Saunier duval COMBITEK F 23 E 06-98 User Manual

COMBITEK F 23 E
Installation and Servicing Instructions
THIS IS A CAT II2H3+ APPLIANCE
IN WARRANTY
TECHNICAL HELPLINE
01773 828400
01773 828100
1
INSTALLATION AND SERVICING INSTRUCTIONS
COMBITEK F 23 E
Note: The boiler serial number is marked on the data label attached to the PCB housing behind the front lower section. Refer to the ‘Introduction’ section for a description of the basic functions of the boiler. The
‘User’ section describes how to safely operate the boiler.
Users’ Instructions
Introduction ..................................................... Page 2
Controls and lighting ................................................. 3
Draining and filling ..................................................... 3
Heating safety valve ................................................. 3
Servicing/maintenance ............................................ 3
Cleaning ..................................................................... 4
Boiler casing ............................................................... 4
Installation Instructions
Introduction ..................................................... Page 4
Changing gas type ................................................... 4
Technical data......................................................4 - 5
Dimensions .................................................................. 5
Boiler schematic ........................................................ 6
Terminal positions ....................................................... 7
Mandatory warning for CE countries
UK
WARNING, these appliances were designed, approved and inspected to meet the requirements of the
English market. The identification plate located on the inside of the appliance certifies the origin where the product was manufactured and the country for which it is intended. If you see any exception to this rule, please contact your nearest stockist. Thank you in advance for your assistance.
Heating and hot water system design ....................7
Boiler installation ........................................................ 8
Horizontal flue installation ......................................... 9
Vertical flue installation ........................................... 10
Electrical connection ..............................................11
Commissioning .........................................................12
Adjustments .............................................................. 13
Safety device ........................................................... 13
Setting ....................................................................... 14
Servicing Instructions
Routine cleaning and inspection ............... Page 15
Replacement of parts ......................................16 - 21
Schematic wiring diagram ..................................... 22
Fault finding ....................................................... 23 - 24
Spare sparts ..............................................................24
INTRODUCTION
The Combitek F 23 E is a wall mounted combination boiler providing central heating and instantaneous domestic hot water.
These instructions should be carefully followed for the safe and economical use of your boiler.
Gas leak or fault
If a gas leak or fault exists or is suspected, turn the boiler and gas supply off and consult the local gas company or your Installer/Service provider.
In case of power supply failure
The boiler no longer operates. As soon as power supply is restored, the boiler will restart automatically.
In case of loss of water in the system
CAUTION. The boiler is installed as part of a sealed system which must only be drained and filled by a competent person.
If the pressure shown on the pressure gauge is less than 1.5 bar the system must be filled up.
Important notice: A central heating system cannot operate satisfactorily unless it is properly filled with water and unless the air initially contained in the piping systems has been properly bled off. If these conditions are not satisfied, air noise will occur within the system and the boiler may fail to operate.
Air in the heating system
Persistent air in the heating system may indicate leaks in the system or corrosion taking place. Call your Installer/Service provider.
Overheating safety
In the event of problem, the overheat safety device causes safety shutdown of the boiler. If this happens, call your Installer/Service provider.
2
The control panel is located on the front bottom section. The controls on this panel allow the boiler to be started, shut down and controlled during use.
1- Pressure / Temperature gauge 2- Hot water / Heating temperature
control & summer / winter switch
3- Timeclock 4- Mains On/Off switch
Diagram 1
CONTROLS AND LIGHTING Make sure that:
The boiler is connected to the electrical supply. The boiler gas service cock is open. The pressure gauge reads between 1.5 and 2 bar. The boiler is now ready to start.
To start the boiler
Switch on using mains switch (4), see diagram 1. Place switch (2) in the Summer or Winter position
To stop the boiler Place switch (4) to the Off position (0).
Setting to ‘Summer’ mode (Hot water only)
Place switch (2) in the Summer position (see
1
2
diagram 2).
Setting to ‘Winter’ mode (Heating and hot water)
Place switch (2) to the Winter position
Diagram 2
Adjust the heating temperature control (2) to the desired temperature. The heating will operate according to the requirements of the timeclock and/or room ther­mostat if fitted or, will operate according to the system requirements. Domestic hot water always has priority over cen­tral heating.
Timeclock
To set the clock rotate actuater mechanism clockwise, by hand, until current time is indicated.
See diagram 3.
