BACnet Integration for SE8000 Series Room Controller
Version 4
BACnet
CONTROLLER
Schneider Electric | IG-SE8000-BNET-A4.EN.07.2016.v4 July 2016
|
2
Table of Contents
SE8000 BACnet Compatibility Specications 3
Object Properties 4-8
Analog Objects
Binary Objects
Multi-state Objects
CSV / PG Objects
CAL / SCH Object Properties
Common SE8000 & SER8000 Series 9-14
AI / AO / AV Property Value Ranges
CSV Property Value Ranges
BV / MSI Property Value Ranges
MV Property Value Ranges
SE8600 Series 15-18
AI / AO / AV Property Value Ranges
BI/BO Property Value Ranges
BV / CVS / MSI Property Value Ranges
MV Property Value Ranges
SE8300 Series 19-21
AI / BO / MV Property Value Ranges
AO / AV / BI / BO / BV Property Value Ranges
MV Property Value Ranges
SER8300 Series 22-23
Technical Support 24
Schneider Electric | IG-SE8000-BNET-A4.EN.07.2016.v4 July 2016
| 3
SE8000 Series BACnet Compatibility Specifications
Note: This document contains BACnet compatibility specifications of the Schneider Electric SE8300, SER8300, and SE8600 Series Room Controllers
and follows the BACnet PICS format. Objects common to all three models appear in one table, where are objects which are model specific appear in
separate tables.
Supported BACnet® Services: The BACnet® communicating controller meets all requirements for designation as an Application Specific Controller
(B-ASC). The BACnet controller supports the following BACnet Interoperability Building Blocks (BIBBs).
Application ServiceDesignation
Data Sharing-COV-BDS-COV-B
Data Sharing – Read Property - BDS-RP-B
Data Sharing – Read Property Multiple - BDS-RPM-B
Data Sharing – Write Property - BDS-WP-B
Data Sharing - Write Property Multiple Service - B DS-WPM-B
Device Management - Time Synchronization - BDM-TS-B
Device Management - Device Communication Control - BDM-DCC-B
Note: The controller does not support segmented requests or responses
Object NameType and InstanceObject PropertyController Parameter
SE8X00UXBXXDevice
Object_Identifier
Property 75 (R,W)
Object_Name
Property 77 (R,W)
Model Name
Property 70 (R)
Firmware Revision
Property 44 (R)
Protocol Version
Property 98 (R)
Protocol Revision
Property 139 (R)
Max ADPU Length
Property 62 (R)
ADPU Timeout
Property 10 (R)
Application-Software-Version
Property 12 (R)
Max_Master (R,W)
Unique ID number of a device on a network
Unique name of a device on a network
Controller model number
Current BACnet
Current BACnet
Default is Version 1
Current BACnet® firmware protocol revision
Default is Version 2
Maximum ADPU Length accepted
Default is 480
ADPU timeout value
Default is 3000 ms
Controller base application software version
Default is based on current released version
Maximum master devices allowed to be part of network.
