Saunier duval ISOFAST CONDENS F 35 E User Manual

Page 1
Page 2
INSTRUCTIONS FOR USE, INSTALLATION AND SERVICING
FOR ISOFAST CONDENS F 35 E
3
4000135500-2 04/04
INSTRUCTIONS FOR USE
Lighting : make sure that:
the boiler is connected
the gas service tap is open,
Switch ON (I). Switch off the boiler : Switch
to OFF (0) : the electrical supply is off. Stop the gas supply if the boiler is to be out of use for a long time.
In case of fault, the red warning light will flash and a code appears on the boiler display .
Code 21: Water pressure too low: open the blue tap (t) situated under the boiler until a pressure of 1.5 bar is obtained.
Other codes: press the key of the room thermostat and read the indications given by the display.
Lighting/switch off the boiler
Fault indication
1-On/Off switch. 2-Room thermostat disabled when the
button light is ON
3-Sanitary function enabled when the
button light is ON
4-Heating function enabled when the
button light is ON
5-Hot water temperature adjuster. 6-Heating temperature adjuster. 7-Graphic display. 8-Green running light. 9-Red, flashing fault light.
10- Yellow running lamp for the burner.
1
4
2
3
5
6
7
8
9
10
Operation without room thermostat
• Press the key (the key will light-up)
• Press the and/or buttons to activate the heating and/or hot water functions
• Use buttons and to determine the heating and hot water temperatures.
• To revert to the operating mode with room thermostat, again press the key (the light will turn OFF;
5
6
9
7
t
21
OK
2
Important notice : The settings performed
on the boiler control panel are not transmitted to the room thermostat.
Perform the temperature settings from the wireless room thermostat supplied together with the boiler, strictly adhering to the instructions given in this manual, pages 10 through 17.
Contents
INSTRUCTION FOR USE
Controls and Lighting page 2 Important informations 3 - 5 Guarantee informations 6 - 7 Controls informations 8 - 17
INSTALLATION INSTRUCTIONS
General informations 18 Dimensions 19 Technical Data 20 - 23 Boiler coponents 24 Schematic layout of boiler 25 Boiler location 26 - 27 Flue location and Ventilation 28 - 31 Heating System 32 - 33 Domestic Hot Water System 33 Boiler Installation 34 Piping installation 35 - 38 Electrical Connection 39 Commissioning on boiler 40 - 43 Commissioning on room thermostat 44 - 51 Gas conversion 52 - 53
SERVICING INSTRUCTION
Routine Cleaning and Inspection 54 - 59 Wiring Diagram 60 - 61 Fault Finding 61 - 63 Replacement of Parts 64 - 72 Spare Parts 73
Important information
The instructions consist of three parts, User, Installation and Servicing Instructions, which includes the Guarantee Registration Card. The instructions are an integral part of the appliance and must, to comply with the current issue of the Gas Safety (Installation and Use) Regulations, be handed to the user on completion of the installation.
General
This combination boiler is able to provide room heating as part of a central heating system, and domestic hot water direct from the cold water supply without the need for secondary storage. The central heating water temperature and domestic hot water temperature can both be adjusted on the boiler. Once the controls are set the boiler operates automatically. A frost protection program is also included.
Please read these instructions and follow them carefully for the safe and economical use of your boiler.
Gas Category
This boiler is for use only on Natural gas (G20) or propane (G31).
Gas Safety (Installation and Use) Regulations
In your own interests and that of safety, it is the Law that ALL gas appliances are installed by a competent person in accordance with the current issue of the above regulations.
Gas Testing and Certification
The boiler is tested and certificated for safety and performance. It is, therefore, important that no alteration is made to the boiler unless approved, in writing, by Saunier Duval. Any alteration not approved by Saunier Duval, could invalidate the certification, boiler warranty and may also infringe the current issue of the statutory requirements.
CE Mark
This boiler meets the requirements of Statutory Instrument, No. 3083 The Boiler (Efficiency) Regulations, and therefore is deemed to meet the requirements of Directive 92/42/EEC on the efficiency requirements for new hot water boilers fired with liquid or gaseous fuels. Type test for purposes of Regulation 5 certified by : Notified body 0086. Product/production certified by : Notified body 0086.
Page 3
USERS
54
Important information
The CE mark on this appliance shows
compliance with :
1. Directive 90/396/EEC on
the approximation of the laws of the Member States relating to appliances burning gaseous fuels.
2. Directive 73/23/EEC on
the harmonisation of the Laws of the Member States relating to electrical equipment designed for use within certain voltage limits.
3. Directive 89/336/EEC on
the approximation of the Laws of the Member States relating to electromagnetic compatibility.
Control of Substances Hazardous to Health
Under Section 6 of The Health and Safety at Work Act 1974, we are required to provide information on substances hazardous to health. The adhesives and sealants used in this appliance are cured and give no known hazard in this state.
Insulation Pads
These can cause irritation to skin, eyes and the respiratory tract. If you have a history of skin complaint you may be susceptible to irritation. High dust levels are usual only if the material is broken. Normal handling should not
cause discomfort, but follow normal good hygiene and wash your hands before eating, drinking or going to the lavatory. If you do suffer irritation to the eyes or severe irritation to the skin seek medical attention.
Spare Parts
REMEMBER, When replacing a part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Saunier Duval.
Manual Handling Guidance
During the appliance installation and the replacement of the heat exchanger it will be necessary to employ caution and assistance whilst lifting as the appliance or component exceeds the recommended weight for a one man lift. In certain situations it may be required to use a mechanical handling aid. Take care to avoid trip hazards, slippery or wet surfaces.
Gas Leak or Fault
If a gas leak or fault exists or
is suspected, turn the boiler mains electrical supply off and turn off the gas supply at the meter. Consult your local gas company or your local installation/ servicing company.
Electrical Supply Failure
The boiler must be earthed. The boiler will not work without an electrical supply. Normal operation of the boiler should resume when the electrical supply is restored. Reset any external controls, to resume normal operation of the central heating. If the boiler does not resume normal operation turn the mains reset switch off and on. If the boiler does not resume normal operation after this the overheat stat may have operated. The overheat stat would only operate under abnormal conditions and, under these circumstances; it would be advisable to consult your installation / servicing company.
Boilers Installed in a Compartment or Cupboard
If the boiler is fitted into a compartment or cupboard, it does not require any ventilation openings. Do not use the compartment or cupboard for storage.
Pluming from flue terminal
Like all condensing boilers this appliance will produce a plume of condensation from the flue terminal in cool weather. This is due to the high efficiency and hence low flue gas temperature of the boiler. It is normal and not a fault indication.
Replacement Parts
If replacement parts are required contact Saunier Duval service using the telephone number on the back cover of this booklet. Please quote the name of the appliance this infomation will be on the front of the appliance.
Protection Against Freezing
The room thermostat automatically ensures a minimum installation temperature of 6°C. This protection is ensured by the room thermostat as long as it is active. This means that the button of the boiler must not be lit and that the batteries of the room thermostat must be in good condition.
If you are out of home for a few days, use the holidays mode of your room thermostat, and set the Start and End dates, as well as the desired temperature.
If the mains electricity and gas are to be turned off for any long periods during severe weather, it is recommended that the whole system, including the boiler, should be drained to avoid the risk of freezing.
Contact your installation/servicing company as draining, refilling and pressurising MUST be carried out by a competent person.
As a safety feature the boiler will stop working if the condensate drain becomes blocked. During freezing conditions this may be due to the forming of ice in the condense drain external to the house. Release an ice blockage by the use of
warm cloths on the pipe. The boiler should then restart. Contact your installation/servicing company if the fault persists.
Draining and Filling
This boiler works in a pressurised system, which must only be drained, refilled and pressurised by a competent person.
Pressure Relief Safety Valve
A pressure relief safety valve and discharge pipe is fitted to the boiler. This valve must not be touched. Should there be any discharge from the pipe, isolate the boiler electrical supply and call your installer or Saunier Duval service using the telephone number on the back cover of this booklet.
Access to the user menu :
+
HOLIDAYS START DATE
OK
MENU
END DATE
CANCEL
OK
+
Page 4
To ensure the continued efficient and safe operation of the appliance it is recommended that it is checked and serviced as necessary at regular intervals. The frequency of servicing will depend upon the particular installation conditions and usage, but in general once a year should be enough. Refer to Section «Routine Cleaning and Inspection».
If this appliance is installed in a rented property there is a duty of care imposed on the owner of the property by
the current issue of the Gas Safety (Installation and Use) Regulations, section 35. Servicing/maintenance should be carried out by a competent person in accordance with the rules in force in the countries of destination.
To obtain service, please call your installer or Saunier Duval service using the telephone number on the back cover of this booklet.
Please be advised that the ‘Benchmark’ logbook
should be completed by the installation engineer on completion of commissioning and servicing. All CORGI Registered Installers carry a CORGI ID card, and have a registration number. Both should be recorded in your boiler Logbook. You can check your installer is CORGI registered by calling CORGI direct on: 01256 372300.
Cleaning
The boiler casing can be cleaned with a damp cloth followed by a dry cloth to polish. Do not use abrasive or solvent cleaners.
Boiler casing
CAUTION. Do not remove or adjust the casing in any way, as incorrect fitting may result in faulty operation. If in doubt, consult your installation/service company.
USERS
76
Servicing, all you need to know
Many thanks for choising Saunier Duval market leaders in boiler manufacture,
Your appliance is guaranteed for a period of 24 months from the date of installation or 30 months from the date of manufacture whichever is
the shorter and covers manufacturing defects only.
We, Saunier Duval, undertake to repair or replace parts free of charge which are recognised by us to be of faulty manufacture ­if necessary after return to our factory for examination ­on condition that : a) The appliance was installed by a qualifled gas installer in accordance with installation instructions, and all the relevant codes of practice, standards and legislation in force. b) The appliance has been used for normal domestic purposes and in accordance with the manufacturer's operating and maintenance
instructions. c) The appliance has not been serviced, maintained, repaired dismantled or tampered with during the guarantee period, by anyone other than an engineer approved by Saunier Duval. d) The appliance is still in the possession of the original user, and proof of purchase in the form of a receipt or invoice is shown to the service engineer on request. The repair or replacement of parts during the guarantee period does not have the effect of extending the period.
This guarantee does not cover :
a) Any defects or damage resulting from incorrect or poor installation, inadequate servicing, or maladjustment of the gas or water used. b) Any defects in the system to which the appliance is connected. c) Any deterioration or maladjustment following changes in the nature or pressure of the gas or the water used, or a change in the characteristics of the electrical supply voltage.
Notification of any fault should be made to the appliance installer. No repairs should be undertaken upon the
Welcome users
appliance, intending it to be covered by the product guarantee without prior authorisation from Saunier Duval.
IMPORTANT : The appliance serial number must be quoted on all correspondence/contact made with Saunier Duval.
