Appendix D - VWA5000 series - wireless door & window switch ..................................... 55
Appendix E - SER7300 controller & SC3000 relay pack ...................................................57
Appendix F - SE7300 low voltage fan coil controller .........................................................59
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4January 2016
Product & application selector
SER7300 & Relay Pack
PowerBuilding
Line
Voltage
Function
CommercialYes2 or 4 pipe,
Hospitality Ye s2 or 4 pipe,
Humidity
Control
No2 Pipe, Up
ApplicationOutputs /
Up to 3
speed fan
to 3 speed
fan
Up to 3
speed fan
Inputs
1H/1C with
Reheat
1H/1C with 4
inputs
and reheat
1H/1C with
4 inputs
reheat and
occ. output
1H/1C with
pulsed
reheat
1H/1C with
pulsed
reheat
and 4 inputs
1H/1C with
Reheat
1H/1C with 4
inputs
and reheat
ControllerRelay PackTypical
Application
SER7350A5045SC3500E5045Page: 38, 42
SER7350A5045SC3504E5045Page: 40, 44
SER7350A5045SC3514E5045Page: 44
SER7300A5045SC3400E5045Page: 42
SER7300A5045SC3404E5045Page: 38
SER7355A5045*SC3500E5045Page: 36, 50
SER7355A5045*SC3504E5045Page: 40, 48
1H/1C with
4 inputs
reheat and
occ. output
No2 Pipe, Up
to 3 speed
fan
Slave fan
control
only
*The Hospitality/Lodging models are identical to the commercial controllers except for the Override key which is replaced
with a °C/°F key to switch between Celsius and Fahrenheit units.
At the end of the model number, add B for BACnet communication or W for Zigbee wireless communication.
Ex: SER7300A5045B or SER7300A5045W
1H/1C with
pulsed
reheat
1H/1C with
pulsed
reheat
and 4 inputs
3 fan
outputs
SER7355A5045*SC3514E5045Page: 44
SER7305A5045*SC3400E5045Page: 42
SER7305A5045*SC3404E5045Page: 38
SER73xxA5045SC3300E5000Page: 46
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4January 2016
SER7300 and SC3000 | Fan coil terminal equipment controllers
This new cost-effective solution for upgrading line-voltage fan coil unit thermostats requires only two components: the SER7300 terminal equipment controller and the SC3000 relay pack. This solution allows existing line voltage wiring between the fan coil unit and temperature controller to be re-used, reducing
overall costs and installation time. The SC3000 relay pack features an onboard universal voltage power supply and line-voltage relays which directly drive
fractional horsepower fan motors and valves. This eliminates the need to install and wire costly pilot relays and transformers.
Commercial interface (local override)
Part NumberDescriptionHumidity PIR Cover Communication
SER730 0A5045Stand-alone fan coil terminal equipment controller NoNoStand-alone (network ready)
SER7300A5045BBACnet fan coil terminal equipment controller NoNoBACnet
SER730 0A5045WWireless fan coil terminal equipment controller NoNoWireless
SER7300A5545Stand-alone fan coil terminal equipment controller NoYesStand-alone (network ready)
SER7300A5545BBACnet fan coil terminal equipment controller NoYesBACnet
SER7300A5545WWireless fan coil terminal equipment controller NoYesWireless
SER7350A5045Stand-alone fan coil terminal equipment controller YesNoStand-alone (network ready)
SER7350A5045BBACnet fan coil terminal equipment controller YesNoBACnet
SER7350A5045WWireless fan coil terminal equipment controller YesNoWireless
SER7350A5545Stand-alone fan coil terminal equipment controller YesYesStand-alone (network ready)
SER7350A5545BBACnet fan coil terminal equipment controller YesYe sBACnet
SER7350A5545WWireless fan coil terminal equipment controller YesYe sWireless
