Schneider Electric GVSMODBC9 Installation

Page 1

Galaxy VS

Modular Battery Cabinet
Installation
Up to 9 Battery Strings GVSMODBC9
1/2021
www.schneider-electric.com
Page 2
Legal Information
This guide and its content are protected under applicable copyright laws and furnished for informational use only. No part of this guide may be reproduced or transmitted in any form or by any means (electronic, mechanical, photocopying, recording, or otherwise), for any purpose, without the prior written permission of Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide or its content, except for a non-exclusive and personal license to consult it on an "as is" basis. Schneider Electric products and equipment should be installed, operated, serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by Schneider Electric and its subsidiaries for any errors or omissions in the informational content of this material or consequences arising out of or resulting from the use of the information contained herein.
Go to IEC: https://www.productinfo.schneider-electric.com/portals/ui/galaxyvs_iec/ or UL: https://www.productinfo.schneider-electric.com/portals/ui/galaxyvs_ul/ or scan the QR code above for digital experience and translated manuals.
Page 3
Table of Contents
Important Safety Instructions — SAVE THESE
Modular Battery Cabinet
INSTRUCTIONS
FCC Statement ..........................................................................................6
Electromagnetic Compatibility .....................................................................6
Safety Precautions .....................................................................................6
Additional Safety Precautions After Installation........................................8
Electrical Safety .........................................................................................8
Battery Safety ............................................................................................9
.........................................................................................5
Modular Battery Cabinet Specifications ................................................ 10
Torque Specifications................................................................................13
Modular Battery Cabinet Weights and Dimensions ...................................... 13
Clearance ................................................................................................13
Environment............................................................................................. 14
Installation Procedure for UPS with Internal Batteries ........................ 15
Installation Procedure for UPS for External Batteries .........................16
Prepare for Installation............................................................................. 18
Install the Conduit Box on the Modular Battery Cabinet .....................19
Prepare Modular Battery Cabinet 1 for Signal Cables ........................20
Install the Seismic Anchoring (Option) ..................................................21
Interconnect Modular Battery Cabinet 1 and the Adjacent
UPS
............................................................................................................. 24
Interconnect the Modular Battery Cabinets .......................................... 26
Connect the Power Cables for a UPS Rated for Maximum 100
kW
...............................................................................................................28
Connect the Power Cables for a UPS Rated over 100 kW................. 30
Connect the Signal Cables......................................................................33
Add Translated Safety Labels to Your Product.....................................37
Final Installation ........................................................................................38
990-6161A-001 3
Page 4
Page 5
Important Safety Instructions — SAVE THESE INSTRUCTIONS Modular Battery Cabinet

Important Safety Instructions — SAVE THESE INSTRUCTIONS

Read these instructions carefully and look at the equipment to become familiar with it before trying to install, operate, service or maintain it. The following safety messages may appear throughout this manual or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a “Danger” or “Warning” safety message indicates that an electrical hazard exists which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages with this symbol to avoid possible injury or death.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result in death or serious injury.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment damage.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.
Please Note
Electrical equipment should only be installed, operated, serviced, and maintained by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction, installation, and operation of electrical equipment and has received safety training to recognize and avoid the hazards involved.
990-6161A-001 5
Page 6
Modular Battery Cabinet

FCC Statement

NOTE: This equipment has been tested and found to comply with the limits for
a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.
Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.