This guarantee is in addition to your statutory and other legal rights, which will not be excluded or diminished by the return of the guarantee registration card.
Page 5
USERS
8 9
SYSTEM PRESSURE TOO LOW FILL IN AT 1,5 BAR
Ambient
temperature display
Time period for the
COMFORT temperature
Hot water mode indicator
Heating mode
indicator
Time display
Time period for the ECO temperature
Low battery indicator
1-Display. 2- Fault indicator. 3-Return to previous menu 4-Confirm OK. 5-Access to the menus. 6 - Menu scrolling 7-Changing the mode 8-Wall bracket 9-Mains power plug
1
2
3
4
5 6
7
8
9
Fault description
Heating demand indicator
Indicators of the current temperature levels for “COMFORT or ECO” (Day/Night).
(Attention: this value may
vary when you hold the
thermostat in your hand).
Your Isofast boiler is factory set to operate within a customary installation.
Nevertheless, as many installations may incorporate specific features, feel free to contact your installer who will be able – by adapting the parameters of the boiler (maximum temperature and/or maximum power of the heating system) - to warrant you the best operating performance of your installation.
These settings being made, you still have the possibility of selecting the ambient temperature to suit your own requirements not only when you are at home, but also during nightime or when you are out
All these settings are achieved from the room thermostat supplied together with your boiler: if you accurately determine the temperatures that best suit to your needs, you will make significant savings in terms of gas consumption.
Control as a source of savings
Essential adjustments to the wireless room thermostat : A – Setting the time B – Setting the date
The thermostat’s weekly programme functions enable you : C – To activate or deactivate the heating function.
D – To have a standard weekly programme by
activating the programme pre-set at the factory.
E – To bypass the current programme, temporarily, to increase or lower the temperature at any time during the day.
F – To set up a custom programme for each day of the week, with 2 temperature levels, for example:
COMFORT for the periods you are present and.
ECO at night or when you are away.
G – To have the same temperature 24 hours a day by deactivating the programme.
H – To leave on holiday, determining the desired temperature according to the date you leave and when you return.
I – To select the temperature of your domestic hot water from 38°C to 60°C. However, keeping the temperature below 50°C, reduces gas consumption and provides good protection against scalds.
J – To prevent undesired alterations to your settings by locking the thermostat’s buttons.
K – To be informed of any operating faults in the
boiler and be instructed in the procedure to follow.
Page 6
USERS
1110
Control as a source of savings
A B
Progress of the operations :
at any time takes you back to the previous step
1 - Accessing the user menu
• Press to call up the next menu:
2 - Setting the time
• Use the buttons to select the "Set time" menu:
3 - Setting the date
• Use the buttons to select the "Set date" menu:
• Press to select the "ON/OFF heating " menu:
1 - Activate the heating
MENU
SET TIME
SET DATE
C
MENU
ON/OFF HEATING
Settings for the time and the dateand
OK
OK
Please note that pressing button
SET COMFORT T¡
SET ECO T¡ PROGRAMME SET HOT WATER T¡ ON/OFF HEATING HOLIDAYS SET TIME SET DATE
17:23
TUE 14/JUA/ 03
+
+
OK
OK
Activating/deactivating the heating function
PROGRAMME
+
OK OK
OFF
SET HOT WATER T¡ ON/OFF HEATING ...
ON
C
OK
D
Progress of the operations:
1 - Activating the weekly programme
PROG
• Press , the room thermostat shows this display:
• Pressing reverses ON and OFF mode every time
• When the ON mode appears, wait 5 seconds for the display to return to normal position and automatically validate the selection.
2 -Accessing the initial programme
• Press to select the "Programme" menu :
PROGRAMME
• Exit from the menu by pressing , which initiates the standard weekly programme pre-set at the factory :
Monday to Friday
• Pressing one of the scroll buttons calls up the menu for setting the ambient temperature :
PROG
MENU
ECO ECOCOMFORT COMFORT
11 PM >> 6 AM>> 8 AM >> 4 PM >> 11 PM
E
Temporarily bypassing the weekly programme
Activating the initial programme
Please note that pressing button at any time takes you back to the previous step.
or
PROGRAMME ON
OK
+
OK
+
PROGRAMME OFF
INITIAL PROGRAMME MONDAY
SET COMFORT T¡ SET ECO T¡ PROGRAMME ...
C
Weekends
ECO temperature 16°C COMFORT temperature 19°C
ECO COMFORT
11 PM >> 7 AM >> 11 PM
C
OK
2 - Deactivate the heating
ON/OFF HEATING
OK OK
ON
OFF
SET ROOM T¡
22¡C
This setting is automatically cancelled when the programme changes to Eco or Confort temperature level.
SET ROOM T¡
20¡C
Confirm by pressing
OK
OK
Page 7
USERS
1312
PROG
OK
MODIFY COPY TO
MONDAY TUESDAY
MONDAY
TUESDAY
OK OK OK
• Press to confirm the parameters you have set for the day.
• Follow the same procedure for every day of the week or use the duplication function, as explained below.
19.5
MODIFY TIME-SLOTS : T¡ CHOICE : PROG
19.5 16.5
Press to switch from COMFORT to ECO temperature
This symbol indicates the mode authorising deletion of black squares to set up operating periods at the stated ECO temperature using the buttons / .
E.g. :
In the case of the illustration opposite, each press of the button adds a blank from 6 AM onwards, corresponding to an extra 30 minutes heating at 16.5°C.
E.g. :
In the case of the illustration opposite, each press of the button adds a square from 11 PM onwards, corresponding to an extra 30 minutes heating at
19.5°C.
This symbol indicates the mode authorising additional operating periods at the stated COMFORT temperature (black squares) using the buttons / .
The squares indicate
the time periods when the boiler will provide the COMFORT temperature level (e.g.: 19.5°C between 4 PM and 11 PM and 6 AM and 8 AM)
The blanks indicate
the time periods when the boiler will provide the ECO temperature level. (e.g.: 16.5°C between 8 AM and 4 PM and 11 PM and 6 AM)
Duplicating a programme
• To save time, you can copy the parameters you have set onto another day via the menu :
/
MODIFY TIME-SLOTS : T¡ CHOICE : PROG
/
MODIFY TIME-SLOTS : T¡ CHOICE : PROG
/
23:00 6:00
Control as a source of savings
OK OK
SET COMFORT T¡
SET COMFORT T¡
SET ECO T¡ PROGRAMME ...
19.0¡C
19.5¡C
18.5¡C
20.0¡C
OK
PROGRAMME
MODIFY COPY TO
MONDAY
TUESDAY WEDNESDAY THURSDAY FRIDAY SATURDAY SUNDAY INITIAL PROGRAMME
OK OK
/...
/...
(to set the desired temperature during the day)
(to set the desired temperature during the night or while you are away)
OK OK
SET ECO T¡
16.0¡C
16.5¡C
16.0¡C
17.0¡C
/...
/...
(to allocate time periods for the Comfort and Eco temperatures)
PROG
PROG
• When the ON mode appears, wait 5 seconds for the display to return to normal position and automatically validate the selection.
PROGRAMME OFF
PROGRAMME ON
or
C
• Press to call up the next menu:
• Press , the room thermostat shows this display:
• Pressing reverses ON and OFF mode every time.
Progress of the operations :
MENU
Setting the custom weekly programme
1 - Activating the weekly programme
2 - Access to the user menu
3 - Setting the Comfort temperature
4 - Setting the Eco temperature
5 - Programme
Please note that pressing button at any time takes you back to the previous step.
F
Page 8
USERS
1514
SET ECO T¡ PROGRAMME SET HOT WATER T¡ ...
OK OK
SET HOT WATER T¡
50¡C
51¡C 49¡C
52¡C
/....
/....
(to set the hot water to the desired temperature)
C
• Press to call up the next menu :
Progress of the operations :
MENU
Setting the hot water temperature
1 - Access to the user menu
2 - Setting the hot water temperature
Please note that pressing button at any time takes you back to the previous step.
+
I
Locking/unlocking the thermostat’s buttons
J
• Holding down the and buttons simultaneously for 3 seconds locks the room thermostat’s buttons.
• Follow the same procedure to unlock the buttons.
Press for 3 seconds
C
OK
OK OK
SET ROOM T¡
SET ROOM T¡ ...
19.0¡C
19.5¡C
18.5¡C
20.0¡C
/...
/...
(to set the constant temperature desired)
PROG
C
• Press to call up the next menu :
• Pressing activates or deactivates the programme mode each time :
• Retain the
PROGRAMME OFF position. After 5 seconds, the display returns to its normal position
and automatically validates this selection.
Progress of the operations :
MENU
Setting the heating temperatures outside Programme mode
1 - Deactivating the weekly programme
2 - Access to the user menu
3 - Setting the ambient temperature
Please note that pressing button at any time takes you back to the previous step.
PROGRAMME ON PROGRAMME OFF
PROG PROG
G
Control as a source of savings
SET HOT WATER T¡ ON/OFF HEATING HOLIDAYS ...
HOLIDAYS
• Press to call up the next menu :
• Determine the temperatures you wish according to your departure and return dates.
MENU
Holiday programme
1 - Access to the user menu
2 - Activating the Holiday programme
+
H
+
OK
OK
START DATE END DATE SET ROOM T¡ CANCEL
Page 9
USERS
1716
Glossary for the user menu
Control as a source of savings
Setting the ambient temperature when the programme has not been activated (Programme inactive).
Setting the Confort temperature for the periods set in “Programme” menu.
Setting the reduced temperature for the periods set in the “Programme” menu.
Allocating operating periods for Confort and Eco temperature for each day of the week. In the morning, for
example, you are recommended to start heating approximately 1 hour before you get up.
Displaying the external temperature when an external sensor is installed.
Setting the hot water temperature. Starting / stopping heating
On = Heating + hot water Off = Hot water only Outdoor T° = displayed when an external sensor is
connected. When “Driven by ext. T°” is selected, the boiler automatically cuts off the heating when the temperature is higher than 18°C (factory setting).
Displayed if your installer has selected "consigne ”manual“ in the “heating control” menu under the “installer” menu
Setting the ambient temperature for while you are away.
Setting the time. Setting the date.
Set room T°
Set comfort T°
Set eco T°
Programme
Outdoor T°
Set hot water T° ON/OFF heating
Set radiator T° or Floor heating T°
Holidays
Set time Set date
K
• If a fault occurs, the red lights on the boiler and on the room thermostat flash
and a pictogram is displayed on the thermostat : , , , or
• Press the button on the thermostat:
Fault level 1
• The thermostat shows the procedure to follow:
• At the same time, the boiler’s screen shows the code for the fault:
OK
Fault indicators
SYSTEM PRESSURE TOO LOW FILL IN AT 1.5 BAR
21
Fault level 2
• The thermostat asks you to call your After-Sales service engineer, informing him of the fault code flashing on the boiler to assist in his diagnosis.
