Saunier Duval ECOSY 24 E,ECOSY SB 24 E,ECOSY 28 E,ECOSY SB 28 E Installation And Operating Instructions Manual

1
ECOSY
Heating and hot water for the professionals
ECOSY 24 E, ECOSY 5B 24 E is CAT II2H3+ appliances
ECOSY 28 E, ECOSY 5B 28 E is CAT I2H appliances
01773 828100
TECHNICAL HELPLINE
01773 828400
2
INSTALLATION AND OPERATING INSTRUCTIONS
ECOSY 24 E, ECOSY SB 24 E ECOSY 28 E, ECOSY SB 28 E
Note!
The boiler serial number is marked on the label attached to the top of the inner bulkhead. Refer to
the 'Introduction' section page 3 for a description of the basic functions of the boiler. The 'Users'
section describes how to safely operate the boiler.
INSTALLATION SECTION
Introduction .................................................. Page 3
Commissioning ....................................................... 3
Controls & lighting ............................................ 4 - 6
Draining................................................................... 7
Servicing/maintenance ........................................ 7
Introduction ................................................. Page 3
Technical data...................................................... 8
Dimensions ............................................................. 9
Boiler schematic ................................................... 9
Connections plate.............................................. 10
Piping system installation ................................... 10
Heating system design ....................................... 11
Domestic hot water system design .................. 12
Boiler location ..................................................... 12
Boiler installation ................................................. 13
Flue installation ............................................. 14 - 15
Electrical installation ........................................... 16
Commissioning .................................................... 17
Operating safety devices .................................. 18
Settings ................................................................. 19
Changing gas type ............................................ 20
USERS SECTION
Mandatory warning for CEE countries Warning: This appliance is designed, approved and inspected to meet the requirements of the
English market. The identification plate located on the inside of the appliance certifies the origin where the product was manufactured and the country for which it is intended. If you see any exception to this rule, please contact your nearest Saunier Duval dealer. Thank you in advance for your assistance.
3
INTRODUCTION
The ECOSY 24 E and ECOSY 28 E boilers are wall mounted combination boilers providing central heating and instantaneous hot water.
The ECOSY SB 24 E and ECOSY SB 28 E boilers are wall mounted system boiler providing central heating only.
The ECOSY 24 E and ECOSY SB 24 E boilers are of the II2H3+ category for use with Natural Gas (G20) and Liquide gas (G30 and G31)as distributed in the United Kingdom.
The ECOSY 28 E and ECOSY SB 28 E boilers are of the I2H category for use with Natural Gas (G20) as distributed in the United Kingdom.
The boilers have a fan assisted balanced flue which both discharges the products of combustion to and draws the combustion air from the outside of the room. The boilers are suitable for top outlet flue connection only but, can be fitted with horizontal flue, vertical flue or twin-pipe flue. Refer to flue catalogue for further details.
On ECOSY 24 E and ECOSY 28 E, both the central heating and domestic hot water temperature are user adjustable from the boiler control panel.
On ECOSY SB 24 E and ECOSY SB 28 E, the central heating temperature is user adjustable from the boiler control panel.
On the ECOSY 24 E and ECOSY 28 E, domestic hot water demand always has priority over heating demand. The boiler is designed for use as part of a sealed water central heating system with fully pumped circulation. The pump, expansion vessel and associated safety devices are all fitted within the boiler.
The boiler can be installed against either an external wall or on an adjacent inside wall, that is, the flue system will pass directly to the rear or to either side to the terminal fitted on the outside wall face.
The installation must be carried out by a competent person in accordance with the relevant requirements of The Building Regulations, The Water Byelaws, The Building Standards (Scotland) Regulations and any applicable local regulations.
These instructions should be carefully followed for the safe and economical use of your boiler.
Ancillary equipment
A range of flue accessories are available including vertical flues, twin-pipe flues, bends etc. For further information contact your supplier.
COMMISSIONING
Ins 048a
Diagram. 1
OPENING THE CONTROL PANEL COVER
Gas safety (Installation and use) Regulations
In your interests and that of gas safety, it is the law that ALL gas appliances are installed and serviced by a competent person in accordance with the above regulations.
Gas leak or fault
If a gas leak or fault exists or is suspected, turn the boiler off and consult the local gas supply company or your installation/service company.
Boiler controls
The control panel, located at the lower front of the boiler casing, see diagram 1, allows the boiler to be started, shut down, controlled and monitored dur­ing use.
Flue
Do not obstruct the outside terminal of the boiler.
Starting the boiler
Before starting the boiler check that:
- The gas meter tap is open.
- The boiler gas service cock is open.
- The boiler is connected to the electrical supply and turned on.
4
CONTROLS AND LIGHTING
The control panel, located at the lower front of the boiler casing, see diagram 2, allows the boiler to be started, shut down, controlled and monitored during use.