Note: The time is set in 24 hour format, for example 1300pm for 1pm
Setting the programme ‘ on & off ’ times
Select the on times by pushing the black tappets to the outside Select the off times by pushing the black tappets to the inside The clock shown in diagram 3 is set as follows
On 07.00am to 09.00am Off 09.00am to 4.00pm On 4.00pm to 10.00pm Off 10.00pm to 07.00am
5
6
7
8
9
3
4
5
1
24
2
23
3
2 2
12
4
2 1
2 0
I
1 9
9
16
0
0
1
6
1 5
1 1
1 4
2 1
1
3
3
1 8
1 7
21
1
2
3
4
5
1
2
3
4
5
6
7
9
8
9
10
11
24
23
12
6
12
13
22
0
1
5
14
4
21
20
I
19
18
17
16
Diagram 3
To override or advance the clock
The clock has a manual on/off switch see diagram 3 which opperates as follows:
Upper position 1 Heating on continuosley Middle position Heating on timed Lower position 0 Heating off
DRAINING AND FILLING Caution: The boiler is installed as part of a sealed
system which must only be drained and filled by a competent person. Note: If there is persistent loss of system pressure, you must consult your Installer/Service Provider.
HEATING SAFETY VALVE CAUTION: A safety valve with a discharge pipe is
fitted to this boiler. The valve MUST NOT BE TOUCHED except by a competent person. If the valve discharges at any time, switch the boiler off and isolate it from the electrical supply. Contact your Installer/Service Provider.
SERVICING/MAINTENANCE
To ensure the continued efficient and safe operation of the boiler, it is recommended that it is checked and serviced at regular intervals. The frequency of servicing will depend upon the installation condi­tions and usage but, in general, once a year should be enough.
3
CLEANING
The boiler casing can be cleaned with a damp cloth followed by a dry cloth to polish. Do not use abrasive or solvent cleaners.
INSTALLATION INSTRUCTIONS
INTRODUCTION
The Combitek F 23 E is a wall mounted combination boiler providing central heating and instantaneous domestic hot water.
Note: this boiler requires no fixing jig and has top outlet flueing only ( there is no rear flue option ).
The boiler is of the II2H3+ category for use with Natural gas (G20). To convert to Butane (G30) or propane (G31), the following kit is required.
Gas conversion kit :part number 86161
The boiler has a fan assisted, balanced, flue which both discharges the product of combustion to, and draws the combustion air from, the outside of the building.
BOILER CASING CAUTION: Do not remove or adjust the casing in any
way, as incorrect fitting may result in faulty operation. If in doubt, contact your Installer/Service Provider.
Accessories
A range of accessories are available including, vertical flue components. For further information, contact you nearest stockist.
Gas Safety (Installation and Use) Regulations
In the interests of gas safety, it is the law that ALL gas appliances are installed and serviced in by a competent person in accordance with the above regulations.
Gas leak or fault
If a gas leak or fault exists or is suspected, turn off the boiler and gas supply and consult the local gas company or your Installer/Service Provider.
TECHNICAL DATA
Heating output
automatically variable from 8,9 kW to 23,3 kW
30,000 BTU/H to 80,000 BTU/H
Efficiency 82,4 % Heating adjustment 38°C to 90°C Expansion vessel effective capacity 6,5 l Expansion vessel charge pressure 0,5 bar Maximum system capacity at 75°C 140 l Safety valve, maximum service pressure 3 bar Products outlet diameter 60 mm Fresh air inlet diameter 100 mm
Natural Gas Butane Propane Town gas
(G20) (G30) (G31) (G130)
Burner injector 1,2 mm 0,73 mm 0,73 mm 2,4 mm Inlet pressure 20 mbar 29 mbar 37 mbar 8 mbar Gas rate (maximum) 2,70 m3/h 2,01 kg/h 1,98 kg/h 3,88 m3/h Gas rate (minimum) 1,13 m3/h 0,84 kg/h 0,74 kg/h 1,63 m3/h
(kW) 8,9 10 11 12 13 14 15 16 17 18 19 20 21 22 23,3
(Btu/h) 30387 34142 37557 40971 44385 47799 51214 54628 58042 61456 64871 68285 71699 75113 79552
(kW) 11,9 13,2 14,4 15,7 16,9 18,1 19,2 20,4 21,5 22,7 23,8 24,9 26,0 26,9 28,3
(Btu/h) 40678 45130 49332 53481 57579 61627 65626 69575 73477 77333 81142 84906 88913 91713 96602
GAS
G 20 (mbar) 1,3 2,1 2,6 3,0 3,5 4,0 4,5 5,1 5,7 6,3 6,9 7,6 8,3 8,8 9,8 G 30 (mbar) 3,7 5,3 6,3 7,4 8,6 9,8 11,1 12,5 13,9 15,4 17,0 18,6 20,4 21,7 24,1 G 31 (mbar) 4,0 6,3 7,5 8,8 10,2 11,7 13,3 14,9 16,7 18,5 20,3 22,2 24,4 26,0 28,8
Hot water output
automatically variable from 8,9 kW to 23,3 kW
30,000 BTU/H to 80,000 BTU/H
Maximum hot water temperature 65 °C Specific flow rate (for 35°C temp rise) 9,6 l/min Threshold flow rate 3 l/min Nominal water flow rate 12 l/min Maximum supply pressure 10 bar Minimum operating pressure 0,5 bar
Electrical supply 230 V Maximum absorbed power 130 W
Heat output
Heat input
4
INSTALLATION INSTRUCTIONS
Pump:
The performance of the pump varies according to the pump bypass setting, see diagram 3.
