PIR Ready SE7200, SE7300 and SER7300 Series
24 VAC Zoning, Fan Coil and Line-Voltage
Fan Coil Controllers for Commercial and
Lodging HVAC Applications
CONTENTS
PID History Revision Tables 2
SNVTs and SCPTs Table per Model 3
Input Network Variables (NVIs) Description 8
Output Network Variables (NVOs) Description 12
Configuration Properties (NCIs) Description 14
Integration - Global Commands 18
SE7200X Integration - GUI Objects 19
SE(R)73xxX Integration - GUI Objects 19
Configuration Property Objects 20
Wiring Guide 20
Software Files 22
Device Identification 23
Tips and Things You Need to Know 24
Troubleshooting 24
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
XIF, APB and NXE File Names and Corresponding PIDs. This manual information
is to be used only with the current released SE7200, SE7300 SER7300 PIR ready
controllers.
Used on current
released controller
PIR Ready SE7200 /
SE7300 Seri es
Used on current
released controller
PIR Ready
SER7300 Seri es
APB / NXE / XIF
file names
Revision
Level
Associated PID
SE72_73_PIR.XIFRev 3.080:00:C5:55:00:04:04:20
APB / NXE / XIF
file names
Revision
Level
Associated PID
SER73_PIR.XIFRev 3.080:00:10:55:00:04:04:23
SE7200 Series
SE73x5X LodgingSE73x0X Commercial
SER7300SC30 00 Relay Pack
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
1nviOutdoorTempSNVT_temp_pXXXX
2nviSetpointSNVT_temp_pXXXX
3nviSpaceRHSNVT_lev_percentN/A X N/A X
4nviFanSpeedCmdSNVT_switchXXXX
5nviOccManCmdSNVT_occupancyXXXX
6nviApplicModeSNVT_hvac_modeXXXX
7nviHeatCoolSNVT_hvac_modeXXXX
10nviRemLockoutUNVT_countXXXX
11nviDhumiLCKSNVT_switchN/A X N/A X
12nvoSpaceTempSNVT_temp_pXXXX
13nvoDischAirTempSNVT_temp_pXXXX
14nvoSpaceRHSNVT_lev_percentN/A X N/A X
15nvoEffectOccupSNVT_occupancyXXXX
16nvoUnitStatusSNVT_hvac_statusXXXX
1bi1_statusTrue bit index 2xxxx
2bi2_statusTrue bit index 1xxxx
3rui1_ statusTrue bit index 47xxxx
4rbi2_ statusTrue bit index 48xxxx
5dehumidification_activeTrue bit index 7N/A x N/A x
6cool_valve_status True bit index13xxxx
7heat_valve_status 15xxxx
8fan_lowTrue bit index 21xxxx
9fan_medTrue bit index 22xxxx
10fan_highTrue bit index 23xxxx
11window_openedTrue bit index 24xxxx
12service_alarmTrue bit index 28xxxx
13filter_alarmTrue bit index 29xxxx
14local_pir_motionTrue bit index 39xxxx
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
0bi1_configEnumeration Set Used: input_cfg_model_a_txxxx
1bi2_configEnumeration Set Used: input_cfg_model_b_txxxx
2rui1_configEnumeration Set Used: input_cfg_model_e_tx
3rbi2_configEnumeration Set Used: input_cfg_model_f_tx
4Fan_ctrlfan_ctrl_tx
5calib_room_sensorSNVT_temp_diff_px
6room_humidity_displayEnumeration Set Used: off_on_state_tN/Ax N/A x
7dehumidification_setpointSNVT_lev_percentN/Ax N/A x
8dehumumidification_hysterisisSNVT_lev_percentN/Ax N/A x
9dehumidification_max_coolingSNVT_lev_percentN/Ax N/A x
