Schneider Electric SEZ7000 Series Data Sheet

SEZ7000 Series
BACnet Commercial Zoning System
A cost-effective, scalable zoning system for the commercial market that delivers unparalleled flexibility via the open BAC­net® communication protocol.
SEZ7000 BACnet Commercial Zoning System Features
Introduction
The SEZ7000 BACnet® commercial zoning system is specifically designed to bring a simple scalable BACnet zoning system solution to the commercial mid-market without the cost associated with a typical DDC zoning system.
Our zoning system provides even more flexibility by offering additional functionality and new models covering more applications while still achieving excellent energy savings. The new central models include rooftop and heat pump units controlling analogue heat, CO and indoor air quality in conjunction with zoning controllers that provide floating and analogue damper control. The most unique feature of the zoning system is its scalability; a single central controller unit can support up to 63 individual zone controllers.
Zoning System
All zone controllers can be ordered with an on-board passive infrared (PIR) occupancy sensor cover that allows for advanced occupancy
AT A GLANCE
Custom design
Best in class system scalability
Provides DDC type control functionality and
accuracy
No external software tools required for
installation, commissioning or servicing with
embedded local HMI utility
ZigBee® communication protocol
Full line of models offer solutions for a wide
range of application
Control IAQ with any typical third-party wall
mounted C02 sensor
Controls and measures fresh air with any
third-party fresh air measurement station
Provides embedded free cooling economizer
loop
Built in Network-ready functionality
Options and accessories
PIR occupancy sensor
strategies. This enables the zone controllers to be able to provide even greater energy savings to zones during scheduled occupied events when no occupants are present. This automatic energy-saving feature reduces overall operating costs and accelerates return on investment.
With exceptional system performance rivalling more costly and complex programmable automation systems, the SEZ7000 can be installed at a fraction of the total cost of a comparable system. System installation, setup, and commissioning have been simplified by eliminating the need for additional external commissioning equipment or tools. All required testing and configuration including addressing and zone-weighting is accomplished using the easy-to-read LCD interface provided on all controllers.
Moreover, since no other programming tools are required, mechanical service technicians can quickly and easily install and service the system without costly support.
The SEZ7000 offers unparalleled flexibility through the use of the open BACnet communication protocol. The system can also be complemented with your choice of BACnet controllers or graphical workstation software. BACnet object mapping can also be accomplished seamlessly without the need for any complex programming tools.
levels,
2
2
SEZ7000 BACnet Zoning System
Airow direction
Return air
Supply air
Typical application
Fresh air measurement station
3
Outdoor
air sensor
SEZ7656E1000B
ZigBee® Wireless
Optional wireless communication
BACnet MS/TP
Wired communication protocol
Return air sensor
Optional supervisory system
Control Board
Bypass damper
Static pressure
sensor
Supply air sensor
SEZ7260F5000B
CO2
sensor
CO2
sensor
Damper control (All Zones) PI modulating 0-10Vdc actuator
TYPICAL INTERNAL ZONE
Reheat control PI time proportioning or 0-10Vdc hydronic or electric reheat
1
TYPICAL DUCT REHEAT ZONE
2
SEZ7260F5000B
Reheat control PI time proportioning or 0-10Vdc hydronic or electric reheat
TYPICAL PERIMETER REHEAT ZONE
SEZ7260F5000B
with PIR motion sensor
3
SEZ7000 BACnet Commercial Zoning System
By installing the zoning system in your building, energy required to render the space comfortable will be used more efficiently when compared to buildings using conventional control systems. Operating costs will be reduced and an overall healthier work and living environment will be achieved.
With LEED certification becoming more prevalent in today’s new and existing commercial buildings, the BACnet zoning system now offers the added advantage of bringing your building one step closer to attaining the credits required for LEED certification.
The BACnet zoning system can help in attaining indoor environmental quality credits when used in conjunction with CO2 sensors and a fresh air measurement device. The IAQ controller can monitor indoor air quality, provide C02 demand-based ventilation, and fresh air measurement and control. It also offers embedded free cooling economiser control, ensuring that cooling energy efficiency is optimised.
