The Schneider Electric brand and any trademarks of Schneider Electric SE and its
subsidiaries referred to in this guide are the property of Schneider Electric SE or its
subsidiaries. All other brands may be trademarks of their respective owners.
This guide and its content are protected under applicable copyright laws and
furnished for informational use only. No part of this guide may be reproduced or
transmitted in any form or by any means (electronic, mechanical, photocopying,
recording, or otherwise), for any purpose, without the prior written permission of
Schneider Electric.
Schneider Electric does not grant any right or license for commercial use of the guide
or its content, except for a non-exclusive and personal license to consult it on an "as
is" basis. Schneider Electric products and equipment should be installed, operated,
serviced, and maintained only by qualified personnel.
As standards, specifications, and designs change from time to time, information
contained in this guide may be subject to change without notice.
To the extent permitted by applicable law, no responsibility or liability is assumed by
Schneider Electric and its subsidiaries for any errors or omissions in the informational
content of this material or consequences arising out of or resulting from the use of the
information contained herein.
Go to: https://www.productinfo.schneider-electric.com/galaxyvx_iec/
or scan the QR code above for digital experience and translated manuals.
Important Safety Instructions — SAVE THESE
INSTRUCTIONS380 V, 400 V, 415 V, and 440 V UPS System
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
Read these instructions carefully and look at the equipment to become familiar
with it before trying to install, operate, service or maintain it. The following safety
messages may appear throughout this manual or on the equipment to warn of
potential hazards or to call attention to information that clarifies or simplifies a
procedure.
The addition of this symbol to a “Danger” or “Warning” safety
message indicates that an electrical hazard exists which will result in
personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential
personal injury hazards. Obey all safety messages with this symbol
to avoid possible injury or death.
DANGER
DANGER indicates a hazardous situation which, if not avoided, will result in
death or serious injury.
Failure to follow these instructions will result in death or serious injury.
WARNING
WARNING indicates a hazardous situation which, if not avoided, could result
in death or serious injury.
Failure to follow these instructions can result in death, serious injury, or
equipment damage.
CAUTION
CAUTION indicates a hazardous situation which, if not avoided, could result in
minor or moderate injury.
Failure to follow these instructions can result in injury or equipment
damage.
NOTICE
NOTICE is used to address practices not related to physical injury. The safety
alert symbol shall not be used with this type of safety message.
Failure to follow these instructions can result in equipment damage.
Please Note
Electrical equipment should only be installed, operated, serviced, and maintained
by qualified personnel. No responsibility is assumed by Schneider Electric for any
consequences arising out of the use of this material.
A qualified person is one who has skills and knowledge related to the construction,
installation, and operation of electrical equipment and has received safety training
to recognize and avoid the hazards involved.
990-5850F-0015
Page 6
380 V, 400 V, 415 V, and 440 V UPS System
Electromagnetic Compatibility
RISK OF ELECTROMAGNETIC DISTURBANCE
This is a product Category C3 according to IEC 62040-2. This is a product for
commercial and industrial applications in the second environment - installation
restrictions or additional measures may be needed to prevent disturbances. The
second environment includes all commercial, light industry, and industrial
locations other than residential, commercial, and light industrial premises
directly connected without intermediate transformer to a public low-voltage
mains supply. The installation and cabling must follow the electromagnetic
compatibility rules, e.g.:
•the segregation of cables,
•the use of shielded or special cables when relevant,
•the use of grounded metallic cable tray and supports.
Failure to follow these instructions can result in equipment damage.
Important Safety Instructions — SAVE THESE
INSTRUCTIONS
NOTICE
Safety Precautions
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•The product must be installed according to the specifications and
requirements as defined by Schneider Electric. It concerns in particular the
external and internal protections (upstream circuit breakers, battery circuit
breakers, cabling, etc.) and environmental requirements. No responsibility is
assumed by Schneider Electric if these requirements are not respected.
