Schneider Electric SE7000 Series Application Information

SE7000 Fan Coil Unit Application Guide
SE7000 Series Room Controllers
Version 4
Table of contents
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4 January 2016
Product & application selector ........................................................................................... 4
Cost-saving, energy-saving applications ............................................................................ 8
SE7000 network ready communication adapters ..............................................................10
SE7350C5045: Heating/cooling: 4-pipe fan coil unit with 3-speed fan,
tri-state floating valves and dehumidification sequence ..................................................... 12
SE7300C5045: Heating/cooling with changeover and reheat:
2-pipe fan coil unit with 3-speed fan, tri-state floating valve and electric reheat. ...............14
SE7350F5045: Heating/cooling: 4-pipe fan coil unit with 3-speed fan,
0-10 VDC Analogue valves and dehumidification sequence ..............................................16
SE7355C5045: Heating/cooling: 4-pipe fan coil unit with 3-speed fan,
2-position valves, and dehumidification sequence ............................................................18
SE7300C5045: Cooling only: 2-pipe fan coil unit with single speed fan,
2-Position cooling valve and fresh air damper ...................................................................20
SE7300F5045: heating/cooling with changeover sensor and reheat: 2-pipe fan coil unit with 3-speed fan, analogue valve, and
electric reheat ...................................................................................................................22
SE7300F5045: Cooling with reheat: 4-pipe fan coil unit with
3-speed fan, analogue cooling valve and on/off heating valve ..........................................24
SE7300F5045: Cooling only: 2-pipe fan coil unit with
3-speed fan and 0-10 VDC analogue cooling valve ...........................................................26
SE7300C5045: Cooling with reheat: 2-pipe fan coil unit with
3-speed fan, 2-position valve and electric reheat .............................................................28
SE7350F5045: Heating/cooling: 4-pipe fan coil unit with
3-speed fan, 0-10 VDC analogue valves and dehumidification sequence ........................ 30
SE7350C5045: Heating/cooling: 4-pipe fan coil unit with
3-speed fan, 2-position valves, and dehumidification sequence .......................................32
SE7350C5045: Heating/cooling: 4-pipe fan coil unit with
3-speed fan, tri-state floating valves and dehumidification sequence ............................... 34
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4 January 2016
SER7300A5045 - SC3500E5045: Heating/cooling: 4-pipe fan coil
unit with 3-speed fan, 2-position valves with wireless door switch .................................. 36
SER7350A5045 - SC3404E5045: Cooling and electric heat: 2-pipe fan coil unit
with 3-speed fan, dehumidification, 2-position valves ...................................................... 38
SER7300A5045 - SC3504E5045: Heating/cooling with changeover sensor:
2-pipe fan coil unit with 3-speed fan and wirelesss window switch .................................. 40
SER7350A5045 - SC3400E5045: Cooling and electric heat: 2-pipe fan coil unit
with 3-speed fan and dehumidification, 2-position valves .................................................42
SER7300A5545 - SC3514E5045: Heating/cooling: 2-pipe fan coil unit
with 3-speed fan and fresh air damper, 2-position valves ................................................ 44
SER7300A5045 -SC3500E5045 -SC3300E5045: Heating/cooling:
4-pipe fan coil unit with 3-speed fan, 2-position valves with slave relay pack .................. 46
SER7300A5045 - SC3504E5045: Cooling and electric heat:
2-pipe fan coil unit with 3-speed fan, 2-position valves with wired window switch ........... 48
SER7300A5045 - SC3500E5045: Heating/cooling: 4-pipe fan coil unit
with 3-speed fan, 2-position valves with wired door switch ............................................. 50
Appendix A - Passive infra-red (PIR) motion detector
cover specifications ......................................................................................................... 53
Appendix B - option network wiring if communicating models are used .......................... 54
Appendix C - controllers’ occupancy sequence of
operation schematic ........................................................................................................ 54
Appendix D - VWA5000 series - wireless door & window switch ..................................... 55
Appendix E - SER7300 controller & SC3000 relay pack ...................................................57
Appendix F - SE7300 low voltage fan coil controller .........................................................59
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4 January 2016
Product & application selector
SER7300 & Relay Pack
Power Building
Line Voltage
Function
Commercial Yes 2 or 4 pipe,
Hospitality Ye s 2 or 4 pipe,
Humidity Control
No 2 Pipe, Up
Application Outputs /
Up to 3 speed fan
to 3 speed fan
Up to 3 speed fan
Inputs
1H/1C with Reheat
1H/1C with 4 inputs and reheat
1H/1C with 4 inputs reheat and occ. output
1H/1C with pulsed reheat
1H/1C with pulsed reheat and 4 inputs
1H/1C with Reheat
1H/1C with 4 inputs and reheat
Controller Relay Pack Typical
Application
SER7350A5045 SC3500E5045 Page: 38, 42
SER7350A5045 SC3504E5045 Page: 40, 44
SER7350A5045 SC3514E5045 Page: 44
SER7300A5045 SC3400E5045 Page: 42
SER7300A5045 SC3404E5045 Page: 38
SER7355A5045* SC3500E5045 Page: 36, 50
SER7355A5045* SC3504E5045 Page: 40, 48
1H/1C with 4 inputs reheat and occ. output
No 2 Pipe, Up
to 3 speed fan
Slave fan control only
*The Hospitality/Lodging models are identical to the commercial controllers except for the Override key which is replaced with a °C/°F key to switch between Celsius and Fahrenheit units.
