The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
Go to
IEC: https://www.productinfo.schneider-electric.com/portals/ui/galaxyvs_iec/ or
UL: https://www.productinfo.schneider-electric.com/portals/ui/galaxyvs_ul/
or scan the QR code above for digital experience and translated manuals.
Connect the Power Cables for a UPS Rated over 100 kW................. 30
Connect the Signal Cables......................................................................33
Add Translated Safety Labels to Your Product.....................................37
Final Installation ........................................................................................38
990-6161A-0013
Page 4
Page 5
Important Safety Instructions — SAVE THESE
INSTRUCTIONSModular Battery Cabinet
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
Read these instructions carefully and look at the equipment to become familiar
with it before trying to install, operate, service or maintain it. The following safety
messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or simplifies a
procedure.
The addition of this symbol to a “Danger” or “Warning” safety
message indicates that an electrical hazard exists which will result in
personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential
personal injury hazards. Obey all safety messages with this symbol
to avoid possible injury or death.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment
damage.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.
Please Note
Electrical equipment should only be installed, operated, serviced, and maintained
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
990-6161A-0015
Page 6
Modular Battery Cabinet
FCC Statement
NOTE: This equipment has been tested and found to comply with the limits for
a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment
generates, uses, and can radiate radio frequency energy and, if not installed
and used in accordance with the instruction manual, may cause harmful
interference to radio communications. Operation of this equipment in a
residential area is likely to cause harmful interference in which case the user
will be required to correct the interference at his own expense.
Any changes or modifications not expressly approved by the party responsible for
compliance could void the user’s authority to operate the equipment.
Electromagnetic Compatibility
RISK OF ELECTROMAGNETIC DISTURBANCE
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
NOTICE
Safety Precautions
This is a product category C2 UPS product. In a residential environment, this
product may cause radio inference, in which case the user may be required to
take additional measures.
Failure to follow these instructions can result in equipment damage.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Read all instructions in the installation manual before installing or working on
this product.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not install the product until all construction work has been completed and the
installation room has been cleaned.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The product must be installed according to the specifications and requirements
as defined by Schneider Electric. It concerns in particular the external and
internal protections (upstream breakers, battery breakers, cabling, etc.) and
environmental requirements. No responsibility is assumed by Schneider Electric
if these requirements are not respected.
Failure to follow these instructions will result in death or serious injury.
6990-6161A-001
Page 7
Important Safety Instructions — SAVE THESE
INSTRUCTIONSModular Battery Cabinet
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS system must be installed according to local and national regulations.
Install the UPS according to:
•IEC 60364 (including 60364–4–41- protection against electric shock, 60364–
4–42 - protection against thermal effect, and 60364–4–43 - protection
against overcurrent), or
•NEC NFPA 70, or
•Canadian Electrical Code (C22.1, Part 1)
depending on which one of the standards apply in your local area.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•Install the product in a temperature controlled indoor environment free of
conductive contaminants and humidity.
•Install the product on a non-flammable, level and solid surface (e.g.
concrete) that can support the weight of the system.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The product is not designed for and must therefore not be installed in the
following unusual operating environments:
•Damaging fumes
•Explosive mixtures of dust or gases, corrosive gases, or conductive or
radiant heat from other sources
•Moisture, abrasive dust, steam or in an excessively damp environment
•Fungus, insects, vermin
•Salt-laden air or contaminated cooling refrigerant
•Pollution degree higher than 2 according to IEC 60664-1
•Exposure to abnormal vibrations, shocks, and tilting
•Exposure to direct sunlight, heat sources, or strong electromagnetic fields
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not drill or cut holes for cables or conduits with the gland plates installed and
do not drill or cut holes in close proximity to the UPS.
Failure to follow these instructions will result in death or serious injury.
WARNING
HAZARD OF ARC FLASH
Do not make mechanical changes to the product (including removal of cabinet
parts or drilling/cutting of holes) that are not described in the installation manual.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
990-6161A-0017
Page 8
Modular Battery Cabinet
RISK OF OVERHEATING
Respect the space requirements around the product and do not cover the
ventilation openings when the product is in operation.
Failure to follow these instructions can result in equipment damage.
Additional Safety Precautions After Installation
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not install the UPS system until all construction work has been completed
and the installation room has been cleaned. If additional construction work is
needed in the installation room after this product has been installed, turn off the
product and cover the product with the protective packaging bag the product
was delivered in.
Failure to follow these instructions will result in death or serious injury.