Electromagnetic Compatibility

RISK OF ELECTROMAGNETIC DISTURBANCE
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
NOTICE

Safety Precautions

This is a product category C2 UPS product. In a residential environment, this product may cause radio inference, in which case the user may be required to take additional measures.
Failure to follow these instructions can result in equipment damage.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Read all instructions in the installation manual before installing or working on this product.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not install the product until all construction work has been completed and the installation room has been cleaned.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The product must be installed according to the specifications and requirements as defined by Schneider Electric. It concerns in particular the external and internal protections (upstream breakers, battery breakers, cabling, etc.) and environmental requirements. No responsibility is assumed by Schneider Electric if these requirements are not respected.
Failure to follow these instructions will result in death or serious injury.
6 990-6161A-001
Page 7
Important Safety Instructions — SAVE THESE INSTRUCTIONS Modular Battery Cabinet
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS system must be installed according to local and national regulations. Install the UPS according to:
IEC 60364 (including 60364–4–41- protection against electric shock, 60364– 4–42 - protection against thermal effect, and 60364–4–43 - protection against overcurrent), or
NEC NFPA 70, or
Canadian Electrical Code (C22.1, Part 1)
depending on which one of the standards apply in your local area.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Install the product in a temperature controlled indoor environment free of conductive contaminants and humidity.
Install the product on a non-flammable, level and solid surface (e.g. concrete) that can support the weight of the system.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The product is not designed for and must therefore not be installed in the following unusual operating environments:
Damaging fumes
Explosive mixtures of dust or gases, corrosive gases, or conductive or radiant heat from other sources
Moisture, abrasive dust, steam or in an excessively damp environment
Fungus, insects, vermin
Salt-laden air or contaminated cooling refrigerant
Pollution degree higher than 2 according to IEC 60664-1
Exposure to abnormal vibrations, shocks, and tilting
Exposure to direct sunlight, heat sources, or strong electromagnetic fields
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not drill or cut holes for cables or conduits with the gland plates installed and do not drill or cut holes in close proximity to the UPS.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD OF ARC FLASH
Do not make mechanical changes to the product (including removal of cabinet parts or drilling/cutting of holes) that are not described in the installation manual.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
990-6161A-001 7
Page 8
Modular Battery Cabinet
RISK OF OVERHEATING
Respect the space requirements around the product and do not cover the ventilation openings when the product is in operation.
Failure to follow these instructions can result in equipment damage.
Additional Safety Precautions After Installation
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not install the UPS system until all construction work has been completed and the installation room has been cleaned. If additional construction work is needed in the installation room after this product has been installed, turn off the product and cover the product with the protective packaging bag the product was delivered in.
Failure to follow these instructions will result in death or serious injury.
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
NOTICE
DANGER

Electrical Safety

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Electrical equipment must be installed, operated, serviced, and maintained only by qualified personnel.
Apply appropriate personal protective equipment (PPE) and follow safe electrical work practices.
Turn off all power supplying the UPS system before working on or inside the equipment.
Before working on the UPS system, check for hazardous voltage between all terminals including the protective earth.
The UPS contains an internal energy source. Hazardous voltage can be present even when disconnected from the utility/mains supply. Before installing or servicing the UPS system, ensure that the units are OFF and that utility/mains and batteries are disconnected. Wait five minutes before opening the UPS to allow the capacitors to discharge.
A disconnection device (e.g. disconnection circuit breaker or switch) must be installed to enable isolation of the system from upstream power sources in accordance with local regulations. This disconnection device must be easily accessible and visible.
The UPS must be properly earthed/grounded and due to a high leakage current, the earthing/grounding conductor must be connected first.
Failure to follow these instructions will result in death or serious injury.
8 990-6161A-001
Page 9
Important Safety Instructions — SAVE THESE INSTRUCTIONS Modular Battery Cabinet

Battery Safety

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Battery circuit breakers must be installed according to the specifications and requirements as defined by Schneider Electric.
Servicing of batteries must only be performed or supervised by qualified personnel knowledgeable of batteries and the required precautions. Keep unqualified personnel away from batteries.
Disconnect charging source prior to connecting or disconnecting battery terminals.
Do not dispose of batteries in a fire as they can explode.
Do not open, alter, or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may be toxic.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Batteries can present a risk of electric shock and high short-circuit current. The following precautions must be observed when working on batteries
Remove watches, rings, or other metal objects.
Use tools with insulated handles.
Wear protective glasses, gloves and boots.
Do not lay tools or metal parts on top of batteries.
Disconnect the charging source prior to connecting or disconnecting battery terminals.
Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source from ground. Contact with any part of a grounded battery can result in electric shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance (applicable to equipment and remote battery supplies not having a grounded supply circuit).
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
When replacing batteries, always replace with the same type and number of batteries or battery packs.
Failure to follow these instructions will result in death or serious injury.
NOTICE
RISK OF EQUIPMENT DAMAGE
Wait until the system is ready to be powered up before installing batteries in the system. The time duration from battery installation until the UPS system is powered up must not exceed 72 hours or 3 days.
Batteries must not be stored more than six months due to the requirement of recharging. If the UPS system remains de-energized for a long period, Schneider Electric recommends that you energize the UPS system for a period of 24 hours at least once every month. This charges the batteries, thus avoiding irreversible damage.
Failure to follow these instructions can result in equipment damage.
990-6161A-001 9
Page 10
Modular Battery Cabinet Modular Battery Cabinet Specifications