50
Bypass fully shut
1
40
30
20
10
heating flow and return
0
Available pressure (kPa) between
(10 kPa = 1 m WG)
Diagram 3
DIMENSIONS
The boiler is delivered in two separate packages:
- The boiler
- The flue system
1
2
3
4
5
500 1000
Flow rate through heating system (I/h)
Pom 052
Open 1/4 turn
2
Open 1/2 turn
3
Open 1 turn
4
Open 2 turns
5
Clearances
The boiler can be installed with the following clearances: 50 mm either side of the boiler 600 mm to the front of the boiler 300 mm below the boiler
Net weight: 41 kg Gross weight: 43 kg
802
234
410
857
623
Hab 271a
378
Diagram 4
5
INSTALLATION INSTRUCTIONS
BOILER SCHEMATIC
3-Ignition module 4-Heating temperature adjuster 6-Pressure gauge 7-non-return valve 8-Expansion vessel
9-Pump 10 - Automatic air vent 11 - Burner 12 - Burner pressure test point 13 - Heat exchanger 14 - Gas valve 16 - Heating and hot water thermistor 17 - Ignition electrode
23
19 - Overheat thermostat 20 - Flame sense electrode 21 - Loss of water pressure switch 22 - Fan 23 - Air pressure switch 24 - Gas cock
A - Heating return
B - Cold water inlet C - Heating flow D - Domestic hot water flow
E - Gas supply
22
13
20
12
11
10
9
8
7
6
21
19
17
16
14
3
4
24
Diagram 5
6
AB CD E
Shy 131b
INSTALLATION INSTRUCTIONS
Minimum dimensions (in mm) for the positioning of flue terminals
A-Under a window .............................................. 300
B-Under an air vent ............................................ 300
C-Under a gutter ................................................. 75
D-Under a balcony ............................................. 300
E-From an adjacent window ............................ 300
F-From an adjacent air vent ............................. 300
G-From vertical drain pipes or soil pipes .......... 75
H-From an external corner of the building ...... 300
I-From an internal corner of the building ....... 300
L-From the ground or from another floor ........ 300
M- Between two terminals vertically .................. 1500
N-Between two terminals horizontally .............. 300
Diagram 6
G
C
N
E
F
M
A
B
D
I
L
H
Ven 060b
TERMINAL POSITIONS
The minimum acceptable spacings from the termi­nal to obstructions and ventilation openings are shown in diagram 6 :
Cupboard or compartment ventilation
The boiler can be fitted in a cupboard or compartment without the need for additional per­manent high and low level ventilation
HEATING SYSTEM DESIGN
The combitek F 23 E is compatible with any type of sealed system installation, i.e. radiators, fan convectors etc.
Pipe sectional areas shall be determined in accordance with normal practices, using the pump curve, refer to ‘Technical Data’. The distribution system shall be calculated in accordance with the output requirements of the actual system, not the maxi­mum output of the boiler. However, provision shall be made to ensure sufficient flow so that the temperature difference between the flow and return pipes is less than or equal to 20
o
C. The minimum flow is 500 l/h.
The piping system shall be routed so as to avoid any air pockets and facilitate permanent venting of the installation. Bleed fittings shall be provided at every high point of the system and on all radiators. The total volume of water permitted for the heating system depends, amongst other things, on the static head in the cold condition. The expansion vessel on the boiler is pressurised at 0,5 bar (corresponding to a static head of 5m wg.) and allows a maximum system volume of 140 litres for an average temperature of 75oC and a maximum service pres­sure of 3 bar. This pressure setting can be modified at commissioning stage if the static head differs.