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
NOTICE
DANGER
Electrical Safety
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
•Electrical equipment must be installed, operated, serviced, and maintained
only by qualified personnel.
•Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices.
•Turn off all power supplying the UPS system before working on or inside the
equipment.
•Before working on the UPS system, check for hazardous voltage between all
terminals including the protective earth.
•The UPS contains an internal energy source. Hazardous voltage can be
present even when disconnected from the utility/mains supply. Before
installing or servicing the UPS system, ensure that the units are OFF and
that utility/mains and batteries are disconnected. Wait five minutes before
opening the UPS to allow the capacitors to discharge.
•A disconnection device (e.g. disconnection circuit breaker or switch) must be
installed to enable isolation of the system from upstream power sources in
accordance with local regulations. This disconnection device must be easily
accessible and visible.
•The UPS must be properly earthed/grounded and due to a high leakage
current, the earthing/grounding conductor must be connected first.
Failure to follow these instructions will result in death or serious injury.
8990-6161A-001
Page 9
Important Safety Instructions — SAVE THESE
INSTRUCTIONSModular Battery Cabinet
Battery Safety
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•Battery circuit breakers must be installed according to the specifications and
requirements as defined by Schneider Electric.
•Servicing of batteries must only be performed or supervised by qualified
personnel knowledgeable of batteries and the required precautions. Keep
unqualified personnel away from batteries.
•Disconnect charging source prior to connecting or disconnecting battery
terminals.
•Do not dispose of batteries in a fire as they can explode.
•Do not open, alter, or mutilate batteries. Released electrolyte is harmful to
the skin and eyes. It may be toxic.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Batteries can present a risk of electric shock and high short-circuit current. The
following precautions must be observed when working on batteries
•Remove watches, rings, or other metal objects.
•Use tools with insulated handles.
•Wear protective glasses, gloves and boots.
•Do not lay tools or metal parts on top of batteries.
•Disconnect the charging source prior to connecting or disconnecting battery
terminals.
•Determine if the battery is inadvertently grounded. If inadvertently grounded,
remove source from ground. Contact with any part of a grounded battery can
result in electric shock. The likelihood of such shock can be reduced if such
grounds are removed during installation and maintenance (applicable to
equipment and remote battery supplies not having a grounded supply
circuit).
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
When replacing batteries, always replace with the same type and number of
batteries or battery packs.
Failure to follow these instructions will result in death or serious injury.
NOTICE
RISK OF EQUIPMENT DAMAGE
•Wait until the system is ready to be powered up before installing batteries in
the system. The time duration from battery installation until the UPS system
is powered up must not exceed 72 hours or 3 days.
•Batteries must not be stored more than six months due to the requirement of
recharging. If the UPS system remains de-energized for a long period,
Schneider Electric recommends that you energize the UPS system for a
period of 24 hours at least once every month. This charges the batteries,
thus avoiding irreversible damage.
Failure to follow these instructions can result in equipment damage.
Installation Procedure for UPS with Internal BatteriesModular Battery Cabinet
Installation Procedure for UPS with Internal
Batteries
NOTE: The modular battery cabinet can be installed adjacent or remote to a
UPS with internal batteries.
Modular Battery Cabinets and Adjacent UPS Rated
for Maximum 100 kW
NOTE: The distance between the modular battery cabinet(s) and the UPS
must not exceed 100 m. Contact Schneider Electric for installations with a
longer distance.
1. Prepare for Installation, page 18.
Modular Battery Cabinets and Remote UPS Rated
for Maximum 100 kW
2. For installation with remote UPS:
a. Install the Conduit Box on the Modular Battery Cabinet, page 19.
b. Prepare Modular Battery Cabinet 1 for Signal Cables, page 20.
3. Install the Seismic Anchoring (Option), page 21.
4. For installation with adjacent UPS: Interconnect Modular Battery Cabinet 1
and the Adjacent UPS, page 24.
5. Interconnect the Modular Battery Cabinets, page 26.
6. Connect the Power Cables for a UPS Rated for Maximum 100 kW, page 28.
7. Connect the Signal Cables, page 33.
8. Add Translated Safety Labels to Your Product, page 37.
9. Final Installation, page 38.
990-6161A-00115
Page 16
Modular Battery CabinetInstallation Procedure for UPS for External Batteries
Installation Procedure for UPS for External Batteries
NOTE: The modular battery cabinet can only be installed remote to a UPS for
external batteries.