• At the same time, the boiler’s screen shows the code for the fault:
FLOW RATE FAULT CALL AFTERSALES TEL 00 00 00 00 00
23
Page 10
INSTALLERS
1918
Dimensions
The boiler is delivered in one package :
the boiler itself, the wireless thermostat, the fixing bracket, the template and pipe connections .
The different packages relating to the flue system will be ordered depending on the actual configuration of the installation
418
890
510
232
Isofast F 35E Net weight (kg) 52 Gross weight (kg) 60
The “as delivered” package consists of :
- 1 wireless thermostat
- 1 fixing bracket
- 3 x 1.5 V alkaline battery cells type LR6
- 1 access cover to the battery cells
ATTENTION: DO NOT FORGET TO RECOVER THE ROOM THERMOSTAT placed in a
polystyrene case in the bottom of the package.
General Information
IMPORTANT NOTICE
The boiler and pipes are supplied in one pack, the flue is supplied seperately. This boiler is factory set for use only on G20 natural gas.
Where no British Standards exists, materials and equipment should be fit for their purpose and of suitable quality and workmanship. Refer to Manual Handling Operations, 1992 regulations.
The installation of this boiler must be carried out by a competent person in accordance the rules in force in the countries of destination.
Manufacturer’s instructions must not be taken as overriding statutory requirements.
Sheet Metal Parts
WARNING: When installing the appliance, care should be taken to avoid any possibility of personal injury when handling sheet metal parts.
Statutory Requirements
The installation of the boiler MUST be carried out by a competent person in accordance with the relevant
requirements of the current issue of : Manufacturer’s instructions, supplied.
The Gas Safety (Installation and Use) Regulations, The Building Regulations, The Building Standards (Scotland) Regulations (applicable in Scotland), local Water Company Bylaws, The Health and Safety at Work Act, Control of Substances Hazardous to Health, The Electricity at Work Regulations and any applicable local regulations. Detailed recommendations are contained in the current issue of the following British Standards and Codes of Practice, BS4814, BS5440 Part 1 and 2, BS5449, BS5546, BS6700, BS6798, BS6891 and BS7074 Part 1 and 2, BS7478, BS7593, BS7671.
We also suggest that you have to hand a copy of the British Gas publication, “Guidance Notes for the Installation of Domestic Condensing Boilers”.
Manufacturer’s notes must not be taken as overriding statutory obligations.
Certification
This boiler certificated to the current issue of EN 483 for
performance and safety. It is important that no alteration is made to the boiler, without permission, in writing, from Saunier Duval.
Any alteration that is not approved by Saunier Duval., could invalidate the warranty and could also infringe the current issue of the Statutory Requirements.
Electrical Supply
All system components shall be of an approved type and all wiring to current I.E.E. wiring regulations. External wiring must be correctly earthed, polarised and in accordance with the relevant standards.
In GB this is BS 6891. In IE this is the current edition of I.S.813 "Domestic Gas Installations". The boiler must be connected to a permanent 230V ac, 50Hz supply. Connection of the whole electrical system of the boiler, including any heating controls, to the electrical supply must be through one common isolator and must be fused 3 Amp maximum.
Wiring to the boiler must be PVC 85°C insulated cable, not less than 0.75mm2 (24/0.20mm).
Page 11
INSTALLERS
2120
Natural Gas (G 20) F 35 E
Ø burner injector (mm) 5,65 inlet pressure (mbar) 20 Sanitary flow rate at maximum input (m
3
/h) 3,62
Heating flow rate at maximum input (m
3
/h) 3,02
Flow rate at minimum input (m
3
/h) 0,85
Electricity F 35 E
Electrical supply (V) 230 Electrical rating (A) 0,9 Maximum absorbed power (W) 206 IP classification IPX4D Class 1
Technical Data Isofast
Heating F 35 E
Heating output at 80°C/60°C (P) adjustable (kW) from 7,6 to 28
(BTU/H) from 25,930 to 95,536
Heating input min. (Q) (kW)/(BTU/H) 8 / 27,296 Heating input max. (Q) (kW)/(BTU/H) 28,6 / 97,583 SEDBUK efficiency (%) ? Heating output at 50°C/30°C adjustable (kW) from 8,6 to 30,6 Maximum heating temperature (°C) 80 Minimum heating temperature (°C) 22 Expansion vessel charge pressure (bar) 0,5 Maximum system capacity at 75°C (l) 215 Safety valve, maximum service pressure (PMS) (bar) 3,0
Hot water F 35 E
Heating output (P) adjustable from… (kW)/(BTU/H) 34,2 / 116,690
to… (kW)/(BTU/H) 7,6 / 25,931
Maximum hot water temperature (°C) 60 Threshold flow rate (l/min.) 1 Specific flow rate (D) (for 30°C temp rise) (l/min.) 16,3 Storage capacity (l) 4 Expansion valve setting (bar) 10 Minimum operating pressure (bar) 0,7 Maximum operating pressure (P
MW) (bar) 10
Combustion F 35 E
Product outlet diameter (mm) 60 Fresh air inlet diameter (mm) 100 Fresh air flow rate (1013 mbar - 0°C) (m
3
/h) 43
Product outlet flow rate (g/s) 15,3 Product outlet temperature (°C) 68 Values of product outlet CO (ppm o mg/kWh) 100 or 176
CO2 (%) 9,2
NOx (ppm o mg/kWh) 21,1 or 37,3
Gas Supply
The gas installation must be in accordance with the relevant standards. In GB this is BS6891. In IE this is the current edition of I.S.813 "Domestic Gas Installations".
The supply from the governed meter must be of adequate size to provide a steady inlet working pressure of 20mbar (8in wg) at the boiler.
On completion, test the gas installation for soundness using the pressure drop method and suitable leak detection fluid, purge in accordance with the above standard.
Technical Data
All dimensions are given in millimetres (except as noted).
The data label is positioned on the inner door.
The Seasonal Efficiency Domestic Boilers UK (SEDBUK) is Band 'A'.
The value is used in the UK Government's Standard Assessment Procedure (SAP) for energy rating of dwellings. The test data from which it has been calculated has been certified by B.S.I.
F 35 E
Gas category II2H3P
Page 12
INSTALLERS
2322
By-pass fully shut Open 1/2 turn
By-pass fully shut Open 1/4 turn Open 1/2 turn Open 2 turns
1 2
NB : Factory seeting : Speed II
III
II
I
Speed III
Bypass
The Isofast boiler has a built-in bypass. This must be adjusted according to the requirements of the system, refer to the flow rate pressure curve. The boiler is supplied with the built-in bypass open a half a turn. It is adjusted by turning the bypass screw (a). Turn the screw clockwise to close the bypass. When using thermostatic radiator valves (TRV’s) on all of the radiators, it is essential that a separate, adjustable bypass of 15 mm minimum diameter is fitted between the flow and return
of the heating circuit.Any bypass must be fitted before system controls.
a
By-pass fully shut Open 1/4 turn
Open 1/2 turn
70 60 50
40 30
20 10
500 14001000
2
3
9
7
8
6
1
4
5
Curve output/pressure
Available pressure (kPa)
between heating supply and return lines
Flow rate through heating system (l/h)
Technical Data
Speed II
Speed I
3 4
5 6
7
8 9
Page 13
INSTALLERS
2524
1
3
22
AB C DE
2
8
9
7
10
14
13
12
11
19
24
15
16
17
18
20
21
23
25
26
27
28
29
30
31
32
6
3
4
5
Isofast F 35 E
Schematic layout of boiler
1-Flue outlet 2-Main heat exchanger 3-Burner 4-Ignition and controle
electrode
5-Fan 6-Gas control valve 7-DHW storage vessel 8-Condensate drain 9-Overheat safety
thermostat.
10 - Temperature sensor for
DHW storage vessel
11 - Expansion vessel 12 - Heating return
thermistor
13 - Heating outlet
thermistor
14 - Ignition module 15 - Pump 16 - Water pressure sensor 17 - Domestic plate to plate
heat exchanger
18 - Three way valve 19 - Heating element 20 - Drain cock 21 - Water flow sensor 22 - Discharge safety valve
3 bars
23 - DHW temperature
sensor
24 - Discharge safety valve
10 bar
25 - Isolating valve 26 - Filter on cold water inlet 27 - Filling system 28 - Filter on heating circuit 29 - Isolating valve 30 - Isolating valve 31 - Isolating valve 32 - Isolating valve
A-Heating return
B-Cold water inlet C-Heating flow D-Domestic hot water
outlet
E-Gas
a-Flue outlet
b-Overheat safety
thermostat.
c-Combustion chamber d-Expansion vessel e- Air/Gas mixture inlet
f-Ignition and control
electrode
g-Fan h-Gas control valve
i-Ignition module j-Condensate drain
k-Heating flow
thermistor
l-Heating return
thermistor
m-Water flow sensor
n-Water pressure sensor o-Pump p-Filter on cold water
inlet
q-Domestic plate to plate
heat exchanger
r-Discharge safety valve
10 bar
s-Discharge safety valve
3 bar
t-Filling system u-Drain cock v-Room thermostat plug
w-Control panel
Boiler components
Isofast F 35 E
a
b
c
d
f
e
j
k
l
m n
q
r
t
u
v
w
g
h
i
s
o
p
Page 14
INSTALLERS
2726
installed in a timber frame building it should be fitted in accordance with the Institute of Gas Engineers document IGE/UP/7/1998. If in doubt seek advice from the local gas undertaking or Saunier Duval.
• The boiler is room sealed, so when it is installed in a room or space, a permanent air vent is not required.
• Due to the high efficiency and hence low casing temperature of this boiler, cupboard or compartment ventilation is not necessary.
Boiler location
• This boiler is not suitable for outdoor installation.
• This boiler may be installed in any room, although particular attention is drawn to the installation of a boiler in a room containing a bath or shower where reference must be made to the relevant requirements. In GB this is the current I.E.E. WIRING REGULATIONS and BUILDING REGULATIONS. In IE reference should be made to the current edition of I.S.813 "Domestic Gas Installations" and the current ETCI rules.
• The boiler should be positioned so that at least the minimum operational and servicing clearances are provided, see diagram opposite. Additional clearances may be beneficial around the boiler for installation and servicing. For flue installations where external access is not practicable, consideration should be given for the space required to insert the flue internally, which may necessitate clearance larger than those specified in diagram.
• If the boiler is to be
Leave existing air vents. A template is supplied with the fixing bracket. Position setting of the assembly shall be performed in compliance with the indications shown on the template. Use two or three screws for the fixing bracket.
The mechanical characteristics of the screws shall – at least – meet the requirements specified on the sketches below. Also, they shall be suited to the characteristics of the carrier wall.
16 kg mini
33 kg mini
16 kg mini
33 kg mini
If the boiler is not immediately installed, protect the different
couplings so that no plaster or paint could jeopardize the tightness of subsequent
connections.
