Schneider Electric SE76xx Series Installation Guide

BACnet® Integration Manual
BACnet® Integration Manual
PIR Ready SE76xx Series With & Without Scheduling Controllers For Commercial HVAC Applications
CONTENTS
SE7600 Series Product Overview Protocol Implementation 2 Conformance Statements (PICS) 3 Device Object Table 3 Standard Object Types Supported 8 List of Proprietary Properties 8 Property Value Range Restrictions for AI and AV Objects 9 Property Enumeration Set for BI and BV Objects 10 List of Property Enumeration Set for MV Objects 12 Integration - Global commands 14 Integration - Graphic User Interface (GUI) Objects 15 Integration - Configuration Objects 15 Wiring Guide 16 Network Configuration 17 Default Device Name and ID 20 Integrating Schneider Devices on MS/TP Network 20 Tips and Things You Need to Know 21 Troubleshooting 22
PIR Ready SE76xx SeriesBACnet® Integration Manual
© 2013 Schneider Electric. All rights reserved.
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
Schneider Electric
IG-SE7000-BNE TSE76XX-A4.EN.4.2013.v1 April 2013
PROTOCOL IMPLEMENTATION CONFORMANCE STATEMENT (PICS)
Vendor Name: Schneider Electric
Supported BACnet
meets all requirements for designation as an Application Specific Controller (B-ASC). The BACnet Interoperability Building Blocks (BIBBs).
Application Service Designation
®
Services: The BACnet® communicating controller
®
controller series supports the following BACnet®
2
Data Sharing – Read Property - B DS-RP-B
Data Sharing – Read Property Multiple - B DS-RPM-B
Data Sharing – Write Property - B DS-WP-B
Device Management - Device Communication Control - B DM-DCC-B
Device Management – Dynamic Device Binding - B DM-DDB-B
Device Management – Dynamic Object Binding - B DM-DOB-B
Note 1: The controller does not support segmented requests or responses.
Note 2: Time synchronization can be made through a network even if the controller does not support the full date. Therefore, the device cannot claim conformance to the DeviceManagement – TimeSynchronization - B (DM-TS-B) service. The device object does not have the Local_Time or Local_Date properties.
SE760 0 Series
© 2013 Schneider Electric. All rights reserved.
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
Schneider Electric
IG-SE7000-BNE TSE76XX-A4.EN.4.2013.v1 April 2013
OBJECTS TABLE
PIR Ready SE76xx SeriesBACnet® Integration Manual
3
Object Name
Type and
Instance
SE76xxX5x45B Device
Object Property Controller Parameter
Object_Identifier Property 75 (R,W)
Object_Name Property 77 (R,W)
Model Name Property 70 (R)
Firmware Revision Property 44 (R)
Protocol Version Property 98 (R)
Protocol Revision Property 139 (R)
Max ADPU Length Property 62 (R)
ADPU Timeout Property 10 (R)
Application­Software-Version
Property 12 (R)
Unique ID number of a device on a network
Unique name of a Device on a network
Controller Model number
Current BACnet
®
firmware revision used by the
controller
Current BACnet
®
firmware protocol version
Default is Version 1
®
Current BACnet
firmware protocol revision
Default is Version 2
Maximum ADPU Length accepted Default is 244
ADPU timeout value Default is 60 000 ms
Controller base application software version Default is based on current released version
Max_Master (R,W)
MS/TP_Address Property 1001 (R,W)
MS/TP_Baud_Rate Property 1002 (R,W)
Maximum master devices allowed to be part of the network. 0 to 127, default is 127
®
BACnet
MS/TP MAC Address. Proprietary attribute.
Default is as assigned by configuration.
®
BACnet
MS/TP Baud-Rate.
Proprietary attribute. Range is: 1 = 9.6 KBps, 2 = 19.2 KBps, 3 = 38.4
KBps, 4 = 76.8 KBps and 5 = Auto Baud Rate. Index 5 is Write only. Reading attribute will state current Baud rate used. Writing index 1 to 4 will fix the Baud rate to the desired value.
PIR Ready SE76xx SeriesBACnet® Integration Manual
© 2013 Schneider Electric. All rights reserved.