Modular Battery Cabinets and Remote UPS Rated
for Maximum 100 kW
Three Modular Battery Cabinets and Remote UPS
Rated over 100 kW
Two Modular Battery Cabinets and Remote UPS
Rated over 100 kW
Four Modular Battery Cabinets and Remote UPS
Rated over 100 kW
NOTE: The distance between the modular battery cabinet(s) and the UPS
must not exceed 100 m. Contact Schneider Electric for installations with a
longer distance.
1. Prepare for Installation, page 18.
2. Install the Conduit Box on the Modular Battery Cabinet, page 19.
3. Prepare Modular Battery Cabinet 1 for Signal Cables, page 20.
4. Install the Seismic Anchoring (Option), page 21.
5. Interconnect the Modular Battery Cabinets, page 26.
6. Perform one of the following:
– UPS rated for maximum 100 kW: Connect the Power Cables for a UPS
Rated for Maximum 100 kW, page 28, OR
– UPS rated over 100 kW: Connect the Power Cables for a UPS Rated
over 100 kW, page 30.
16990-6161A-001
Page 17
Installation Procedure for UPS for External BatteriesModular Battery Cabinet
7. Connect the Signal Cables, page 33.
8. Add Translated Safety Labels to Your Product, page 37.
9. Final Installation, page 38.
990-6161A-00117
Page 18
Modular Battery CabinetPrepare for Installation
Prepare for Installation
1. Set the battery breaker BB to the open (OFF) position.
2. Remove the battery covers.
3. Remove side panels that will be adjacent to another modular battery cabinet
or an adjacent UPS.
4. Remove the indicated covers.
18990-6161A-001
Page 19
Install the Conduit Box on the Modular Battery CabinetModular Battery Cabinet
Install the Conduit Box on the Modular Battery
Cabinet
Only for installation with remote UPS.
UPS rated for maximum 100 kW: Perform the steps below on modular battery
cabinet 1.
UPS rated over 100 kW: Perform the steps below on all the modular battery
cabinets with external power cabling.
1. Remove the conduit box from the rear of the modular battery cabinet.
Rear View of the Modular Battery Cabinet
2. Remove the top or bottom gland plate from the conduit box.
3. Drill/punch holes for power cables/conduits in the top or bottom gland plate.
Install conduits (not provided), if applicable.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not drill or punch holes with the gland plates installed and do not drill or
punch holes in close proximity to the cabinet.
Failure to follow these instructions will result in death or serious
injury.
4. Reinstall the top or bottom gland plate on the conduit box.
5. Install the conduit box on the modular battery cabinet. Note that the conduit
box is installed in the reverse position.
Rear View of the Modular Battery Cabinet
990-6161A-00119
Page 20
Modular Battery CabinetPrepare Modular Battery Cabinet 1 for Signal Cables
Prepare Modular Battery Cabinet 1 for Signal Cables
Only for installation with remote UPS.
1. Remove the gland plates and the brush plates from the front of modular
battery cabinet 1.
2. Perform one of the following:
– For installation without conduits: Reinstall the brush plates.
– For installation with conduits: Drill a hole in the gland plates for
conduits, install conduits, and reinstall the gland plates.
Modular Battery Cabinet 1 without Conduits
3. Route the Class 2/SELV signal cable through the right gland/brush plate and
into modular battery cabinet 1.
Modular Battery Cabinet 1 with Conduits
4. Route the non-Class 2/non-SELV signal cable through the left gland/brush
plate and into modular battery cabinet 1.
20990-6161A-001
Page 21
Install the Seismic Anchoring (Option)Modular Battery Cabinet
Install the Seismic Anchoring (Option)
Use the optional seismic kit GVSOPT016.
1. For installations with adjacent cabinets: Connect the rear anchoring
assemblies with the interconnection plate. Repeat the step for all anchoring
assemblies for adjacent cabinets.
Rear View of Installation with Adjacent Cabinets
2. Mount the rear anchoring assembly to the floor. Use appropriate hardware for
the floor type – the hole diameter in the rear anchors is ø13 mm. Minimum
requirement is M12 grade 8.8 hardware.
Rear View of Installation with Adjacent Cabinets
3. Remove all the screws and the interconnection plate.
Rear View of Installation with Adjacent Cabinets
990-6161A-00121
Page 22
Modular Battery CabinetInstall the Seismic Anchoring (Option)
4. Remove the anchoring brackets.
Rear View of Installation with Adjacent Cabinets
5. For installations with adjacent cabinets: Reinstall the interconnection
plate.