Hotel/lodging interface (°C/°F selection)
Part NumberDescriptionHumidity PIR Cover Communication
SER7305A5045BBACnet fan coil terminal equipment controller NoNoBACnet
SER730 5A504 5WWireless fan coil terminal equipment controller NoNoWireless
SER7305A5545Stand-alone fan coil terminal equipment controller NoYesStand-alone (network ready)
SER7305A5545BBACnet fan coil terminal equipment controller NoYe sBACnet
SER7305A5545WWireless fan coil terminal equipment controller NoYe sWireless
SER7355A5045Stand-alone fan coil terminal equipment controller YesNoStand-alone (network ready)
SER7355A5045BBACnet fan coil terminal equipment controller YesNoBACnet
SER7355A5045WWireless fan coil terminal equipment controller YesNoWireless
SER7355A5545Stand-alone fan coil terminal equipment controller YesYesStand-alone (network ready)
SER7355A5545BBACnet fan coil terminal equipment controller YesYesBACnet
SER7355A5545WWireless fan coil terminal equipment controller YesYe sWireless
Transformer relay packs for fan coil units
Part NumberDescription
SC3500E50451 heat/cool output, 1 cool output, and 3 fan outputs
SC3504E50451 heat/cool output, 1 cool output, 3 fan outputs and four inputs
SC 3514 E5 04 51 heat/cool output, 1 cool output, 3 fan outputs, Occupancy output (7Vdc), and four inputs
SC3400E50451 heat/cool output, 1 Modulating pulsed Vdc output for SSR ele ctric reh eat contro l, and 3 fan outputs
SC3404E50451 heat/cool ou tput, 1 Modulating pulsed Vdc outpu t for SSR electric reheat control, and 3 fan outputs
SC3300E5045
3 slave fan o utputs
Wireless accessories*
Part NumberDescription
VWA5000D5045WWireless door switch
VWA5000W5045WWireless window switch
* Wireless accessories are compatible with all the VWA, SER7300, and wireless models.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4January 2016
SE7300 | Fan coil room controllers
PowerApplicationBuilding
Low
- 2 or 4 Pipe
Function
CommercialYesOn-Off
Voltage
- Hot/Chill water valves
- Up to 3 speed fan
- Automatic Changeover
-Auxiliary contact output
Hospitality /
Lodging
Humidity
Control
Outputs /
Inputs
1H/1C
Floating
1H/1C
Analogue
1H/1C
NoOn-Off
1H/1C
Floating
1H/1C
Analogue
1H/1C
Yes
On-Off
1H/1C
Floating
1H/1C
ControllerTypical
Application
SE7350C5045Page: 20, 32
SE7350C5045Page: 12, 34
SE7350F5045Page: 16, 30
SE7300C5045Page: 28
SE7300C5045Page: 14
SE7300F5045Page: 22, 24, 26
SE7355C5045*Page: 18, 20, 32
SE7355C5045*Page: 12, 34
Analogue
SE7355F5045*Page: 16, 30
1H/1C
NoOn-Off
SE7305C5045*Page: 28
1H/1C
Floating
SE7305C5045*Page: 14
1H/1C
Analogue
SE7305F5045*Page: 22, 24, 26
1H/1C
*The Hospitality/Lodging models are identical to the commercial controllers except for the Override key which is replaced with
a °C/°F key to switch between Celsius and Fahrenheit units.
Note: At the end of the model number, add B for BACnet communication, E for Echelon communication or
W for Zigbee wireless communication. Ex: SER7300A5045B or SER7300A5045E or SER7300A5045W
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4January 2016
SE7300 | Fan coil room controllers
Achieve better energy efficiency and reduce operating costs with SE7300 Series room controllers. Ideal for commercial and hotel applications, these fan coil
units function with electronically commutated motors to optimise fan control sequences. With the full proportional operating of the SE7300, as opposed to
the traditional three-speed tap operation, customers will experience better control and a more comfortable environment.