Modular Battery Cabinet Specifications

NOTICE
HAZARD OF EQUIPMENT DAMAGE
Refer to the UPS installation manual for detailed specifications for the UPS system.
Failure to follow these instructions can result in equipment damage.
Maximum four modular battery cabinets can be connected to a UPS.
Number of battery blocks 40
Maximum number of battery strings 9
Nominal battery voltage (VDC) 480
Nominal float voltage (VDC) 545
Maximum boost voltage (VDC) 572
Temperature compensation Enabled
End of discharge voltage (full load) (VDC) 384
Maximum battery current (A) 271
Maximum short circuit rating 10 kA
Trip Settings for Battery Breaker
Breaker type JDF36250
Ir setting 250 (fixed)
Im setting 1250
10 990-6161A-001
Page 11
Modular Battery Cabinet Specifications Modular Battery Cabinet
Recommended Cable Sizes for 380/400/415 V
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
All wiring must comply with all applicable national and/or electrical codes.
Failure to follow these instructions will result in death or serious injury.
NOTE: Overcurrent protection is to be provided by others.
Cable sizes in this manual are based on table B.52.3 and table B.52.5 of IEC 60364-5-52 with the following assertions:
90 °C conductors
An ambient temperature of 30 °C
Use of copper conductors
Installation method C
PE cable size is based on table 54.2 of IEC 60364-4-54.
If the ambient temperature is greater than 30 °C, larger conductors are to be selected in accordance with the correction factors of the IEC.
DC+/DC- (mm2) 70
DC PE (mm
2
) 35
Recommended Cable Sizes for 200/208/220/480 V
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
All wiring must comply with all applicable national and/or electrical codes.
Failure to follow these instructions will result in death or serious injury.
Cable sizes in this manual are based on Table 310.15 (B)(16) of the National Electrical Code (NEC) with the following assertions:
90 °C (194 °F) THHN conductors (75 °C (167 °F) termination)
An ambient temperature of 30 °C (86 °F)
Use of copper conductors
Equipment grounding conductors (PE in this manual) are sized in accordance with NEC Article 250.122 and Table 250.122.
If the ambient temperature is greater than 30 °C (86 °F), larger conductors are to be selected in accordance with the correction factors of the NEC.
DC+/DC- (AWG/ kcmil)
DC PE (AWG/kcmil) 4
990-6161A-001 11
3/0
Page 12
Modular Battery Cabinet Modular Battery Cabinet Specifications
Recommended Bolt and Lug Sizes
NOTICE
RISK OF EQUIPMENT DAMAGE
Use only UL approved compression cable lugs.
Failure to follow these instructions can result in equipment damage.
Copper – One Hole Cable Lugs
Cable size Bolt size Cable lug type Crimping tool Die
4 AWG M8 x 25 mm LCA4-56-L CT-720 CD-720-1 Gray P29
3/0 AWG M8 x 25 mm LCA3/0-56-X CT-720 CD-720-2 Orange P50
Copper – Two Hole Cable Lugs
Cable size Bolt size Cable lug type Crimping tool Die
4 AWG M8 x 25 mm LCC4-12-L CT-930
3/0 AWG M8 x 25 mm LCC3/0-12-X CT-930
CD-920-4 Gray P29
CD-920-3/0 Orange P50
12 990-6161A-001
Page 13
Modular Battery Cabinet Specifications Modular Battery Cabinet

Torque Specifications

Bolt size Torque
M4 1.7 Nm (1.25 lb-ft / 15 lb-in)
M5 2.2 Nm (1.62 lb-ft / 19.5 lb-in)
M6 5 Nm (3.69 lb-ft / 44.3 lb-in)
M8 17.5 Nm (12.91 lb-ft / 154.9 lb-in)
M10 30 Nm (22 lb-ft / 194.7 lb-in)