At the end of the model number, add B for BACnet communication or W for Zigbee wireless communication. Ex: SER7300A5045B or SER7300A5045W
1H/1C with pulsed reheat
1H/1C with pulsed reheat and 4 inputs
3 fan outputs
SER7355A5045* SC3514E5045 Page: 44
SER7305A5045* SC3400E5045 Page: 42
SER7305A5045* SC3404E5045 Page: 38
SER73xxA5045 SC3300E5000 Page: 46
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4 January 2016
SER7300 and SC3000 | Fan coil terminal equipment controllers
This new cost-effective solution for upgrading line-voltage fan coil unit thermostats requires only two components: the SER7300 terminal equipment control­ler and the SC3000 relay pack. This solution allows existing line voltage wiring between the fan coil unit and temperature controller to be re-used, reducing overall costs and installation time. The SC3000 relay pack features an onboard universal voltage power supply and line-voltage relays which directly drive fractional horsepower fan motors and valves. This eliminates the need to install and wire costly pilot relays and transformers.
Commercial interface (local override)
Part Number Description Humidity PIR Cover Communication
SER730 0A5045 Stand-alone fan coil terminal equipment controller No No Stand-alone (network ready)
SER7300A5045B BACnet fan coil terminal equipment controller No No BACnet
SER730 0A5045W Wireless fan coil terminal equipment controller No No Wireless
SER7300A5545 Stand-alone fan coil terminal equipment controller No Yes Stand-alone (network ready)
SER7300A5545B BACnet fan coil terminal equipment controller No Yes BACnet
SER7300A5545W Wireless fan coil terminal equipment controller No Yes Wireless
SER7350A5045 Stand-alone fan coil terminal equipment controller Yes No Stand-alone (network ready)
SER7350A5045B BACnet fan coil terminal equipment controller Yes No BACnet
SER7350A5045W Wireless fan coil terminal equipment controller Yes No Wireless
SER7350A5545 Stand-alone fan coil terminal equipment controller Yes Yes Stand-alone (network ready)
SER7350A5545B BACnet fan coil terminal equipment controller Yes Ye s BACnet
SER7350A5545W Wireless fan coil terminal equipment controller Yes Ye s Wireless
Hotel/lodging interface (°C/°F selection)
Part Number Description Humidity PIR Cover Communication
SER730 5A504 5 Stand-alone fan coil terminal equipment controller No No Stand-alone (network ready)
SER7305A5045B BACnet fan coil terminal equipment controller No No BACnet
SER730 5A504 5W Wireless fan coil terminal equipment controller No No Wireless
SER7305A5545 Stand-alone fan coil terminal equipment controller No Yes Stand-alone (network ready)
SER7305A5545B BACnet fan coil terminal equipment controller No Ye s BACnet
SER7305A5545W Wireless fan coil terminal equipment controller No Ye s Wireless
SER7355A5045 Stand-alone fan coil terminal equipment controller Yes No Stand-alone (network ready)
