Appendix C - Controllers’ Occupancy Sequence of Operation Schematic 13
Appendix D - Wireless door & window switch 14
Appendix E - Terminal Correnspondance 15
Schneider Electric | AG-SE8600-RTUIAQ-A4.EN.10.2016.v4November 2016
OVERVIEW
SE8600
The SE8600 Rooftop and Indoor Air Quality Controller is a new, cost-effective solution for upgrading rooftop unit thermostats.
This solution allows existing wiring between the rooftop unit and the temperature controller to be re-used, reducing overall
costs and installation time. The SE8600 can also add new features like CO
a rooftop unit.
The SE8600 Rooftop and Indoor Air Quality Controller can be configured to handle a broad variety of applications covering all
the standard implementations necessary for rooftop HVAC systems.
In addition to controlling heating, cooling and air quality, depending on the model and accessories, the SE8600 can handle
wireless networking and switches, Passive Infrared (PIR) occupancy detection using either onboard or remote sensors, and can
have custom programs implemented to fulfill specific user requirements.
The applications described here cover all these features, and in combination with the SE8600’s advanced scheduling and
occupancy controls can provide the functionality for any required rooftop HVAC implementation.
and fresh air monitoring to the existing functions of
2
3
SE8600 ROOFTOP UNIT AND INDOOR AIR QUALITY ROOM CONTROLLERS
Commercial and Hospitality Interface (Local Override and Degrees C/F Selection)
Power
ZigBee Pro Module for SE(R)8000 Series
Power
Part NumberDescriptionPIR SensorCommunication
U0BXX
SE8600
SE8600U5BXX
Part NumberDescription
VCM8000V5045POptional ZigBee® Pro module for SE8000 Series room controllers.
Schneider Electric | AG-SE8600-RTUIAQ-A4.EN.10.2016.v4November 2016
Cooling coil Fan Heating coil
Return air
Supply air
Filter
SE8600UXBXX 2 HEATING / 2 COOLING FOR ROOFTOP UNIT AND INDOOR AIR QUALITY
Fresh air
measurement station
Outside air sensor
Outside air
Control Board
DPS
Supply air sensor
CO2 air sensor
ZigBee® Pro
Optional wireless communication
Configuration
Parameter Name
BACnet MS/TP
Wired communication protocol
Configuration Settings
UI17Filter
UI19CO2
Econo. CongOn
FA RangeSet Max CFM, cannot be zero
Min fresh airSet Min CFM, cannot be zero
Max fresh airSet Max CFM, cannot be zero
Min CO2Set Min CO2, cannot be zero
Max CO2Set Max CO2, cannot be zero
Note: Only required conguration parameters are listed. Other settings are congurable as needed by user.
Schneider Electric | AG-SE8600-RTUIAQ-A4.EN.10.2016.v4November 2016
SE8600
5
BO 1 - Aux
RC (24 Vac)
C (Common)
BO 4 - G
BO 2 - Y2
BO 3 - Y1
1 2 3 4 5 6
13 14 15 16 17 18
RH
BO 8 - W1
UO 9 - W2
UO 10 - Econo
- Heat
UO 11
UO 12
7 8 9 10 11 12
19 20 21 22 23 24
ECONO
W2 W1 C R G Y1 Y2
C R
CO2
TRANSMITTER
(0-10 VDC)
OUT
COUT
R
MEASURING STATION
FILTER
DPS
AIR FLOW
(0-10 VDC)
SAT
SENSOR
OAT
SENSOR
UI 19 - CO2
UI 20 - RS
Common
UI 22 - SS
UI 23 - OS
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those dened by occupied cooling and heating.
UI 24 - Airow
Options
•Wireless adapter modules for BACnet models are available. (see
Appendix B for network wiring).
•3 universal inputs can be used and congured for advanced
Stand-by Mode (only available when PIR motion detector
functionality as required by the application.
sensor is used)
Setpoints revert to those dened by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those dened by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime”
parameter.
In all Occupancy Modes
If room relative humidity is higher than the user-dened Dehumidication setpoint, both Dehumidication, UO12 and Fan BO4, outputs are
energized to reach the setpoint and the Room Controller Cooling and Heating outputs will not trigger. If room relative humidity is higher than the
dehumidication set point + hysteresis, the Room Controller will energize dehumidication terminal UO12, BO8 and the cooling terminal BO3.
During the dehumidication cycle, the Room Controller modulates heating output UO11 to maintain the room temperature set point.
*A multi-pole relay may be required to activate Cooling and Heating stage(s).