Modular Battery Cabinet Weights and Dimensions

Commercial reference Weight kg (lbs) Height mm (in) Width mm (in) Depth mm (in)
GVSMODBC9 – Empty – With nine battery strings

Clearance

186 (410)
1970 (77.56) 550 (21.65) 847 (33.35)
1338 (2950)
NOTE: One battery module weighs approximately 32 kg (70.5 lbs).
NOTE: Clearance dimensions are published for airflow and service access
only. Consult with the local safety codes and standards for additional requirements in your local area.
NOTE: The required minimum rear clearance is 150 mm (5.91 in).
990-6161A-001 13
Page 14
Modular Battery Cabinet Modular Battery Cabinet Specifications

Environment

Operating Storage
Temperature 0 °C to 40 °C (32 °F to 104 °F) -15 °C to 40 °C (5 °F to 104 °F)
Relative humidity 0-95% non-condensing 10-80% non-condensing
Elevation 0-3000 m (0-10000 feet)
Protection class IP20
Color RAL 9003, gloss level 85%
14 990-6161A-001
Page 15
Installation Procedure for UPS with Internal Batteries Modular Battery Cabinet

Installation Procedure for UPS with Internal Batteries

NOTE: The modular battery cabinet can be installed adjacent or remote to a
UPS with internal batteries.
Modular Battery Cabinets and Adjacent UPS Rated for Maximum 100 kW
NOTE: The distance between the modular battery cabinet(s) and the UPS
must not exceed 100 m. Contact Schneider Electric for installations with a longer distance.
1. Prepare for Installation, page 18.
Modular Battery Cabinets and Remote UPS Rated for Maximum 100 kW
2. For installation with remote UPS:
a. Install the Conduit Box on the Modular Battery Cabinet, page 19.
b. Prepare Modular Battery Cabinet 1 for Signal Cables, page 20.
3. Install the Seismic Anchoring (Option), page 21.
4. For installation with adjacent UPS: Interconnect Modular Battery Cabinet 1
and the Adjacent UPS, page 24.
5. Interconnect the Modular Battery Cabinets, page 26.
6. Connect the Power Cables for a UPS Rated for Maximum 100 kW, page 28.
7. Connect the Signal Cables, page 33.
8. Add Translated Safety Labels to Your Product, page 37.
9. Final Installation, page 38.
990-6161A-001 15
Page 16
Modular Battery Cabinet Installation Procedure for UPS for External Batteries

Installation Procedure for UPS for External Batteries

NOTE: The modular battery cabinet can only be installed remote to a UPS for
external batteries.
Modular Battery Cabinets and Remote UPS Rated for Maximum 100 kW
Three Modular Battery Cabinets and Remote UPS Rated over 100 kW
Two Modular Battery Cabinets and Remote UPS Rated over 100 kW
Four Modular Battery Cabinets and Remote UPS Rated over 100 kW
NOTE: The distance between the modular battery cabinet(s) and the UPS
must not exceed 100 m. Contact Schneider Electric for installations with a longer distance.
1. Prepare for Installation, page 18.
2. Install the Conduit Box on the Modular Battery Cabinet, page 19.
3. Prepare Modular Battery Cabinet 1 for Signal Cables, page 20.
4. Install the Seismic Anchoring (Option), page 21.
5. Interconnect the Modular Battery Cabinets, page 26.
6. Perform one of the following:
UPS rated for maximum 100 kW: Connect the Power Cables for a UPS
Rated for Maximum 100 kW, page 28, OR
UPS rated over 100 kW: Connect the Power Cables for a UPS Rated
over 100 kW, page 30.
16 990-6161A-001
Page 17
Installation Procedure for UPS for External Batteries Modular Battery Cabinet
7. Connect the Signal Cables, page 33.
8. Add Translated Safety Labels to Your Product, page 37.
9. Final Installation, page 38.
990-6161A-001 17
Page 18
Modular Battery Cabinet Prepare for Installation