SER7355A5045B BACnet fan coil terminal equipment controller Yes No BACnet
SER7355A5045W Wireless fan coil terminal equipment controller Yes No Wireless
SER7355A5545 Stand-alone fan coil terminal equipment controller Yes Yes Stand-alone (network ready)
SER7355A5545B BACnet fan coil terminal equipment controller Yes Yes BACnet
SER7355A5545W Wireless fan coil terminal equipment controller Yes Ye s Wireless
Transformer relay packs for fan coil units
Part Number Description
SC3500E5045 1 heat/cool output, 1 cool output, and 3 fan outputs
SC3504E5045 1 heat/cool output, 1 cool output, 3 fan outputs and four inputs
SC 3514 E5 04 5 1 heat/cool output, 1 cool output, 3 fan outputs, Occupancy output (7Vdc), and four inputs
SC3400E5045 1 heat/cool output, 1 Modulating pulsed Vdc output for SSR ele ctric reh eat contro l, and 3 fan outputs
SC3404E5045 1 heat/cool ou tput, 1 Modulating pulsed Vdc outpu t for SSR electric reheat control, and 3 fan outputs
SC3300E5045
3 slave fan o utputs
Wireless accessories*
Part Number Description
VWA5000D5045W Wireless door switch
VWA5000W5045W Wireless window switch
* Wireless accessories are compatible with all the VWA, SER7300, and wireless models.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4 January 2016
SE7300 | Fan coil room controllers
Power Application Building
Low
- 2 or 4 Pipe
Function
Commercial Yes On-Off
Voltage
- Hot/Chill water valves
- Up to 3 speed fan
- Automatic Changeover
-Auxiliary contact output
Hospitality / Lodging
Humidity Control
Outputs / Inputs
1H/1C
Floating 1H/1C
Analogue 1H/1C
No On-Off
1H/1C
Floating 1H/1C
Analogue 1H/1C
Yes
On-Off 1H/1C
Floating 1H/1C
Controller Typical
Application
SE7350C5045 Page: 20, 32
SE7350C5045 Page: 12, 34
SE7350F5045 Page: 16, 30
SE7300C5045 Page: 28
SE7300C5045 Page: 14
SE7300F5045 Page: 22, 24, 26
SE7355C5045* Page: 18, 20, 32
SE7355C5045* Page: 12, 34
Analogue
SE7355F5045* Page: 16, 30
1H/1C
No On-Off
SE7305C5045* Page: 28
1H/1C
Floating
SE7305C5045* Page: 14
1H/1C
Analogue
SE7305F5045* Page: 22, 24, 26
1H/1C
*The Hospitality/Lodging models are identical to the commercial controllers except for the Override key which is replaced with a °C/°F key to switch between Celsius and Fahrenheit units.
Note: At the end of the model number, add B for BACnet communication, E for Echelon communication or
W for Zigbee wireless communication. Ex: SER7300A5045B or SER7300A5045E or SER7300A5045W
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4 January 2016
SE7300 | Fan coil room controllers
Achieve better energy efficiency and reduce operating costs with SE7300 Series room controllers. Ideal for commercial and hotel applications, these fan coil units function with electronically commutated motors to optimise fan control sequences. With the full proportional operating of the SE7300, as opposed to the traditional three-speed tap operation, customers will experience better control and a more comfortable environment.