•After the UPS system has been electrically wired, do not start up the system.
Start-up must only be performed by Schneider Electric.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS System must be installed according to local and national regulations.
Install the UPS according to:
•IEC 60364 (including 60364–4–41- protection against electric shock, 60364–
4–42 - protection against thermal effect, and 60364–4–43 - protection
against overcurrent), or
•NEC NFPA 70
depending on which one of the standards apply in your local area.
Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•Install the UPS system in a temperature controlled area free of conductive
contaminants and humidity.
•Install the UPS system on a non-inflammable, level, and solid surface (e.g.
concrete) that can support the weight of the system.
Failure to follow these instructions will result in death or serious injury.
6990-5850F-001
Page 7
Important Safety Instructions — SAVE THESE
INSTRUCTIONS380 V, 400 V, 415 V, and 440 V UPS System
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The UPS is not designed for and must therefore not be installed in the following
unusual operating environments:
•Damaging fumes
•Explosive mixtures of dust or gases, corrosive gases, or conductive or
radiant heat from other sources
•Moisture, abrasive dust, steam or in an excessively damp environment
•Fungus, insects, vermin
•Salt-laden air or contaminated cooling refrigerant
•Pollution degree higher than 2 according to IEC 60664-1
•Exposure to abnormal vibrations, shocks, and tilting
•Exposure to direct sunlight, heat sources, or strong electromagnetic fields
Failure to follow these instructions will result in death or serious injury.
NOTICE
RISK OF OVERHEATING
Respect the clearance requirements around the UPS system and do not cover
the product’s ventilation openings when the UPS system is in operation.
Failure to follow these instructions can result in equipment damage.
NOTICE
RISK OF EQUIPMENT DAMAGE
Do not connect the UPS output to regenerative load systems including
photovoltaic systems and speed drives.
Failure to follow these instructions can result in equipment damage.
990-5850F-0017
Page 8
380 V, 400 V, 415 V, and 440 V UPS SystemTechnical Data
Technical Data
System Overview
Each Galaxy VX UPS consists of the following components:
•An I/O cabinet for wield wiring containing the static switch, a backfeed
protection switch, and the user interface.
•A number of 250 kW power cabinets containing the power electronics.
UPSs with 1250 kW I/O Cabinet
The 1250 kW I/O cabinet is used for UPS systems from a minimum configuration
of 500 kW with two power cabinets to a maximum configuration of 1250 kW N+1
with six power cabinets. The I/O cabinet is placed to the left and two to six power
cabinets (depending on system size) are placed to the right. The image below
shows the maximum configuration.
UPSs with 1500 kW I/O Cabinet
The 1500 kW I/O cabinet is used for UPS systems from a minimum configuration
of 500 kW with two power cabinets to a maximum configuration of 1500 kW N+1
with seven power cabinets. The image below shows the maximum configuration.
8990-5850F-001
Page 9
Technical Data380 V, 400 V, 415 V, and 440 V UPS System
Technical Data380 V, 400 V, 415 V, and 440 V UPS System
1500 kW UPS
Number of
LIBATTSMGGIEC
cabinets
25% load73:3079:0084:0089:3094:30100:00105:00
50% load36:3039:0041:3044:3047:0049:3052:30
75% load23:3025:3027:0029:0030:3032:3034:30
100% load17:3018:3020:0021:3022:3024:0025:30
14151617181920
End of Discharge Voltage
The voltage is 1.6 to 1.75 per cell depending on discharge ratio.