6
Schneider Electric | AG-SE8600-RTUIAQ-A4.EN.10.2016.v4November 2016
Airflow direction
Return air
Supply air
Cooling coil Fan Heating coil
SE8600UXBXX 2 COOLING / MODULATING HEAT FOR ROOFTOP UNIT AND INDOOR AIR QUALITY
Optional economizer
damper control output
Outdoor
air sensor
DPS
Control Board
ZigBee® Pro
Optional wireless communication
BACnet MS/TP
Wired communication protocol
Configuration
Parameter Name
UI17Filter
UI19CO2
Econo. CongOn
FA RangeSet Max CFM, cannot be zero
Min fresh airSet Min CFM, cannot be zero
Max fresh airSet Max CFM, cannot be zero
Min CO2Set Min CO2, cannot be zero
Max CO2Set Max CO2, cannot be zero
Note: Only required conguration parameters are listed. Other settings are congurable as needed by user.
Configuration Settings
Supply air sensor
Schneider Electric | AG-SE8600-RTUIAQ-A4.EN.10.2016.v4November 2016
SE8600
7
BO 1 - Aux
RC (24 Vac)
C (Common)
BO 4 - G
BO 2 - Y2
BO 3 - Y1
1 2 3 4 5 6
13 14 15 16 17 18
UO 10 - Econo
UO 12
UO 11 - Heat
RH
BO 8 - W1
UO 9 - W2
7 8 9 10 11 12
19 20 21 22 23 24
Mod. Heat
(0-10 VDC)
ECONO
C R G Y1 Y2
C R
CO2
TRANSMITTER
(0-10 VDC)
OUT
COUT
R
MEASURING STATION
FILTER
DPS
AIR FLOW
(0-10 VDC)
SAT
SENSOR
OAT
SENSOR
UI 19 - CO2
UI 20 - RS
Common
UI 22 - SS
UI 23 - OS
BACnet +
BACnet -
BACnet REF
UI 16
UI 17
Common
Sequence of Operation and Wiring
Occupied Mode
Setpoints revert to those dened by occupied cooling and heating.
UI 24 - Airow
Options
•Wireless adapter modules for BACnet models are available. (see
Appendix B for network wiring).
•3 universal inputs can be used and congured for advanced
Stand-by Mode (only available when PIR motion detector
functionality as required by the application.
sensor is used)
Setpoints revert to those dened by stand-by cooling and heating.
Unoccupied Mode
Setpoints revert to those dened by unoccupied heating and cooling.
Occupied Override Mode
System reverts to occupied mode for duration determined by “ToccTime”
parameter.
In all Occupancy Modes
If room relative humidity is higher than the user-dened Dehumidication setpoint, both Dehumidication, UO12 and Fan BO4, outputs are
energized to reach the setpoint and the Room Controller Cooling and Heating outputs will not trigger. If room relative humidity is higher than the
dehumidication set point + hysteresis, the Room Controller will energize dehumidication terminal UO12, BO8 and the cooling terminal BO3.
During the dehumidication cycle, the Room Controller modulates heating output UO11 to maintain the room temperature set point.
*A multi-pole relay may be required to activate Cooling and Heating stage(s).
8
Schneider Electric | AG-SE8600-RTUIAQ-A4.EN.10.2016.v4November 2016
Cooling coil Fan Heating coil
Return air
Supply air
FRESH AIR DAMPER CONTROL SEQUENCES
The fresh air damper can be controlled through more than one sequence to achieve different control strategies such as free cooling (economizer
mode), minimum fresh air control and CO2 level control. Here are the control sequences available:
Note: For the sequences mentioned below, the following conditions must be met in order for the sequences to be performed as stated:
•Max Pos parameter value must be greater than Min Pos Parameter value.
•Mac CO2 parameter value must be greater than Min CO2 Parameter value.
•Max FA parameter value must be greater than Min FA Parameter value.
Outside air sensor
Outside air
Control Board
Supply air sensor
ZigBee® Pro
BACnet MS/TP
Wired communication protocol
Optional wireless communication
Economizer Control Mode Only
If the fresh air damper is to be used only for free cooling purposes (economizer mode, without fresh air measurement station or CO2 control), only
the Min Pos parameter and the free cooling sequence will be active.
•The FA Range parameter should be set to 0 CFM. (Default Value = 0 CFM)
•Set the Chngstpt parameter to desired value which free cooling is enabled. (Default Value = 55°F)
If the outside air temperature is greater than the changeover setpoint, then normal mechanical cooling will be used. If the outside air temperature is
less than or equal to the changeover setpoint, then free cooling will be enabled and mechanical cooling stages will be locked out.
Schneider Electric | AG-SE8600-RTUIAQ-A4.EN.10.2016.v4November 2016
measurement station
Cooling coil Fan Heating coil
Return air
Supply air
Outside air sensor
Outside air
9
Fresh air
Control Board
Supply air sensor
ZigBee® Pro
BACnet MS/TP
Wired communication protocol
Optional wireless communication
Economizer Control Mode and Fresh Air Measurement Station
If the fresh air damper is to be used for both free cooling and minimum fresh air volume control (economizer mode and fresh air measurement
station, but without CO2 level control), only the Min FA parameter and the free cooling sequence will be active.