Commercial interface (local override)
Part Number Description Humidity Output PIR Cover Communication
SE730 0C504 5
SE730 0C504 5B
SE7300C5045E
SE730 0C504 5W
SE730 0C5545
SE730 0C5545B
SE7300C5545E
SE730 0C5545W
SE730 0F504 5
SE730 0F504 5B
SE7300F5045E
SE730 0F504 5W
SE730 0F554 5
SE730 0F554 5B
SE7300F5545E
SE730 0F554 5W
SE7350C5045
SE7350C5045B
SE7350C5045E
SE7350C5045W
SE7350C554 5
SE7350C554 5B
SE7350C5545E
SE7350C554 5W
SE7350F5045
SE7350F5045B
SE7350F5045E
SE7350F5045W
SE7350F5545
SE7350F5545B
SE7350F5545E
SE7350F5545W
Stand-alone fan coil controller No Floating or on/of f No Stand-alone (network ready)
BACnet fan coil controller No Floating or on/off No BACnet
LON fan coil controller No Floating or on/off No LonWorks
Wireless fan coil controller No Floating or on /off No Wireless
Stand-alone fan coil controller No Floating or on/of f Ye s Stand-alone (network ready)
BACnet fan coil controller No Floating or on/off Ye s BACnet
LON fan coil controller No Floating or on/off Ye s LonWorks
Wireless fan coil controller No Floating or on /off Yes Wireless
Stand-alone fan coil controller No 0 - 10 V No Stand-alone (network ready)
BACnet fan coil controller No 0 - 10 V No BACnet
LON fan coil controller No 0 - 10 V No LonWorks
Wireless fan coil controller No 0 - 10 V No Wireless
Stand-alone fan coil controller No 0 - 10 V Yes Stand-alone (network ready)
BACnet fan coil controller No 0 - 10 V Yes BACnet
LON fan coil controller No 0 - 10 V Yes LonWorks
Wireless fan coil controller No 0 - 10 V Ye s Wireless
Stand-alone fan coil controller Ye s Floating or on/off No Stand-alone (network ready)
BACnet fan coil controller Yes Floating or on/off No BACnet
LON fan coil controller Yes Floating or on/off No LonWorks
Wireless fan coil controller Ye s Floating or on/ off No Wireless
Stand-alone fan coil controller Ye s Floating or on/off Yes Stand-alone (network ready)
BACnet fan coil controller Yes Floating or on/off Yes BACnet
LON fan coil controller Yes Floating or on/off Yes LonWorks
Wireless fan coil controller Ye s Floating or on/ off Ye s Wireless
Stand-alone fan coil controller Ye s 0 - 10 V No Stand-alone (network ready)
BACnet fan coil controller Yes 0 - 10 V No BACnet
LON fan coil controller Yes 0 - 10 V No LonWorks
Wireless fan coil controller Ye s 0 - 10 V No Wireless
Stand-alone fan coil controller Ye s 0 - 10 V Ye s Stand-alone (network ready)
BACnet fan coil controller Yes 0 - 10 V Yes BACnet
LON fan coil controller Yes 0 - 10 V Yes LonWorks
Wireless fan coil controller Ye s 0 - 10 V Yes Wireless
The Hospitality/Lodging models are identical to the commercial controllers except for the Override key which is replaced with a °C/°F key to switch between Celsius and Fahrenheit units.The only difference in the p/n is that the 6th character is a 5 instead of a zero - Example: SE7305 rather than SE7300.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4 January 2016
Cost-saving, energy-saving applications
From hotels and hospitals to schools, retail, and commercial buildings, Schneider Electric offers wide-ranging room control solutions for your building management needs. Whether retrofitting current systems with a more technologically advanced room controller or going green with a more environmentally friendly option, SE7000 Series is the ideal, cost-competitive solution. The SE7000 Series room controllers can be equipped with an integrated passive infrared motion sensor for demand-based occupancy control that opens up new opportunities in smart energy management.
Open communications
Advance control of your building with truly open, integrated communications. Open protocol options include ZigBee® wireless, BACnet®, and LonWorks® infrastructure.
Lower total install co st
Accelerate your return on investment by saving time and resources from the beginning. Our easy-to-install systems integrate into any new or existing building, with no requirement for costly, specialised labour.
Efficient control
Take full control of your building’s HVAC equipment. We’ll make it simple with intuitive, application-based products specifically designed for your needs.
Occupancy sensing
Equip your room controller with an integrated passive infrared motion sensor for demand-based occupancy control that raises your energy efficiency to a whole new level.
Energy savings
Save energy. Save money. With SE7000 Series room controllers you’ll reduce energy costs without sacrificing comfort one bit.
Temperature and humidity sensing
Deliver efficient, measureable control. If you can measure it, you can control it — providing more precise occupant comfort and productivity.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4 January 2016
Energy savings for a healthy bottom line.
Increase the c omfort of patients, visitors, and employees while reducing energy consumption with SE7000 Series room c ontrollers.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4 January 2016
SE7000 network ready communication adapters
All current “Network Ready” Schneider-Electric SE7000 controllers are capable of being retrofit in the field with accessory communication adapters that enables the controllers to be integrated into virtually all leading building automation systems
This approach allows the flexibility to add network communication strategies as budgets allow or as the buildings needs change.