Battery Voltage Range
990-5850F-00123
Page 24
380 V, 400 V, 415 V, and 440 V UPS SystemTechnical Data
Compliance
SafetyIEC 62040-1: 2008-06, 1st edition Uninterruptible Power Systems (UPS) - Part 1: General and safety requirements
EMC/EMI/RFIIEC 62040-2: 2005-10, 2nd edition Uninterruptible Power Systems (UPS) - Part 2: Electromagnetic compatibility
PerformanceIEC 62040-3: 2011-03, 2nd edition Uninterruptible Power Systems (UPS) - Part 3: Method of specifying the
EnvironmentalIEC 62040-4: 2013-04, 1st edition Uninterruptible Power Systems (UPS) - Part 4: Environmental aspects –
MarkingsCE, C-Tick
TransportationISTA 2B
SeismicOSHPD, IBC2012 and CBC2013 to S
for UPS
EN 62040-1: 2013-01, 1st edition amendment 1
(EMC) requirements
performance and test requirements
Requirements and reporting
= 1.83 g
DS
Communication and Management
Local Area Network100 Mbps
ExtensionsTwo optional Network Management Cards
MODBUSMODBUS TCP/IP
Output relays6 configurable
Input dry contacts5 configurable
Standard control panel7–inch touchscreen display
Audible alarmYes
Emergency Power Off (EPO)Options:
•Normally Open (NO)
•Normally Closed (NC)
•External 24 VDC SELV
External synchronizationYes
Battery monitoringYes — string level monitoring
EPO Connections
24990-5850F-001
Page 25
Technical Data380 V, 400 V, 415 V, and 440 V UPS System
Overview of Input Contacts and Output Relays
Input Contacts
Do not connect any circuit to the input contacts unless it can be confirmed that the
circuit is Class 2/SELV.
All circuits connected must have the same 0 V reference.
The switch SW5500 on 0P6548 is used to select between internal SELV supply for
inputs (standard setting) and external supply
3
. If external supply is selected, the
supply must be connected to J5530.
NameDescriptionLocation
IN 1 (Contact 1)Configurable input contact0P6548 terminal J5502
IN 2 (Contact 2)Configurable input contact0P6548 terminal J5503
IN 3 (Contact 3)Configurable input contact0P6548 terminal J5504
IN 4 (Contact 4)Configurable input contact0P6548 terminal J5505
IN 5 (Contact 5)Configurable input contact0P6548 terminal J5510
IN 6UOB redundant AUX contact0P6548 terminal J5509
IN 7Transformer temperature switch0P6548 terminal J5508
IN 8External bonding contact0P6548 terminal J5507
IN 9Forced external synchronization input0P6548 terminal J5506
IN 10External synchronization requested0P6548 terminal J5511
IN 11Use static bypass standby0P6548 terminal J5512
IN 14MegaTie0P6552 terminal J9027
4
4
4
4
4
4
4
4
4
4
4
4
Output Relays
NOTE: Maximum 250 VAC 5 A must be connected to the output relays.
All external circuitry must be fused with maximum 5 A fast acting fuses.
NameDescriptionLocation
OUT 1 (Relay 1)Configurable output relay0P6547 terminal J4939
OUT 2 (Relay 2)Configurable output relay0P6547 terminal J4940
OUT 3 (Relay 3)Configurable output relay0P6547 terminal J4941
3.An external supply is useful in parallel systems where inputs are connected between different UPSs. This is to have a common reference
and to avoid cross currents.
4.Class 2/SELV wiring
990-5850F-00125
Page 26
380 V, 400 V, 415 V, and 440 V UPS SystemTechnical Data
NameDescriptionLocation
OUT 4Forced external synchronization output0P6548 terminal J5520
OUT 5MegaTie0P6548 terminal J5521
OUT 6External synchronization requested output0P6548 terminal J5522
OUT 7UPS in inverter ON0P6548 terminal J5523
OUT 8 (Relay 4)Configurable output relay0P6548 terminal J5524
OUT 9 (Relay 5)Configurable output relay0P6548 terminal J5525
OUT 10 (Relay 6)Configurable output relay0P6548 terminal J5528
OUT 14Bonding contactor0P6552 terminal J9029
5
5
5
5
5
5
5
5
NOTE: Refer to the operation manual for configuration options.