Rear View of Installation with Adjacent Cabinets
6. Remove the two transport brackets and the indicated bolts from the rear of
the modular battery cabinet.
Rear View of the Modular Battery Cabinet
22990-6161A-001
Page 23
Install the Seismic Anchoring (Option)Modular Battery Cabinet
7. Install the rear anchoring bracket on the modular battery cabinet with the
provided M8 bolts.
Rear View of the Modular Battery Cabinet
8. Push the modular battery cabinet into position so the rear anchoring bracket
connects to the rear anchors. The front anchoring bracket is installed in the
final installation steps.
Rear View of the Modular Battery Cabinet
990-6161A-00123
Page 24
Modular Battery Cabinet
Interconnect Modular Battery Cabinet 1 and the Adjacent
Interconnect Modular Battery Cabinet 1 and the
Adjacent UPS
Use installation kit 0H-220042 and optional seismic kit GVSOPT016 for this
procedure.
1. Remove the static switch module.
UPS
2. Push the UPS into place. For seismic anchoring, ensure that the rear
anchoring bracket connects to the rear anchor.
a. Lower the front and rear leveling feet with a wrench until they connect
with the floor. Note that the UPS must match the height of modular
battery cabinet 1. Use a bubble-leveler to check that the UPS is level.
3. Push modular battery cabinet 1 into place. For seismic anchoring, ensure that
the rear anchoring bracket connects to the rear anchor.
a. Lower the front and rear leveling feet with a wrench until they connect
with the floor. Use a bubble-leveler to check that modular battery cabinet
1 is level.
NOTICE
RISK OF EQUIPMENT DAMAGE
Do not move the cabinet after the leveling feet have been lowered.
Failure to follow these instructions can result in equipment damage.
24990-6161A-001
Page 25
Interconnect Modular Battery Cabinet 1 and the Adjacent UPSModular Battery Cabinet
4. Only for seismic anchoring: Install the two interconnection brackets
between modular battery cabinet 1 and the UPS.
Modular Battery Cabinet 1 and the UPS
5. Install the interconnection screws between modular battery cabinet 1 and the
UPS.
6. Install the baying covers in the top and bottom between modular battery
cabinet 1 and the UPS.
7. Reinstall the static switch module.
990-6161A-00125
Page 26
Modular Battery CabinetInterconnect the Modular Battery Cabinets
Interconnect the Modular Battery Cabinets
Use installation kit 0H-220042 and optional seismic kit GVSOPT016 for this
procedure.
1. Push the rightmost modular battery cabinet into place.
a. Lower the front and rear leveling feet on the modular battery cabinet with
a wrench until they connect with the floor. Use a bubble-leveler to check
that the cabinet is level.
NOTICE
RISK OF EQUIPMENT DAMAGE
Do not move the cabinet after the leveling feet have been lowered.
Failure to follow these instructions can result in equipment damage.
2. Repeat the previous step for each modular battery cabinet.
26990-6161A-001
Page 27
Interconnect the Modular Battery CabinetsModular Battery Cabinet
3. Only for seismic anchoring: Install the two interconnection brackets
between the modular battery cabinets.
4. Install the interconnection screws between the modular battery cabinets.
5. Install the baying covers in the top and bottom between the modular battery
cabinet.
990-6161A-00127
Page 28
Modular Battery Cabinet
Connect the Power Cables for a UPS Rated for Maximum
Connect the Power Cables for a UPS Rated for
Maximum 100 kW
NOTICE
RISK OF EQUIPMENT DAMAGE
Only connect the DC cables from battery breaker to battery breaker in
installations with a UPS rated for maximum 100 kW. For installations with a UPS
rated over 100 kW, see Connect the Power Cables for a UPS Rated over 100
kW, page 30.
Failure to follow these instructions can result in equipment damage.
1. Connect the preinstalled PE cables (0W50448) between the modular battery
cabinets as shown.
2. Connect the preinstalled DC cables (0W50425) between the modular battery
cabinets as shown. Connect DC- to DC- and connect DC+ to DC+ between
the modular battery cabinets.
NOTE: The preinstalled DC cables come in pairs: Two cables for DCconnection and two cables for DC+ connection. Ensure to connect all
pairs between the modular battery cabinets.
100 kW
Front Left View of the Modular Battery Cabinet
Top View of the Modular Battery Cabinets
Front Right View of the Modular Battery Cabinet
3. For installation with adjacent UPS: Follow the UPS installation manual to
connect the PE and DC cables in the UPS.