Commercial interface (local override)
Part NumberDescriptionHumidity OutputPIR Cover Communication
SE730 0C504 5
SE730 0C504 5B
SE7300C5045E
SE730 0C504 5W
SE730 0C5545
SE730 0C5545B
SE7300C5545E
SE730 0C5545W
SE730 0F504 5
SE730 0F504 5B
SE7300F5045E
SE730 0F504 5W
SE730 0F554 5
SE730 0F554 5B
SE7300F5545E
SE730 0F554 5W
SE7350C5045
SE7350C5045B
SE7350C5045E
SE7350C5045W
SE7350C554 5
SE7350C554 5B
SE7350C5545E
SE7350C554 5W
SE7350F5045
SE7350F5045B
SE7350F5045E
SE7350F5045W
SE7350F5545
SE7350F5545B
SE7350F5545E
SE7350F5545W
Stand-alone fan coil controllerNoFloating or on/of f NoStand-alone (network ready)
BACnet fan coil controllerNoFloating or on/off NoBACnet
LON fan coil controllerNoFloating or on/off NoLonWorks
Wireless fan coil controllerNoFloating or on /off NoWireless
Stand-alone fan coil controllerNoFloating or on/of f Ye sStand-alone (network ready)
BACnet fan coil controllerNoFloating or on/off Ye sBACnet
LON fan coil controllerNoFloating or on/off Ye sLonWorks
Wireless fan coil controllerNoFloating or on /off YesWireless
Stand-alone fan coil controllerNo0 - 10 VNoStand-alone (network ready)
BACnet fan coil controllerNo0 - 10 VNoBACnet
LON fan coil controllerNo0 - 10 VNoLonWorks
Wireless fan coil controllerNo0 - 10 VNoWireless
Stand-alone fan coil controllerNo0 - 10 VYesStand-alone (network ready)
BACnet fan coil controllerNo0 - 10 VYesBACnet
LON fan coil controllerNo0 - 10 VYesLonWorks
Wireless fan coil controllerNo0 - 10 VYe sWireless
Stand-alone fan coil controllerYe sFloating or on/off NoStand-alone (network ready)
BACnet fan coil controllerYesFloating or on/off NoBACnet
LON fan coil controllerYesFloating or on/off NoLonWorks
Wireless fan coil controllerYe sFloating or on/ off NoWireless
Stand-alone fan coil controllerYe sFloating or on/off YesStand-alone (network ready)
BACnet fan coil controllerYesFloating or on/off YesBACnet
LON fan coil controllerYesFloating or on/off YesLonWorks
Wireless fan coil controllerYe sFloating or on/ off Ye sWireless
Stand-alone fan coil controllerYe s0 - 10 VNoStand-alone (network ready)
BACnet fan coil controllerYes0 - 10 VNoBACnet
LON fan coil controllerYes0 - 10 VNoLonWorks
Wireless fan coil controllerYe s0 - 10 VNoWireless
Wireless fan coil controllerYe s0 - 10 VYesWireless
The Hospitality/Lodging models are identical to the commercial controllers except for the Override key which is replaced
with a °C/°F key to switch between Celsius and Fahrenheit units.The only difference in the p/n is that the 6th character is a 5
instead of a zero - Example: SE7305 rather than SE7300.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4January 2016
Cost-saving, energy-saving applications
From hotels and hospitals to schools, retail, and commercial buildings, Schneider Electric offers
wide-ranging room control solutions for your building management needs. Whether retrofitting
current systems with a more technologically advanced room controller or going green with a
more environmentally friendly option, SE7000 Series is the ideal, cost-competitive solution. The
SE7000 Series room controllers can be equipped with an integrated passive infrared motion
sensor for demand-based occupancy control that opens up new opportunities in smart energy
management.
Open
communications
Advance control of
your building with
truly open, integrated
communications.
Open protocol options
include ZigBee® wireless,
BACnet®, and LonWorks®
infrastructure.
Lower total install co st
Accelerate your return
on investment by saving
time and resources
from the beginning. Our
easy-to-install systems
integrate into any new or
existing building, with no
requirement for costly,
specialised labour.
Efficient control
Take full control of
your building’s HVAC
equipment. We’ll make
it simple with intuitive,
application-based
products specifically
designed for your needs.
Occupancy sensing
Equip your room
controller with an
integrated passive
infrared motion sensor
for demand-based
occupancy control that
raises your energy
efficiency to a whole
new level.
Energy savings
Save energy. Save
money. With SE7000
Series room controllers
you’ll reduce energy
costs without sacrificing
comfort one bit.
Temperature and
humidity sensing
Deliver efficient,
measureable control.
If you can measure it,
you can control it —
providing more precise
occupant comfort
and productivity.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4January 2016
Energy savings for
a healthy bottom line.
Increase the c omfort of patients, visitors, and
employees while reducing energy consumption
with SE7000 Series room c ontrollers.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4January 2016
SE7000 network ready communication adapters
All current “Network Ready” Schneider-Electric SE7000 controllers are
capable of being retrofit in the field with accessory communication adapters
that enables the controllers to be integrated into virtually all leading building
automation systems
This approach allows the flexibility to add network communication strategies as budgets allow
or as the buildings needs change.