Hab 197a
Diagram 2
Control panel description (diagram 2): 1 - ON/OFF switch 2 - Summer/winter switch 3 - PC connector 4 - Reset button
5 - Display 6, 7, 8 and 9 - Program selection buttons 10 - Pressure gauge
0 6 5
O
1
2
3
4
bAR
IMIT
MODE
ENTER
SETPC
98
10
765431 2
SETTING TO SUMMER MODE
(Hot water only)
PUSH BUTTON TO POSITION TO SET THE
BOILER TO SUMMER MODE
2
SETTING TO WINTER MODE
(heating and hot water)
PUSH BUTTON TO POSITION
TO SET THE
BOILER TO WINTER MODE
Make sure that:
The boiler is connected to the electrical supply.
The boiler gas service cock is open.
The pressure gauge reads between 1 and 2 bar.
PUSH IN BUTTON TO START BOILER
OFF
ON
PUSH IN BUTTON IN
SUMMER POSITION
TO
STOP THE BOILER
Assuming that any remote heating controls are calling for heat, the above procedure is all that is required to start the boiler in heating mode. Hot water has priority over heating.
To obtain domestic hot water, open a hot water tap.
OFF
ON
OFF
ON
OFF
ON
To ensure maximum life of the boiler control system, it is recommended that the mains is left switched on all the time. Power consumption during stand by is only 7 to 8 watts.
1
2
2
Stopping the boilerStarting the boiler
5
CONTROLS AND LIGHTING
Setting domestic hot water temperature
0 6 5
In all cases, by pressing the «Mode» button until the decimal point disappears, the display reverts to normal position :
No decimal point displayed
1 - Press «Mode» button once
3 - Press «enter» until the display starts flashing, and press «mode» twice : the boiler is now
operational at the desired hot water temperature.
twice
Note : On the SB versions, this setting is done using the tank thermostat in the tank.
1. 6 5
set
2. 6 5
set
mode
➭➭
1. 6 5
enter
-
2. 60
+
2. 60
2 - Press «+» or «-» button to set the desired hot water temperature from 40°C to 65°C
(factory set at 65°C)
Hab 198a
Setting heating temperature
Note : 1/ In case of under floor heating systems, the CH flow temperature can be set to between 20°C and
45°C - contact
the Saunier Duval Technical Helpline 01773 828400.
6. 7 0
set
mode
➭➭
6. 85
+
-
1. 6 5
mode
-
1. 60
3 - Press «+» or «-» button to set the desired heating temperature from 20°C to 90°C (factory set at 70°C)
1 - Press «Mode» button once 2 - Press «Set» button 4 times to show 5 on the left
4 - Press «enter» until the display starts flashing, and press «mode» twice : the boiler is now
operational at the desired heating temperature.
Hab 198a
twice
6
The Ecosy display has three display modes : A - Reading mode only - this gives information about the operation in progress. B - Programming mode - this allows the user to change selected settings of the boiler. C - Diagnostic mode - this allows the user to check selected temperatures during boiler operation.
BOILER OPERATING MODES AND DISPLAY READINGS
A- Reading mode only
0 6 5
No decimal point displayed
During boiler operation, the display gives infor­mation about the operation in progress (left hand digit) and the temperature of that operation (right hand digits).
0 - No demand 1 - Safety purge 2 - Ignition 3 - Boiler on - central heating 4 - Boiler on - hot water 5 - Waiting for closing air pressure switch 6 - Boiler off after reaching temp. 7 - Pump overrun after heating 8 - Pump overrun after hot water 9 - Boiler safety shut down
C - Diagnostic mode :
1. 7 0
Flashing decimal point displayed
1. 7 0
Five settings of the boiler can be changed by the user.
1 - Press «Mode» button once : The number 1
mode
1. 7 0
3. 0 0
set
Decimal point displayed
will be displayed with a decimal point after it.
2 - Press «Set» button to select the setting that you wish to change (see table below).
3 - Press «+» or «-» button to adjust the settings according to the table below
4 - Press «Enter» button and then press «Mode» button twice to exit from the programming mode into the display mode.
3. 01
-
B - Programming mode
Programme Setting
1 Domestic hot water temperature ............................... adjustable from 40°C to 65°C (factory set at 65°C)
2 Domestic hot water comfort level...............................factory set at 02 - do not adjust
3 Pump operation.............................................................00 = do not use
.........................................................................................01 = Intermittent pump (factory setting)
.........................................................................................02 = continuous pump
4 Heating economy .......................................................... factory set at 02 - do not adjust
5 Heating flow temperature ............................................ adjustable from 20°C to 90°C (factory set at 70°C)
1. 6 5
set
enter
2. 60
Flow temperature
1 6 5 2 6 5 3 6 5 4 6 5 5 6 5 6 6 5 7 6 5 8 6 5 9 6 5
0 6 5
Allows the user to check selected temperatures during boiler operation.
1 - Press «Mode» button twice : The number 1 will be displayed with a flashing decimal point after it.
2 - Press «Set» button to select the setting that you wish to check (see table below).
3. 5 0
set
mode
1. 7 0
1 - Central heating flow temperature 2 - Central heating return temperature 3 - Cylinder temperature 4 - Not applicable 5 - Not applicable 6 - Not applicable 7 - Calculated temperature set 8 - Temperature rise of central heating flow 9 - Temperature rise of cylinder
Hab 206
Reg 025