Provision shall be made for a drain valve at the lowest point of the system.
DOMESTIC HOT WATER SYSTEM DESIGN
Copper tubing must be used for the domestic hot water system. Unnecessary pressure losses should be avoided. The domestic hot water supply pressure must be between 0.5 and 10 bar. If the pressure exceeds 3 bar, a pressure reducing valve must be fitted.
Hard water areas
In areas where the water hardness exceeds 200 mg/ litre, it is recommended that a suitable scale reducing device is fitted.
Heating system connections - Pipe Ø 22 mm. Hot water system connections - Pipe Ø 15 mm. Gas connection - Pipe Ø 22mm.
Safety valve discharge WARNING: It must not discharge above an entrance
or window or any type of public access area. Connect the safety valve discharge pipe to the valve, the discharge must be extended using not less than 15 mm o.d. pipe, to discharge in a visible position outside the building, facing downward, preferably over a drain. The pipe must have a continuous fall and be routed to a position so that any discharge of water, possibly boiling or steam, cannot create any danger to persons, damage to property or external electrical components and wiring. Tighten all pipe connection joints.
Gas connection
The supply from the governed meter must be of adequate size to provide a constant inlet working pressure of 20 mbar (8 in wg). To avoid low pressure problems, it is recommended that the supply is taken to the boiler using 22 mm pipe as far as possible. On completion, the gas installation must be tested using the pressure drop method and purged in accordance with the current issue of BS6891.
Thermostatic radiator valves are permitted.
A suitable WRC approved filling loop must be fitted to enable correct filling of the system. In all cases, it is ESSENTIAL that the system be thoroughly flushed prior to installing the new boiler.
Gas Safety (Installation and Use) Regulations.
In your interests and that of gas safety, it is the law that ALL gas appliances are installed and serviced by a competent person in accordance with the above regulations.
7
INSTALLATION INSTRUCTIONS
Boiler connections A Heating return B Cold water mains inlet C Heating flow D Hot water outlet E Gas connection F Safety valve discharge connection
A
B
Flow restrictor
Filter
Diagram 7b
C
F
Fibre washer
D
Isolating cock
B
Pla 277
Pla 275
E
Diagram 7a
Statutory requirements
The installation of this boiler must be carried out by a competent person in accordance with the rele­vant requirements of the current issue of: The Gas Safety (Installation and Use) Regulations The Building Regulations The local water company Bylaws The Building Standards Regulations (Scotland) The Health and Safety at Work Act
Sheet metal parts
WARNING: When installing or servicing this boiler, care should be taken when handling the edges of
BOILER INSTALLATION
To install the boiler, proceed as follows:
· Allowing sufficient clearances for servicing/ repair, place the template on the wall Determine the position of the flue hole and drill hole for flue, preferably using a 120 mm core drill.
· Drill two holes for the hanging bracket, Plug and screw to wall.
· Fasten lower spacing brackets to boiler (see template)
· Remove template.
· Hang the boiler on the hanging bracket.
sheet metal parts to avoid the possibility of personal injury.
Installing the boiler
Prior to installing the boiler, the system must be thoroughly flushed to eliminate any foreign bodies and contaminents such as filings, solder, particles, oil, grease etc.
Note: Solvent products could cause damage to the system.
Boiler Template
34
2
857
802
410
8
7
3
Spacing plate must be attached to
boiler prior to hanging
WALL SIDE
Ø 105
Ø 8Ø 8 Ø 8
BOILER SIDE
110665 B
120 mm
65 mm
691 mm
Diagram 8
55 55 57,5 57,5
Ins 071a
8
INSTALLATION INSTRUCTIONS
HORIZONTAL FLUE INSTALLATION
• Fit gasket (H) onto underside of elbow (C)
• Carefully insert ‘o’ rings (J) into upper and lower
parts of inner elbow
• Fit elbow onto boiler using screws provided (I)
• Offer flue pipes to elbow, note that pipe (B) should
be inside pipe (A) before connection. Push pipe (B) into inner elbow socket and connect pipe (A) with collar (D). Locking clips (E) are used to lock collar into position.
• Parts (F) and (G) are used to seal brickwork gaps
if required. If using part (G) to seal inner wall, this should be placed over flue before installation.
Calculation of flue cutting lengths
· Measure wall thickness e (mm)
· For side flues, measure distance from inside face of
the side wall to the centre line of the boiler and subtract 205 mm to get dimension a (mm) see diagram 10.