10calib_room_humidity_sensorSNVT_lev_percentN/Ax N/A x
0passwordUnsigned-Longxxxx
1Cool_CPHunsigned shortxxxx
2Heat_CPHunsigned shortxxxx
3Cool_NO_NCaux_contact_cfg_txxxx
4Heat_ NO_NCaux_contact_cfg_txxxx
5menu_scrollEnumeration Set Used: scroll_type_txxxx
6
7temperature_scaleEnumeration Set Used: temp_unit_txxxx
8pipe_number_main_out_configEnumeration Set Used: pipe_system_txxxx
9sequence_of_operationEnumeration Set Used: seq_operation_vtr_txxxx
10fan_menu_sequenceEnumeration Set Used: fan_sequence_txxxx
11
12cool_minimum_setpointSNVT_temp_pxxxx
13
14cool_ demand_limitSNVT_lev_percentxxxx
15deadbandUnsigned-Shortxxxx
16setpoint_typeEnumeration Set Used: permanent_temporary_txxxx
17setpoint_function
18temporary_occ_timeUnsigned-Shortxxxx
19proportional_bandUnsigned-Shortxxxx
20pulsed_heat_enableoff_on_state_txxxx
21fan_modeEnumeration Set Used: fan_mode_txxxx
22auto_fanEnumeration Set Used: auto_fan_txxxx
23pir_standby_timeUnsigned-Shortxxxx
24pir_unoccupied_timeUnsigned-Shortxxxx
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
1bi1_statusTrue bit index 2xxxxxxxxxxxx
2bi2_statusTrue bit index 1xxxxxxxxxxxx
3ui3_ statusTrue bit index 0xxxxxxxxxx
4dehumidification_activeTrue bit index 7N/A N/A N/A N/A X N/A N/A X N/A X N/A X
5state_terminal_bo1True bit index 13xxxxxxxxxxxx
6state_terminal_bo2True bit index 12xxxxxxxxxxxx
7state_terminal_bo3True bit index 15xxxxxxxxxxxx
8state_terminal_bo4True bit index 14xxxxxxxxxxxx
9state_terminal_bo5True bit index 20xxxxxxxxxxxx
10fan_lowTrue bit index 21xxxxxxxxxxxx
11fan_medTrue bit index 22xxxxxxxxxxxx
12fan_highTrue bit index 23xxxxxxxxx
13window_openedTrue bit index 24xxxxxxxxxxxx
14service_alarmTrue bit index 28xxxxxxxxxxxx
15filter_alarmTrue bit index 29xxxxxxxxxxxx
16local_pir_motionTrue bit index 39xxxxxxxxxxxx
nvoTerminalLoad
nciSetpoints
1occupied_coolxxxxxxxxxxxx
2standby_coolxxxxxxxxxxxx
3unoccupied_coolxxxxxxxxxxx
4occupied_heatxxxxxxxxxxxx
5standby_heatxxxxxxxxxxxx
6unoccupied_heatxxxxxxxxxxxx
SNVT_temp_pXXXXXXXXXXXX
SNVT_temp_pXXXXXXXXXXXX
SNVT_temp_pXXXXXXXXXXXX
SNVT_lev_percentN/A N/A N/A N/A X N/A N/A X N/A X N/A X
SNVT_switchN/A N/A XXXXXXXXXX
SNVT_switchXXXXXXXXXXXX
SNVT_occupancyXXXXXXXXXXXX
SNVT_hvac_modeXXXXXXX
SNVT_hvac_modeXXXXXXXXXXXX
UNVT_countXXXXXXXXXXXX
SNVT_switchN/A N/A N/A N/A X N/A N/A X N/A X N/A X
SNVT_switchXXXXXXXXXXXX
SNVT_temp_pXXXXXXXXXXXX
SNVT_temp_pXXXXXXXXXXXX
SNVT_lev_percentN/A N/A N/A N/A X N/A N/A X N/A X N/A X
SNVT_occupancyXXXXXXXXXXXX
SNVT_hvac_statusXXXXXX
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
5dehumidification_setpointSNVT_lev_percentN/A N/A N/A N/A x N/A N/A x N/A x N/A x
6dehumumidification_hysterisisSNVT_lev_percentN/A N/A N/A N/A x N/A N/A x N/A x N/A x
7dehumidification_max_cooling
8calib_room_humidity_sensorSNVT_lev_percentN/A N/A N/A N/A x N/A N/A x N/A x N/A x