If required, Network Ready (stand-alone) Terminal Equipment Controllers can be field retrofitted with the following communication adapters.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4 January 2016
Comf ortable workers are more productive.
Accelerate your return on investment with SE7000 Ser ies room c ontrollers.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4 January 2016
SE7350C5045: Heating/cooling: 4-pipe fan coil unit with 3-speed fan, tri-state floating valves and dehumidification sequence
Valve
Heating Coil
Tri-state Floating
Valve
Optional PIR cover: COV-PIR-FCU-C-5045.
Refer to Schneider Electric Catalogue for valves and actuators.
Cooling Coil
FAN
Tri-state Floating
SE7350C
Configuration parameter name
PswrdSet 0 is factory set, range is: 0-1000 BI1 None BI2 None UI3 None MenuScro ON AutoMode ON C or F As per user. Default value = °F %RH disp ON Lockout As per user. Default value = 0 No lock Pipe No 4.0 CntrlTyp Floating SeqOpera 4 = Cooling / Heating 4 pipes Fan Menu 2 DHumiLCK ON %RH set As per user. Default value = 50%. Range = 30% to 95% DehuHyst As per user. Default value = 5%. Range = 2% to 20% DehuCool As per user. Default value = 100%. Range = 20% to 100% St-By TM 0.5 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments Unocc TM 0.0 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments St-By HT 69 °F is factory set, range is: 40 to 90 °F ( 4.5 to 32.0 °C ) St-By CL 78 °F is factory set, range is: 54 to 100 °F ( 12.0 to 37.5 °C ) Unocc HT As per user. Default value = 62 °F ( 17 °C ). Range = 40 to 90 °F ( 4.5 to 32.0 °C ) Unocc CL As per user. Default value = 80 °F ( 27 °C ). Range = 54 to 100 °F ( 12 to 37.5 °C ) heat max As per user. Default value = 90 °F ( 32 °C ). Range = 40 to 90 °F ( 4.5 to 32.0 °C ) cool min As per user. Default value = 54 °F ( 12 °C ). Range = 54 to 100 °F ( 12 to 37.5 °C ) Pband 2 °F is factory set, range is: 2 to 10 °F ( 0.6 to 5.6 °C ) Set Type Permanent SptFunc Dual Stp or AttchStp TOccTime As per user. Default value 2 hours. Range = 0 to 24 hours DoorTime N/A
deadband
cal RS 0 °F or °C cal RH 0 °F or °C aux cont 0 Auto Fan AS or AS AD FL time As per user. Default value = 1.5 minutes. Range 0.5 to 9.0 in 0.5 minutes increments cph N/A Reheat 0 for ON/OFF ( 4CPH ), 1 for PWM ( 10 second ) UI3 dis Displays supply air temperature
Configuration settings
As per user. Default value 2.0 °F ( 1.0 °C ). Range = 2, 3, 4 or 5 °F, 1.0 °F increments ( 1.0 to 2.5 °C, 0.5 °C increments )
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4 January 2016
Sequence of operation and wiring
%RH Setpoint
Hysterisys = 10%
(adjustable)
1/2 Hysterisys = 5%
1/2 Hysterisys = 5%
ON
OFF
Dehumidification = OFF
Dehumidification = ON
24V
COM
FAN-L
FAN-M
FAN-H
BO1
BO2
HEATING
BO3
BO4
COOLING
Close
Open
Close
Open
Fan coil relay control center (Generic)
24V
Com
L
M
H
24V
Com
R
R
R
To Fan Coil Unit
Com
L
M
H
24V
Com
120V
SE7350C Controller
24VAC - 230VAC
Occupied Mode:
Setpoints will revert to those defined by occupied cooling and heating.
The changeover sensor will send the supply air temperature to the controller.
Stand-by Mode (only available when PIR motion detector cover is used):
Setpoints will revert to those defined by stand­by cooling and heating.
Unoccupied Mode:
Setpoints will revert to those defined by unoccupied heating and cooling.
Occupied Override Mode:
The system will revert to occupied mode for the duration determined by the “ToccTime” parameter.
On a call for cool:
Cooling valve will modulate to maintain room temperature. Heating valve is closed. Dehumidification is enabled.