· Refere to table 1 for the cutting lenghs of both
the inner and outer flue pipes for each of the various flue options available.
· Important: All flue cutting lengths must be
measured from the terminal end of the flue pipes, see diagram 11.
· When the dimension x measured on site is greater
than that given in table 1 a flue extension kit will be required, refere to table 2 for details.
A
B
C
H
Diagram 9
The flue kit 86285 is 1000 mm long and com­prises:
- Outer pipe .................................................... A
- Inner pipe....................................................... B
- Flue elbow..................................................... C
- Fixing collar ................................................... D
- Locking clips .................................................. E
- External rubber sealing collar ..................... F
- Internal flange .............................................. G
- Gasket ........................................................... H
- Screws.............................................................. I
- 'O' rings ........................................................... J
D
F
I
J
GE
Pho 422
Table 1
Flue cutting lengths
Cutting length (mm)
Flue option outer pipe inner pipe Comments
Top outlet e + 144 e + 224 maximum rear flue wall thickness "e"
without
extension
511 mm
Table 2 Number of extension kits required
Flue option Dimension 'X' No. of
extension kits
Side flue 745 to 1745 mm 1
(left or right) 1527 to 2745 mm 2
Maximum horizontal flue run 3m For each 90o flue bend fitted, reduce overall flue length by 1 m. For each 45o flue bend fitted, reduce overall flue length by 0.5 m.
Horizontal flue kit 86285 Flue extension kit 85091 90o bend kit 85092 45o bend kit 85093
Diagram 10
Diagram 11
a
X
Cutting length
Cutting length
Outer pipe
Inner pipe
ee
a
X
Hab 210
Ven 089
9
INSTALLATION INSTRUCTIONS
VERTICAL FLUE INSTALLATION
A .................................................................... Gasket
B ..................................................... Vertical adaptor
C .................................................................... ‘O’ ring
D....................................................................... Collar
E ...................................................................... Clamp
F ...................................................................... Screws
G .................................................................. Terminal
H ...................................................................... Screws
· Fit gasket (C) onto underside of vertical adaptor (B)..
· Carefully insert ‘O’ ring (A) into vertical adaptor inner spigot.
· Fit adaptor correctly onto fan outlet.
· For flat roof installation, fit flat roof flashing collar (part no. 85107)
· Fit flue terminal (L) onto roof ensuring flashing makes a watertight joint.
· For pitch roof installation, fit pitch roof flashing collar (part no. 85105)
· Fit flue terminal (G) onto roof ensuring flashing makes a watertight joint.
NOTE: Maximum vertical height with no bends is 4 m.
Diagram 12 Show vertical kit adaptor & terminal
A
B
F
C
D
E
H
Note: Should it be necessary to cut the flue, always cut equal amounts from both inner and outer pipes.
Maximum vertical flue run 11.5m For each 90o flue bend fitted, reduce overall flue height by 1 m. For each 45o flue bend fitted, reduce overall flue height by 0.5 m.
Vertical flue terminal (Black) 85103
Pitched roof flashing 85105 Flat roof flashing 85107 Flue extension pipe 85099 90o bend kit 85101 45o bend kit 85102
G
Diagram 12
10
INSTALLATION INSTRUCTIONS
°C
ELECTRICAL CONNECTION
Warning: This boiler must be earthed.
All system components must be of an approved type. Connection of the whole electrical system and any heating system controls to the electrical supply must be through a common isolator. Isolation should preferably be by a double pole switched fuse spur box having a minimum contact separation of 3 mm on each pole. The fused spur box should be readily accessible and preferably adjacent to the boiler. It should be identified as to its use. A fused three pin plug and shuttered socket outlet may be used instead of the fused spur box, provided that: a) They are not used in a room containing a bath or
shower.
b) Both the plug and socket comply with the current
issue of BS1363. The mains electrical supply must be maintained at all times in order to provide domestic hot water and frost protection
Note: For further information, see The Building Regulations 1991 - Conservation of fuel and power
- 1995 edition - Appendix G, table 4b.
DO NOT INTERRUPT THE MAINS SUPPLY TO THE BOILER WITH A TIME SWITCH OR PROGRAMMER.
The combitek F 23 E is delivered with 1metre mains supply lead ready connected.
External controls
The boiler will work for heating AS DELIVERED without a room thermostat fitted provided the two wires on the integral external controls connection REMAIN LINKED TOGETHER (as supplied). If a room thermostat is required, it must be connected as shown below and the link must be removed.
ANY ROOM THERMOSTAT USED MUST BE OF THE VOL­TAGE FREE TYPE.