232
GAS
70 102 702115
20 mini
160
11875066
160
Ø 105
890
510
Page 15
INSTALLERS
2928
Flue location and Ventilation
Flue Position and Length
The standard horizontal flue is fitted onto the top of the boiler using the flue elbow. See diagrams to determine whether a standard flue can be used.
An elevated flue system can be installed with the addition of a vertical flue adapter, extension kits and elbow, see section flue options.
When extension pipes are used the flue system must be designed to have a continuous fall to the boiler of at least 3% to allow condensate to run back into the boiler and out via the drain.
Internal Flue Installation
The flue can be installed from inside the building, when access to the outside wall face is not practicale.
Additional accessories are available. See Saunier Duval "Flue Options Guide" for configurations available.
Minimum siting dimensions for fanned flues terminals poritions Horizontal flues A-directly below an opening, air brick,
opening windows . . . . . . . . . . . . . . . . . . . . . . . . .300
B-above an opening, air brick, opening windows . . . .300
C - horizontally to an opening, air brick,
opening windows . . . . . . . . . . . . . . . . . . . . . . . . .300
D- below gutter, drain/soil pipe . . . . . . . . . . . . . . . . . . .25
E-below eaves . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25
F-below a balcony or car port . . . . . . . . . . . . . . . . . .25
G- from vertical drain pipes and soil pipes . . . . . . . . . .25
H- from internal/external corners . . . . . . . . . . . . . . . . .25
H*- to a boundary alongside the terminal . . . . . . . . . . .300
I-above adjacent ground or balcony level . . . . . . . . .300
J-from surface or a boundary facing the terminal . . .600
K-facing terminals . . . . . . . . . . . . . . . . . . . . . . . . .1200
L-from opening (door/window) in car port
into dwelling . . . . . . . . . . . . . . . . . . . . . . . . . . . .1200
M - vertical from a terminal . . . . . . . . . . . . . . . . . . . .1500
N - horizontally from a terminal . . . . . . . . . . . . . . . . . .300
Vertical flues
P-from another terminal . . . . . . . . . . . . . . . . . . . . . .600
Q- above roof level . . . . . . . . . . . . . . . . . . . . . . . . . . .300
R-from adjacent opening window . . . . . . . . . . . . . .1000
S-from adjacent wall to flue . . . . . . . . . . . . . . . . . . . .300
H* and J* : These dimensions comply with the building regulations, but they may need to be increased to avoid wall staining and nusance from pluming depending on site conditions.
Warning notice :
Use only flue accessories developed for
Saunier Duval condensing boilers.
Page 16
INSTALLERS
3130
Flue location and Ventilation
• Terminal Position
The minimum acceptable siting dimensions for the terminal from obstructions, other terminals and ventilation openings are shown in page 29. For Ireland the minimum distances for flue terminal positioning must be those detailed in I.S.813 "Domestic Gas Installations".
The terminal must be exposed to the external air, allowing free passage of air across it at all times.
Being a condensing boiler some pluming may occur from the flue outlet. This
should be taken into consideration when selecting the position for the terminal.
It may be necessary to increase dimensions H & J if there is a risk that the boiler products could stain any adjoining surface.
Carports or similar extensions of a roof only, or a roof and one wall, require special consideration with respect to any openings, doors, vents or windows under the roof. Care is required to protect the roof if made of plastic sheeting. If the carport comprises of a
roof and two or more walls, seek advice from the local gas supply company before installing the boiler.
• Terminal Guard
A terminal guard is required if persons could come into contact with the terminal or the terminal could be subject to damage. If a terminal guard is required, it must be positioned to provide minimum of 50mm clearance from any part of the terminal and be central over the terminal.
3%
The flue system pipes must feature a slope of 3% towards the boiler in order to recover any condensates.
Attention : The flue system terminal supplied by Saunier Duval already integrates this slope. Therefore, it shall be
applied to any flue system extensions.
L
64
Gasket
The maximum head loss is reached with an elbow and flue system length (L) of 10 m.
Horizontal flues (installation type C13)
Page 17
INSTALLERS
3332
Heating system
General
The boiler is for use only with sealed central heating systems. The safety valve is an integral part of the boiler and it cannot be adjusted. The digital readout on the controls fascia indicates the system pressure when there is no central heating demand. The circulation pump is integral with the boiler.
Expansion vessel
The boiler has an integral expansion vessel with a capacity of 10 litres, with a charge pressure of 0.5 bar. Note : The expansion vessel volume depends on the total water system volume and the initial system design pressure. Guidance on vessel sizing is also given in the current issue of BS5449 and BS7074 Part 1, for IE refer to the current edition of I.S.813 "Domestic Gas Installations".
Flow rate
If it is necessary to alter the flow rate, the system can be fitted with a lockable balancing valve in the main flow or return pipes shown as valve "A" in diagram. The flow rate through the boiler must not be allowed to fall below 14 l/min.
Bypass
The boiler is fitted with an adjustable automatic bypass. Ensure that under no circumstances does the flow rate drop below 14l/min.
The installation of the boiler must comply with the requirements of the current issue of BS6798, in Ireland, refer also to the current edition of I.S.813 "Domestic Gas Installations".
In GB it is necessary to comply with the Water Supply (Water Fittings) Regulations 1999 (for Scotland, the Water Byelaws 2000, Scotland).
To comply with the Water regulations your attention is drawn to : The Water Regulations guide published by the Water Regulations Advisory Service (WRAS) gives full details of the requirements.
Heating system
In IE the requirements given in the current edition of I.S.813 "Domestic Gas Installations" and the current Building Regulations must be followed.
Water tratment
In the case of an existing installation, it is ESSENTIAL that prior to installing the new boiler the system is thoroughly flushed. For optimum performance after installation of a new system, the boiler and its associated central heating system should also be flushed. Flushing should be carried
out in accordance with BS7593: 1992 using a cleanser such as Sentinel X300 or X400, Fernox Superfloc or Salamander corrosion guard cleaner. For long-term corrosion protection, after flushing, an inhibitor suitable for stainless steel heat exchangers should be used, refer to the current issue of BS 5449 and BS 7593 on the use of inhibitors in central heating systems. Examples are Sentinel X100 Fernox or Salamander corrosion guard inhibitor.
Draining Tap
A draining tap must be provided at the lowest points of the system, which will allow the entire system to be drained. A drain tap for the appliance is provided as an integral part of the hydroblock, see diagram page 24. General - All domestic hot water circuits, connections, fittings must be in accordance with the relevant standards and water supply regulations.
Domestic Hot Water System
For GB: Guidance G17 to G24 and recommendation R17 to R24 of the Water Regulations Guide. For IE: The current edition of I.S.813 "Domestic Gas Installations".
Water Pressure
The maximum working pressure of the domestic hot water circuit is 10 bar. If the cold water supply pressure exceeds this, then
a pressure-reducing valve must be fitted in the supply to the boiler.
'Hard' Water Areas
The temperatures within the heat exchanger are limited by the boiler control system to minimise scale formation within the hot water pipework. However, in areas where the water is 'hard' (i.e. more than 200mg/litre), it is recommended that the hot
water setting is reduced and that a scale reducer is fitted. Refer to the manufacturer's instructions or consult the local water company for additional advice.
Domestic Water Flow Rate
The water flow rate is restricted to a maximum 16 l/min by a restrictor fitted on the cold water inlet.
Page 18
INSTALLERS
3534
2
Boiler installation
Prior to performing any operation, it is essential that the piping systems be flushed with a suitable product in order to eliminate any impurities such as fillings, weld spatters, oils and greases.
Such foreign materials could be driven into the boiler, and could impair its operation. NB: Solvents may cause damages to the piping system. Remove the wooden beam placed behind the boiler.
Appliance Connection
IMPORTANT: With regards to the Manual Handling Operations, 1992
Regulations, the following lift operation exceeds the recommended weight for a one man lift, refer to Manual Handling section, on page 4. The appliance will contain a small amount of water, place a water container beneath the boiler connections before removing the protective caps.
1 - Lifting the boiler into position, lean the top of the boiler slightly to the wall and position just above the hanging bracket.
2 - Lower the boiler slowly and engage onto the hanging bracket.
Connect isolating valves using washers and domestic flow restrictor supplied with the boiler.
3 - Do not forget to connect the blue extension on the filling tap, as shown on the picture below.
1
3
A
B
C
D
E
GAS
70
70
115
250
223
WALL
102
u
t
v
w
x
Piping installation
Make connections to boiler, gas, water and heating cocks with the tube assemblies supplied in piping pack as shown in the diagram below :
A-Heating return with isolating tap (t) and (u), B-Cold water inlet with isolating tap (v) and water restrictor to 16 l/min, C-Heating flow with isolating tap (w), D-Domestic hot water outlet, E-Gas inlet with isolating tap (x).
Water restrictor
16 l/min.
Pressure connection
Gas Connection
Before connection check supply of local gas. Refer also to page 18. Do not subject the gas service cock to heat. Fit the sealing washer into the union nut and make good the connection to the gas service cock on the wall.
Make sure the on / off lever is accessible. The whole of the gas installation, including the meter, should be inspected, tested for soundness and purged in accordance with the current issue of BS6891 and in IE the current edition of I.S.813 "Domestic Gas Installations".
A - C : Central heating
Ø 22 mm
B- D : Domestic hot
water Ø 15 mm
E : Gas supply Ø 15 mm
Page 19
INSTALLERS
3736
Water Connections
Flush out the domestic hot water and the heating systems before connecting to the boiler. Make the connections to the domestic hot water and heating systems by fitting the sealing washers into the securing nuts and make good the connection to the isolating valves. Do not subject the isolation valves to heat. Make sure the drain point is accessible.
• The heating return coupling is equipped with a filter, accessible after removing the end nut.
•The proof-test pressure can be read on a pressure gauge screwed instead of the heating return coupling end nut (A).
u
A
t
Filter on heating return (A)
A pressure gauge can be screwed instead of the heating return coupling
Piping installation
Safety Discharge Valve
The pipes from the safety discharge valves S1 and S2 must not discharge above an entrance, window or any type of public access area. Take the short safety discharge tube, union nut and seal, supplied loose in the boiler fittings pack and fit as shown in diagram below. This must be extended, using not less than 15mm
o.d. pipe, to discharge, in a visible position, outside the building, facing downwards, preferably over a drain. The pipe must have a continuous fall and be routed to a position so that any discharge of water, possibly boiling, or steam cannot create any danger to persons, damage to property or external electrical components and wiring.
To ease future servicing it is advisable to use a compression type fitting supplied with the boiler to extend the safety discharge valve tube.
s
2
s
1
Page 20
39
WARNING : This appliance
must be earthed.
This appliance must be wired in accordance with these instructions. Any fault arising from incorrect wiring cannot be put right under the terms of the Saunier Duval guarantee. All system components must be of an approved type.
Electrical components have been tested to meet the equivalent requirements of the BEAB. Do not interrupt the mains supply with a time switch or programmer. Connection of the whole electrical system and any heating system controls to the electrical supply must be through a common isolator.
