYPICAL PERIMETER REHEAT ZONE
SEZ7260F5000B
with PIR motion sensor
3

Schneider Electric | SDS-SE Z7000BZONE- EN.A4.08.2015.v2 August 2015
SEZ7000 BACnet Commercial Zoning System
By installing the zoning system in your building, energy required to render the space comfortable will be used more efficiently
when compared to buildings using conventional control systems. Operating costs will be reduced and an overall healthier work
and living environment will be achieved.
With LEED certification becoming more prevalent in today’s new and existing commercial buildings, the BACnet zoning system
now offers the added advantage of bringing your building one step closer to attaining the credits required for LEED certification.
The BACnet zoning system can help in attaining indoor environmental quality credits when used in conjunction with CO2 sensors
and a fresh air measurement device. The IAQ controller can monitor indoor air quality, provide C02 demand-based ventilation,
and fresh air measurement and control. It also offers embedded free cooling economiser control, ensuring that cooling energy
efficiency is optimised.
When used with central scheduling functions, the optional PIR motion sensor with occupancy logic based on actual occupancy
detection can also help attain HVAC energy-efficiency LEED credits.
The zoning system allows building owners to maintain a healthy environment for their occupants as well as maximise the overall
environmental and economic performance of
their buildings.
4
SEZ7000 Specifications
Specifications
Dimensions
12.5cm/4.9in (H) x 8.6cm/3.38in (W) x 2.9cm/1in (D)
Power Requirements
19-30 VAC 50 or 60 Hz; 2 VA Class 2
Operating Conditions
0 °C - 50 °C ( 32 °F - 122 °F )
0% - 95% R.H. non-condensing
Storage Conditions
-30 °C - 50 °C ( -22 °F - 122 °F )
0% - 95% R.H. non-condensing
Temperature Sensor
Local 10 K NTC thermistor
Temperature Sensor Resolution
± 0.1 °C ( ± 0.2 °F )
Temperature Control Accuracy
±0.5 ° C ( ± 0.9 °F ) @ 21 °C ( 70 °F ) typical
calibrated
Contact Output Rating
Relay outputs: 30 VAC, 1 Amp. Maximum, 3 Amp.
In-rush.
0 to 10 VDC into 2 KΩ resistance min.
12.0 to 37.5 °C ( 54 to 100 °F )
Occ, Stand-By and Unocc Cooling
Setpoint Range
12.0 to 37.5 °C ( 54 to 100 °F )
Occ, Stand-By and Unocc Heating
Setpoint Range
4.5 °C to 32 °C ( 40 °F to 90 °F )
Room and Outdoor Air Temperature
Display Range
-40 °C to 50 °C ( -40 °F to 122 °F )
Proportional Band for Room Temperature
control
Cooling & Heating: Default: 1.8°C ( 3.2°F )
Binary Inputs
Dry contact across terminal BI1,BI2 & UI3 to Scom
AI4 Analog Input
0 to 10 VDC into 10KΩ resistance min.
Wire Gauge
18 gauge maximum, 22 gauge recommended
Approximate Shipping Weight
0.75 lb (0.34 kg)
Agency Approvals All Models
UL: UL 873 (US) and CSA C22.2 No. 24 (Canada),
File E27734 with CCN XAPX (US) and XAPX7
(Canada)
Industry Canada: ICES-003 (Canada)
FCC: Compliant to CFR 47, Part 15, Subpart B (US)
CE: EMC Directive 89/336/EEC (Europe Union)
C-Tick: AS/NZS CISPR 22 Compliant (Australia /
New Zealand) Supplier Code Number N10696
Agency Approvals Wireless Models
FCC: Compliant to: Part 15, Subpart C
CE: R&RTTE Directive 1999/5/EC (Europe Union)
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC
RULES. OPERATION IS SUBJECT TO THE FOLLOWING
TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE
HARMFUL INTERFERENCE, AND (2) THIS DEVICE
MUST ACCEPT ANY INTERFERENCE RECEIVED,
INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.
Check with your
local government
for instruction on
disposal of these
products.

BACnet commercial zoning system
SEZ7260 Series ordering matrix
SEZ7260 45
PIR options:
-50 = PIR ready, but PIR cover not included
-55 = Factory assembled with PIR cover
5
Example:
SEZ7260F5545B
• Zoning system controller
• Analogue outputs
• Factory assembled PIR cover
• BACnet MS/TP communication
SEZ7656 Series ordering matrix
SEZ7656 1045
Example:
SEZ7656E1045B
• Zoning system controller
• 2H/2C IAQ application
• PIR ready
• ZigBee wireless communication
Control output type:
-C = Floating damper actuator
-F = Analog 0 - 10 VDC damper actuator
* Some part number configurations may not be available.
Please refer to the tables for available versions.
Communication options:
-E = 2H/2C IAQ applications
-F = 1H/2C modulating heat applications
-H = 3H/2C heat pump applications
-R = 2H /2C roof top aplications
* Some part number configurations may not be available.
Please refer to the tables for available versions.
Communication options:
-B = BACnet MS/ TP
-W = ZigBee wir eless
Communication options:
-B = BACnet MS/ TP
-W = ZigBee wir eless
Refer to the SE7000 Series - Product Comparison Guide for all available part numbers. The latest SE7000 Series - Product Comparison Guide is
available as a pdf document on the web at: http://schneider-electric.com/buildings.
Schneider Electric | SDS-SE Z7000BZONE- EN.A4.08.2015.v2 August 2015