WARNING: ON NO ACCOUNT MUST ANY ELECTRICAL VOLTAGE BE APPLIED TO EITHER OF THE TERMINALS OF THE EXTERNAL CONTROLS CONNECTION
WARNING: This boiler must be wired in accordance with these instructions. Any fault arising from incor­rect wiring cannot be put right under the terms of the guarantee.
When fitting an external control,
E
For no external controls
leave wire link (E) in place
sch 228
remove wire link (E) and connect voltage free thermostat as shown
sch 229
The mains electrical cable is supplied with the boiler. It is coiled and tucked
inside the boiler
Diagram 13
sch 227
11
INSTALLATION INSTRUCTIONS
COMMISSIONING
The commissioning and first firing of the boiler must only be done by a competent person.
Gas installation
It is recommended that any air is purged from the supply at the gas inlet test point on the left hand side of the gas valve, see diagram 14.
Filling the system
1
Open isolating coks to boiler
(see diagram 7a)
3
Open the tap on the sys­tem filling loop and fill the system until the pressure indicated on the display is between 1 and 2 bar.
Bleed each radia
4
tor until a continu­ous jet of water is ob­tained.
Diagram 14
2
Sec 058
Open various
5
hot water taps to
bleed system.
Undo, but do not remove, cap on automatic air vent on top of pump. Do not re­tighten cap.
Make sure that
6
pressure gauge reads between 1 and 2 bar. Re-pressurise system as necessary.
mec 117
008
Reg
Ins 061
Important:
- If this procedure is not carried out properly, the boiler will go into safety lock-out until all of the air has been purged.
- When venting air from boiler, do not touch the schrader valve on the expansion vessel, it is NOT a vent.
- Before starting the boiler, turn the pump impellor to make sure it is free to move.
• Unscrew black cap on front of pump.
• Using screwdriver, push in pump spindle and turn pump impellor 3 to 4 times. DO NOT HIT SPINDLE. Re­place black cap.
Starting the boiler
Before starting the boiler check that:
- The gas meter tap is open. If using Butane or Pro­pane, check that valve on storage cylinder or tank is open.
- You have removed the two fan transit clips from fan.
12
Ins 062
- The boiler gas service cock is open.
- The boiler is connected to the electrical supply and switched on.
- The front casing is fitted.
First starting up
• Following the instructions given in the 'User Instruc­tions' set boiler to run in central heating mode.
• Set boiler thermostat for maximum temperature ensure timeclock is "ON" and check that any exter­nal controls, if fitted, are calling for heat.
• Allow the temperature to rise to the maximum value, with all radiator valves open. The temperature rise will cause release of the gases contained in the water of central heating system.
- Gases driven towards the boiler will be automati­cally released through the automatic air vents.
- Gases trapped at the highest point of the system must be released by bleeding the radiators.
Sec 058
INSTALLATION INSTRUCTIONS
ADJUSTMENTS
On reaching maximum temperature, the boiler should be turned off and the system drained as rapidly as possible whilst still hot.
• Refill system to a pressure of 1.5 bar and vent as before.
• Restart boiler and operate until a maximum tem­perature is reached. Shut down boiler and vent heating system. If necessary, top up heating sys­tem and make sure that a pressure of 1.5 bar is indicated on the pressure gauge when system is COLD.
Gas pressures
The main burner pressure should be checked dur­ing commissioning to make sure the correct out­put is obtained. Proceed as follows:
• Shut down boiler.
• Undo screw on burner pressure test point below sealed combustion chamber and connect a suitable manometer, see diagram 15.
• Start boiler as described in 'User Instructions'.
• Set boiler thermostat to maximum and check that any external controls are calling for heat.
• Check that the reading on the gauge matches that given in 'Technical Data' for the type of gas being used.
• Adjust the range rating adjuster screw as neces­sary to obtain the desired input, see diagram 16.
• Shut down boiler.
• Remove manometer, tighten up test point screws and check for gas soundness.
• Using a ball point pen, clearly indicate on the data label the input the boiler is set to.
Note: This adjustment does not affect the domes­tic hot water output. If measured burner pressure differs greatly from the given figure, check the gas inlet pressure as follows:
• Shut down boiler.
• Remove screw from inlet test point on the side of the gas valve, see diagram 14.
Diagram 15
Diagram 16
• Connect a suitable pressure gauge.
• Start boiler as described in 'User Instructions'.
• Check that the inlet pressure reading matches that given in 'Technical Data' for the type of gas being used.
