Power Monitoring Single-Circuit |
Enercept® kW/kWh Transducers
(4 to 20 mA or Pulse Output)
H804x
& H805x Series
H804x/H805x
Patent #6,373,238
SPECIFICATIONS
Agency Approvals UL508
INPUTS
Voltage Input 208/240 or 4 80 Vac, 50/60 Hz RMS
Current Input Up to 2400 A cont inuous per phase
ACCURACY
System Accuracy
Output 4 to 20 mA
Supply Power
(current loop)
Pulsed Output Field sele ctable; 1, 0.5, 0.25, 0.1 kWh/pulse
Pulsed Output Type Normally O pen, Opto-FET, 100 mA@24 Vdc
Operating Temp Range 0 to 60 °C (32 to 140 °F), 50 ° C (122 °F) f or 2400 A
Humidity Range 0 to 95% non-c ondensing; indoor u se only
Limited Warranty 5 years
1. Do not install on the line or load side of a VFD unit, or on any other equipment
generating harmonics. For line side applications, use the E5x Series meters.
2. Contact factory to interface with voltages above 480 Vac or current above 2400 A.
3. Do not apply 600 V Class current transformers to circuits having a phase-to-phase
voltage greater than 600 V, unless adequate additional insulation is applied between
the primary conductor and the current transformers. Veris assumes no responsibility for
damage of equipment or personal injury caused by products operated on circuits above
their published ratings.
4. Count must be multiplied by the number of phases when using single CT models to
monitor balanced multiphase systems.
±1% of rea ding from 10% to 100% of t he rated current of
the CTs, accomp lished by matching th e CTs with electro nics
and calibrating them as a system
OUTPUTS
H804X
9 to 30 Vdc, 30 mA max.
H805X
ENVIRONMENTAL
WARRANTY
1,2,3
2,3
4
INTEGRAL MONITORING SOLUTION ELIMINATES THE NEED FOR SEPARATE ENCLOSURES
DESCRIPTION
The Enercept H804x and H805x Series kW (real power)/kWh
(consumption) transducers combine processing electronics & industrial grade
CTs in an easy-to-install split-core package. These devices continuously
measure voltage and current values for the monitored conductors and
update calculations to provide highly accurate true RMS power readings.
Models designed for balanced loads include one CT only, while models for
unbalanced loads have three CTs for improved accuracy.
The unique design of the H804x/H805x Series transducers reduces the
number of installed components, making them ideal for monitoring electrical
power in commercial and industrial facilities The H804x provides industrystandard 4 to 20 mA output, and the H805x provides a pulse output.
Installation is simple. The H804x/H805x eliminates the need to mount and
wire a transducer and enclosure. CTs and voltage leads are color-matched, &
the meters are designed to detect and automatically compensate for phase
reversal. No more worries about CT load orientation.
TM
FEATURES
• Revenue Grade measurements
• Fast split-core installation virtually eliminates the need
to remove conductors...perfect for retrofits
• Precision meter electronics and current transformers
in a single package... reduces the number of installed
components...creating significant labor savings
• Smart electronics virtually eliminate the need to be concerned with CT
orientation...fast trouble-free installation
APPLICATIONS
• Optimize chillers, pumps and cooling towers
• Energy management and performance contracting
• Control processes
• Activity-based costing in commercial and industrial facilities
• Monitor real-time power
• Load shedding
HQ0001811.F 0116
H804x/H805x 208 or 480 Vac 3Ø, 3/4-Wire
120
Yellow Voltage
Lead Capped
N
120
Yellow CT
4 to 20 mA Output
Red CT
Black CT
Black
Red
A
B
E
F
C
D
B
E
F
C
D
A
A
B
E
C
F
D
SMALL
100/300 Amp
MEDIUM
400/800 Amp
LARGE
800/1600/2400 Amp
A = 3.8" (96 mm)
B = 1.2" (30 mm)
C = 1.3" (31 mm)
D = 1.2" (30 mm)
E = 4.0" (100 mm)
F = 4.8" (121 mm)
A = 4.9" (125 mm)
B = 2.9" (73 mm)
C = 2.5" (62 mm)
D = 1.2" (30 mm)
E = 5.2" (132 mm)
F = 6.0" (151 mm)
A = 4.9" (125 mm)
B = 5.5" (139 mm)
C = 2.5" (62 mm)
D = 1.2" (30 mm)
E = 7.9" (201 mm)
F = 6.0" (151 mm)
ØB
ØA
Black
Red
ØC
H804x 240 Vac 1Ø, 3-Wire
Yellow
Power Monitoring Single-Circuit | H804x & H805x Series
DIMENSIONAL DRAWINGSWIRING DIAGRAMS
4 to 20 mA or Pulse Output
Black CT
Red CT
Yellow CT
H805x 208 or 480 Vac 3Ø, 3/4-Wire
ØB
ØA
ØC
ORDERING INFORMATION
Pulse Output Power Transducers
Single CT Models for Use with Balanced 3Ø Loads
Three CT Models for Use with Unbalanced 3Ø Loads
MODEL VOLTA GE MAX. AMPS OUTPUT CT SIZE C T TYPE
H8051-0100-2
H8051-0300-2 300 SMALL
208 /480
H8051-0400-3 400 MEDIUM
H8051-0800-3 800 MEDIUM
H8051-0800-4 800 LARGE
H8 051-1 600 -4 1600 LARGE
H8 051-240 0- 4 2400 LARGE
H8053-0100-2 100 SMALL
H8053-0300-2 300 SMALL
H8053-0400-3 400 MEDIUM
H8053-0800-3 800 MEDIUM
H8053-0800-4 800 LARGE
H8 053 -160 0-4 1600 LARGE
H8 053-24 00- 4 2400 LARGE
ACCESSORIES
CT Mounting brackets (AH06)
HQ0001811.F 0116
100
Pulse
ORDERING INFORMATION
4 to 20 mA Output Power Transducers
Single CT Models for Use with Balanced 3Ø Loads
Three CT Models for Use with Unbalanced 3Ø Loads
MODEL VOLTA GE MAX. AMPS OUTPUT CT SIZE CT T YPE
H8041-0100-2
H8041-0300-2 300 SMALL
H8041-0400-3 400 MEDIUM
H8041-0800-3 800 MEDIUM
208 /240
H8041-0800-4 800 L ARGE
H8 041-1 600 -4 16 00 LARGE
H8 041-240 0- 4 2400 LARGE
H8042-0100-2
H8042-0300-2 300 SMALL
SMALL
H8042-0400-3 400 MEDIUM
H8042-0800-3 800 MEDIUM
480
H8042-0800-4 800 L ARGE
Single CT
Model
H8 042 -160 0-4 16 00 LARGE
H8 042-24 00- 4 2400 LARGE
H8043-0100-2
H8043-0300-2 300 SMALL
H8043-0400-3 400 MEDIUM
H8043-0800-3 800 MEDIUM
208 /240
H8043-0800-4 800 L ARGE
Three CT
Model
H8 043 -160 0- 4 1600 LARGE
H8 043-24 00- 4 2400 LARGE
H8044-0100-2
H8044-0300-2 300 SMALL
H8044-0400-3 400 MED IUM
H8044-0800-3 800 MEDIUM
480
H8044-0800-4 800 L ARGE
AH06
H8 04 4-16 00 -4 1600 LARGE
H8 044 -2400 -4 2400 LARGE
Power Monitoring Single-Circuit | H804x & H805x Series
100
100 SMALL
4 to 20 mA
100 SMALL
100 SMALL
SMALL
Single CT
Model
Single CT
Model
Three CT
Model
Three CT
Model