22nciSccModelUNVT_model_info_2XXXXXXXXXXXX
Associate with UNVT_model_info_2 format file
1Controller Modelxxxxxxxxxxxx
2Controller Software Versionxxxxxxxxxxxx
23nciHvacTypeSNVT_hvac_typeXXXXXXXXXXXX
24nciSndHrtBtSNVT_time_secXXXXXXXXXXXX
25nciMinOuttMSNVT_time_secXXXXXXXXXXXX
26nciRcvHrtBtSNVT_time_secXXXXXXXXXXXX
27nciMajVerSCPT_maj_verXXXXXXXXXXXX
28nciMinVerSCPT_min_verXXXXXXXXXXXX
Snivet Type
Enumeration and
Signature Type T
SE7200F5x00E
SE7200C5x00E
Enumeration Set Used:
input_cfg_model_a_t
Enumeration Set Used:
input_cfg_model_b_t
Enumeration Set Used:
input_cfg_model_c_t
Enumeration Set Used:
off_on_state_t
SNVT_lev_percentN/A N/A N/A N/A x N/A N/A x N/A x N/A x
xxxxxxxxxxxx
xxxxxxxxxxxx
xxxxxxxxxxxx
N/A N/A N/A N/A x N/A N/A x N/A x N/A x
SE7300A5x00E
SE7300C5x00E
SE7305A5x00E
SE7350C5x00E
SE7305C5x00E
SE7300F5x00E
SE7355C5x00E
SE7350F5x00E
SE7305F5x00E
SE7355F5x00E
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
This input network variable provides a network remote temperature value
to the controller. When linked or written to, the internal temperature reading
(internal sensor) is no longer used.
Valid Range: 40 to 122°F (-40 to 50°C)
Default Null (release) Value: 621.81°F (327.67°C or 0x7FFF)
This network variable is subject to the Receive HeartBeat Time,
nviRcvHrtBt.
This input network variable provides outdoor air temperature information
to the controller from a network value temperature value. The device will
automatically display the value on its display when linked.
Valid Range: 40 to 122°F (-40 to 50°C)
Default Null (release) Value: 621.81°F (327.67°C or 0x7FFF)
This input network variable is used to allow the occupied temperature
setpoints to be changed only via the network from a single analog value.
(Note: the Stand-By and Unoccupied setpoints are not changed). The
corresponding heating and cooling values are derived from the minimum
deadband configuration value
Default Null Value: 621.81°F (327.67°C or 0x7FFF)
Ex. If the minimum deadband configuration value = 2 °F and nviSetpoint =
70°F.
The resulting Occupied heating setpoint will equal 69 °F which is derived
from 70 °F minus ½ the minimum deadband configuration value of 2 °F
The resulting Occupied cooling setpoint will equal 71 °F which is derived
from 70 °F plus ½ the minimum deadband configuration value of 2 °F
Room
Temperature
Outdoor Air
Temperature
Occupied
Cool & Heat
Setpoints
network input
SNVT_temp_p
nviSpaceTemp
network input
SNVT_temp_p
nviOutdoorTemp
network Input
SNVT_temp_p
nviSetpoint
Room
Humidity
network input
SNVT_lev_percent
nviSpaceRH
This input network variable is the measured room humidity in percent
monitored by the controller.
Valid Range: 5 to 90%
Default Null Value: +163.835 (0x7FFF)
This network variable is subject to the Receive HeartBeat Time, nviRcvHrtBt