PIR Ready SE76xx Series
With & Without Scheduling Controllers
For Commercial HVAC Applications
CONTENTS
SE7600 Series Product Overview Protocol Implementation 2
Conformance Statements (PICS) 3
Device Object Table 3
Standard Object Types Supported 8
List of Proprietary Properties 8
Property Value Range Restrictions for AI and AV Objects 9
Property Enumeration Set for BI and BV Objects 10
List of Property Enumeration Set for MV Objects 12
Integration - Global commands 14
Integration - Graphic User Interface (GUI) Objects 15
Integration - Configuration Objects 15
Wiring Guide 16
Network Configuration 17
Default Device Name and ID 20
Integrating Schneider Devices on MS/TP Network 20
Tips and Things You Need to Know 21
Troubleshooting 22
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
Note 1: The controller does not support segmented requests or responses.
Note 2: Time synchronization can be made through a network even if the controller
does not support the full date. Therefore, the device cannot claim conformance to the
DeviceManagement – TimeSynchronization - B (DM-TS-B) service. The device object
does not have the Local_Time or Local_Date properties.
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
Schneider Electric
IG-SE7000-BNE TSE76XX-A4.EN.4.2013.v1 April 2013
OBJECTS TABLE
PIR Ready SE76xx SeriesBACnet® Integration Manual
3
Object Name
Type and
Instance
SE76xxX5x45BDevice
Object PropertyController Parameter
Object_Identifier
Property 75 (R,W)
Object_Name
Property 77 (R,W)
Model Name
Property 70 (R)
Firmware Revision
Property 44 (R)
Protocol Version
Property 98 (R)
Protocol Revision
Property 139 (R)
Max ADPU Length
Property 62 (R)
ADPU Timeout
Property 10 (R)
ApplicationSoftware-Version
Property 12 (R)
Unique ID number of a device on a network
Unique name of a Device on a network
Controller Model number
Current BACnet
®
firmware revision used by the
controller
Current BACnet
®
firmware protocol version
Default is Version 1
®
Current BACnet
firmware protocol revision
Default is Version 2
Maximum ADPU Length accepted
Default is 244
ADPU timeout value
Default is 60 000 ms
Controller base application software version
Default is based on current released version
Max_Master (R,W)
MS/TP_Address
Property 1001 (R,W)
MS/TP_Baud_Rate
Property 1002 (R,W)
Maximum master devices allowed to be part of the
network. 0 to 127, default is 127
®
BACnet
MS/TP MAC Address. Proprietary attribute.
Default is as assigned by configuration.
®
BACnet
MS/TP Baud-Rate.
Proprietary attribute.
Range is: 1 = 9.6 KBps, 2 = 19.2 KBps, 3 = 38.4
KBps, 4 = 76.8 KBps and 5 = Auto Baud Rate. Index
5 is Write only. Reading attribute will state current
Baud rate used. Writing index 1 to 4 will fix the Baud
rate to the desired value.
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
Control OutputGR 19Present_Value (R)√√√√√√√√√√√√√√√√
PI Heating DemandAV 20Present_Value (R)√√√√√√√√√√√√√√√√
PI Cooling DemandAV 21Present_Value (R)√√√√√√√√√√√√√√√√
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
Schneider Electric
IG-SE7000-BNE TSE76XX-A4.EN.4.2013.v1 April 2013
OBJECTS TABLE
PIR Ready SE76xx SeriesBACnet® Integration Manual
7
Object Name
Eff (Effective) Reset
Humidification RH Spt
(Setpoint)
Supply Heat Lockout
temperature
Humidification High
Limit Spt (Setpoint)
Supply PI Heat DemandAV 97Present_Value (R)√√√√
Low RH SetpointAV 98Present_Value (R,W)√√
Minimum Fresh AirAV 98Present_Value (R,W)√√
Low Temp Reset RH
Setpoint
Maximum Fresh AirAV 99Present_Value (R,W)√√
High Temp Reset RH
Setpoint
Minimum CO2 LevelAV 100Present_Value (R,W)√√
Humidifier OutputAV 101Present_Value (R)√√
Maximum CO2 LevelAV 101Present_Value (R,W)√√
Local ScheduleSCH 102Present_Value (R,W)√√√√√√√√
Type and
Instance
AV 96Present_Value (R)√√
AV 96Present_Value (R,W)√√√√
AV 97Present_Value (R,W)√√
AV 99Present_Value (R,W)√√
AV 100Present_Value (R,W)√√
Object Property
SE7600A5x45B
SE7652A5x45B
SE7600B5x45B
SE7652B5x45B
SE7605B5x45B
SE7656B5x45B
SE7607B5x45B
SE7657B5x45B
SE7600H5x45B
SE7652H5x45B
SE7600W5x45B
SE7652W5x45B
SE7606E5x45B
SE7656E5x45B
SE7600F5x45B
SE7652F5x45B