28990-6161A-001
Page 29
Connect the Power Cables for a UPS Rated for Maximum 100
kWModular Battery Cabinet
4. For installation with remote UPS:
a. Optional: You can remove the right side panel from modular battery
cabinet 1 for easier access. Reinstall the side panel after power cabling
is completed.
b. Disconnect the preinstalled PE cable and DC cables from modular
battery cabinet 1. The preinstalled power cables are not long enough for
connection to a remote UPS.
c. Connect the PE cable and the DC cables (not provided) in modular
battery cabinet 1.
d. Route the PE and DC cables out through the conduit box and into the
UPS power cabling area.
e. Follow the UPS installation manual to connect the PE and DC cables in
the UPS.
Front Left View of Modular Battery Cabinet 1
Front Right View of Modular Battery Cabinet 1
990-6161A-00129
Page 30
Modular Battery CabinetConnect the Power Cables for a UPS Rated over 100 kW
Connect the Power Cables for a UPS Rated over 100
kW
NOTE: The power cabling method depends on the number of modular battery
cabinets in your UPS system.
Top View of System with Two Modular Battery Cabinets
Top View of System with Three Modular Battery Cabinets
30990-6161A-001
Page 31
Connect the Power Cables for a UPS Rated over 100 kWModular Battery Cabinet
Top View of System with Four Modular Battery Cabinets
1. For internal power cabling between two modular battery cabinets:
a. Connect the preinstalled PE cables (0W50448) between the modular
battery cabinets as shown.
b. Connect the preinstalled DC cables (0W50425) between the modular
battery cabinets as shown. Connect DC- to DC- and connect DC+ to DC
+ between the modular battery cabinets.
NOTE: The preinstalled DC cables come in pairs: Two cables for DCconnection and two cables for DC+ connection. Ensure to connect all
pairs between the modular battery cabinets.
Front Left View of the Modular Battery Cabinet
Front Right View of the Modular Battery Cabinet
990-6161A-00131
Page 32
Modular Battery CabinetConnect the Power Cables for a UPS Rated over 100 kW
2. For external power cabling between a modular battery cabinet and the UPS:
a. Optional: You can remove the right side panel from modular battery
cabinet 1 for easier access. Reinstall the side panel after power cabling
is completed.
b. Disconnect the preinstalled PE cable and DC cables from the modular
battery cabinet. The preinstalled power cables are not long enough for
connection to a remote UPS.
c. Connect the PE cable and the DC cables (not provided) in the modular
battery cabinet.
d. Route the PE and DC cables out through the conduit box and into the
UPS power cabling area.
e. Follow the UPS installation manual to connect the PE and DC cables in
the UPS.
Front Left View of the Modular Battery Cabinet
Front Right View of the Modular Battery Cabinet
32990-6161A-001
Page 33
Connect the Signal CablesModular Battery Cabinet
Connect the Signal Cables
1. Assign an ID to each modular battery cabinet with the switch below the
battery breaker. Set the IDs according to numbering on the installation
overview images in Installation Procedure for UPS with Internal Batteries,
page 15 or Installation Procedure for UPS for External Batteries, page 16.
Front View of the Modular Battery Cabinet
990-6161A-00133
Page 34
Modular Battery CabinetConnect the Signal Cables
2. Connect the provided signal cables between all the modular battery cabinets:
a. Connect the provided signal cable 0W12908 from J8008 to J8007 on
board 640-7572 between the modular battery cabinets.
b. Connect the provided signal cable 0W76627 from J8011 to J8014 on
board 640-7572 between the modular battery cabinets.
c. Mount a termination plug (T) in the unused J8007 connector in the last
a. Connect the signal cable 0W12908 to J8008 on board 640-7572 in
modular battery cabinet 1, route through the right side, and follow the
UPS installation manual to connect the signal cables in the UPS.
b. Connect the provided signal cable 0W76627 to J8011 on board 640-7572
in modular battery cabinet 1, route through the right side, and follow the
UPS installation manual to connect the signal cables in the UPS.
34990-6161A-001
Page 35
Connect the Signal CablesModular Battery Cabinet
4. For installation with remote UPS:
a. Connect signal cables to J8008 on board 640-7572 in modular battery
cabinet 1, route up along the right side and out through the top of the
modular battery cabinet, and follow the UPS installation manual to
connect the signal cables in the UPS.