Prepare for Installation

1. Set the battery breaker BB to the open (OFF) position.
2. Remove the battery covers.
3. Remove side panels that will be adjacent to another modular battery cabinet or an adjacent UPS.
4. Remove the indicated covers.
18 990-6161A-001
Page 19
Install the Conduit Box on the Modular Battery Cabinet Modular Battery Cabinet

Install the Conduit Box on the Modular Battery Cabinet

Only for installation with remote UPS.
UPS rated for maximum 100 kW: Perform the steps below on modular battery cabinet 1.
UPS rated over 100 kW: Perform the steps below on all the modular battery cabinets with external power cabling.
1. Remove the conduit box from the rear of the modular battery cabinet.
Rear View of the Modular Battery Cabinet
2. Remove the top or bottom gland plate from the conduit box.
3. Drill/punch holes for power cables/conduits in the top or bottom gland plate. Install conduits (not provided), if applicable.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not drill or punch holes with the gland plates installed and do not drill or punch holes in close proximity to the cabinet.
Failure to follow these instructions will result in death or serious injury.
4. Reinstall the top or bottom gland plate on the conduit box.
5. Install the conduit box on the modular battery cabinet. Note that the conduit box is installed in the reverse position.
Rear View of the Modular Battery Cabinet
990-6161A-001 19
Page 20
Modular Battery Cabinet Prepare Modular Battery Cabinet 1 for Signal Cables

Prepare Modular Battery Cabinet 1 for Signal Cables

Only for installation with remote UPS.
1. Remove the gland plates and the brush plates from the front of modular battery cabinet 1.
2. Perform one of the following:
For installation without conduits: Reinstall the brush plates.
For installation with conduits: Drill a hole in the gland plates for
conduits, install conduits, and reinstall the gland plates.
Modular Battery Cabinet 1 without Conduits
3. Route the Class 2/SELV signal cable through the right gland/brush plate and into modular battery cabinet 1.
Modular Battery Cabinet 1 with Conduits
4. Route the non-Class 2/non-SELV signal cable through the left gland/brush plate and into modular battery cabinet 1.
20 990-6161A-001
Page 21
Install the Seismic Anchoring (Option) Modular Battery Cabinet

Install the Seismic Anchoring (Option)

Use the optional seismic kit GVSOPT016.
1. For installations with adjacent cabinets: Connect the rear anchoring assemblies with the interconnection plate. Repeat the step for all anchoring assemblies for adjacent cabinets.
Rear View of Installation with Adjacent Cabinets
2. Mount the rear anchoring assembly to the floor. Use appropriate hardware for the floor type – the hole diameter in the rear anchors is ø13 mm. Minimum requirement is M12 grade 8.8 hardware.
Rear View of Installation with Adjacent Cabinets
3. Remove all the screws and the interconnection plate.
Rear View of Installation with Adjacent Cabinets
990-6161A-001 21
Page 22
Modular Battery Cabinet Install the Seismic Anchoring (Option)
4. Remove the anchoring brackets.
Rear View of Installation with Adjacent Cabinets
5. For installations with adjacent cabinets: Reinstall the interconnection plate.
Rear View of Installation with Adjacent Cabinets
6. Remove the two transport brackets and the indicated bolts from the rear of the modular battery cabinet.
Rear View of the Modular Battery Cabinet
22 990-6161A-001
Page 23
Install the Seismic Anchoring (Option) Modular Battery Cabinet
7. Install the rear anchoring bracket on the modular battery cabinet with the provided M8 bolts.
Rear View of the Modular Battery Cabinet
8. Push the modular battery cabinet into position so the rear anchoring bracket connects to the rear anchors. The front anchoring bracket is installed in the final installation steps.
Rear View of the Modular Battery Cabinet
990-6161A-001 23
Page 24
Modular Battery Cabinet
Interconnect Modular Battery Cabinet 1 and the Adjacent