If required, Network Ready (stand-alone) Terminal Equipment Controllers can be field retrofitted
with the following communication adapters.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4January 2016
Comf ortable workers
are more productive.
Accelerate your return on investment with
SE7000 Ser ies room c ontrollers.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4January 2016
SE7350C5045: Heating/cooling: 4-pipe fan coil unit with 3-speed
fan, tri-state floating valves and dehumidification sequence
Valve
Heating Coil
Tri-state
Floating
Valve
Optional PIR cover: COV-PIR-FCU-C-5045.
Refer to Schneider Electric Catalogue for
valves and actuators.
Cooling Coil
FAN
Tri-state
Floating
SE7350C
Configuration
parameter name
PswrdSet0 is factory set, range is: 0-1000
BI1None
BI2None
UI3None
MenuScroON
AutoModeON
C or FAs per user. Default value = °F
%RH dispON
LockoutAs per user. Default value = 0 No lock
Pipe No 4.0
CntrlTypFloating
SeqOpera4 = Cooling / Heating 4 pipes
Fan Menu2
DHumiLCKON
%RH setAs per user. Default value = 50%. Range = 30% to 95%
DehuHystAs per user. Default value = 5%. Range = 2% to 20%
DehuCoolAs per user. Default value = 100%. Range = 20% to 100%
St-By TM0.5 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments
Unocc TM0.0 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments
St-By HT 69 °F is factory set, range is: 40 to 90 °F ( 4.5 to 32.0 °C )
St-By CL 78 °F is factory set, range is: 54 to 100 °F ( 12.0 to 37.5 °C )
Unocc HTAs per user. Default value = 62 °F ( 17 °C ). Range = 40 to 90 °F ( 4.5 to 32.0 °C )
Unocc CLAs per user. Default value = 80 °F ( 27 °C ). Range = 54 to 100 °F ( 12 to 37.5 °C )
heat maxAs per user. Default value = 90 °F ( 32 °C ). Range = 40 to 90 °F ( 4.5 to 32.0 °C )
cool minAs per user. Default value = 54 °F ( 12 °C ). Range = 54 to 100 °F ( 12 to 37.5 °C )
Pband2 °F is factory set, range is: 2 to 10 °F ( 0.6 to 5.6 °C )
Set TypePermanent
SptFuncDual Stp or AttchStp
TOccTimeAs per user. Default value 2 hours. Range = 0 to 24 hours
DoorTimeN/A
deadband
cal RS0 °F or °C
cal RH0 °F or °C
aux cont0
Auto FanAS or AS AD
FL timeAs per user. Default value = 1.5 minutes. Range 0.5 to 9.0 in 0.5 minutes increments
cphN/A
Reheat0 for ON/OFF ( 4CPH ), 1 for PWM ( 10 second )
UI3 disDisplays supply air temperature
Configuration settings
As per user. Default value 2.0 °F ( 1.0 °C ). Range = 2, 3, 4 or 5 °F, 1.0 °F increments
( 1.0 to 2.5 °C, 0.5 °C increments )
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4January 2016
Sequence of operation and wiring
%RH Setpoint
Hysterisys = 10%
(adjustable)
1/2 Hysterisys = 5%
1/2 Hysterisys = 5%
ON
OFF
Dehumidification = OFF
Dehumidification = ON
24V
COM
FAN-L
FAN-M
FAN-H
BO1
BO2
HEATING
BO3
BO4
COOLING
Close
Open
Close
Open
Fan coil relay control center (Generic)
24V
Com
L
M
H
24V
Com
R
R
R
To Fan Coil Unit
Com
L
M
H
24V
Com
120V
SE7350C Controller
24VAC - 230VAC
Occupied Mode:
Setpoints will revert to those defined by
occupied cooling and heating.
The changeover sensor will send the supply air
temperature to the controller.
Stand-by Mode (only available when PIR
motion detector cover is used):
Setpoints will revert to those defined by standby cooling and heating.
Unoccupied Mode:
Setpoints will revert to those defined by
unoccupied heating and cooling.
Occupied Override Mode:
The system will revert to occupied mode for
the duration determined by the “ToccTime”
parameter.
On a call for cool:
Cooling valve will modulate to maintain
room temperature. Heating valve is closed.