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
Schneider Electric
IG-SE7000-BNE TSE76XX-A4.EN.4.2013.v1 April 2013
OBJECTS TABLE
Type
Object Name
Room Temperature AV 7 Present_Value (R,W) Room Temp Override BV 8 Present_Value (R,W) Outdoor Temperature AV 9 Present_Value (R,W)
Outdoor Temp Override BV 10 Present_Value (R,W)
Room Humidity AV 11 Present_Value (R,W)
Room Humidity Override
Occupancy Command MV 12 Present_Value (R,W)
System Mode HP MV 13 Present_Value (R,W)
System Mode RTU MV 14 Present_Value (R,W))
Fan Mode MV 15 Present_Value (R,W)
Supply Temperature AI 16 Present_Value (R)
Supply RH AV 17 Present_Value (R)
Water Temperature AV 17 Present_Value (R,W)
Keypad Lockout MV 18 Present_Value (R,W)
Fresh Air Level AI 46 Present_Value (R)
Control Output GR 19 Present_Value (R) PI Heating Demand AV 20 Present_Value (R) PI Cooling Demand AV 21 Present_Value (R)
AI1 Value AI 23 Present_Value (R)
Economizer Output AV 22 Present_Value (R)
Analog Heat Output AV 35 Present_Value (R)
Controller Status GRP 23 Present_Value (R)
AUX BI 24 Present_Value (R)
G Fan BI 25 Present_Value (R) Y1 Cool BI 26 Present_Value (R) Y2 Cool BI 27 Present_Value (R)
W1 Heat BI 28 Present_Value (R) W2 Heat BI 29 Present_Value (R)
Reversing Valve BI 30 Present_Value (R)
DI 1 Status BI 31 Present_Value (R) DI 2 Status BI 32 Present_Value (R)
Local Motion BI 33 Present_Value (R)
Effective Occupancy MV 34 Present_Value (R)
Controller Alarms GRP 35 Present_Value (R)
Analog Heat Output AV 35 Present_Value (R)
Frost Alarm BI 36 Present_Value (R) Clock Alarm BI 37 Present_Value (R)
Filter Alarm BI 38 Present_Value (R)
Service Alarm BI 39 Present_Value (R)
Fan Lock Alarm BI 40 Present_Value (R)
Temperature Setpoints GRP 41 Present_Value (R)
and
Object Property
Instance
SE7600A5x45B
SE7652A5x45B
SE7600B5x45B
SE7652B5x45B
SE7605B5x45B
SE7656B5x45B
SE7607B5x45B
SE7657B5x45B
SE7600H5x45B
SE7652H5x45B
BV 13 Present_Value (R,W)
SE7600W5x45B
SE7652W5x45B
SE7606E5x45B
SE7656E5x45B
SE7600F5x45B
4
SE7652F5x45B
© 2013 Schneider Electric. All rights reserved.
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
Schneider Electric
IG-SE7000-BNE TSE76XX-A4.EN.4.2013.v1 April 2013
OBJECTS TABLE
PIR Ready SE76xx SeriesBACnet® Integration Manual
5
Object Name
Occupied Heat Setpoint AV 42 Present_Value (R,W) Occupied Cool Setpoint AV 43 Present_Value (R,W)
Unoccupied Heat
Setpoint
Unoccupied Cool
Setpoint
Fresh Air Level AI 46 Present_Value (R,W)
General Options 1- GRP 46 Present_Value (R,W)
Temperature Scale BV 47 Present_Value (R,W)
Heating Setpoint Limit AV 48 Present_Value (R,W) Cooling Setpoint Limit AV 49 Present_Value (R,W)
Heating Lockout
Temperature
Cooling Lockout
Temperature
Deadband AV 52 Present_Value (R,W)
Heating CPH MV 53 Present_Value (R,W)
Cooling CPH MV 54 Present_Value (R,W)
Frost Protection BV 55 Present_Value (R)
Aux Contact BV 56 Present_Value (R)
Menu Scroll BV 57 Present_Value (R,W)
Supply Heat Lockout
Status
General Options 2- GRP 58 Present_Value (R)
Password Value AV 59 Present_Value (R) Power-up Delay AV 60 Present_Value (R,W)
Temporary Occ. Time MV 61 Present_Value (R,W)
Fan Control BV 62 Present_Value (R,W)
Anticycle MV 63 Present_Value (R,W)
Fan Purge Delay BV 64 Present_Value (R,W) DI 1 Configuration MV 65 Present_Value (R,W) DI 2 Configuration MV 66 Present_Value (R,W) Proportional Band MV 67 Present_Value (R,W)
Unoccupied Time AV 68 Present_Value (R,W)
CO2 Level AI 69 Present_Value (R,W)
With schedule Model Configuration Options
Progressive Recovery BV 70 Present_Value (R,W)
Event Display MV 71 Present_Value (R,W)
Stages Configuration
Options
Discharge Air Alarm BI 72 Present_Value (R,W)
Type and
Instance
AV 44 Present_Value (R)
AV 45 Present_Value (R)
AV 50 Present_Value (R,W)
AV 51 Present_Value (R,W)
BV 58 Present_Value (R,W)
GRP 69 Present_Value (R,W)
GRP 72 Present_Value (R,W)
Object Property
SE7600A5x45B
SE7652A5x45B
SE7600B5x45B
SE7652B5x45B
SE7605B5x45B
SE7656B5x45B
SE7607B5x45B
SE7657B5x45B
SE7600H5x45B
SE7652H5x45B
SE7600W5x45B
SE7652W5x45B
SE7606E5x45B
SE7656E5x45B
SE7600F5x45B
SE7652F5x45B
PIR Ready SE76xx SeriesBACnet® Integration Manual
© 2013 Schneider Electric. All rights reserved.