Interconnect Modular Battery Cabinet 1 and the Adjacent UPS

Use installation kit 0H-220042 and optional seismic kit GVSOPT016 for this procedure.
1. Remove the static switch module.
UPS
2. Push the UPS into place. For seismic anchoring, ensure that the rear anchoring bracket connects to the rear anchor.
a. Lower the front and rear leveling feet with a wrench until they connect
with the floor. Note that the UPS must match the height of modular battery cabinet 1. Use a bubble-leveler to check that the UPS is level.
3. Push modular battery cabinet 1 into place. For seismic anchoring, ensure that the rear anchoring bracket connects to the rear anchor.
a. Lower the front and rear leveling feet with a wrench until they connect
with the floor. Use a bubble-leveler to check that modular battery cabinet 1 is level.
NOTICE
RISK OF EQUIPMENT DAMAGE
Do not move the cabinet after the leveling feet have been lowered.
Failure to follow these instructions can result in equipment damage.
24 990-6161A-001
Page 25
Interconnect Modular Battery Cabinet 1 and the Adjacent UPS Modular Battery Cabinet
4. Only for seismic anchoring: Install the two interconnection brackets between modular battery cabinet 1 and the UPS.
Modular Battery Cabinet 1 and the UPS
5. Install the interconnection screws between modular battery cabinet 1 and the UPS.
6. Install the baying covers in the top and bottom between modular battery cabinet 1 and the UPS.
7. Reinstall the static switch module.
990-6161A-001 25
Page 26
Modular Battery Cabinet Interconnect the Modular Battery Cabinets

Interconnect the Modular Battery Cabinets

Use installation kit 0H-220042 and optional seismic kit GVSOPT016 for this procedure.
1. Push the rightmost modular battery cabinet into place.
a. Lower the front and rear leveling feet on the modular battery cabinet with
a wrench until they connect with the floor. Use a bubble-leveler to check that the cabinet is level.
NOTICE
RISK OF EQUIPMENT DAMAGE
Do not move the cabinet after the leveling feet have been lowered.
Failure to follow these instructions can result in equipment damage.
2. Repeat the previous step for each modular battery cabinet.
26 990-6161A-001
Page 27
Interconnect the Modular Battery Cabinets Modular Battery Cabinet
3. Only for seismic anchoring: Install the two interconnection brackets between the modular battery cabinets.
4. Install the interconnection screws between the modular battery cabinets.
5. Install the baying covers in the top and bottom between the modular battery cabinet.
990-6161A-001 27
Page 28
Modular Battery Cabinet
Connect the Power Cables for a UPS Rated for Maximum

Connect the Power Cables for a UPS Rated for Maximum 100 kW

NOTICE
RISK OF EQUIPMENT DAMAGE
Only connect the DC cables from battery breaker to battery breaker in installations with a UPS rated for maximum 100 kW. For installations with a UPS rated over 100 kW, see Connect the Power Cables for a UPS Rated over 100
kW, page 30.
Failure to follow these instructions can result in equipment damage.
1. Connect the preinstalled PE cables (0W50448) between the modular battery cabinets as shown.
2. Connect the preinstalled DC cables (0W50425) between the modular battery cabinets as shown. Connect DC- to DC- and connect DC+ to DC+ between the modular battery cabinets.
NOTE: The preinstalled DC cables come in pairs: Two cables for DC­connection and two cables for DC+ connection. Ensure to connect all pairs between the modular battery cabinets.
100 kW
Front Left View of the Modular Battery Cabinet
Top View of the Modular Battery Cabinets
Front Right View of the Modular Battery Cabinet
3. For installation with adjacent UPS: Follow the UPS installation manual to connect the PE and DC cables in the UPS.
28 990-6161A-001
Page 29
Connect the Power Cables for a UPS Rated for Maximum 100 kW Modular Battery Cabinet
4. For installation with remote UPS:
a. Optional: You can remove the right side panel from modular battery
cabinet 1 for easier access. Reinstall the side panel after power cabling is completed.
b. Disconnect the preinstalled PE cable and DC cables from modular
battery cabinet 1. The preinstalled power cables are not long enough for connection to a remote UPS.
c. Connect the PE cable and the DC cables (not provided) in modular
battery cabinet 1.
d. Route the PE and DC cables out through the conduit box and into the
UPS power cabling area.
e. Follow the UPS installation manual to connect the PE and DC cables in
the UPS.
Front Left View of Modular Battery Cabinet 1
Front Right View of Modular Battery Cabinet 1
990-6161A-001 29
Page 30
Modular Battery Cabinet Connect the Power Cables for a UPS Rated over 100 kW