5.Class 2/SELV wiring
26990-5850F-001
Page 27
Facility Planning380 V, 400 V, 415 V, and 440 V UPS System
Facility Planning
Specifications for 500 kW UPS
Voltage (V)380400415440 V480 V
ConnectionsIEC: L1, L2, L3, PE
Input voltage range (V)
Frequency (Hz)40-70
Nominal input current (A)800760731685633
Maximum input current (A)
Input current limitation (A)890832760
Total harmonic distortion (THDI)<3% at 100% load, <4% at 50% load, <9% at 25% load
Input Specifications
Input power factor0.99 at >40% load, 0.98 at >20% load, 0.97 at >10% load
ProtectionContactors
Ramp-inAdaptive 1-300 seconds
ConnectionsIEC: L1, L2, L3, N, PE or L1, L2, L3, PE
Bypass voltage range (V)342-418360-440374-457396-484432-528
8
9
UL: L1, L2, L3 + G
340-456340-480353-498374-528408-576
886851819767728
UL: L1, L2, L3, G or L1, L2, L3, N, G
6
7
10
Frequency (Hz)50 or 60
Frequency range (Hz)Programmable: ±0.1, ±3, ±10. Default is ±3
Nominal bypass current (A)767729703663606
Maximum short circuit rating100 kA RMS (conditioned by an internal molded switch with 90 kA peak magnetic trip)
Thyristor I²t (kA*s²)9680 (1250 kW I/O)
Bypass Specifications
BF2 magnetic trip39 kA
ProtectionMolded switch with trip for backfeed protection
16245 (1500 kW I/O)
9165 (1250 kW I/O)
16245 (1500 kW I/O)
6.TN, TT, and IT power distribution systems are supported.
7.WYE source – solid grounded and high resistance grounded sources are supported. Corner (line) grounding is not supported.
8.The system can operate at 600 V for 1 minute.
9.At nominal input voltage and full charge.
10. TN, TT, and IT power distribution systems with no earthed line conductors are supported.
990-5850F-00127
Page 28
380 V, 400 V, 415 V, and 440 V UPS SystemFacility Planning
Voltage (V)380400415440 V480 V
ConnectionsIEC: L1, L2, L3, N, PE or L1, L2, L3, PE
UL: L1, L2, L3, G, GEC
11
or L1, L2, L3, N, G
Overload capacityNormal operation: 150% for 1 minute, 125% for 10 minutes
Battery operation: 115% for 1 minute
Bypass operation: 110%
12
continuous, 1000% for 60 milliseconds for systems with
1250 kW I/O cabinet and 100 milliseconds for systems with 1500 kW I/O cabinet
Output voltage toleranceBalanced load: ±1%, Unbalanced load: ±3%
Dynamic load response±5% after 2 ms, ±1% after 50 ms
Output power factor1
Nominal output current (A)760722696656601
Total harmonic distortion (THDU)<2% at 100% linear load, <3% at 100% non-linear load
Output frequency (Hz)50/60 (synchronized to bypass), 50/60 Hz ±0.1% (free-running)
Load power factor0.7 leading to 0.5 lagging without derating
55. TN, TT, and IT power distribution systems are supported.
56. WYE source – solid grounded and high resistance grounded sources are supported. Corner (line) grounding is not supported.