When used with central scheduling functions, the optional PIR motion sensor with occupancy logic based on actual occupancy detection can also help attain HVAC energy-efficiency LEED credits.
The zoning system allows building owners to maintain a healthy environment for their occupants as well as maximise the overall environmental and economic performance of their buildings.
4
SEZ7000 Specifications
Specifications
Dimensions
12.5cm/4.9in (H) x 8.6cm/3.38in (W) x 2.9cm/1in (D)
Power Requirements
19-30 VAC 50 or 60 Hz; 2 VA Class 2
Operating Conditions
0 °C - 50 °C ( 32 °F - 122 °F ) 0% - 95% R.H. non-condensing
Storage Conditions
-30 °C - 50 °C ( -22 °F - 122 °F ) 0% - 95% R.H. non-condensing
Temperature Sensor
Local 10 K NTC thermistor
Temperature Sensor Resolution
± 0.1 °C ( ± 0.2 °F )
Temperature Control Accuracy
±0.5 ° C ( ± 0.9 °F ) @ 21 °C ( 70 °F ) typical calibrated
Contact Output Rating
Relay outputs: 30 VAC, 1 Amp. Maximum, 3 Amp. In-rush.
0 to 10 VDC into 2 KΩ resistance min.
12.0 to 37.5 °C ( 54 to 100 °F )
Occ, Stand-By and Unocc Cooling Setpoint Range
12.0 to 37.5 °C ( 54 to 100 °F )
Occ, Stand-By and Unocc Heating Setpoint Range
4.5 °C to 32 °C ( 40 °F to 90 °F )
Room and Outdoor Air Temperature Display Range
-40 °C to 50 °C ( -40 °F to 122 °F )
Proportional Band for Room Temperature control
Cooling & Heating: Default: 1.8°C ( 3.2°F )
Binary Inputs
Dry contact across terminal BI1,BI2 & UI3 to Scom
AI4 Analog Input
0 to 10 VDC into 10KΩ resistance min.
Wire Gauge
18 gauge maximum, 22 gauge recommended
Approximate Shipping Weight
0.75 lb (0.34 kg)
Agency Approvals All Models
UL: UL 873 (US) and CSA C22.2 No. 24 (Canada),
File E27734 with CCN XAPX (US) and XAPX7 (Canada)
Industry Canada: ICES-003 (Canada) FCC: Compliant to CFR 47, Part 15, Subpart B (US) CE: EMC Directive 89/336/EEC (Europe Union) C-Tick: AS/NZS CISPR 22 Compliant (Australia /
New Zealand) Supplier Code Number N10696
Agency Approvals Wireless Models
FCC: Compliant to: Part 15, Subpart C CE: R&RTTE Directive 1999/5/EC (Europe Union)
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDE­SIRED OPERATION.
Check with your local government for instruction on disposal of these products.
BACnet commercial zoning system
SEZ7260 Series ordering matrix
SEZ7260 45
PIR options:
-50 = PIR ready, but PIR cover not included
-55 = Factory assembled with PIR cover
5
Example:
SEZ7260F5545B
Zoning system controller
Analogue outputs
Factory assembled PIR cover
BACnet MS/TP communication
SEZ7656 Series ordering matrix
SEZ7656 1045
Example:
SEZ7656E1045B
Zoning system controller
2H/2C IAQ application
PIR ready
ZigBee wireless communication
Control output type:
-C = Floating damper actuator
-F = Analog 0 - 10 VDC damper actuator
* Some part number configurations may not be available.
Please refer to the tables for available versions.
Communication options:
-E = 2H/2C IAQ applications
-F = 1H/2C modulating heat applications
-H = 3H/2C heat pump applications
-R = 2H /2C roof top aplications
* Some part number configurations may not be available.
Please refer to the tables for available versions.
Communication options:
-B = BACnet MS/ TP
-W = ZigBee wir eless
Communication options:
-B = BACnet MS/ TP
-W = ZigBee wir eless
Refer to the SE7000 Series - Product Comparison Guide for all available part numbers. The latest SE7000 Series - Product Comparison Guide is available as a pdf document on the web at: http://schneider-electric.com/buildings.
Schneider Electric | SDS-SE Z7000BZONE- EN.A4.08.2015.v2 August 2015