Schneider Electric SE8000 Series Installation Guide

SE8000 Series BACnet Integration
BACnet Integration for SE8000 Series Room Controller
Version 4
BACnet
CONTROLLER
Schneider Electric | IG-SE8000-BNET-A4.EN.07.2016.v4 July 2016
|
2
Table of Contents
SE8000 BACnet Compatibility Specications 3
Object Properties 4-8
Analog Objects Binary Objects Multi-state Objects CSV / PG Objects CAL / SCH Object Properties
Common SE8000 & SER8000 Series 9-14
AI / AO / AV Property Value Ranges CSV Property Value Ranges BV / MSI Property Value Ranges MV Property Value Ranges
SE8600 Series 15-18
AI / AO / AV Property Value Ranges BI/BO Property Value Ranges BV / CVS / MSI Property Value Ranges MV Property Value Ranges
SE8300 Series 19-21
AI / BO / MV Property Value Ranges AO / AV / BI / BO / BV Property Value Ranges MV Property Value Ranges
SER8300 Series 22-23
Technical Support 24
Schneider Electric | IG-SE8000-BNET-A4.EN.07.2016.v4 July 2016
| 3
SE8000 Series BACnet Compatibility Specifications
Note: This document contains BACnet compatibility specifications of the Schneider Electric SE8300, SER8300, and SE8600 Series Room Controllers and follows the BACnet PICS format. Objects common to all three models appear in one table, where are objects which are model specific appear in separate tables.
Supported BACnet® Services: The BACnet® communicating controller meets all requirements for designation as an Application Specific Controller (B-ASC). The BACnet controller supports the following BACnet Interoperability Building Blocks (BIBBs).
Application Service Designation
Data Sharing-COV-B DS-COV-B
Data Sharing – Read Property - B DS-RP-B
Data Sharing – Read Property Multiple - B DS-RPM-B
Data Sharing – Write Property - B DS-WP-B
Data Sharing - Write Property Multiple Service - B DS-WPM-B
Device Management - Time Synchronization - B DM-TS-B
Device Management - Device Communication Control - B DM-DCC-B
Device Management – Dynamic Device Binding - B DM-DDB-B
Device Management – Dynamic Object Binding - B DM-DOB-B
Scheduling-Internal-B SCHED-I-B
Note: The controller does not support segmented requests or responses
Object Name Type and Instance Object Property Controller Parameter
SE8X00UXBXX Device
Object_Identifier Property 75 (R,W)
Object_Name Property 77 (R,W)
Model Name Property 70 (R)
Firmware Revision Property 44 (R)
Protocol Version Property 98 (R)
Protocol Revision Property 139 (R)
Max ADPU Length Property 62 (R)
ADPU Timeout Property 10 (R)
Application-Software-Version Property 12 (R)
Max_Master (R,W)
Unique ID number of a device on a network
Unique name of a device on a network
Controller model number
Current BACnet
Current BACnet Default is Version 1
Current BACnet® firmware protocol revision Default is Version 2
Maximum ADPU Length accepted Default is 480
ADPU timeout value Default is 3000 ms
Controller base application software version Default is based on current released version
Maximum master devices allowed to be part of network. 0 to 127, default is 127
®
firmware revision used by controller
®
firmware protocol version
Description Property 28 (R,W)
Location Property 58 (R,W)
Local Date Property 56 (R)
Local Time Property 57 (R)
String of printable characters (Same as “Long Screen Message” CSV2)
String of printable characters (Same as “Short Screen Message” CSV1)
Indicates date to best of device knowledge
Indicated time of day best of the device knowledge
Schneider Electric | IG-SE8000-BNET-A4.EN.07.2016.v4 July 2016
|
4
Object Properties
Analog Objects
Object Type Read/Write Settings
Input AI Output AO Values AV
Read Only Read Only Read Only
Read Only Read Only Read Only
Read Only Read Only Read Only
Read Only Read Only Read Only
Read / Write Read / Write Read / Write
Read / Write* Read / Write Read / Write
N/A Read Only Read Only
Read Only Read Only Read Only
N/A Read Only Read / Write
Object Property Controller Parameter
Event State Property 36
Object Identifier Property 75
Object Name Property 77
Object Type Property 79
Out of Service Property 81
Present Value Property 85
Priority Array Property 87
Reliability Property 103
Relinquish Default
Property 104
Indicates if object has an active event state associated with it
Unique ID number of an object on a network
Unique name of an object on a network
Indicates membership in a particular object type class
Indicates whether (TRUE/FALSE) the physical input object represents is not in service
Contains values of all properties specified
Read-only array of prioritized values
Indicates if Present_Value is "reliable"
Default value used for Present_Value when values in Priority_Array have a NULL value
Read Only Read Only Read Only
Read Only Read Only Read Only
N/A Read Only N/A
N/A Read Only N/A
N/A = Not Applicable, property not used for objects of that type * The Present_Value is only writeable when Out_Of_Service is TRUE. † Relinquish default is Read Only for AV100+
Status Flags Property 111
Units Property 177
Hight Limit Property 1101
Low Limit Property 1100
Represents flags that indicate general health of life safety point object
Indicates measurement units of Present_Value
Specifies a limit Present_Value must exceed before an event is generated
Specifies a limit Present_Value must fall below before an event is generated
Schneider Electric | IG-SE8000-BNET-A4.EN.07.2016.v4 July 2016
Binary Objects
| 5
Object Type Read/Write Settings
Input BI Output BO Values BV
Read Only Read Only Read Only
Read Only Read Only Read Only
Read Only Read Only Read Only
Read Only Read Only Read Only
Read Only Read Only Read Only
Read Only Read Only Read Only
Read / Write Read / Write Read / Write
Read Only Read / Write N/A
Read / Write Read / Write Read / Write
Object Property Controller Parameter
Active Text Property 4
Event State Property 36
Inactive Text Property 46
Object Identifier Property 75
Object Name Property 77
Object Type Property 79
Out of Service Property 81
Polarity Property 84
Present Value Property 85
Characterizes intended effect of the ACTIVE state of Present_Value property
Indicates if object has an active event state associated with it
Characterizes intended effect of INACTIVE state of Present_Value property