Dehumidification is enabled.
Dehumidification ON/OFF Sequence:
On a call for heat:
Heating valve will modulate to maintain
room temperature. Cooling valve is closed.
Dehumidification is disabled.
On a demand for dehumidification:
Dehumidification is achieved via the cooling coil
using the heating coil for reheat if necessary.
Dehumidification is only allowed in COOL mode
(or if cooling is enabled in AUTO mode).
Dehumidification is disabled if the room
temperature falls below the low ambient lockout
temperature. Which is the cooling setpoint
minus the configuration defined deadband
value.
Reheat is disabled if cooling demand reaches
100%.
Options
BACnet, Echelon and Wireless communication models available (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Analogue outputs available (SE73xxF5045).
Can be configured for 2 pipe systems.
Binary inputs can be configured to control occupancy via door or window contact, remote night
setback or to provide alarms for service or filter monitoring.
Universal input can be configured for a changeover sensor.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4January 2016
SE7300C5045: Heating/cooling with changeover and reheat:
2-pipe fan coil unit with 3-speed fan, tri-state floating valve and
electric reheat.
Heating/Cooling
Coil
FAN
Sensor: 10K Ohm Type 2.
Floating
Valve
SE7300C
Configuration
parameter name
PswrdSet0 is factory set, range is: 0-1000
BI1None
BI2None
UI3COS
MenuScroON
AutoModeON
C or FAs per user. Default value = °F
LockoutAs per user. Default value = 0 No lock
Pipe No 2.0
CntrlTypFloating
SeqOpera2 = Cooling with Reheat
Fan Menu2
St-By TM0.5 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments
Unocc TM0.0 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments
St-By HT 69 °F is factory set, range is: 40 to 90 °F ( 4.5 to 32.0 °C )
St-By CL 78 °F is factory set, range is: 54 to 100 °F ( 12.0 to 37.5 °C )
Unocc HTAs per user. Default value = 62 °F ( 17 °C ). Range = 40 to 90 °F ( 4.5 to 32.0 °C )
Unocc CLAs per user. Default value = 80 °F ( 27 °C ). Range = 54 to 100 °F ( 12 to 37.5 °C )
heat maxAs per user. Default value = 90 °F ( 32 °C ). Range = 40 to 90 °F ( 4.5 to 32.0 °C )
cool minAs per user. Default value = 54 °F ( 12 °C ). Range = 54 to 100 °F ( 12 to 37.5 °C )
Pband2 °F is factory set, range is: 2 to 10 °F ( 0.6 to 5.6 °C )
Set TypePermanent
SptFuncDual Stp or AttchStp
TOccTimeAs per user. Default value 2 hours. Range = 0 to 24 hours
DoorTimeN/A
deadband
cal RS0 °F or °C
cal RH0 °F or °C
aux cont0
Auto FanAS or AS AD
FL timeAs per user. Default value = 1.5 minutes. Range 0.5 to 9.0 in 0.5 minutes increments
cphN/A
Reheat0 for ON/OFF ( 4CPH ), 1 for PWM ( 10 second )
UI3 disDisplays supply air temperature
Configuration settings
As per user. Default value 2.0 °F ( 1.0 °C ). Range = 2, 3, 4 or 5 °F, 1.0 °F increments
( 1.0 to 2.5 °C, 0.5 °C increments )
Optional PIR cover: COV-PIR-FCU-C-5045.
Refer to Schneider Electric Catalogue for valves and
actuators.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4January 2016
Sequence of operation and wiring
24V
COM
FAN-L
FAN-M
FAN-H
BO1
BO2
actuator
UI3
Scom
BO5
BO5
C/O Sensor
SE7300C Controller
Cooling/heating valve
Fan coil relay control center (Generic)
24VAC - 230VAC
24V
Com
L
M
H
R
R
R
To Fan Coil Unit
Com
L
M
H
120V
R
Perimeter Heating
Occupied Mode:
Setpoints will revert to those defined by
occupied cooling and heating.
The changeover sensor will send the supply air
temperature to the controller.
Stand-by Mode (only available when PIR
motion detector cover is used):
Setpoints will revert to those defined by standby cooling and heating.
Unoccupied Mode:
Setpoints will revert to those defined by
unoccupied heating and cooling.