57. The system can operate at 600 V for 1 minute.
58. At nominal input voltage and full charge.
59. TN, TT, and IT power distribution systems with no earthed line conductors are supported.
60. Per NEC 250.30.
990-5850F-00141
Page 42
380 V, 400 V, 415 V, and 440 V UPS SystemFacility Planning
Voltage (V)380400415440 V480 V
Charging power in % of output power35% at ≤ 80% load, 12% at 100% load40% at ≤ 80% load,
Maximum charging power (kW)525 at < 80% load, 180 at 100% load,600 at <80% load, 225
Nominal battery voltage (VDC)480
Nominal float voltage (VDC)546
End of discharge voltage (full load) (VDC)384
End of discharge voltage (no load) (VDC)420
Battery current at full load and nominal
battery voltage (A)
Battery current at full load and minimum
battery voltage (A)
Battery Specifications
Maximum battery backup time1 hour
Temperature compensation (per cell)-3.3 mV per °C for T ≥ 25 °C, 0 mV per °C for T < 25 °C
Ripple current< 5% C20 (5 minutes backup time)
Battery testManual/automatic (selectable)
Deep discharge protectionYes
Recharge according to battery temperatureYes
3269
4086
15% at 100% load
at 100% load
Recommended Upstream Protection and Cable Sizes – IEC
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
An easily accessible breaker is required for upstream protection. Maximum fault
current disconnection time: 46 seconds at 200% input.
Failure to follow these instructions will result in death or serious injury.
NOTE: Overcurrent protection is to be provided by others.
Cable sizes in this manual are based on table B.52.12 and B.52.13 of IEC 60364–
5–52 with the following assertions:
•90 °C conductors
•An ambient temperature of 30 °C
•Use of copper or aluminium conductors
•Installation method F4 for DC cables and installation method F5 for AC
cables, corrected for single layer in perforated cable tray.
PE cables are sized in accordance with IEC 60364-5-54 table 54.2 Minimum
cross-sectional area of protective conductors.
NOTE: Always consider the PE size according to the complete electrical
installation.
If the ambient temperature is greater than 30 °C, larger conductors are to be
selected in accordance with the correction factors of the IEC.
NOTE: The use of aluminium conductors can limit the number of parallel Li-ion
battery cabinets. Please contact Schneider Electric for more information.
42990-5850F-001
Page 43
Facility Planning380 V, 400 V, 415 V, and 440 V UPS System
Recommended Upstream Protection and Cable Sizes for 500 kW UPS
Maximum OCPD (A)Conductors per Phase Copper/
PE Conductor (mm²)
Aluminium (mm²)
Voltage
380400415440380400415440380400415440
(V)
Input1000
I
=0.90
r
Bypass800
I
=0.98
r
Output800
=0.98
I
r
Battery15001500150015003x185/
1000
Ir=0.90
800
Ir=0.95
800
Ir=0.95
1000
Ir=0.90
800
Ir=0.9
800
Ir=0.9
1000
Ir=0.90
800
Ir=0.9
800
Ir=0.9
2x240/
3x185
2x185/
2x240
2x185/
2x240
3x240
2x240/
3x185
2x150/
2x240
2x150/
2x240
3x185/
3x240
2x240/
3x185
2x150/
2x240
2x150/
2x240
3x185/
3x240
2x240/
3x185
2x150/
2x240
2x150/
2x240
3x185/
3x240
1x240/
2x150
1x185/
1x240
1x185/
1x240
2x150/
2x185
Recommended Upstream Protection and Cable Sizes for 625 kW UPS
Weights and Dimensions for UPSs with 1250 kW I/O Cabinet
Commercial ReferencePartsWeight kgHeight mmWidth mmDepth mm
•GVX500K500NHS
•GVX500K750NHS
•GVX500K1000NHS
•GVX500K1250NHS
•GVX625K625NHS
•GVX625K1000NHS
•GVX750K500NHS
•GVX750K750NHS
•GVX750K1000NHS
•GVX750K1250NHS
•GVX800K800NHS
•GVX1000K750NHS
•GVX1000K1000NHS
•GVX1000K1250NHS
•GVX1100K1100NHS
•GVX1250K1000NHS
•GVX1250K1250NHS
•GVX1500K1100NHS
•GVX1500K1250NHS
Total
– Power cabinets
– I/O cabinet
Total
– Power cabinets
– I/O cabinet
Total
– Power cabinets
– I/O cabinet
Total
– Power cabinets
– I/O cabinet
Total
– Power cabinets
– I/O cabinet
2030 (4475)
2x540 (2x1190)
950 (2094)
2570 (5666)
3x540 (3x1190)
950 (2094)
3110 (6856)
4x540 (4x1190)
950 (2094)
3650 (8047)
5x540 (5x1190)
950 (2094)
4190 (9237)
6x540 (6x1190)
950 (2094)
1970 (77.6)2400 (94.5)
2x600 (2x23.6)
1200 (47.2)
1970 (77.6)3000 (118.1)
3x600 (3x23.6)
1200 (47.2)
1970 (77.6)3600 (141.7)
4x600 (4x23.6)
1200 (47.2)
1970 (77.6)4200 (165.4)
5x600 (5x23.6)
1200 (47.2)
1970 (77.6)4800 (189.0)
6x600 (6x23.6)
1200 (47.2)
900 (35.4)
900 (35.4)
900 (35.4)
900 (35.4)
900 (35.4)