Dehumidification ON/OFF Sequence:
On a call for heat:
Heating valve will modulate to maintain room temperature. Cooling valve is closed. Dehumidification is disabled.
On a demand for dehumidification:
Dehumidification is achieved via the cooling coil using the heating coil for reheat if necessary.
Dehumidification is only allowed in COOL mode (or if cooling is enabled in AUTO mode).
Dehumidification is disabled if the room temperature falls below the low ambient lockout temperature. Which is the cooling setpoint minus the configuration defined deadband value.
Reheat is disabled if cooling demand reaches 100%.
Options
BACnet, Echelon and Wireless communication models available (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Analogue outputs available (SE73xxF5045).
Can be configured for 2 pipe systems.
Binary inputs can be configured to control occupancy via door or window contact, remote night setback or to provide alarms for service or filter monitoring.
Universal input can be configured for a changeover sensor.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4 January 2016
SE7300C5045: Heating/cooling with changeover and reheat: 2-pipe fan coil unit with 3-speed fan, tri-state floating valve and electric reheat.
Heating/Cooling
Coil
FAN
Sensor: 10K Ohm Type 2.
Floating
Valve
SE7300C
Configuration parameter name
PswrdSet 0 is factory set, range is: 0-1000 BI1 None
BI2 None
UI3 COS MenuScro ON AutoMode ON C or F As per user. Default value = °F Lockout As per user. Default value = 0 No lock Pipe No 2.0 CntrlTyp Floating SeqOpera 2 = Cooling with Reheat Fan Menu 2 St-By TM 0.5 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments Unocc TM 0.0 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments St-By HT 69 °F is factory set, range is: 40 to 90 °F ( 4.5 to 32.0 °C ) St-By CL 78 °F is factory set, range is: 54 to 100 °F ( 12.0 to 37.5 °C ) Unocc HT As per user. Default value = 62 °F ( 17 °C ). Range = 40 to 90 °F ( 4.5 to 32.0 °C ) Unocc CL As per user. Default value = 80 °F ( 27 °C ). Range = 54 to 100 °F ( 12 to 37.5 °C ) heat max As per user. Default value = 90 °F ( 32 °C ). Range = 40 to 90 °F ( 4.5 to 32.0 °C ) cool min As per user. Default value = 54 °F ( 12 °C ). Range = 54 to 100 °F ( 12 to 37.5 °C ) Pband 2 °F is factory set, range is: 2 to 10 °F ( 0.6 to 5.6 °C ) Set Type Permanent SptFunc Dual Stp or AttchStp TOccTime As per user. Default value 2 hours. Range = 0 to 24 hours DoorTime N/A
deadband
cal RS 0 °F or °C cal RH 0 °F or °C aux cont 0 Auto Fan AS or AS AD FL time As per user. Default value = 1.5 minutes. Range 0.5 to 9.0 in 0.5 minutes increments cph N/A Reheat 0 for ON/OFF ( 4CPH ), 1 for PWM ( 10 second ) UI3 dis Displays supply air temperature
Configuration settings
As per user. Default value 2.0 °F ( 1.0 °C ). Range = 2, 3, 4 or 5 °F, 1.0 °F increments ( 1.0 to 2.5 °C, 0.5 °C increments )
Optional PIR cover: COV-PIR-FCU-C-5045.
Refer to Schneider Electric Catalogue for valves and actuators.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4 January 2016
Sequence of operation and wiring
24V
COM
FAN-L
FAN-M
FAN-H
BO1
BO2
actuator
UI3
Scom
BO5
BO5
C/O Sensor
SE7300C Controller
Cooling/heating valve
Fan coil relay control center (Generic)
24VAC - 230VAC
24V
Com
L
M
H
R
R
R
To Fan Coil Unit
Com
L
M
H
120V
R
Perimeter Heating
Occupied Mode:
Setpoints will revert to those defined by occupied cooling and heating.
The changeover sensor will send the supply air temperature to the controller.
Stand-by Mode (only available when PIR motion detector cover is used):
Setpoints will revert to those defined by stand­by cooling and heating.
Unoccupied Mode:
Setpoints will revert to those defined by unoccupied heating and cooling.
Occupied Override Mode:
The system will revert to occupied mode for the duration determined by the “ToccTime” parameter.