Isolation should preferably be by a double pole switched fused spur box having a minimum contact separation of 3mm on each pole. The fused spur box should be readily accessible and preferably adjacent to the boiler. It should be identified as to its use.
Mains Cable
Important: If a replacement supply cable is required it must be purchased from Saunier Duval.
• The 630 mA fuse of the PCB must be connected to the neutral.
Electrical connection
INSTALLERS
38
Connect the A elbow Ø 22 mm to a discharge
system leading to the sewer, in compliance with the instructions below:
- Use a rigid PVC tube or a flexible silicon pipe resistant to condensate.
- The pipe must have a continuous fall.
- Do not use copper pipes
Important notice :
The float of the condensate recovery system also ensures fume tightness. Therefore, it is useless to add water in the condensate box.
Condensate discharge elbow.
Condensate box with access plugs for cleaning purposes.
Ø 22 mm
A
NO
YES
Piping installation
Page 21
Cold water inlet
Heating return
Heating flow
INSTALLERS
4140
Commissioning on boiler
Please ensure the "Benchmark" logbook is completed and left with the user .
Filling the system 1 to 8
The commissioning and first firing of the boiler must only be done by a qualified registered person.
Make sure that the boiler is connected to the electrical supply and the gas service cock is open.
Switch ON (I). Open the isolating
taps (t), (u), (v) and (w)
on boiler: slot in line wi th the lenght of the valve
21
Undo cap on automatic air vent on top of pump and leave undone.
Fill the system until the pressure
indicated on the display is between 1 and 2 bar. Close filling device.
4
3
v
t
w
Bleed each radiator to remove the air, re-tighten bleed screws.
Leave the cap on the pump auto air vent open.
6
5
Open various hot water taps to bleed system.
Make sure the display indicates a system pressure of between
1 and 2 bar. Re-fill system as necessary.
8
7
1,5 bar
u
Page 22
INSTALLERS
Commissioning on boiler
4342
Press the key to operate the boiler without room thermostat.
• Adjust heating temperature to maximum.
• Allow the temperature to rise to the maximum value, with all radiator valves open. The temperature rise will cause release of the gases contained in the water of the central heating system.
• Gases driven towards the boiler will be automatically released through the automatic air vent.
• The gases trapped at the highest point of the system must be released by bleeding the radiators. Check the burner gas rate required, ten minutes from lighting. Refer to Data Label on electrical controls box. Should there be any doubt about the gas rate it should be checked at
the meter. On reaching maximum temperature, the boiler should be turned off and the system drained as rapidly as possible whilst still hot.
• Refill system to a pressure of between 1 and 2 bar and vent as before.
• Restart boiler and operate until a maximum temperature is reached. Shut down boiler and vent heating system. If necessary, top up heating system and make sure that a pressure of at least 1 bar is indicated when system is COLD. Flush the domestic hot water system by opening the hot water taps for several minutes.
Instruct the User
• Instruct and demonstrate the lighting procedure and advise the user on the safe
and efficient operation of the boiler.
• Instruct on and demonstrate the operation of heating system control.
• Advise the user on the use and maintenance of any scale reducer and pass on any relevant instructional documents.
• Advise that to ensure the continued efficient and safe operation of the boiler it is recommended that it is checked and serviced at regular intervals. The frequency of servicing will depend upon the installation conditions and usage, but in general, once a year should be enough.
• Draw attention, if applicable, to the current issue of the Gas Safety (Installation and Use) Regulations, Section 35,
which imposes a duty of care on all persons who let out any property containing a gas appliance in the UK.
• The user shall not interfere with or adjust sealed components.
• It is the Law that any servicing is carried out by a competent person.
• Advise the user that, like all condensing boilers this appliance will produce a plume of condensation from the flue terminal in cool weather. This is due to the high efficiency and hence low flue gas temperature of the boiler.
• Advise the user of the precautions necessary to prevent damage to the system, boiler and the building, in the event of the heating system being out of
use during frost or freezing conditions.
• Advise the user that the permanent mains electrical supply SHOULD NOT be switched off, as the built in frost protection and pump/valve saver program would not be operable.
• Reminder, leave these instructions and the ‘Benchmark’ logbook with the user.
• For IE, it is necessary to complete a "Declaration of Conformity" to indicate compliance to I.S.813. An example of this is given in the current edition of I.S.813.
Page 23
INSTALLERS
4544
Settings
The description below specifies the operations to be performed to make adjustments to an installation fitted with radiators or for a direct floor system. For other types of
installation (for example with a floor-heating system) , follow the instructions in the appropriate accessories manual.
Your installation consists of a single radiator zone or direct floor system
1/3
Access to the boiler’s technical data (reserved for use by the installers and After-Sales service personnel). This enables adjustments to be made and any malfunctions to be analysed :
Commissioning on room thermostat
The wireless room thermostat (R.O.) has been specially developed for the Isofast.
• It is powered by 3 LR6
1.5V alkaline batteries.
• The boilers various functions are parametered from the room thermostat.
Installing the room thermostat
• Fasten the bracket for the room thermostat on an internal wall approximately
1.50 m from the floor, in an area sheltered from direct sunlight and any source of interference, such as television, lamps, draughts, etc.
• Insert the batteries in the thermostat.
When commissioning for the first time, At initial
commissioning stage, the boiler automatically shifts to manual mode (the control panel keys are lit, and the key is blinking), thus meaning that the wireless room thermostat has not yet been acknowledged by the boiler. To do this :
• Open the control panel
• Locate connector (A) on the left-hand side and insert it in the thermostat for a few seconds as shown in the photo opposite.
When the red indicator light stops flashing, this shows that the boiler has recognised the thermostat.
A
LCD display
Confirm OK
Access to the menus
Weekly
programme
Scroll
Up/Down
Return
Mains power point or power cable
Fault indicator (red)
Wall
bracket
A
Your installation consists of a single radiator zone or direct floor system
Progress of the operations :
1 - Accessing the installer menu
• Connect connector (A) to the room thermostat as detailed on the previous page.
• Press for 5 seconds to call up the following menu :
• Select installer menu :
2 - Select the language
3 - Installation configuration
MENU
INSTALLER MENU
SELECT THE LANGUAGE
INSTALLATION TYPE
Please note that pressing button at any time takes you back to the previous step.
OK
OK
ACCESS CODE
96
+
+
OK
+
INSTALLER MENU
AFTERSALES MENU FAULT HISTORY BOILER DATA
OK
1 RADIATOR ZONE
CHOOSE LANGAGE
INSTALLATION TYPE RADIO SATELLITE HEATING REGULATION BOILER CONFIG.
ENGLISH
C
OK
OK
Page 24
INSTALLERS
4746
f
Your installation consists of a single radiator zone or direct floor system
3/3
Settings
Your installation consists of a single radiator zone or direct floor system
2/3
4 - Radio accessories
RADIO SATELLITE
5 - Heating control
HEATING CONTROL
Selecting is recommended so that you can benefit from automatic circuit temperature control.
However, if you wish to adjust the radiator temperature yourself, select Then return to the user menu to set the radiator temperature.
AUTO
a/ Press for 5 seconds
b/
MENU
6 - Boiler configuration
BOILER CONFIG.
Warning : This menu must only be used when installing one or more of these accessories > please refer to the section on "Activating the accessories".
OK
OK OK
SET RADIATOR T¡
OK
IN OUTDOOR SENSOR OFF
REPEATER OFF THERMOSTAT 2 OFF MODEM OFF
HEATING SETPOINT
OK
+
MAX OUTPUT
CHIMNEY SET MAX RADIATOR T¡ MIN RADIATOR T¡ PUMP MODE
MANUAL
SET RADIATOR T¡
50¡C
OK TO VALIDATE
AUTO MANUAL
6.2 Adapting the length of the vent
CHIMNEY SET
6.3 Selecting the maximum radiator temperature
MAX RADIATOR T¡
6.4 Selecting the minimum radiator temperature
MIN RADIATOR T¡
6.5 Selecting the pump’s operation
PUMP MODE
Operation WITH THERMOSTAT is recommended in all cases except for direct floor heating, in which case you should select:
6.6 Choice of preheat
In ON mode, the boiler holds the exchanger at the required temperature between 5 O’clock a.m. and 11 O’clock p.m. in order to warrant optimal reactivity for the supply of sanitary hot water.
In AUTO mode, the boiler memorizes the day to day requirements of the family, and triggers the pre-heating a few minutes before the first use of sanitary hot water of the day.
In OFF mode, the function is inhibited.
WITH THERMOSTAT
PREHEAT
No setting is required for this type of boiler. Codes displayed do not af functionning of the boiler.
OK
OK
OK
PERMANENT
OK
MAX 73¡C MAX 65¡C MAX 50¡C
MIN 50¡C MIN 38¡C MIN 28¡C MIN 22¡C
WITH BURNER WITH THERMOSTAT PERMANENT
OFF
AUTO ON
Warning : for direct floor systems, do not exceed a temperature of 50°C.
OK
OK
OK
6.1 Limiting the maximum heating power
MAX OUTPUT
OK
/...
16kW 15kW 14kW
/...
OK
WHEN YOU HAVE COMPLETED PARAMETERS, press for approx. 5 seconds to return to the initial display.
MENU
Page 25
INSTALLERS
4948
OK
EXT. SENSOR ON
HEATING REGULATION
BOILER CONFIG. CHOOSE LANGUAGE
+
C
• Reach into the Heating Set Point menu to select the desired regulating mode.
Select the code following curves given on diagram below. NB: Zone 2 settings are only displayed when two heating zones have been selected in the “config. Installation” menu.
MANUAL
AUTO
AUTO
OK
HEATING SETPOINT
T¡ HEATING OFF
T¡ HEATING OFF
HEATING SETPOINT
Note : we recommend selecting 17 or 18°C.
You may retain the advantages conferred by the external sensor, while setting yourself the slopes of the sensor. Select the setting and adapt the following parameters :
OK OK
CORRECT T¡ ZONE1
SLOPE ZONE 2
SLOPE ZONE 1
CORRECT T¡ ZONE2
0,70,80,60,2
......
OK OK
1,61,51,40,2
4,0 4,0
......
... ...
OK OK
... ...
OK OK
... ...
OK OK
Temperature setting curves.
30
-30 -20 -10 100
40
50
60
70
80
90
100
Heating temperature outlet (°C)
Outside temperature (°C)
b/ T° heating off
a/ Heating setpoint
2.2 Heating setpoint
0,2
0,5
0,7
1,0
1,2
1,5
1,7
2,0
2,2 2,5 2,7 3,0 3,5 4,0
MANUAL
The setting is recommended to obtain automatic regulation of circuit temperatures. In such case, no slope adjustment is required. The boiler will itself select, after a few days, the slope which is the most suited to the heating installation.