3x240/
4x240
3x240/
3x240
3x240/
3x240
4x240/
5x240
61. Long-time setting (Ir) = 0.9.
62. Long-time setting (I
63. Long-time setting (I
) = 1.0.
r
) = 0.95.
r
990-5850F-00145
Page 46
380 V, 400 V, 415 V, and 440 V UPS SystemFacility Planning
Weights and Dimensions for UPSs with 1500 kW I/O Cabinet
Part NumberPartsWeight kg (lbs)Height mm (in)Width mm (in)Depth mm (in)
•GVX500K1500HS
•GVX750K1500HS
•GVX1000K1500HS
•GVX1250K1500HS
•GVX1500K1500HS
•GVX1750K1500HS
In total
– Power cabinets
– I/O cabinet
In total
– Power cabinets
– I/O cabinet
In total
– Power cabinets
– I/O cabinet
In total
– Power cabinets
– I/O cabinet
In total
– Power cabinets
– I/O cabinet
In total
– Power cabinets
– I/O cabinet
1956 (4312)
2x540 (2x1190)
876 (1931)
2496 (5503)
3x540 (3x1190)
876 (1931)
3036 (6693)
4x540 (4x1190)
876 (1931)
3576 (7884)
5x540 (5x1190)
876 (1931)
4116 (9074)
6x540 (6x1190)
876 (1931)
4656 (10265)
7x540 (7x1190)
876 (1931)
Clearance
Clearance for UPSs with 1250 kW I/O Cabinet
1970 (77.6)3200 (126.0)
2x600 (2x23.6)
2000 (78.7)
1970 (77.6)3800 (149.6)
3x600 (3x23.6)
2000 (78.7)
1970 (77.6)4400 (173.2)
4x600 (4x23.6)
2000 (78.7)
1970 (77.6)5000 (196.9)
5x600 (5x23.6)
2000 (78.7)
1970 (77.6)5600 (220.5)
6x600 (6x23.6)
2000 (78.7)
1970 (77.6)6200 (244.1)
7x600 (7x23.6)
2000 (78.7)
900 (35.4)
900 (35.4)
900 (35.4)
900 (35.4)
900 (35.4)
900 (35.4)
NOTE: Clearance dimensions are published for airflow and service access
only. Consult with the local safety codes and standards for additional
requirements in your local area.
NOTE: The UPS system can be placed up against a wall and there is no
requirement for rear or side access.
Clearance for UPSs with 1500 kW I/O Cabinet
NOTE: Clearance dimensions are published for airflow and service access
only. Consult with the local safety codes and standards for additional
requirements in your local area.
NOTE: The UPS system can be placed up against a wall with no requirement
for rear or side access.
46990-5850F-001
Page 47
Facility Planning380 V, 400 V, 415 V, and 440 V UPS System
Front View
Guidance for Organizing Battery Cables
NOTE: For 3rd party batteries, use only high rate batteries for UPS
applications.
NOTE: When the battery bank is placed remotely, the organizing of the cables
is important to reduce voltage drop and inductance. The distance between the
battery bank and the UPS must not exceed 200 m (656 ft). Contact Schneider
Electric for installations with a longer distance.