Occupied Override Mode:
The system will revert to occupied mode for
the duration determined by the “ToccTime”
parameter.
On a call for cool:
If water temperature is less than 24°C (75°F),
valve will open to allow water flow. If supply air
temperature is greater than 25°C (77°F), valve
will close. Baseboard is always desactivated.
On a call for heat:
If water temperature is less than 24°C (75°F),
valve will close and the duct heater will be
activated. If water temperature is greater than
25°C (77°F), valve will open to allow water flow.
If the water flow is unable to satisfy the demand,
the baseboard is activated.
Options
BACnet, Echelon and Wireless models available (see Appendix B for network wiring).
Analogue 0-10 VDC outputs available (SE73xxF5045).
Remote wall mount or duct sensor ready.
Can be configured for 4 pipe systems.
Can be configured to single or two speed fan.
Binary inputs can be configured to control occupancy via door or window contact, remote night
setback or to provide alarms for service or filter monitoring.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4January 2016
SE7350F5045: Heating/cooling: 4-pipe fan coil unit with 3-speed
fan, 0-10 VDC Analogue valves and dehumidification sequence
Cooling Coil
FAN
Analogue
Cooling
Valve
SE7350F
Configuration
parameter name
PswrdSet
BI1
BI2
UI3
MenuScro
AutoMode
C or F
%RH disp
Lockout
Pipe No
SeqOpera
Fan Menu
DHumiLCK
%RH set
DehuHyst
DehuCool
St-By TM
Unocc TM
St-By HT
St-By CL
Unocc HT
Unocc CL
heat max
cool min
Pband
Set Type
SptFunc
TOccTime
DoorTime
deadbandAs per user. Default value 2.0 °F ( 1.0 °C ). Range = 2, 3, 4 or 5 °F, 1.0 °F increments
cal RS
cal RH
aux cont
Auto Fan
RA/DA
Reheat
UI3 disDisplays supply air temperature
Configuration settings
0 is factory set, range is: 0-1000
None
None
None
ON
ON
As per user. Default value = °F
ON
As per user. Default value = 0 No lock
4.0
4 = Cooling / Heating 4 pipes
2
ON
As per user. Default value = 50%. Range = 30% to 95%
As per user. Default value = 5%. Range = 2% to 20%
As per user. Default value = 100%. Range = 20% to 100%
0.5 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments
0.0 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments
69 °F is factory set, range is: 40 to 90 °F ( 4.5 to 32.0 °C )
78 °F is factory set, range is: 54 to 100 °F ( 12.0 to 37.5 °C )
As per user. Default value = 62 °F ( 17 °C ). Range = 40 to 90 °F ( 4.5 to 32.0 °C )
As per user. Default value = 80 °F ( 27 °C ). Range = 54 to 100 °F ( 12 to 37.5 °C )
As per user. Default value = 90 °F ( 32 °C ). Range = 40 to 90 °F ( 4.5 to 32.0 °C )
As per user. Default value = 54 °F ( 12 °C ). Range = 54 to 100 °F ( 12 to 37.5 °C )
2 °F is factory set, range is: 2 to 10 °F ( 0.6 to 5.6 °C )
Permanent
Dual Stp or AttchStp
As per user. Default value 2 hours. Range = 0 to 24 hours
N/A
( 1.0 to 2.5 °C, 0.5 °C increments )
0 °F or °C
0 °F or °C
0
AS or AS AD
Reverse Acting (RA) or Direct Acting (DA), depends on actuator
0 for ON/OFF ( 4CPH ), 1 for PWM ( 10 second )
Heating Coil
Analogue
Heating
Valve
Optional PIR cover: COV-PIRFCU-C-5045.
Refer to Schneider Electric Catalogue for
valves and actuators.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4January 2016
%RH Setpoint
Hysterisys = 10%
(adjustable)
1/2 Hysterisys = 5%1/2 Hysterisys = 5%
ONOFF
Dehumidification = OFF
Dehumidification = ON
Sequence of operation and wiring
24V
COM
FAN-L
FAN-M
FAN-H
AO1
AO2
Fan coil relay control center (Generic)
HEATING
0-10VDC
COOLING
24V
Com
L
M
H
24V
Com
R
R
R
To Fan Coil Unit
SE7350F Controller
0-10VDC
Com
L
M
H
24V
Com
120V
24VAC - 230VAC
Occupied Mode:
Setpoints will revert to those defined by
occupied cooling and heating.