•The FA Range parameter should be set to a value higher than 0 CFM (0 CFM disables the fresh air control).
•Min FA (minimum fresh air) parameter should be set to the desired level.
The FA Range parameter value should be set to the maximum capacity of the fresh air measurement station. Therefore the relationship between air
volumes and input signals can be established. For example, if the fresh air station capacity is 10000 CFM, set FA Range to 10000.
This will set the relationship of 0 VDC = 0 CFM and 10VDC = 10000 CFM.
10
Schneider Electric | AG-SE8600-RTUIAQ-A4.EN.10.2016.v4November 2016
Cooling coil Fan Heating coil
Return air
Supply air
Current Fresh Setpoint
Outside air sensor
Outside air
CO2 air sensor
BACnet MS/TP
Wired communication protocol
Control Board
Supply air sensor
ZigBee® Pro
Optional wireless communication
Economizer Control Mode and CO2 Level Control
If the fresh air damper is to be used for both free cooling and CO2 level control (economizer mode and CO2 level control, but without fresh air
measurement station), only the Min Pos, Max Pos, Min CO2 and Max CO2 parameters as well as the free cooling sequence will be active.
•The FA Range parameter should be set to 0 CFM.
•Set AI1 parameter to CO2 (0 VDC = 0ppm ; 10VDC = 2000ppm)
•Min Pos, Max Pos, Min CO2 and Max CO2 parameters should be set according to the required setting.
The highest value between free cooling demand output and interpolation output for the fresh air setpoint will be the output to the fresh air damper.
Max FA
Setpoint
Min FA
Setpoint
Min CO
Current CO2 Level
2
Max CO
2
Schneider Electric | AG-SE8600-RTUIAQ-A4.EN.10.2016.v4November 2016
measurement station
Cooling coil Fan Heating coil
Return air
Supply air
Current Fresh Setpoint
Outside air sensor
Outside air
Fresh air
CO2 air sensor
BACnet MS/TP
Wired communication protocol
11
Control Board
Supply air sensor
ZigBee® Pro
Optional wireless communication
Economizer Control Mode, CO2 Level Control and Fresh Air Measurement Station
If the fresh air damper is to be used for both free cooling and CO2 level control with a fresh air measurement station, only the Min
FA, Max FA, Min CO2 and Max CO2 parameters as well as the free cooling sequence will be active.
•The FA Range parameter should be set to something other than 0 CFM.
•Use an air ow transmitter to read fresh air level with AI2 input (0-5 VDC input)
•Min FA, Max FA, Min CO2 and Max CO2 parameters should be set according to the required setting.
The highest value between free cooling demand output and interpolation output for the fresh air setpoint based on the CO2 level
will be the output to the fresh air damper.
Max FA
Setpoint
Min FA
Setpoint
Min CO
Current CO2 Level
2
Max CO
2
12
Schneider Electric | AG-SE8600-RTUIAQ-A4.EN.10.2016.v4November 2016
Typical PIR Lens Detection Pattern
Typical detection pattern for the PIR cover is illustrated below.
O
140
Side view
O
60
O
25
O
25
15
15
O
O
(6 m)(5 m)(4 m)
O
15
Top view
O
15
13 ft20 ft16 ft13 ft
20 ft16 ft
(6 m)(5 m)(4 m)
Fresnel lens beam and detection field
Forward movement
140
Lateral movement
O
20 ft (6 m)
20 ft (6 m)
20 ft (6 m)
Top view
Schneider Electric | AG-SE8600-RTUIAQ-A4.EN.10.2016.v4November 2016
Deployment
It is recommended to install the Room Controller as close to a door as possible (but not so as to be blocked by the door), or in an
area with high occupant movement.
Ideally the Room Controller should be installed 5 feet (1.5 meters) above the floor surface to ensure maximum detection range is
achieved. As well, Room Controller placement should ensure the occupant crosses the lens beam in a perpendicular path within
the prescribed detection zone.
Example of Recommended Deployment
The below shows Room Controllers installed in ideal locations for two rooms.
The examination room shows one Room Controller installed adjacent to the door. In this area of the room, occupant traffic is high
and ensures the occupant will almost always cross the PIR detection path laterally and within the detection range.
The waiting room shows one Room Controller installed beside a door in the middle of the room. As shown in the diagram below,
occupant traffic is high in several areas of the room including the entrance, waiting room, access to the door and activity around
the
reception desk. Moreover, for each case aforementioned, occupant movement almost always moves lateral to the PIR, which
ensures detection by the PIR, as well as respecting the PIR detection range of 20 feet (6 meters) at 140°, and 16 feet (5 meters)
between 15° to 30° laterally.