On a call for cool:
If water temperature is less than 24°C (75°F), valve will open to allow water flow. If supply air temperature is greater than 25°C (77°F), valve will close. Baseboard is always desactivated.
On a call for heat:
If water temperature is less than 24°C (75°F), valve will close and the duct heater will be activated. If water temperature is greater than 25°C (77°F), valve will open to allow water flow. If the water flow is unable to satisfy the demand, the baseboard is activated.
Options
BACnet, Echelon and Wireless models available (see Appendix B for network wiring).
Analogue 0-10 VDC outputs available (SE73xxF5045).
Remote wall mount or duct sensor ready.
Can be configured for 4 pipe systems.
Can be configured to single or two speed fan.
Binary inputs can be configured to control occupancy via door or window contact, remote night setback or to provide alarms for service or filter monitoring.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4 January 2016
SE7350F5045: Heating/cooling: 4-pipe fan coil unit with 3-speed fan, 0-10 VDC Analogue valves and dehumidification sequence
Cooling Coil
FAN
Analogue
Cooling
Valve
SE7350F
Configuration parameter name
PswrdSet BI1 BI2
UI3 MenuScro AutoMode C or F %RH disp Lockout Pipe No SeqOpera Fan Menu DHumiLCK %RH set DehuHyst DehuCool St-By TM Unocc TM St-By HT St-By CL Unocc HT Unocc CL heat max cool min
Pband Set Type SptFunc TOccTime DoorTime deadband As per user. Default value 2.0 °F ( 1.0 °C ). Range = 2, 3, 4 or 5 °F, 1.0 °F increments
cal RS cal RH aux cont Auto Fan RA/DA Reheat
UI3 dis Displays supply air temperature
Configuration settings
0 is factory set, range is: 0-1000 None
None
None ON ON As per user. Default value = °F ON As per user. Default value = 0 No lock
4.0 4 = Cooling / Heating 4 pipes 2 ON As per user. Default value = 50%. Range = 30% to 95% As per user. Default value = 5%. Range = 2% to 20% As per user. Default value = 100%. Range = 20% to 100%
0.5 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments
0.0 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments 69 °F is factory set, range is: 40 to 90 °F ( 4.5 to 32.0 °C ) 78 °F is factory set, range is: 54 to 100 °F ( 12.0 to 37.5 °C ) As per user. Default value = 62 °F ( 17 °C ). Range = 40 to 90 °F ( 4.5 to 32.0 °C ) As per user. Default value = 80 °F ( 27 °C ). Range = 54 to 100 °F ( 12 to 37.5 °C ) As per user. Default value = 90 °F ( 32 °C ). Range = 40 to 90 °F ( 4.5 to 32.0 °C ) As per user. Default value = 54 °F ( 12 °C ). Range = 54 to 100 °F ( 12 to 37.5 °C ) 2 °F is factory set, range is: 2 to 10 °F ( 0.6 to 5.6 °C ) Permanent Dual Stp or AttchStp As per user. Default value 2 hours. Range = 0 to 24 hours N/A
( 1.0 to 2.5 °C, 0.5 °C increments ) 0 °F or °C
0 °F or °C 0 AS or AS AD Reverse Acting (RA) or Direct Acting (DA), depends on actuator 0 for ON/OFF ( 4CPH ), 1 for PWM ( 10 second )
Heating Coil
Analogue
Heating
Valve
Optional PIR cover: COV-PIR­FCU-C-5045.
Refer to Schneider Electric Catalogue for valves and actuators.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4 January 2016
%RH Setpoint
Hysterisys = 10%
(adjustable)
1/2 Hysterisys = 5% 1/2 Hysterisys = 5%
ONOFF
Dehumidification = OFF
Dehumidification = ON
Sequence of operation and wiring
24V
COM
FAN-L
FAN-M
FAN-H
AO1
AO2
Fan coil relay control center (Generic)
HEATING
0-10 VDC
COOLING
24V
Com
L
M
H
24V
Com
R
R
R
To Fan Coil Unit
SE7350F Controller
0-10 VDC
Com
L
M
H
24V
Com
120V
24VAC - 230VAC
Occupied Mode:
Setpoints will revert to those defined by occupied cooling and heating.
The changeover sensor will send the supply air temperature to the controller.