NOTE: To minimize the risk of electromagnetic radiation, it is highly
recommended to follow the below guidance and to use grounded metallic tray
supports.
64. For temperatures between 40 °C and 50 °C, the load power rating must be derated with 2.5% per °C of rated output power. Above 40 °C
the minimum input voltage is 340 V, and from 380 V to 340 V, the charge power must be linearly derated from 12% to 1%.
65. Maximum operation altitude is 3000 m (10000 ft).
48990-5850F-001
Page 49
Facility Planning380 V, 400 V, 415 V, and 440 V UPS System
•Standard top cable entry battery cabinets or custom front terminal battery
cabinets
•Optional remote 10–inch LCD
•Optional Modbus RS-485 card
Configuration Options
•Single or dual feed
•Default top or bottom cable entry
•N+1 redundancy
•Up to 4+1 UPSs in parallel
•ECO mode
•ECOnversion mode
•StruxureWare Data Center Expert compatible
•Generator compatible
•Internal synchronization to alternate source (single system)
•Seismic rated brackets included
•Touchscreen LCD
990-5850F-00153
Page 54
380 V, 400 V, 415 V, and 440 V UPS SystemLimited Factory Warranty
Limited Factory Warranty
One-Year Factory Warranty
The limited warranty provided by Schneider Electric in this Statement of Limited
Factory Warranty applies only to products you purchase for your commercial or
industrial use in the ordinary course of your business.
Terms of Warranty
Schneider Electric warrants that the product shall be free from defects in materials
and workmanship for a period of one year from the date of product start-up when
start-up is performed by Schneider Electric-authorized service personnel and
occurs within six months of the Schneider Electric shipment date. This warranty
covers repairing or replacing any defective parts including on-site labor and travel.
In the event that the product fails to meet the foregoing warranty criteria, the
warranty covers repairing or replacing defective parts at the sole discretion of
Schneider Electric for a period of one year from the shipment date. For Schneider
Electric cooling solutions, this warranty does not cover circuit breaker resetting,
loss of refrigerant, consumables, or preventive maintenance items. Repair or
replacement of a defective product or part thereof does not extend the original
warranty period. Any parts furnished under this warranty may be new or factoryremanufactured.
Non-transferable Warranty
This warranty is extended to the first person, firm, association or corporation
(herein referred to by “You” or “Your”) for whom the Schneider Electric product
specified herein has been purchased. This warranty is not transferable or
assignable without the prior written permission of Schneider Electric.
Assignment of Warranties
Schneider Electric will assign you any warranties which are made by
manufacturers and suppliers of components of the Schneider Electric product and
which are assignable. Any such warranties are assigned “AS IS” and Schneider
Electric makes no representation as to the effectiveness or extent of such
warranties, assumes no responsibility for any matters which may be warranted by
such manufacturers or suppliers and extends no coverage under this Warranty to
such components.
Drawings, Descriptions
Schneider Electric warrants for the warranty period and on the terms of the
warranty set forth herein that the Schneider Electric product will substantially
conform to the descriptions contained in the Schneider Electric Official Published
Specifications or any of the drawings certified and agreed to by contract with
Schneider Electric if applicable thereto (“Specifications”). It is understood that the
Specifications are not warranties of performance and not warranties of fitness for
a particular purpose.