NOTE: The provided signal cable 0W12908 is not long enough for a
remote UPS installation. A 5 meter signal cable (0J-0W4527) or 50
meter signal cable (0J-0W3758) can be ordered from Schneider
Electric. For other signal cable lengths, please contact Schneider
Electric. This signal cable is classified as Class 2/SELV.
b. Connect signal cables to J8011 on board 640-7572 in modular battery
cabinet 1, route up along the left side and out through the top of the
modular battery cabinet, and follow the UPS installation manual to
connect the signal cables in the UPS.
NOTE: The provided signal cable 0W76627 is not long enough for a
remote UPS installation. Reuse the connectors from the provided
signal cable 0W76627 to make new signal cables in the correct
length. This signal cable is classified as non-Class 2/non-SELV.
Signal Cable for UPS with Internal Batteries
Signal Cable for UPS for External Batteries
990-6161A-00135
Page 36
Modular Battery CabinetConnect the Signal Cables
Front View of Modular Battery Cabinet 1 for Installation with Remote
UPS
36990-6161A-001
Page 37
Add Translated Safety Labels to Your ProductModular Battery Cabinet
Add Translated Safety Labels to Your Product
The safety labels on your product are in English and French. Sheets with
translated safety labels are provided with your product.
1. Find the sheets with translated safety labels provided with your product.
2. Check which 885-XXX numbers are on the sheet with translated safety
labels.
3. Locate the safety labels on your product that match the translated safety
labels on the sheet – look for the 885-XXX numbers.
4. Add the replacement safety label in your preferred language to your product
on top of the existing French safety label.
990-6161A-00137
Page 38
Modular Battery CabinetFinal Installation
Final Installation
Use optional seismic kit GVSOPT016 for this procedure.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Batteries can present a risk of electric shock and high short-circuit current. The
following precautions must be observed when working on batteries
•Remove watches, rings, or other metal objects.
•Use tools with insulated handles.
•Wear protective glasses, gloves and boots.
•Do not lay tools or metal parts on top of batteries.
•Disconnect the charging source prior to connecting or disconnecting battery
terminals.
•Determine if the battery is inadvertently grounded. If inadvertently grounded,
remove source from ground. Contact with any part of a grounded battery can
result in electric shock. The likelihood of such shock can be reduced if such
grounds are removed during installation and maintenance (applicable to
equipment and remote battery supplies not having a grounded supply
circuit).
Failure to follow these instructions will result in death or serious injury.
WARNING
RISK OF EQUIPMENT DAMAGE
Wait until the system is ready to be powered up before installing batteries in the
system. The time duration from battery installation until the UPS system is
powered up must not exceed 72 hours or 3 days.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
1. If not done already, lower the front and rear leveling feet on the modular
battery cabinet with a wrench until they connect with the floor. Use a bubbleleveler to check that the modular battery cabinet is level.
NOTICE
RISK OF EQUIPMENT DAMAGE
Do not move the cabinet after the leveling feet have been lowered.
Failure to follow these instructions can result in equipment damage.
38990-6161A-001
Page 39
Final InstallationModular Battery Cabinet
2. Only for seismic anchoring:
a. Remove the M8 bolts from the front of the modular battery cabinet.
b. Install the front anchoring bracket on the modular battery cabinet with the
provided M8 bolts.
c. Mount the front anchoring bracket to the floor. Use appropriate hardware
for the floor type – the hole diameter in the front anchoring bracket is ø13
mm. Minimum requirement is M12 grade 8.8 hardware.
3. Reinstall the indicated plates and covers.
4. Set the battery breaker BB to the open (OFF) position.
5. Push the battery modules into the slot. Fill the shelves from the bottom and
upwards. Always install a complete battery string (four battery modules) on
each shelf.
6. Turn down the battery module handle and fasten the handle to the shelf with
the provided screw.
990-6161A-00139
Page 40
Modular Battery CabinetFinal Installation
7. Connect the battery terminals to the front of the battery modules.
Front View of Battery Module
8. Only for seismic anchoring: Remove the narrow plate from the bottom of
the lower battery cover and reinstall the lower battery cover.
NOTE: When reinstalling the lower battery cover, note that the screws in
the bottom must be installed in the two center holes now. Use the two M6
screws from the optional seismic kit GVSOPT016.
40990-6161A-001
Page 41
Final InstallationModular Battery Cabinet
9. Reinstall the battery covers.
990-6161A-00141
Page 42
Page 43
Page 44
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
*990-6161A-001*
As standards, specifications, and design change from time to time,
please ask for confirmation of the information given in this publication.