13
Recommended Installation
14
Schneider Electric | AG-SE8600-RTUIAQ-A4.EN.10.2016.v4November 2016
Example of Non-Recommended Deployment
The below shows four Room Controllers (two for each room) installed in non-ideal locations for the two rooms.
The examination room shows one Room Controller installed in a low traffic area near the door, and a second Room Controller
installed on the wall directly opposite the door. For the Room Controller installed in the corner wall near the door, the PIR could be
blocked by the opened door, thereby restricting PIR detection. For the second Room Controller installed opposite the door, the
PIR detection could fall outside the specified detection zone, while at the same time most occupant movement may not respect
lateral crossing patterns for PIR detection.
The waiting room shows one Room Controller installed near the entrance, and a second Room Controller installed beside the
reception area. For the Room Controller installed at the entrance, the opening/closing of the door creates high probability the PIR
would get blocked, and therefore, occupancy going undetected. For the Room Controller installed beside the reception area, occupant traffic could fall outside the detection zone, while the receptionist would often be below the 5 foot recommended installation height for the Room Controller.
Non-Recommended Installation
Schneider Electric | AG-SE8600-RTUIAQ-A4.EN.10.2016.v4November 2016
APPENDIX B - OPTIONAL NETWORK SET-UP
Setpoints
e
Stand-by timer reset
Unoccupied timer reset
15
BACnet communication wiring
BACnet
thermostat
1
BACnet
thermostat
2
BACnet
thermostat
3
re
re
re
+
-
f
+
-
f
+
-
f
Notes:
• Wiring should be daisy chained
• Respect polarity
• If using 2 conductors shielded wires, connect the shield
of each feed together on the back of the controller. ONLY
ground the shield at one location. DO NOT connect the
shield to the ref terminal.
Wireless Communication
No communication wires required
APPENDIX C - CONTROLLERS’ OCCUPANCY SEQUENCE OF OPERATION SCHEMATIC
26.5°C
Unoccupied cool
Stand-by cool
Occupied cool
Occupied heat
Stand-by heat
noccupied heat
Deadband
Movement detected
-
24.5°C
76°F
22°C
72°F
70°F
21°C21°C
Stand-by
time
Into Stand-by mode
-
Deadband
66°F
19°C
Unoccupied
time
Into Unoccupied
mode
80°F
Deadband
62°F
16.5°C
Next movement
22°C
72°F
70°F
detected
Tim
16
Schneider Electric | AG-SE8600-RTUIAQ-A4.EN.10.2016.v4November 2016
APPENDIX D - WIRELESS SENSORS
Wireless ZigBee Pro Motion Sensors
Rooftop Unit and Indoor Air Quality Controllers with ZigBee Pro wireless sensors can be used in stand-alone mode, or with
integration to a central management system, to allow for advanced functions such as central reservation and occupancy functions.
Up to ten different ZigBee motion sensors and switches (SED-WMS, SED-CMS, or SED-WDS) can be used with a SE8600 Room
Controller.
No tools are required for commissioning or servicing the ZigBee devices. A simple interface on the devices with an on-board LED
and hidden switch provides all required functions for local interaction. The SE8600 user interface has screens used to pair and
congure ZigBee devices (SED-WMS, SED-CMS, or SED-WDS only). Local information for battery life and connectivity (heartbeat)
are also displayed through the ZigBee Pro wireless network.
MODEL SELECTION
Window SwitchDoor Switch
Door/window switchSED-WDS-P-5045
Wall mounted
motion sensor
Ceiling mounted
motion sensor
SED-WMS-P-5045
SED-CMS-P-5045
17
Schneider Electric | AG-SE8600-RTUIAQ-A4.EN.10.2016.v4November 2016
SED-CMS
LED
SED-WMS
Hidden switch
LED
LED
SED-WIN
SED-DOR
SED-WDS
LED
Hidden switchHidden switch
Hidden switch
APPENDIX E: TERMINAL CORRESPONDENCE
The terminals of an SE8600 are identied differently and have a wider range of possible functions compared to those of any of
the SE7000 series Room Controllers. Nonetheless, there is a direct correspondence of functions between the terminals of the
SE7000 series and the SE8600 series. Consult the table below to verify the appropriate terminal when replacing a SE7000 Room
Controller with a SE8600 Room Controller.
SE7000SE8600
Terminal nameTerminal IDTerminal nameTerminal ID
Binary Input 1BI1Universal Input 16UI16
Binary Input 2BI2Universal Input 17UI17
Universal Input 3UI3Universal Input 19UI19
Sensor CommonScomTerminal 18 CommonCOM
Remote SensorRSUniversal Input 20UI20 - RS
Sensor CommonScomTerminal 21 CommonCOM
Mix/Supply SensorMSUniversal Input 22UI22 - SS
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.