The changeover sensor will send the supply air
temperature to the controller.
Stand-by Mode (only available when PIR
motion detector cover is used):
Setpoints will revert to those defined by standby cooling and heating.
Unoccupied Mode:
Setpoints will revert to those defined by
unoccupied heating and cooling.
Occupied Override Mode:
The system will revert to occupied mode for
the duration determined by the “ToccTime”
parameter.
On a call for cool:
Cooling valve will modulate to maintain room
temperature. Heating valve is closed.
Dehumidification is enabled.
On a call for heat:
Heating valve will modulate to maintain room
temperature. Cooling valve is closed.
Dehumidification is disabled.
ON/OFF Sequence:
On a demand for dehumidification:
Dehumidification is achieved via the cooling coil
using the heating coil for reheat if necessary.
Dehumidification is only allowed in COOL mode
(or if cooling is enabled in AUTO mode).
Dehumidification is disabled if the room
temperature falls below the low ambient lockout
temperature. Which is the cooling setpoint
minus the configuration defined deadband value.
Reheat is disabled if PI cooling demand
reaches 100%.
Options
BACnet, Echelon and Wireless communication models available (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Can be configured for 2 pipe systems.
Binary inputs can be configured to control occupancy via door or window contact, remote night
setback or to provide alarms for service or filter monitoring.
Universal input can be configured for a changeover sensor.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4January 2016
SE7355C5045: Heating/cooling: 4-pipe fan coil unit with 3-speed
fan, 2-position valves, and dehumidification sequence
Valve
Heating Coil
2-Position
Heating
Valve
Optional PIR cover: COV-PIR-FCU-L-5045.
Refer to Schneider Electric Catalogue for
valves and actuators.
Cooling Coil
FAN
2-Position
Cooling
SE7355C
Configuration
parameter name
PswrdSet0 is factory set, range is: 0-1000
BI1None
BI2None
UI3None
MenuScroON
AutoModeON
C or FAs per user. Default value = °F
%RH dispON
LockoutAs per user. Default value = 0 No lock
Pipe No 4.0
CntrlTypOn/Off
SeqOpera4 = Cooling / Heating 4 pipes
Fan Menu2
DHumiLCKON
%RH setAs per user. Default value = 50%. Range = 30% to 95%
DehuHystAs per user. Default value = 5%. Range = 2% to 20%
DehuCoolAs per user. Default value = 100%. Range = 20% to 100%
St-By TM0.5 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments
Unocc TM0.0 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments
St-By HT 69 °F is factory set, range is: 40 to 90 °F ( 4.5 to 32.0 °C )
St-By CL 78 °F is factory set, range is: 54 to 100 °F ( 12.0 to 37.5 °C )
Unocc HTAs per user. Default value = 62 °F ( 17 °C ). Range = 40 to 90 °F ( 4.5 to 32.0 °C )
Unocc CLAs per user. Default value = 80 °F ( 27 °C ). Range = 54 to 100 °F ( 12 to 37.5 °C )
heat maxAs per user. Default value = 90 °F ( 32 °C ). Range = 40 to 90 °F ( 4.5 to 32.0 °C )
cool minAs per user. Default value = 54 °F ( 12 °C ). Range = 54 to 100 °F ( 12 to 37.5 °C )
Pband2 °F is factory set, range is: 2 to 10 °F ( 0.6 to 5.6 °C )
Set TypePermanent
SptFuncDual Stp or AttchStp
TOccTimeAs per user. Default value 2 hours. Range = 0 to 24 hours
DoorTimeN/A
deadband
cal RS0 °F or °C
cal RH0 °F or °C
aux cont0
Auto FanAS or AS AD
FL timeAs per user. Default value = 1.5 minutes. Range 0.5 to 9.0 in 0.5 minutes increments
cphAs per user. 4 to 8 CPH
Reheat0 for ON/OFF ( 4CPH ), 1 for PWM ( 10 second )
UI3 disDisplays supply air temperature
Configuration settings
As per user. Default value 2.0 °F ( 1.0 °C ). Range = 2, 3, 4 or 5 °F, 1.0 °F increments
( 1.0 to 2.5 °C, 0.5 °C increments )