• Shut down boiler.
• Remove pressure gauge, tighten up test point screws and check for gas soundness.
• If the gas pressure is incorrect, refer to the Fault Finding section in 'Servicing Instructions'.
• If the inlet pressure is below that given, the gas supply pipework/meter must be checked and any fault corrected.
• In the case of an LPG installation, check the stor­age tank or cylinder, regulator and pipework.
Des 044
Reg 056
SAFETY DEVICES
Air flow rate safety device
If an obstruction, even partial, of the flue occurs, for any reason whatsoever, the built in safety sys­tem of the boiler will turn the boiler OFF and the fan will continue to run. The boiler will be ready to operate when the fault has been cleared.
In case of power supply failure
The boiler no longer operates. As soon as power supply is restored, the boiler will be automatically restarted.
Overheat safety
In the event of a problem, the overheat thermos­tat causes safety shutdown of the boiler. Should this occur, reset the thermostat by pressing the red button. The overheat thermostat is located on the RHS of the heat exchanger.
Important notice: A central heating system cannot operate satisfactorily unless it is properly filled with water and unless the air initially contained in the piping systems has been properly bled off. If these conditions are not satisfied, air noise will occur within the system.
The COMBITEK F 23 E boiler has a built in frost pro­tection device that protects the boiler from freez­ing. If the boiler is to be left and there is a risk of frost, ensure that the gas and electrical supplies are left connected and the summer/winter switch is in the position. The frost protection device will light the boiler when the temperature of the boiler wa­ter falls below 6°C. When the temperature reaches 16°C, the boiler stops.
Note: This device works irrespective of any room thermostat setting and only protects the boiler.
13
INSTALLATION INSTRUCTIONS
SETTINGS
Gas valve setting
All boilers are tested and factory set during manu­facture. Should it be necessary to reset a gas valve, for example after replacement, proceed as follows:
• Shut down boiler.
• Connect a suitable pressure gauge as described in 'Commissioning'.
Maximum setting
• Remove one electrical connector from the modulating gas valve coil.
• Turn the domestic hot water temperature ad­juster to maximum setting.
• Remove the protective cover from the gas valve ad­juster. Using a 2 mm Ø rod, press in the spindle in the middle of screw.
• Turn nut 'B' to obtain the de­sired pressure, see technical data.
B
A
Diagram 17
A
Reg 013
Minimum setting
This must be done AFTER the maximum setting.
• Hold nut B to prevent from turning, turn nut 'A' to obtain the desired pressure, see technical data.
After adjustment, refit the cover to the gas valve adjuster and refit electrical connector.
Bypass
The COMBITEK F 23 E has a built-in bypass. This must be adjusted according to the requirements of the system, refer to the flow rate pressure curve (dia- gram 3). The boiler is supplied with the built-in by­pass open a half a turn. It is adjusted by turning the bypass screw (A), see diagram 17. Turn the screw clockwise to close the bypass. When using thermostatic radiator valves (TRV's), it is recommended that an additional, adjustable bypass of 15 mm minimum diameter is fitted be­tween the flow and return of the heating circuit, see diagram 6. Any bypass must be fitted before system controls.
PCB Settings
The combitek has a switch SW1 on the main PCB which incorporates two dip switches. Both these dip switches should normaly be set to the Off position.
Mec 121
Diagram 18
Reg 057
Purpose of dip switch 1 :
In the Off position the pump will be on and off with the room stat (this is the normal position).
In the On position, the pump will be on and off with the burner.
Purpose of dip switch 2 :
Not used in UK. Leave in off position.
14
SERVICING INSTRUCTIONS
ROUTINE CLEANING ANS INSPECTION
To ensure the continued efficient and safe opera­tion of the boiler it is recommended that it is checked and serviced at regular intervals. The fre­quency of servicing will depend upon the particu­lar installation conditions and usage, but in gen­eral once a year should be enough.
It is the law that any servicing is carried out by a competent person.
Service Check and Preparation.
• Operate boiler and check for any faults that need to be put right.
• Isolate boiler from the gas and electrical supplies.
• On completion check all gas carrying parts for soundness with leak detection fluid.
• The maximum domestic hot water flow rate is 12 litres/minute.
• Remove boiler casing as follows:
Upper front panel
• Disengage the two 'quarter turn' fasteners by turning the heads of the screws a quarter of a turn towards the centre of the boiler.
• Carefully lower the panel down on its hinge until it is horizontal.
• Turn both plastic catches to release upper front panel.