0 to 127, default is 127
®
firmware revision used by controller
®
firmware protocol version
Description
Property 28 (R,W)
Location
Property 58 (R,W)
Local Date
Property 56 (R)
Local Time
Property 57 (R)
String of printable characters
(Same as “Long Screen Message” CSV2)
String of printable characters
(Same as “Short Screen Message” CSV1)
Indicates date to best of device knowledge
Indicated time of day best of the device knowledge
Schneider Electric | IG-SE8000-BNET-A4.EN.07.2016.v4 July 2016
|
4
Object Properties
Analog Objects
Object Type Read/Write Settings
Input AIOutput AOValues AV
Read OnlyRead OnlyRead Only
Read OnlyRead OnlyRead Only
Read OnlyRead OnlyRead Only
Read OnlyRead OnlyRead Only
Read / WriteRead / Write Read / Write
Read / Write* Read / Write Read / Write
N/ARead OnlyRead Only
Read OnlyRead OnlyRead Only
N/ARead OnlyRead / Write
Object PropertyController Parameter
Event State
Property 36
Object Identifier
Property 75
Object Name
Property 77
Object Type
Property 79
Out of Service
Property 81
Present Value
Property 85
Priority Array
Property 87
Reliability
Property 103
Relinquish Default
†
Property 104
Indicates if object has an active event state associated with it
Unique ID number of an object on a network
Unique name of an object on a network
Indicates membership in a particular object type class
Indicates whether (TRUE/FALSE) the physical input object represents is not in
service
Contains values of all properties specified
Read-only array of prioritized values
Indicates if Present_Value is "reliable"
Default value used for Present_Value when values in Priority_Array have a
NULL value
Read OnlyRead OnlyRead Only
Read OnlyRead OnlyRead Only
N/ARead OnlyN/A
N/ARead OnlyN/A
N/A = Not Applicable, property not used for objects of that type
* The Present_Value is only writeable when Out_Of_Service is TRUE.
† Relinquish default is Read Only for AV100+
Status Flags
Property 111
Units
Property 177
Hight Limit
Property 1101
Low Limit
Property 1100
Represents flags that indicate general health of life safety point object
Indicates measurement units of Present_Value
Specifies a limit Present_Value must exceed before an event is generated
Specifies a limit Present_Value must fall below before an event is generated
Schneider Electric | IG-SE8000-BNET-A4.EN.07.2016.v4 July 2016
Binary Objects
| 5
Object Type Read/Write Settings
Input BIOutput BOValues BV
Read OnlyRead OnlyRead Only
Read OnlyRead OnlyRead Only
Read OnlyRead OnlyRead Only
Read OnlyRead OnlyRead Only
Read OnlyRead OnlyRead Only
Read OnlyRead OnlyRead Only
Read / WriteRead / Write Read / Write
Read OnlyRead / Write N/A
Read / WriteRead / Write Read / Write
Object PropertyController Parameter
Active Text
Property 4
Event State
Property 36
Inactive Text
Property 46
Object Identifier
Property 75
Object Name
Property 77
Object Type
Property 79
Out of Service
Property 81
Polarity
Property 84
Present Value
Property 85
Characterizes intended effect of the ACTIVE state of Present_Value property
Indicates if object has an active event state associated with it
Characterizes intended effect of INACTIVE state of Present_Value property
Unique ID number of an object on a network
Unique name of an object on a network
Indicates membership in a particular object type class
Indicates whether (TRUE/FALSE) physical input object represents is not in
service
Indicates relationship between physical state of input and Present_Value
Contains values of all properties specified
Read OnlyRead OnlyRead Only
N/ARead Only Read Only
Read OnlyRead OnlyRead Only
N/A = Not Applicable, property not used for objects of that type
Priority Array
Property 87
Relinquish Default
Property 104
Status Flags
Property 111
Read-only array of prioritized values
Default value to be used for Present Value when values in Priority_Array have a
NULL value
Represents flags that indicate general health of life safety point object
Schneider Electric | IG-SE8000-BNET-A4.EN.07.2016.v4 July 2016
|
6
Multi-state Objects
Object Type Read/Write Settings
Input MSIValues MV
Read OnlyRead Only
Read OnlyRead Only
Read OnlyRead Only
Read OnlyRead Only
Read OnlyRead Only
Read / WriteRead / Write
Read / Write* Read / Write
N/ARead Only
N/ARead / Write
Object PropertyController Parameter
Event State
Property 36
Number of States
Property 74
Object Identifier
Property 75
Object Name
Property 77
Object Type
Property 79
Out of Service
Property 81
Present Value
Property 85
Priority Array
Property 87
Relinquish Default
Property 104
Indicates if object has an active event state associated with it
Defines number of states Present_Value may have
Unique ID number of an object on a network
Unique name of an object on a network
Indicates membership in a particular object type class
Indicates whether (TRUE/FALSE) physical input object represents is not in
service
Contains values of all properties specified
Indicates relationship between physical state of input and Present_Value
Default value used for Present_Value when values in Priority_Array have a
NULL value
Read OnlyRead Only
Read OnlyRead Only
N/A = Not Applicable, property not used for objects of that type
*The Present_Value is only writeable when Out_Of_Service is TRUE.