49
Accessories settings
2/3
Settings
Accessories settings
OK
OK
C
INSTALLER MENU
• Press for 5 seconds to call up the following menu:
Progress of the operations :
RADIO ACCESSORIES
HEATING REGULATION BOILER CONFIG.
INSTALLER MENU
AFTERSALES MENU FAULT HISTORY BOILER DATA
ACCESS CODE
96
OK
OK
RADIO ACCESSORIES
EXT. SENSOR OFF
REPEATER OFF THERMOSTAT 2 OFF MODEM OFF
EXT. SENSOR OFF
EXT. SENSOR ON
REPEATER OFF THERMOSTAT 2 OFF MODEM OFF
CONNECT
+
+
MENU
1 - Access to the Radio accessories menu
• Select the installer menu:
• Select the Radio accessories menu:
Please note that pressing button at any time takes you back to the previous step.
2.1 External sensor recognition
OK
2 - External sensor
The external sensor is now operating
Hold the satellite button, situated on the backside of the external sensor box, depressed for 10 seconds. To establish connection, the sensor transmits signals – this may require several minutes – until it is acknowledged by the room thermostat which then validates the connection through the following display :
• Connect connector (A) on the room thermostat as described page 44.
1/3
Page 26
Selecting the language on the thermostat’s display. Selecting the type of heating installation. The ON position of this menu assigns the TA1
clock function to the radiator zone. In such case, the ambient temperature at floor level is selected from the TA1 user’s menu.
Activating the various radio accessories on the installation.
Selecting Automatic or Manual control mode. In Automatic mode, the radiator temperature adapts automatically to the heating requirements of the room in which the thermostat is located, opera­ting between the maximum and minimum tempera­ture values set.
Selecting the boiler’s main operating parameters (power and heating circuit temperatures, pump mode and airflow configuration).
INSTALLERS
5150
Glossary for the installater menu
Select the language Installation config. Clock zone 2
Radio accessories
Heating regulation
Boiler config.
Settings
Accessories settings
OK
REPEATER OFF
REPEATER ON
THERMOSTAT 2 OFF MODEM OFF EXT. SENSOR OFF
CONNECT
The repeater is now operating
OK
OK
3 - Repeater
OK
THERMOSTAT2 OFF
THERMOSTAT 2 ON
MODEM OFF EXT. SENSOR OFF REPEATER OFF
CONNECT
The room thermostat 2 is now operating
C
4 - Room thermostat 2
Hold the satellite button situated on the back side of the radio relay box depressed for 10 s. To establish the connection, the radio relay transmits signals until it is recognized by the room thermostat which validate the connection by the following display :
Disconnect the cable of the zone 1 room thermostat, and connect it to thermostat
2. This is sufficient to have it recognized by the boiler. Take the cable and reconnect it to zone 1 room thermostat and press the key. The following display will confirm the connection:
3/3
Page 27
INSTALLERS
5352
2/ Minimum HEATING input setting, through the CO2 : a - Connect a CO2 analyser
to sample point B of the adapter or flue elbow.
b - Adjust the boiler at its minimum heating power using the room thermostat menus described in the below.
c - Perform a heating demand and record the
CO2 value after stabilization (2 minutes or so).
d - Adjust the screw D to obtain the G31 CO2 value stated in the table, taking the following principle into account :
To increase the CO2 value,
turn the screw clockwise
To decrease the CO2 value, turn the screw
anti-clockwise
Note : After re-installation of the sealed front face, the CO2 value changes, and must correspond to that given in the table.
3/ After setting and reassembly, restore the maximum heating power to its initial value (20 kW) and stick the gas data tag close to the nameplate.
Gas conversion
Your Isofast boiler is factory-set to operate with G20 gas. For operation with G31 gas, some adjustments must be made on the gas valve after removal of the sealed front cover in order to obtain the CO2 values given in the adjacent table.
1/ Maximum hot water input setting, through the CO2. a - Connect a CO2 analyser
to sample point B of the adapter or flue elbow.
b - Fully open a hot water tap.
c - Wait for 2 minutes or so, until the CO2 reading has stabilized.
d - Adjust the screw C to obtain the G31 CO2 value stated in the table, taking the following principle into account:
To increase the CO2 value,
turn the screw anti-clockwise
To decrease the CO2 value,
turn the screw clockwise
Note : After re-installation of the sealed front face, the CO2 value changes, and must correspond to that given in the table.
Isofast F 35 E G20 G31
Heating output max. hot water kW 34,2 34,2 Heating output max. heating kW 6,4 6,4 C02 case off % 9±0,2 10,3±0,2 C02 case on % 9,2±0,3 10,5±0,3
B
C
D
1 - Access to the installer menu
• Connect A connector on the room thermostat as indicated page 44.
• Press for 5 seconds to call up the following menu:
MENU
• Select the Installer menu:
INSTALLER MENU
2 - Access to boiler configuration
BOILER CONFIG.
• Set MAX OUTPUT on the minimal value:
MAX OUTPUT
WHEN YOU HAVE COMPLETED PARAMETERING, press for approx. 5 seconds to return to the initial display.
OK
+
OK
ACCESS CODE
96
OK
+
INSTALLER MENU
AFTERSALES MENU FAULT HISTORY BOILER DATA
OK
MAX OUTPUT
CHIMNEY SET MAX. RADIATOR T¡
6 kW
5 kW
MENU
CHOOSE LANGUAGE
INSTALLATION TYPE RADIO SATELLITE HEATING REGULATION BOILER CONFIG.
/...
OK
OK
Page 28
Push the gas pipe upwards further into gas valve connection and then rotate anti-clockwise (looking down) until the gas pipe end is over the large hole in boiler chassis. Withdraw the gas pipe from gas valve connection and remove. Note : When replacing ensure that the sealing grommet, situated below the gas valve is correctly re-seated. Disconnect the gas valve electrical plug at the gas valve. Disconnect the electrical leads from the fan. Remove the five combustion chamber front retaining nuts, see diag. 5. Gently remove the fan, gas valve and burner assembly from the combustion chamber, see diag. 5. Clean the burner with a soft brush taking great care not to damage the front insulation. DO NOT use
wire or sharp instruments to clean the holes of the burner. Inspect the burner for any signs of damage. Inspect the sealing rings and replace if necessary.
Removal of the burner is not necessary during a normal service. NOTE : IF THE BURNER HAS TO BE REMOVED IT WILL REQUIRE A NEW GASKET WHEN REFITTED.
INSTALLERS
5554
Servicing
Important Notes
To ensure the continued efficient and safe operation of the boiler it is recommended that it is checked and serviced at regular intervals. The frequency of servicing will depend upon the particular installation and usage, but in general once a year should be enough. It is the Law that any servicing is carried out by a competent person. When replacing a part on this appliance, use only spare parts that you can be assured conform to the safety and performance specification that we require. Do not use reconditioned or copy parts that have not been clearly authorised by Saunier Duval.
General
Measurement of the products of combustion can be achieved by connection of a probe to the combustion analyser test point, see diagram 1.
IMPORTANT NOTE :
Products of combustion will be discharged when the cap is removed. It is important to replace the cap immediately. Before commencing with a service or replacement of parts, the boiler should be
isolated from the electrical supply and the gas supply should be turned off at the gas isolation valve, see
page 35.
All routine servicing requirements can be achieved by the removal of the front panel and inner panel only. To remove simply undo the two screws on the underside of the front panel and lift off. Undo the two screws on the front of inner panel and lift off, see diag. 2. Unless stated otherwise any part removed during servicing should be replaced in the reverse order to removal. Servicing should always include the removal of any debris from the condensate pipe and siphon. After completing any servicing of gas carrying components, ALWAYS test for gas soundness and carry out a functional test of the controls.
Spark Electrode
Disconnect the electrode lead and two securing screws. Withdraw the spark electrode carefully from the combustion chamber, see
diagram 3.
Inspect the tips for damage. Clean away any debris and check the spark gap is 3.5 to 4.5 mm.
Check the electrode gasket for signs of damage and replace if necessary.
Burner
Drop down the control panel into the service position. Disconnect the gas supply at the gas service cock. Remove the two gas pipe retaining clips, one located below gas valve and the other one located on the underside of the boiler chassis. Pull sealing grommet down gas pipe diagram. 4.
Diagram 1
Combustion analyser test point
Diagram 2
Torx screws
Diagram 3
Diagram 4 Diagram 5
Sealing grommet
Gas pipe retaining clip
Electrode
Gasket
Spark Gap 3.5 to 4.5
Heat exchanger
Combustion chamber
Burner
Sealing ring
Gas valve
Fan
Securing Nut (5)
Page 29
Draining of Boiler Heating Circuit
Drain down the Heating Circuit of the boiler only, by closing the heating flow and return isolating taps (t, u and w), on the boiler connections, see diag. 10. Attach a length of hose to the drain point and open the drain valve (r), see diag. 9. After servicing or replacing parts, close the drain valve and remove the hose. Open the heating flow and return isolating valves and refill, vent and pressurise the heating circuit. Check for leaks.
Draining of Boiler Hot Water Circuit
Drain the Domestic Hot Water circuit by closing the cold-water isolation tap (v) on the boiler connection. Open one or more hot water taps to drain the hot water circuit. After servicing or replacing parts open the cold-water isolation valve and slowly open a hot water tap to
remove air. Close the hot water tap and check for any leaks.
Inner Casing Panel Seal Check.
Check the condition of the seal, replace as required. To replace remove the old seal, thoroughly clean the casing sufaces. Fit the new seal, it is supplied to the correct length.
Cold water inlet
Heating return
Heating flow
v
t
u
INSTALLERS
Servicing
5756
Combustion Chamber and Heat Exchanger
Remove loose debris from combustion chamber using a soft brush and vacuum cleaner. Carefully flush by spraying water removing any remaining debris through the condensate trap (Ensure the water is kept away from electrical components).
Condensate Drain
The condense drain does not normally need removing during servicing. To flush the condense drain carefully pour water into the heat exchanger and check that water flows freely to drain.
Combustion Check.
If a gas carrying component has been replaced, the combustion of the appliance should be checked. Once the appliance has been re-assembled (apart from the front and inner casing panels) connect a CO2 combustion analyser to the test point on the flue adapter, and follow indications given on page 52-53.
Domestic Cold Water Inlet Filter
If the water flow rate through the appliance has reduced it may be necessary to clean or
replace the water inlet filter. Turn off the electrical supply to the boiler. Drain the domestic hot water circuit. Slide out the securing clip, and remove the filter to clean or renew if necessary,
see diag. 6.
Replace the filter into its housing and replace the securing clip. Open the cold water isolating valve and test the Domestic Hot Water circuit for soundness. Check for leaks.
“Mouss” Filter
Turn off the electrical supply to the boiler. Drain the heating circuit of the boiler. Remove the filter retaining clip under the pump see diag. 7, and filter clean or renew if necessary. Refit the filter. Open the heating flow and return isolating valves and refill, vent and pressurise the heating circuit. Check for leaks.