Stand-by Mode (only available when PIR motion detector cover is used):
Setpoints will revert to those defined by stand­by cooling and heating.
Unoccupied Mode:
Setpoints will revert to those defined by unoccupied heating and cooling.
Occupied Override Mode:
The system will revert to occupied mode for the duration determined by the “ToccTime” parameter.
On a call for cool:
Cooling valve will modulate to maintain room temperature. Heating valve is closed.
Dehumidification is enabled.
On a call for heat:
Heating valve will modulate to maintain room temperature. Cooling valve is closed.
Dehumidification is disabled.
ON/OFF Sequence:
On a demand for dehumidification:
Dehumidification is achieved via the cooling coil using the heating coil for reheat if necessary.
Dehumidification is only allowed in COOL mode (or if cooling is enabled in AUTO mode).
Dehumidification is disabled if the room temperature falls below the low ambient lockout temperature. Which is the cooling setpoint minus the configuration defined deadband value.
Reheat is disabled if PI cooling demand reaches 100%.
Options
BACnet, Echelon and Wireless communication models available (see Appendix B for network wiring).
Remote wall mount or duct sensor ready.
Can be configured for 2 pipe systems.
Binary inputs can be configured to control occupancy via door or window contact, remote night setback or to provide alarms for service or filter monitoring.
Universal input can be configured for a changeover sensor.
Schneider Electric | AG-SE7000-FCU-A4.EN.01.2016.v4 January 2016
SE7355C5045: Heating/cooling: 4-pipe fan coil unit with 3-speed fan, 2-position valves, and dehumidification sequence
Valve
Heating Coil
2-Position
Heating
Valve
Optional PIR cover: COV-PIR-FCU-L-5045.
Refer to Schneider Electric Catalogue for valves and actuators.
Cooling Coil
FAN
2-Position
Cooling
SE7355C
Configuration parameter name
PswrdSet 0 is factory set, range is: 0-1000 BI1 None BI2 None UI3 None MenuScro ON AutoMode ON C or F As per user. Default value = °F %RH disp ON Lockout As per user. Default value = 0 No lock Pipe No 4.0 CntrlTyp On/Off SeqOpera 4 = Cooling / Heating 4 pipes Fan Menu 2 DHumiLCK ON %RH set As per user. Default value = 50%. Range = 30% to 95% DehuHyst As per user. Default value = 5%. Range = 2% to 20% DehuCool As per user. Default value = 100%. Range = 20% to 100% St-By TM 0.5 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments Unocc TM 0.0 hours is factory set, range is: 0.0 to 24.0 hours in 0.5hr increments St-By HT 69 °F is factory set, range is: 40 to 90 °F ( 4.5 to 32.0 °C ) St-By CL 78 °F is factory set, range is: 54 to 100 °F ( 12.0 to 37.5 °C ) Unocc HT As per user. Default value = 62 °F ( 17 °C ). Range = 40 to 90 °F ( 4.5 to 32.0 °C ) Unocc CL As per user. Default value = 80 °F ( 27 °C ). Range = 54 to 100 °F ( 12 to 37.5 °C ) heat max As per user. Default value = 90 °F ( 32 °C ). Range = 40 to 90 °F ( 4.5 to 32.0 °C ) cool min As per user. Default value = 54 °F ( 12 °C ). Range = 54 to 100 °F ( 12 to 37.5 °C ) Pband 2 °F is factory set, range is: 2 to 10 °F ( 0.6 to 5.6 °C ) Set Type Permanent SptFunc Dual Stp or AttchStp TOccTime As per user. Default value 2 hours. Range = 0 to 24 hours DoorTime N/A
deadband
cal RS 0 °F or °C cal RH 0 °F or °C aux cont 0 Auto Fan AS or AS AD FL time As per user. Default value = 1.5 minutes. Range 0.5 to 9.0 in 0.5 minutes increments cph As per user. 4 to 8 CPH Reheat 0 for ON/OFF ( 4CPH ), 1 for PWM ( 10 second ) UI3 dis Displays supply air temperature
Configuration settings
As per user. Default value 2.0 °F ( 1.0 °C ). Range = 2, 3, 4 or 5 °F, 1.0 °F increments ( 1.0 to 2.5 °C, 0.5 °C increments )