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
Schneider Electric
IG-SE7000-BNE TSE76XX-A4.EN.4.2013.v1 April 2013
OBJECTS TABLE
Type
Object Name
Heating Stages MV 73 Present_Value (R,W) Cooling Stages MV 74 Present_Value (R,W)
Heatpump Stages MV 75 Present_Value (R,W)
Economizer Model
Configuration Options
Fresh Air Max Range AV 76 Present_Value (R,W)
Economizer
Changeover Setpoint
Economizer Minimum
Position
Mechanical Cooling
Enabled
Mixed Air Setpoint AV 80 Present_Value (R,W)
Heatpump Model
Configuration Options
Economizer Max
Position
High Balance Point AV 82 Present_Value (R,W)
Discharge High Limit
Setpoint
Low Balance Point AV 83 Present_Value (R,W)
Discharge Low Limit
Setpoint
Comfort Mode BV 84 Present_Value (R,W)
High CO2 Alarm BI 84 Present_Value (R,W)
Reversing Valve
Configuration
Compressor Interlock BV 86 Present_Value (R,W)
Fresh Air Alarm BI 86
Dehumidification Model
Configuration Options
RH Display BV 88 Present_Value (R,W)
Dehumidification RH
Setpoint
Dehumidification
Hysterisys
Dehumidification Low
OA Lockout
Dehumidification
Lockout Functions
Dehumidification Lockout Functions
Dehumidification Output
Status
Humidification Model
Configuration Options
AI1 Config BV 94 Present_Value (R,W)
Humidification RH
Setpoint
Minimum Supply Heat
Setpoint
and
Object Property
Instance
SE7600A5x45B
SE7652A5x45B
SE7600B5x45B
SE7652B5x45B
SE7605B5x45B
SE7656B5x45B
SE7607B5x45B
SE7657B5x45B
SE7600H5x45B
SE7652H5x45B
SE7600W5x45B
SE7652W5x45B
SE7606E5x45B
GRP 76 Present_Value (R)
AV 77 Present_Value (R,W)
AV 78 Present_Value (R,W)
BV 79 Present_Value (R,W)
GRP 81 Present_Value (R)
AV 81 Present_Value (R,W)
AV 82 Present_Value (R,W)
AV 83 Present_Value (R,W)
BV 85 Present_Value (R,W)
GRP 87 Present_Value (R)
AV 89 Present_Value (R,W)
AV 90 Present_Value (R,W)
AV 91 Present_Value (R,W)
BV 92 Present_Value (R,W)
MV 92 Present_Value (R,W)
BI 93 Present_Value (R)
GRP 94 Present_Value (R)
AV 95 Present_Value (R,W)
AV 95 Present_Value (R,W)
6
SE7656E5x45B
SE7600F5x45B
SE7652F5x45B
© 2013 Schneider Electric. All rights reserved.
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
Schneider Electric
IG-SE7000-BNE TSE76XX-A4.EN.4.2013.v1 April 2013
OBJECTS TABLE
PIR Ready SE76xx SeriesBACnet® Integration Manual
7
Object Name
Eff (Effective) Reset
Humidification RH Spt
(Setpoint)
Supply Heat Lockout
temperature
Humidification High
Limit Spt (Setpoint)
Supply PI Heat Demand AV 97 Present_Value (R)
Low RH Setpoint AV 98 Present_Value (R,W)
Minimum Fresh Air AV 98 Present_Value (R,W)
Low Temp Reset RH
Setpoint
Maximum Fresh Air AV 99 Present_Value (R,W)
High Temp Reset RH
Setpoint
Minimum CO2 Level AV 100 Present_Value (R,W)
Humidifier Output AV 101 Present_Value (R)
Maximum CO2 Level AV 101 Present_Value (R,W)
Local Schedule SCH 102 Present_Value (R,W)
Type and
Instance
AV 96 Present_Value (R)
AV 96 Present_Value (R,W)
AV 97 Present_Value (R,W)
AV 99 Present_Value (R,W)
AV 100 Present_Value (R,W)
Object Property
SE7600A5x45B
SE7652A5x45B
SE7600B5x45B
SE7652B5x45B
SE7605B5x45B
SE7656B5x45B
SE7607B5x45B
SE7657B5x45B
SE7600H5x45B
SE7652H5x45B
SE7600W5x45B
SE7652W5x45B
SE7606E5x45B
SE7656E5x45B
SE7600F5x45B
SE7652F5x45B