Schneider Electric SE7600F Data Sheet

SmartStruxure™ solution SmartStruxure Lite solution
Room Controller
SE7600F Rooftop Unit with Modulating Heat Controller
The SE7600F Rooftop terminal equipment room controller with modulating heat can make your building more comfortable while still meeting the ventilation codes for minimum building fresh air requirements. The easy-to-install SE7600F includes modulating heat functionality, which allows the addition of an extra supply air temperature control loop to better control and condition the supply air levels for a more comfortable occupant environment.
Compatible with
Schneider Electric | SDS-SE7600-EN. A4.08.2015.v2 August 2015
SE7600F RTU with Modulating Heat Features
The SE7600F is easy to install and includes modulating heat functionality, which allows for the addition of an extra supply air temperature control loop to better control and condition the supply air levels, providing a more comfortable occupant environment.
Introduction
Maintaining fresh air requirements for buildings located in colder climates has always been a challenge. In low outdoor air temperature conditions, supply air is often too cold to be used directly without conditioning when no heating demand is present. This creates an uncomfortable environment for occupants that is difficult to control.
RTU terminal equipment controllers for modulating heat
The SE7600F roof top terminal equipment room controller with modulating heat makes your building more comfortable while still meeting ventilation codes for minimum building fresh air requirements.
The SE7600F is easy to install and includes modulating heat functionality. This allows for the addition of an extra supply air temperature control loop to better control and condition the supply air levels, providing a more
AT A GLANCE
comfortable occupant environment.
2
Custom design
Function with any open protocols
Network ready units can be retrofit in the field
with optional communication modules
One simple wall-mounted device to install,
wire, and commission
Application-specific controllers
No special software required
Fully embedded local configuration utility
Options and accessories
PIR occupancy sensor
Advanced occupancy and monitoring
functions
7-day scheduling
This easy-to-install wall-mounted SE7600F room controller features an easy­to-read digital display and built-in commissioning and configuration utility, temperature sensor, optional humidity sensor, and optional Passive Infrared (PIR) occupancy sensor cover.
Open protocol design provides compatibility to BACnet® MS/TP and wireless ZigBee® Pro network systems. Our network ready “stand-alone” versions can be field retrofit with optional communication modules that enable the SE7600F to be integrated into virtually any building automation system as building requirements change.
No previous building automation training is required for the easy installation and commissioning process. Installation can be completed in fifteen minutes.
Schneider Electric | SDS-SE7600-EN. A4.08.2015.v2 August 2015
SE7600F RTU with Modulating Heat Applications
Outside air sensor
Outside air
Cooling coil Fan Heating coil
Return air
Supply air
Simplified HMI
Unique 5 button menu driven user interface simplifies programming and commissioning time during typical installation of unit.
3
TYPICAL APPLICATION
BACnet MS/TP
Wired communication protocol
Control Board
Supply air sensor
ZigBee® Pro
Optional wireless communication
SE7600
Controller
Schneider Electric | SDS-SE7600-EN. A4.08.2015.v2 August 2015
SE7600F RTU with Modulating Heat Specifications
Specifications
4
Dimensions
12.5cm/4.9in (H) x 8.6cm/3.38in (W) x 2.9cm/1in (D)
Power Requirements
19-30Vac, 50/60 Hz; 2 VA (RC & C) Class 2 RC to RH jumper 2.0 Amps 48 VA maximum
Operating Conditions
0 °C - 50 °C ( 32 °F - 122 °F ) 0% - 95% R.H. non-condensing
Storage Conditions
-30 °C - 50 °C ( -22 °F - 122 °F ) 0% - 95% R.H. non-condensing
Temperature Sensor
Local 10 K NTC thermistor
Temperature Sensor Resolution
± 0.1 °C ( ± 0.2 °F )
Temperature Control Accuracy
±0.5 ° C ( ± 0.9 °F ) @ 21 °C ( 70 °F ) typical calibrated
Occ and Unocc Cooling Setpoint Range
12.0 - 37.5 °C ( 54 - 100 °F )
Occ and Unocc Heating Setpoint Range
4.5 °C - 32 °C ( 40 °F - 90 °F )
Room and Outdoor Air Temperature Display Range
-40 °C - 50 °C ( -40 °F - 122 °F )
Proportional Band for Room Temperature control
Factory set, heating and cooling at: 1.1°C ( 2.0°F )
Digital Inputs
Relay dry contact only across C terminal to DI1 or DI2
Contact Output Rating
Each relay output: ( Y1, Y2, G, W1, W2 & AU ) 30 Vac, 1 Amp. maximum 30 Vac, 3 Amp. in-rush
Modulating Heat, Analog Output Rating
0 to 10 Vdc into 2KΩ resistance min.
Wire Gauge
18 gauge maximum, 22 gauge recommended
Approximate Shipping Weight
0.75 lb (0.34 kg)
Agency Approvals All Models
UL: UL 873 (US) and CSA C22.2 No. 24 (Canada),
File E27734 with CCN XAPX (US) and XAPX7 (Canada)
Industry Canada: ICES-003 (Canada) FCC: Compliant to CFR 47, Part 15, Subpart B,
Class A (US)
CE: EMC Directive 89/336/EEC (Europe Union) C-Tick: AS/NZS CISPR 22 Compliant (Australia /
New Zealand) Supplier Code Number N10696
Agency Approvals Wireless Models
FCC: Compliant to: Part 15, Subpart C
THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDE­SIRED OPERATION.
Check with your local government for instruction on disposal of these products.
Ordering information
SE76
Programmability:
-00 = No local scheduling / Non programmable
-52= Local scheduling / programmable
F
PIR options:
-50 = PIR ready but PIR cover not included
-55 = Factory ass embled with PIR cover
45
* Some part number configurations
may not be available.
Communication options:
-B = BACnet® MS/TP
-P = ZigBee Pro wireless
-W = Zig Bee® wireless
- = Network ready
Loading...