Connect the Power Cables for a UPS Rated over 100 kW

NOTE: The power cabling method depends on the number of modular battery
cabinets in your UPS system.
Top View of System with Two Modular Battery Cabinets
Top View of System with Three Modular Battery Cabinets
30 990-6161A-001
Page 31
Connect the Power Cables for a UPS Rated over 100 kW Modular Battery Cabinet
Top View of System with Four Modular Battery Cabinets
1. For internal power cabling between two modular battery cabinets:
a. Connect the preinstalled PE cables (0W50448) between the modular
battery cabinets as shown.
b. Connect the preinstalled DC cables (0W50425) between the modular
battery cabinets as shown. Connect DC- to DC- and connect DC+ to DC + between the modular battery cabinets.
NOTE: The preinstalled DC cables come in pairs: Two cables for DC­connection and two cables for DC+ connection. Ensure to connect all pairs between the modular battery cabinets.
Front Left View of the Modular Battery Cabinet
Front Right View of the Modular Battery Cabinet
990-6161A-001 31
Page 32
Modular Battery Cabinet Connect the Power Cables for a UPS Rated over 100 kW
2. For external power cabling between a modular battery cabinet and the UPS:
a. Optional: You can remove the right side panel from modular battery
cabinet 1 for easier access. Reinstall the side panel after power cabling is completed.
b. Disconnect the preinstalled PE cable and DC cables from the modular
battery cabinet. The preinstalled power cables are not long enough for connection to a remote UPS.
c. Connect the PE cable and the DC cables (not provided) in the modular
battery cabinet.
d. Route the PE and DC cables out through the conduit box and into the
UPS power cabling area.
e. Follow the UPS installation manual to connect the PE and DC cables in
the UPS.
Front Left View of the Modular Battery Cabinet
Front Right View of the Modular Battery Cabinet
32 990-6161A-001
Page 33
Connect the Signal Cables Modular Battery Cabinet

Connect the Signal Cables

1. Assign an ID to each modular battery cabinet with the switch below the battery breaker. Set the IDs according to numbering on the installation overview images in Installation Procedure for UPS with Internal Batteries,
page 15 or Installation Procedure for UPS for External Batteries, page 16.
Front View of the Modular Battery Cabinet
990-6161A-001 33
Page 34
Modular Battery Cabinet Connect the Signal Cables
2. Connect the provided signal cables between all the modular battery cabinets:
a. Connect the provided signal cable 0W12908 from J8008 to J8007 on
board 640-7572 between the modular battery cabinets.
b. Connect the provided signal cable 0W76627 from J8011 to J8014 on
board 640-7572 between the modular battery cabinets.
c. Mount a termination plug (T) in the unused J8007 connector in the last
modular battery cabinet.
Modular Battery Cabinet 3 Modular Battery Cabinet 2 Modular Battery Cabinet 1
Front View of Two Modular Battery Cabinets
3. For installation with adjacent UPS:
a. Connect the signal cable 0W12908 to J8008 on board 640-7572 in
modular battery cabinet 1, route through the right side, and follow the UPS installation manual to connect the signal cables in the UPS.
b. Connect the provided signal cable 0W76627 to J8011 on board 640-7572
in modular battery cabinet 1, route through the right side, and follow the UPS installation manual to connect the signal cables in the UPS.
34 990-6161A-001
Page 35
Connect the Signal Cables Modular Battery Cabinet
4. For installation with remote UPS:
a. Connect signal cables to J8008 on board 640-7572 in modular battery
cabinet 1, route up along the right side and out through the top of the modular battery cabinet, and follow the UPS installation manual to connect the signal cables in the UPS.
NOTE: The provided signal cable 0W12908 is not long enough for a remote UPS installation. A 5 meter signal cable (0J-0W4527) or 50 meter signal cable (0J-0W3758) can be ordered from Schneider Electric. For other signal cable lengths, please contact Schneider Electric. This signal cable is classified as Class 2/SELV.
b. Connect signal cables to J8011 on board 640-7572 in modular battery
cabinet 1, route up along the left side and out through the top of the modular battery cabinet, and follow the UPS installation manual to connect the signal cables in the UPS.
NOTE: The provided signal cable 0W76627 is not long enough for a remote UPS installation. Reuse the connectors from the provided signal cable 0W76627 to make new signal cables in the correct length. This signal cable is classified as non-Class 2/non-SELV.
Signal Cable for UPS with Internal Batteries
Signal Cable for UPS for External Batteries
990-6161A-001 35
Page 36
Modular Battery Cabinet Connect the Signal Cables
Front View of Modular Battery Cabinet 1 for Installation with Remote UPS
36 990-6161A-001
Page 37
Add Translated Safety Labels to Your Product Modular Battery Cabinet

