Schneider Electric SER7300 Series Installation Guide

SER7300 Series
Installation Guide for HVAC FCU Applications
CONTENTS
Installation 2
Location 2 Installation 2
Terminal, Identification and Function 3 Communication wiring to SC3xxxX Relay Pack 3
Network wiring topology 3
SC3xxx LED Operation 4 Wiring of local inputs to SER73xxA Room Controller 4 Configuring and Status Display Instructions 4
Status display 4
User Interface 6
Schneider Electric | II-SER7300 -A4.EN.12.2015.v2 December 2015
INSTALLATION
• Remove security screw on bottom of Room Controller cover.
Open unit by pulling on bottom side of Room Controller (Figure 1).
• Remove wiring terminals from sticker.
• Read FCC ID and IC label installed in the cover.
Location
1. Should not be installed on outside wall.
2. Must be installed away from any direct heat source.
3. Should not be installed near air discharge grill.
4. Should not be affected by direct sun radiation.
5. Nothing should restrict vertical air circulation to Room Controller.
Installation
1. Swing open Room Controller PCB to left by pressing PCB locking tabs (Figure 2).
2. Pull out cables 6” out from wall. Ensure wall surface is flat and clean.
4. Insert cable in central hole of base.
5. Align base and marklocation of two mounting holes on wall ensuring proper side of base is up.
6. Install anchors in wall.
7. Insert screws in mounting holes on each side of base (Figure 2).
8. Gently swing back circuit board on base and push until tabs lock.
9. Strip each wire 1/4 inch from end.
10. Insert each wire according to wiring diagram (next page).
11. Gently push excess wiring back into hole (Figure 3).
12. Re-Install wiring terminals in correct locations (Figure 3).
13. Re-install cover (top side first) and gently push extra wire length back into hole in wall.
14. Install security screw.
2
Figure-1 Ope ning the Cover
• If replacing an existing Line Voltage FCU Controller, label the wires before removal of the controller.
• Electronic controls are static sensitive devices. Discharge yourself properly before manipulating and installing the Room Controller.
• A short circuit or wrong wiring may permanently damage the Room Controller or the equipment.
• All SER7300 series controls are designed for use as operating controls only and are not safety devices. These instruments have undergone rigorous tests and verification prior to shipping to ensure proper and reliable operation in the field. Whenever a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the user / installer / electrical system designer to incorporate safety devices ( such as relays, flow switch, thermal protections, etc…) and/or an alarm system to protect the entire system against such catastrophic failures. Tampering with the devices or unintended application of the devices will result in a void of warranty.
Figure-2 Op ening the PCB
Figure-3 Terminal Block Reinstall
3
Schneider Electric | II-SER7300 -A4.EN.12.2015.v2 December 2015
TERMINAL, IDENTIFICATION AND FUNCTION
Terminal Identification
Terminal 3 Tx – Rx Communication
Terminal 4 Power Hot 7.0 VDC
Terminal 5 Power Common
Terminal 13 BI 1 ( Configurable )
Terminal 14 Scom
Terminal 15 BI 2 ( Configurable )
All SER73XXA5X45(X) Room Controller
COMMUNICATION WIRING TO SC3XXXX RELAY PACK
Only ONE SC3xxxX Relay Pack with remote monitoring inputs can be used under a single SER73xxA Controller. All other slave units must be SC3xxxX Relay Pack(s) WITHOUT remote inputs. A maximum of 10 SC3xxxX Relay Packs can be used for a single SER73xxA Room Controller.
From the SER73xxA to the first SC3xxxX Relay Pack
• Uses existing or new field wires
• A minimum of 3 wires are required 14-22 Ga Solid or Stranded. Shield not necessary.
From the first SC3xxxX to all other slave SC3xxxX Relay Pack(s)
• Uses existing or new field wires
• A minimum of 2 wires are required 14-22 Ga Solid or Stranded. Shield not necessary.
• Connect only wires #1 Power Common and #2 Tx/Rx Communication
Network Wiring Topology
Loading...
+ 4 hidden pages