Central Heating Return Filter
Turn off the electrical supply to the boiler. Drain the heating circuit of the boiler. Unscrew the filter placed on heating return, see diag. 8, and clean filter or renew if necessary. Refit the filter. Open the heating flow and return isolating taps and refill, vent and pressurise the heating circuit. Check for leaks.
t
u
Cold Water Inlet Filter
Diagramm 6
Diagramm 7
Diagramm 8
Heating Return Filter
Diagramm 10
r
Diagramm 9
w
Page 30
INSTALLERS
5958
• Press for 5 seconds to call up the following menu:
• Select Aftersales menu
INSTALLER MENU
AFTERSALES MENU FAULT HISTORY BOILER DATA
BOILER CODE
MIN. FAN SPEED MAX. FAN SPEED START FAN SPEED BURNER OVERRIDE FAULT RESET AFTERSALES TEL
TEST RADIO SIGNAL
AFTERSALES MENU
FAULT HISTORY BOILER DATA
ACCESS CODE
XX
OK
OK
+
OK
+
OK
+
OK
+
OK
+
MENU
• Press for 5 seconds to call up the following menu :
The room thermostat then transmits signals every 10 s. Successive display of the numbers , , , means that the signals are properly routed.
MENU
Accessing the Aftersales menu
Communication test
BOILER CODE
MIN. FAN SPEED
MAX. FAN SPEED
OK
+
START FAN SPEED
BURNER OVERRIDE
FAULT RESET
AFTERSALES TEL
OK OK
+
WHEN YOU HAVE COMPLETED PARAMETERS, press for approx. 5 seconds to return to the initial display.
MENU
• Connect boiler connector (A) to the room thermostat as described page 44 :
• DO NOT connect the boiler connector to the room thermostat.
1 2 3 4
Attention: The code is pre-recorded at the factory. Note: The code corresponding to the boiler is indicated on the nameplate.
This factory-set value corresponds to the minimum input.
This factory-set value corresponds to the maximum input.
Fan start-up speed selection
Allows analysing boiler operation at its minimum or maximum power.
Erases the fault log.
Recording of after sales service telephone No. This No. will be displayed on thermostat screen in case of malfunction requiring attendance by a professional.
The use of the menus described here after is exclusively reserved for the after-sales personnel.
Servicing
• Press for 5 seconds to call up the following menu:
• Connect boiler connector (A) on the room thermostat as described page 44.
Every validation through the OK key will cause display of the corresponding value during boiler operation.
INSTALLER MENU
AFTERSALES MENU FAULT HISTORY BOILER DATA
BOILER DATA
INSTALLER MENU AFTERSALES MENU FAULT HISTORY
WATER PRESSURE
RADIATOR SETPOINT FLOW T¡ RETURN T¡ DHW T¡ TANK T¡ FAN SPEED DHW FLOW BURNER PHASE POWER
MENU
Access to the data menu
1 - "Fault history" menu
2 - "Boiler data" menu
OK
FAULT HISTORY
BOILER DATA INSTALLER MENU
OK
FAULT HISTORY TUE 04/02/03 10
--/--/--
• Use the buttons to select the "Fault history" menu:
• Use the buttons to select the "Boiler data" menu
The display shows the fault N° and its date of occurrence.
OK
+
The after-sales menus, accessible from the room thermostat, allow investigating possible malfunctions and modifying certain factory set values.
WHEN YOU HAVE COMPLETED PARAMETERS, press for approx. 5 seconds to return to the initial display.
MENU
Page 31
INSTALLERS
Fault finding
6160
NOTE
Before trying to operate the boiler make sure that :
• All gas supply cocks are open and that the gas supply has been purged of air.
• There is a permanent mains supply to the boiler.
• There is a heating demand from the external control.
WARNING.
Always isolate the boiler from the electrical supply before carrying out any electrical replacement work.
Always check for gas soundness after any service work.
Electrical Testing
Should there be any doubt about the voltage supply to any of the components, it is possible to carry out a simple electrical test.
Important. On completion of the Service/Fault Finding tasks which have required the breaking and remaking of the electrical connections the earth continuity, polarity,
short circuit and resistance to earth checks must be repeated using a suitable multimeter. To carry out the electrical test, gain access, as follows : Hinge down the control box and remove Torx screws and unhook the rear panel, refer diagram 2 page 54. Refer to the Wiring diagram and fault finding charts diagrams.
2
12
3
1
11
13
15
16
17
4
5
8
9
10
6
7
14
Wiring diagram
1-Overheat thermostat 2-Fan 3-Gas valve 4-Heating return
thermistor
5-Heating flow thermistor 6-Water pressure sensor 7-Pump 8-Water flow sensor
9-User interface 10 - Room thermostat 11 - Ignition and controle
electrode
12 - Ignition module 13 - DHW temperature
sensor
14 - Three way valve 15 - Fuse 630 mA
16 - Chassis earth 17 - Main reset switch
Wiring diagram
Page 32
INSTALLERS
Fault finding
6362
FOLLOWING PAGE
Page 33
INSTALLERS
6564
Replacement of parts
General
Replacement of parts must be carried out by a competent person. Before replacing any parts the boiler should be isolated from the mains electric supply and the gas should be turned off at the service cock on the boiler. Unless stated otherwise parts are replaced in the reverse order to removal. After replacing any parts always test for gas soundness and if necessary carry out functional test of the controls. For replacement of parts the front casing and the inner casing panel of the boiler will need to be removed. To remove undo the two screws on the underside of the front casing and lift off. Undo the two screws on the front of the inner front panel and lift off. The side panels can be hinged sideways to aid replacement of parts. To hinge a side panel undo and remove the three screws securing each side panel to the boiler, two at the front and one at the top.
Spark Electrode
For access, refer to section “General”. Remove the spark plug lead, earth lead and two
securing screws. Withdraw the spark electrode carefully from the combustion chamber, see diagram3
page 55.
Igniter Unit
For access, refer to section “General”. Remove ignition lead and electrical connections then remove igniter unit by removing two securing screws, see diagram 1.
Ignition Lead
For access, refer to section “General”. Pull the spark plug style connector off the spark electrode and the spade connector connected to the igniter unit, see diagram 1.
Gas Valve
For access, refer to section “General”. Remove the electrical plug from the gas valve, see
diagram 2. Refer to pages 54 and 55 for removal of the fan, gas valve and burner assembly. Before removing the gas valve note its position on the fan. Remove the three securing screws, which fix the gas valve and plastic swirl plate to the venturi on the fan, see diagram 3. Remove the gas valve.
Diagram 1
Securing screws (2)
Spade connector
Igniter unit
When re-fitting the gas valve take care as it can be fitted more than one way. After re-fitting check the combustion CO2 and adjust if necessary, see page
52-53.
After assembly test for gas soundness and purge in accordance with the current issue of BS6891or in IE, the current edition of I.S.813 "Domestic Gas Installations".
Fan
For access, refer to section “General”. Refer to pages 54 and 55 for removal of the fan, gas valve and burner assembly. Remove the gas valve. Remove the venturi plate secured with three screws, see diagram 3. Remove the two screws securing the fan to the gas manifold, see diagram 4, check the gasket and replace if necessary.
Burner
For access, refer to section “General”. Refer to pages 54 and 55 for removal of the fan, gas valve and burner assembly. Remove the four screws that secure the burner, see diagram 5. NOTE : THE BURNER WILL REQUIRE A NEW GASKET WHEN REFITTED.
Front Insulation
For access, refer to section “General”. Refer to pages 56 and 57 for removal of the fan, gas valve and burner assembly. Remove burner as previous section. Remove spark electrode.. NOTE: THE BURNER WILL REQUIRE A NEW GASKET WHEN REFITTED.
Rear Insulation
For access, refer to section “General”. Refer to pages 54 and 55 for removal of the fan, gas valve and burner assembly. Remove securing screw and washer in the centre of the insulation and withdraw insulation, see diagram 6.
Viewing Window
For access, refer to section “General”. Refer to diagram 7. Remove circlip. Remove steel washer. Remove glass. Remove fibre washer. Replace in reverse order.
Diagram 2
Electrical plug
Gas valve
Pressure test point
Diagram 3
Securing screws (3)
Venturi plate
Diagram 4
Diagram 5
Gas manifold
Securing screws (2)
Burner
Securing screws (4)
Insulation
Diagram 6
Washer
rear insulation
Securing screw
Circlip
Steel washer
Glass
Fibre washer
Diagram 7
Page 34
INSTALLERS
Replacement of parts
6766
Expansion Vessel
For access, refer to section “General”. Refer to page 57 and drain the boiler heating circuit. Undo the coupling at the base of the vessel, see diagram 8. While holding the vessel remove the securing bolt on the top panel of the boiler. Remove upper support bracket. Lift the vessel up, draw bottom out to the left, lower and remove. Fit the replacement unit. Fit a new gasket between the expansion vessel and coupling. Refill, vent and pressurise the boiler. Check for leaks.
Heat Exchanger
For access, refer to section “General”. Refer to pages 54 and 55 for removal of the fan, gas valve and burner assembly. Drain the boiler heating circuit, and the hot water circuit see page 57. Remove the clip securing the clear condense pipe to heat exchanger. Pull to remove the clear condense pipe out of the bottom of the heat exchanger. Undo the two nuts of the flow and return pipes from
the heat exchanger.
Move the pipes away from
the heat exchanger.
Loosen the three heat
exchanger securing screws
and clamps (two at the top
and one at the bottom) to
remove the heat exchanger,
see diagram 9.
CAUTION: There will be
water in the heat exchanger.
Remove condense pipe
connector from bottom of
heat exchanger.
Carefully ease heat
exchanger out.
Flue Hood
For access, refer to section
“General”.
Remove heat exchanger as
per previous section.
Remove the two securing
screws and pull the flue
hood down and away from
the flue hood bracket and
flue elbow, see diagram 10.
Diverter Valve Motor
For access, refer to section
“General”.
Refer to diagram 11.
Remove the electrical plug.
Unscrew the retaining nut.
Remove the diverter valve
motor.
Pump (head only)
For access, refer to section
“General”.
Drain the boiler heating
circuit.
Diagram 8
Expansion vessel
Diagram 9
Securing screws and clamps
Flow and return pipe nuts
Diagram 10
Securing screws (2)
Flue hood
Flue hood bracket
Refer to diagram 12. Remove the four cap head screws. Carefully remove the pump head together with cable. Do not strain cable. Support the pump head, unscrew cable cover at the side of pump head and take off. Disconnect wiring from pump head. Reconnect wiring to new pump head and fit cover. Fit the new pump head with 'O' ring. Refill, vent and pressurise the boiler. Check for leaks.
Safety Discharge Valve
For access, refer to section “General”. Drain the boiler heating circuit. Refer to diagram 13. Undo the safety discharge valve union and remove from the pipework. Remove the securing clip and withdraw the safety discharge valve. Fit new 'O' ring. Refill, vent and pressurise the boiler. Check for leaks.