Add Translated Safety Labels to Your Product

The safety labels on your product are in English and French. Sheets with translated safety labels are provided with your product.
1. Find the sheets with translated safety labels provided with your product.
2. Check which 885-XXX numbers are on the sheet with translated safety labels.
3. Locate the safety labels on your product that match the translated safety labels on the sheet – look for the 885-XXX numbers.
4. Add the replacement safety label in your preferred language to your product on top of the existing French safety label.
990-6161A-001 37
Page 38
Modular Battery Cabinet Final Installation

Final Installation

Use optional seismic kit GVSOPT016 for this procedure.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Batteries can present a risk of electric shock and high short-circuit current. The following precautions must be observed when working on batteries
Remove watches, rings, or other metal objects.
Use tools with insulated handles.
Wear protective glasses, gloves and boots.
Do not lay tools or metal parts on top of batteries.
Disconnect the charging source prior to connecting or disconnecting battery terminals.
Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source from ground. Contact with any part of a grounded battery can result in electric shock. The likelihood of such shock can be reduced if such grounds are removed during installation and maintenance (applicable to equipment and remote battery supplies not having a grounded supply circuit).
Failure to follow these instructions will result in death or serious injury.
WARNING
RISK OF EQUIPMENT DAMAGE
Wait until the system is ready to be powered up before installing batteries in the system. The time duration from battery installation until the UPS system is powered up must not exceed 72 hours or 3 days.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
1. If not done already, lower the front and rear leveling feet on the modular battery cabinet with a wrench until they connect with the floor. Use a bubble­leveler to check that the modular battery cabinet is level.
NOTICE
RISK OF EQUIPMENT DAMAGE
Do not move the cabinet after the leveling feet have been lowered.
Failure to follow these instructions can result in equipment damage.
38 990-6161A-001
Page 39
Final Installation Modular Battery Cabinet
2. Only for seismic anchoring:
a. Remove the M8 bolts from the front of the modular battery cabinet.
b. Install the front anchoring bracket on the modular battery cabinet with the
provided M8 bolts.
c. Mount the front anchoring bracket to the floor. Use appropriate hardware
for the floor type – the hole diameter in the front anchoring bracket is ø13 mm. Minimum requirement is M12 grade 8.8 hardware.
3. Reinstall the indicated plates and covers.
4. Set the battery breaker BB to the open (OFF) position.
5. Push the battery modules into the slot. Fill the shelves from the bottom and upwards. Always install a complete battery string (four battery modules) on each shelf.
6. Turn down the battery module handle and fasten the handle to the shelf with the provided screw.
990-6161A-001 39
Page 40
Modular Battery Cabinet Final Installation
7. Connect the battery terminals to the front of the battery modules.
Front View of Battery Module
8. Only for seismic anchoring: Remove the narrow plate from the bottom of the lower battery cover and reinstall the lower battery cover.
NOTE: When reinstalling the lower battery cover, note that the screws in the bottom must be installed in the two center holes now. Use the two M6 screws from the optional seismic kit GVSOPT016.
40 990-6161A-001
Page 41
Final Installation Modular Battery Cabinet
9. Reinstall the battery covers.
990-6161A-001 41
Page 42
Page 43
Page 44
Schneider Electric
35 rue Joseph Monier 92500 Rueil Malmaison France
+ 33 (0) 1 41 29 70 00
*990-6161A-001*
As standards, specifications, and design change from time to time, please ask for confirmation of the information given in this publication.
© 2019 – 2021 Schneider Electric. All rights reserved.
990-6161A-001
Loading...