State Text
Property 110
Status Flags
Property 111
Represents descriptions of all possible states of Present_Value
Represents flags that indicate general health of life safety point object
Schneider Electric | IG-SE8000-BNET-A4.EN.07.2016.v4 July 2016
CSV Objects
Read/WriteObject PropertyController Parameter
| 7
Read Only
Read Only
Read Only
Read Only
Read / Write
Read Only
Event State
Property 36
Object Identifier
Property 75
Object Name
Property 77
Object Type
Property 79
Present Value
Property 85
Status Flags
Property 111
Indicates object has an active event state associated with it
Unique ID number of an object on a network
Unique name of an object on a network
Indicates membership in a particular object type class
Contains values of all properties specified
Represents flags that indicate general health of life safety point object
PG Objects
Read/WriteObject PropertyController Parameter
Read / Write
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Write Only
Read Only
Read Only
Read Only
Description
Property 28
Description Of Halt
Property 29
Instance Of
Property 48
Object Identifier
Property 75
Object Name
Property 77
Object Type
Property 79
Out Of Service
Property 81
Program Change
Property 90
Program State
Property 92
Reason For Halt
Property 100
Status Flags
Property 111
String of printable characters whose content is not restricted. Contains the LUA program
script (max size = 480 bytes)
Describes the reason why a program has been halted Text is also displayed in the HMI
debug log
Local name of the application program being executed by this process
Unique ID number of an object on a network
Unique name of an object on a network
Indicates membership in a particular object type class
Indicates whether (TRUE/FALSE) the process this object represents is not in service
Used to request changes to the operating state of the program. Writing to property affects
all 10 PG objects
Current logical state of all 10 PG objects executing application programs
If program halts, this property reflects the reason for halt for all 10 PG objects
Represents flags that indicate general health of life safety point object
Schneider Electric | IG-SE8000-BNET-A4.EN.07.2016.v4 July 2016
|
8
CAL Object Properties
Read/WriteObject PropertyController Parameter
Read / Write
Read Only
Read Only
Read Only
Read Only
Date List
Property 23
Object Identifier
Property 75
Object Name
Property 77
Object Type
Property 79
Present Value
Property 85
List of calender entries.
Unique ID number of an object on a network
Unique name of an object on a network
Indicates membership in a particular object type class
This property is TRUE when
current date matches an entry.
SCH Object Properties
Read/WriteObject PropertyController Parameter
Read Only
Read / Write
Read Only
Read Only
Read Only
Read / Write
Read / Write
Read Only
Read Only
Read / Write
Read Only
Effective Period
Property 32
Exception Schedule
Property 38
Object Identifier
Property 75
Object Name
Property 77
Object Type
Property 79
Present Value
Property 85
Out Of Service
Property 81
Reliability
Property 103
Status Flags
Property 111
Weekly Schedule
Property 123
Schedule Default
Property 174
Range of dates within which the Schedule object is active. All dates are in range, so always Effective
Sequence of schedule actions that takes precedence over normal behavior on a specific day or days.
By default, this property refers to the calendar.
Unique ID number of an object on a network
Unique name of an object on a network
Indicates membership in a particular object type class
Contains the current value of the schedule (0:unoccupied, 1:occupied)
Only writeable when Out Of Service is TRUE
Indicates whether (TRUE/FALSE) the internal calculations of the schedule object are used to determine the value of the Present Value property
Indicates if Present Value is "reliable"
Represents flags that indicate general health of life safety point object
7 elements that describe the sequence of schedule actions for each day of the week.
Default value to be used when no other scheduled value is in effect. Always Unoccupied
Loading...