54990-5850F-001
Page 55
Limited Factory Warranty380 V, 400 V, 415 V, and 440 V UPS System
Exclusions
Schneider Electric shall not be liable under the warranty if its testing and
examination disclose that the alleged defect in the product does not exist or was
caused by end user or any third person misuse, negligence, improper installation
or testing. Further, Schneider Electric shall not be liable under the warranty for
unauthorized attempts to repair or modify wrong or inadequate electrical voltage
or connection, inappropriate on-site operation conditions, corrosive atmosphere,
repair, installation, start-up by non-Schneider Electric designated personnel, a
change in location or operating use, exposure to the elements, Acts of God, fire,
theft, or installation contrary to Schneider Electric recommendations or
specifications or in any event if the Schneider Electric serial number has been
altered, defaced, or removed, or any other cause beyond the range of the
intended use.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, BY OPERATION OF
LAW OR OTHERWISE, OF PRODUCTS SOLD, SERVICED OR FURNISHED
UNDER THIS AGREEMENT OR IN CONNECTION HEREWITH. SCHNEIDER
ELECTRIC DISCLAIMS ALL IMPLIED WARRANTIES OF MERCHANTABILITY,
SATISFACTION AND FITNESS FOR A PARTICULAR PURPOSE. SCHNEIDER
ELECTRIC EXPRESS WARRANTIES WILL NOT BE ENLARGED, DIMINISHED,
OR AFFECTED BY AND NO OBLIGATION OR LIABILITY WILL ARISE OUT OF,
SCHNEIDER ELECTRIC RENDERING OF TECHNICAL OR OTHER ADVICE OR
SERVICE IN CONNECTION WITH THE PRODUCTS. THE FOREGOING
WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER
WARRANTIES AND REMEDIES. THE WARRANTIES SET FORTH ABOVE
CONSTITUTE SCHNEIDER ELECTRIC SOLE LIABILITY AND PURCHASER’S
EXCLUSIVE REMEDY FOR ANY BREACH OF SUCH WARRANTIES.
SCHNEIDER ELECTRIC WARRANTIES RUN ONLY TO PURCHASER AND ARE
NOT EXTENDED TO ANY THIRD PARTIES.
Warranty Claims
IN NO EVENT SHALL SCHNEIDER ELECTRIC, ITS OFFICERS, DIRECTORS,
AFFILIATES OR EMPLOYEES BE LIABLE FOR ANY FORM OF INDIRECT,
SPECIAL, CONSEQUENTIAL OR PUNITIVE DAMAGES, ARISING OUT OF THE
USE, SERVICE OR INSTALLATION, OF THE PRODUCTS, WHETHER SUCH
DAMAGES ARISE IN CONTRACT OR TORT, IRRESPECTIVE OF FAULT,
NEGLIGENCE OR STRICT LIABILITY OR WHETHER SCHNEIDER ELECTRIC
HAS BEEN ADVISED IN ADVANCE OF THE POSSIBILITY OF SUCH
DAMAGES, SPECIFICALLY, SCHNEIDER ELECTRIC IS NOT LIABLE FOR ANY
COSTS, SUCH AS LOST PROFITS OR REVENUE, LOSS OF EQUIPMENT,
LOSS OF USE OF EQUIPMENT, LOSS OF SOFTWARE, LOSS OF DATA,
COSTS OF SUBSTITUANTS, CLAIMS BY THIRD PARTIES, OR OTHERWISE.
NO SALESMAN, EMPLOYEE OR AGENT OF SCHNEIDER ELECTRIC IS
AUTHORIZED TO ADD TO OR VARY THE TERMS OF THIS WARRANTY.
WARRANTY TERMS MAY BE MODIFIED, IF AT ALL, ONLY IN WRITING
SIGNED BY AN SCHNEIDER ELECTRIC OFFICER AND LEGAL DEPARTMENT.
Customers with warranty claims issues may access the SCHNEIDER ELECTRIC
worldwide customer support network through the SCHNEIDER ELECTRIC web
site: http://www.schneider-electric.com. Select your country from the country
selection pull-down menu. Open the Support tab at the top of the web page to
obtain contact information for customer support in your region.
990-5850F-00155
Page 56
Schneider Electric
35 rue Joseph Monier
92500 Rueil Malmaison
France
+ 33 (0) 1 41 29 70 00
*990-5850F-001*
As standards, specifications, and design change from time to time,
please ask for confirmation of the information given in this publication.