Unique ID number of an object on a network
Unique name of an object on a network
Indicates membership in a particular object type class
Indicates whether (TRUE/FALSE) physical input object represents is not in service
Indicates relationship between physical state of input and Present_Value
Contains values of all properties specified
Read Only Read Only Read Only
N/A Read Only Read Only
Read Only Read Only Read Only
N/A = Not Applicable, property not used for objects of that type
Priority Array Property 87
Relinquish Default Property 104
Status Flags Property 111
Read-only array of prioritized values
Default value to be used for Present Value when values in Priority_Array have a NULL value
Represents flags that indicate general health of life safety point object
Schneider Electric | IG-SE8000-BNET-A4.EN.07.2016.v4 July 2016
|
6
Multi-state Objects
Object Type Read/Write Settings
Input MSI Values MV
Read Only Read Only
Read Only Read Only
Read Only Read Only
Read Only Read Only
Read Only Read Only
Read / Write Read / Write
Read / Write* Read / Write
N/A Read Only
N/A Read / Write
Object Property Controller Parameter
Event State Property 36
Number of States Property 74
Object Identifier Property 75
Object Name Property 77
Object Type Property 79
Out of Service Property 81
Present Value Property 85
Priority Array Property 87
Relinquish Default Property 104
Indicates if object has an active event state associated with it
Defines number of states Present_Value may have
Unique ID number of an object on a network
Unique name of an object on a network
Indicates membership in a particular object type class
Indicates whether (TRUE/FALSE) physical input object represents is not in service
Contains values of all properties specified
Indicates relationship between physical state of input and Present_Value
Default value used for Present_Value when values in Priority_Array have a NULL value
Read Only Read Only
Read Only Read Only
N/A = Not Applicable, property not used for objects of that type *The Present_Value is only writeable when Out_Of_Service is TRUE.
State Text Property 110
Status Flags Property 111
Represents descriptions of all possible states of Present_Value
Represents flags that indicate general health of life safety point object
Schneider Electric | IG-SE8000-BNET-A4.EN.07.2016.v4 July 2016
CSV Objects
Read/Write Object Property Controller Parameter
| 7
Read Only
Read Only
Read Only
Read Only
Read / Write
Read Only
Event State Property 36
Object Identifier Property 75
Object Name Property 77
Object Type Property 79
Present Value Property 85
Status Flags Property 111
Indicates object has an active event state associated with it
Unique ID number of an object on a network
Unique name of an object on a network
Indicates membership in a particular object type class
Contains values of all properties specified
Represents flags that indicate general health of life safety point object
PG Objects
Read/Write Object Property Controller Parameter
Read / Write
Read Only
Read Only
Read Only
Read Only
Read Only
Read Only
Write Only
Read Only
Read Only
Read Only
Description Property 28
Description Of Halt Property 29
Instance Of Property 48
Object Identifier Property 75
Object Name Property 77
Object Type Property 79
Out Of Service Property 81
Program Change Property 90
Program State Property 92
Reason For Halt Property 100
Status Flags Property 111
String of printable characters whose content is not restricted. Contains the LUA program script (max size = 480 bytes)
Describes the reason why a program has been halted Text is also displayed in the HMI debug log
Local name of the application program being executed by this process
Unique ID number of an object on a network
Unique name of an object on a network
Indicates membership in a particular object type class
Indicates whether (TRUE/FALSE) the process this object represents is not in service
Used to request changes to the operating state of the program. Writing to property affects all 10 PG objects
Current logical state of all 10 PG objects executing application programs
If program halts, this property reflects the reason for halt for all 10 PG objects
Represents flags that indicate general health of life safety point object
Schneider Electric | IG-SE8000-BNET-A4.EN.07.2016.v4 July 2016
|
8
CAL Object Properties
Read/Write Object Property Controller Parameter
Read / Write
Read Only
Read Only
Read Only
Read Only
Date List Property 23
Object Identifier Property 75
Object Name Property 77
Object Type Property 79
Present Value Property 85
List of calender entries.
Unique ID number of an object on a network
Unique name of an object on a network
Indicates membership in a particular object type class
This property is TRUE when current date matches an entry.
SCH Object Properties
Read/Write Object Property Controller Parameter
Read Only
Read / Write
Read Only
Read Only
Read Only
Read / Write
Read / Write
Read Only
Read Only
Read / Write
Read Only
Effective Period Property 32
Exception Schedule Property 38
Object Identifier Property 75
Object Name Property 77
Object Type Property 79
Present Value Property 85
Out Of Service Property 81
Reliability Property 103
Status Flags Property 111
Weekly Schedule Property 123
Schedule Default Property 174
Range of dates within which the Schedule object is active. All dates are in range, so always Effective
Sequence of schedule actions that takes precedence over normal behavior on a specific day or days. By default, this property refers to the calendar.
Unique ID number of an object on a network
Unique name of an object on a network
Indicates membership in a particular object type class
Contains the current value of the schedule (0:unoccupied, 1:occupied) Only writeable when Out Of Service is TRUE
Indicates whether (TRUE/FALSE) the internal calculations of the schedule object are used to deter­mine the value of the Present Value property
Indicates if Present Value is "reliable"
Represents flags that indicate general health of life safety point object
7 elements that describe the sequence of schedule actions for each day of the week.
Default value to be used when no other scheduled value is in effect. Always Unoccupied