Domestic Hot Water Thermistor
For access, refer to section “General”. Drain the boiler domestic
hot water circuit. Refer to diagram 14. Disconnect the domestic hot water thermistor electrical connections Remove retaining clip. Withdraw domestic hot water thermistor from its housing. Note : When reconnecting electrical connections, polarity is not important. Fit new 'O' ring. Carry out a functional test of the controls.
Heating Flow Thermistor
For access, refer to section “General”. Refer to diagram 15. Remove the electrical connections from the thermistor. Remove the retaining clip from the flow pipe. Note: When reconnecting the polarity of the wiring to thermistors is unimportant.
Diagram 11
Diagram 12
cap head screw (4)
Cable cover
Pump head
Diagram 13
Diagram 14
Electrical plug
Diverter valve motor
Safety discharge valve
Domestic hot water thermistor
Page 35
INSTALLERS
6968
Heating Return Thermistor
For access, refer to section “General”. Refer to diagram 15. Remove the electrical connections from the thermistor. Remove the retaining clip from the flow pipe. Note: When reconnecting the polarity of the wiring to thermistors is unimportant.
Overheat Thermostat
For access, refer to section “General”. Refer to diagram 15. Remove the electrical connections from the overheat thermostat. Remove the retaining clip from the flow pipe. Remove the overheat thermostat from the retaining clip. NOTE. When fitting new thermostat, please ensure that it is located correctly onto the flat area of the pipe and the retaining clip is secure.
Automatic Air Vent
For access, refer to section “General”. Drain the boiler heating circuit. Refer to diagram 16. Remove the retaining clip and remove the automatic air vent. Fit the new automatic air
vent and 'O' ring ensuring
the vent cap is left loose.
Refill, vent and pressurise
the boiler.
Check for leaks.
Flow Sensor
For access, refer to section
“General”.
Drain down the hot water
circuit.
• Undo the union nut on the
cold water inlet isolating
valve.
• Pull out slotted metal clip
securing filling system tap
into housing, swing the tap
forwards.
• Pull out the two slotted
metal clips retaining the
domestic water inlet filter
housing.
• Remove domestic water
inlet filter housing.
• Remove electrical
connections from water flow
sensor.
• Pull off slotted metal clip
and remove water flow
sensor.
Replacement of parts
Diagram 15
Diagram 16
Automtic air vent
Retaining clip
Diagram 17
Low Water Pressure Sensor
For access, refer to section “General”. Drain the boiler heating circuit. Refer to diagram 18. Disconnect the electrical lead by pushing up retaining tab to withdraw the lead plug. Remove the retaining clip to remove the low water pressure sensor. Fit new 'O' ring. Fit the new low water pressure sensor. Refill vent and pressurise the boiler. Check for leaks.
Bypass Valve
For access, refer to section “General”. Drain the boiler heating circuit. Refer to diagram 19. Remove the retaining clip to remove the bypass valve. Fit new 'O' rings. Replace the bypass valve, refill, vent and pressurise the boiler. Adjust the bypass as described pages 22-23. Check for leaks.
Filling Loop Tube
For access, refer to section “General”. Drain the boiler hot water circuit. Refer to diagram 20.
Remove the retaining clips to remove the filling loop tube. Fit new 'O' rings. After replacing the filling loop tube open the cold­water isolation valve and slowly open a hot water tap to remove air. Close the hot water tap and check for any leaks.
Filling Loop Valve
For access, refer to section “General”. Drain the boiler hot water circuit. Refer to diagram 20. Remove the clip securing the filling loop valve to the domestic water filter housing. Disengage by pulling forward. Remove the clip securing the filling loop to the filling loop valve. Remove the filling loop valve from the filling loop. Fit new 'O' rings. After replacing the filling
loop valve open the cold water isolation valve and slowly open a hot water tap to remove air. Close the hot water tap and check for any leaks.
Diagram 18
Retaining clip
Flow sensor
Water flow sensor
Diagram 19
Bypass valve
Diagram 20
Retaining clip
Filling loop tube
Filling loop valve
Retaining clip
Return thermistor
Overheat thermostat
Flow thermistor
Reduced pressure zone valve
Page 36
INSTALLERS
Replacement of parts
7170
Reduced Pressure Zone Valve
For access, refer to section “General”. Refer to diagram 20. Drain the boiler hot water circuit. Remove the filling loop Remove the retaining clip to remove the reduced pressure zone valve. Fit new 'O' rings. Replace the reduced pressure zone valve, refill, vent and pressurise the boiler. Check for leaks.
Domestic Cold Water Inlet Filter
For access, refer to section “General”. Refer to page 56. Fit new 'O' rings.
Central Heating Filter
Refer to section page 56. Fit new 'O' rings.
Heating Circuit Drain Point
Refer to page 57 to drain the boiler heating circuit. Refer to diagram 21. Remove the retaining clip to remove the drain point. Fit new 'O' rings. Replace the drain point, refill, vent and pressurise the boiler. Check for leaks.
Inner Casing Panel Seal
For access, refer to section
“General”.
Remove the inner casing
panel.
To replace remove the old
seal, thoroughly clean the
casing surfaces. Fit the new
seal, it is supplied to the
correct length.
Refit the inner casing panel.
NOTE: Ensure the seal is
fitted correctly giving an
airtight joint.
Condense Drain
For access, refer to section
“General”.
Refer to diagram 22.
Remove the clips securing
the flexible tubes to the
siphon adapter by twisting
the clips slightly to
disengage the clip jaws from
each other.
Remove black flexible tubes
from siphon adapter.
Lift off the siphon adapter.
Remove the drain
connection downstream of
the condense trap.
Remove the two condense
trap securing screws. Lift
up and carefully remove the
condense trap taking care
not to spill any water which
may be left in the unit. As
the unit is lifted remove the
flexible pipe on the outlet.
Remove the cap at the base
of the condense trap.
Remove any solids found.
Remove the float to clean it. Flush water through the trap to remove any remaining solids. Check for any debris in the outlet pipe of the condensate drain and clean as necessary. Reassemble and refit the condense trap. When refitting the cap ensure that a watertight seal
Diagram 21
Diagram 22
Siphon adapter
Float
Condens trap
Screw
Seal
is achieved, but do not use excessive force. Remove the siphon adaptor from the flexible tubes, using a suitable container, flush the heat exchanger until the water appears clear in the container.
Plate-to-Plate Heat Exchanger
For access, refer to section “General”. Drain the boiler heating and hot water circuits. Remove the water flow sensor, refer to previous section. Unclip the central heating thermistor. Unscrew the heating flow pipe union nut, swing pipe forwards. Remove the system water pressure sensor. Supporting domestic hot water plate to plate heat exchanger, unscrew and remove two screws securing it onto pump mounting and 3-way valve/bypass housing. Remove plate to plate heat exchanger from boiler. Fit replacement plate to plate heat exchanger in reverse order to removal using new seals, supplied. Note: Plate to plate heat exchanger mounting screws are offset to ensure correct fitting.
Domestic safety valve (10 bar BLUE), refer to diagram 24.
For access, refer to section “General”. Drain down the hot water circuit only. Undo discharge pipe union nut. Pull out slotted metal clip from valve body and remove valve.
Micro accumulator vessel thermistor, refer to diagram 25.
For access, refer to section “General”. For this operation the boiler must be removed from the wall. IMPORTANT: With regards to the manual handling operations, 1992 regulations, the following operation exceeds the recommended weight for one man lift.
Cap
Diagram 23
Diagram 24
Diagram 25
Micro accumulator vessel
Thermistor
Heating element
Electrical cable
Page 37
73
When ordering spare parts, quote the part number and description, stating the appliance model number and serial number from the data badge.
Short parts list
No. Description Part No. G.C. No.
1 Central heating thermistor S5739800 ••••••• 2 Fan S152000 ••••••• 3 Domestic water flow sensor S5720200 ••••••• 4 Printed circuit board - Main S1040000 ••••••• 5 Pump head S1024000 ••••••• 6 System water pressure sensor S5720500 ••••••• 7 Gas control valve S1043900 ••••••• 8 Overheat thermostat S1040100 ••••••• 9 Three way valve S1025500 ••••••• 10 Pressure relief valve S1006700 ••••••• 11 Heat exchanger S1041100 ••••••• 12 Burner S1042200 ••••••• 13 Micro accumulation vessel S1025000 ••••••• 14 Micro accumulation vessel thermistor S1027300 •••••••
Spare parts
INSTALLERS
Replacement of parts
72
Note : It is not necessary to drain down entire heating system to carry out this work. Disconnect the flue system. Disconnect the boiler connections pipes . Disconnect the pressure relief valve discharge pipes. Disconnect the mains cable and any external controls cables. Lift up to remove the boiler from the wall. Locate micro accumulator vessel thermistor, on side of the micro accumulation vessel. Disconnect the inline electrical connection plug to the micro accumulator vessel thermistor. Pull out to remove the thermistor.
Micro accumulator vessel, refer to diagram 25.
For access, refer to section “General”. For this operation the boiler must be removed from the wall, see previous section.
From the rear of the boiler, disconnect the inline electrical connection plug to the micro accumulator vessel thermistor. Remove the heating element electrical cable. Unscrew the retaining nuts
pipes.
• Remove the vessel from
the boiler.
Micro accumulator vessel
heating element, refer to
diagram 25.
For access, refer to section
“General”.
For this operation the boiler
must be removed from the
wall, see previous section.
Disconnect the electrical
connection plug to the
micro accumulator vessel
heating element at the
control board PCB
connection.
• Release the micro
accumulator vessel heating
element cable from the
securing clips, note the
routing of the cable for
reassembly.
• Pull out micro accumulator
vessel heating element.
Printed circuit board (PCB), refer to diagram 26
For access, refer to section “General”. Gain access to rear of control panel. Undo and remove the two front retaining screws. Hinge up the control panel cover and ease forwards from the rear retaining lugs to gain access to PCB. Do not strain the cables attached to the PCB. Note the routing of the cables.
• Carefully pull off electrical connections to PCB. Unclip and lift out PCB. Fit replacement PCB in reverse order to removal. Be careful not trap any of the cables. Make sure that PCB connections are fully pushed onto replacement PCB.
Diagram 26
Because of our constant endeavour for improvement, details may vary slightly from those shown in these instructions.
Retaining clips
Page 38
07/04 - 4000135500-2 Isofast UK
PLEASE DO NOT FORGET
TO COMPLETE YOUR
GUARANTEE REGISTRATION
CARD
Saunier Duval's specialist organisation
offering Saunier Duval boiler owners :
An experienced team of professionally qualified locally based service engineers
Unrivalled technical knowledge from people who manufactured your Saunier Duval boiler
FAST response
Reliable and efficient repairs
We carry most spare parts on our vans - over 98% of faults are fixed first time round.
Saunier Duval Service N° 01773 525914
✔ ✔
Loading...