• Remove upper front panel by pulling forward at the bottom and lifting off. Note: The upper front panel is retained by a plastic safety strap, disengage this before removal.
Side panels
• From below boiler, unscrew and remove black plastic screws securing side panels to the boiler.
• Prise out black plastic inserts and lift panel off boiler.
Combustion chamber
• Loosen two wing nuts on combustion chamber cover.
• Disengage retaining lugs from holes in either side of combustion chamber and move rods away to clear combustion chamber sides, see diagram 19.
• Unclip two toggle clips holding upper part of combustion chamber in place.
• Holding both sides, pull chamber forward to re­lease it from underside of heat exchanger and out of boiler.
• Take care not to damage insulation material on inside faces of combustion chamber.
Cleaning the burner
• Pull off leads to ignition electrode.
• Pull off lead to flame sense electrode.
• Unscrew and remove screw holding earth lead to flame sense electrode.
• Undo main gas supply nut from main burner.
• Unscrew and remove locking nut from both main gas connection and burner pressure tapping point.
• Lift front edge of burner until tapping point and gas supply connection are free. Remove burner from boiler taking care to retain both fibre washers and seal on gas supply for use on reassembly.
Diagram 19
• Unscrew and remove two injector bar retaining screws and separate injector bar from burner.
• Examine and clean injectors as necessary. Note: Do not use a wire or sharp instrument on the holes.
• Replace burner in reverse order to removal.
Heat exchanger
• After removal of burner, examine heat ex­changer for any blockages or build up of deposits.
• Clean using soft brush or vacuum cleaner. Important: Take care not to scratch or otherwise damage painted surface of heat exchanger.
Reassembly of parts removed for servicing
• Replace all parts in reverse order to removal.
Flue system
• Check externally to make sure flue is not blocked.
• Inspect flue system to make sure all fittings are secure.
Operation of fan
• Switch on electrical supply and turn on gas.
• Switch boiler On/Off switch to 1 (On).
• Light burner by opening a hot tap.
• Without upper front panel in place, burner should be prevented from lighting by air flow detection system.
• Refit upper front panel.
• Check that fan runs when burner is lit and stops when it goes out.
Cold water inlet filter
• Drain down hot water circuit of boiler as follows:
• Close isolating valve on cold water inlet connec­tion, see diagram 5.
• Open one or more hot water taps to drain boiler.
• Undo connecting nut from cold water inlet con­nection to gain access to filter.
• Remove restrictor, then filter from cold water in­let connection.
• Clean and inspect filter, replace if necessary.
• With both flow restrictor and filter in place, re­connect pipe to inlet connection and tighten.
• Fully open isolating cock on cold water inlet con­nection and check for leaks.
Operation of water valve
• With the Summer/Winter control in the 'Summer' position, slowly open a convenient tap until boiler lights.
• Measure water flow, it should not be greater than 3,5 litres/minute.
• If necessary, replace diaphragm.
• Replace all outer panels.
Des 047
15
SERVICING INSTRUCTIONS
REPLACEMENT OF PARTS
To replace microswitch assembly
• Disconnect microswitch by pulling off plug.
• Unclip external controls connector from mount­ing bracket.
• Undo two screws securing microswitch assembly to reversing valve assembly, see diagram 20.
• Remove microswitch assembly from reversing valve.
• Fit replacement microswitch assembly in reverse order to removal.
• Reconnect plug and refit external controls con­nection to bracket.
To replace fan
• Disconnect power supply and earth leads to fan.
• Unscrew and remove two fan retaining screws located at front edge of fan mounting plate.
• Remove fan with mounting plate attached by pulling forwards and out of boiler.
• Unscrew and remove three screws securing fan to fan mounting plate.
• Fit replacement fan to mounting plate and se­cure with screws.
• Fit replacement fan to boiler in reverse order to removal making sure that mounting plate retain­ing lugs are properly engaged into flue hood.
• Reconnect power supply and earth leads. Important: Make sure that fan outlet is correctly fit­ted into the flue elbow at the top of the boiler. Before commissioning boiler, remove the two plas­tic transit clips from replacement fan.
To replace air pressure switch
• Locate air pressure switch in upper left hand cor­ner of sealed chamber.
• Pull off plastic tube from left hand connection.
• Grasp pressure switch and disengage it from bracket clips by pulling from the top.
• Remove electrical connections from switch.
• Fit electrical connections to terminals 1 and 3 of replacement switch.
• Fit replacement switch in reverse order to re­moval. Important: Refit plastic tube to LEFT hand connec­tor (marked P1).
To replace spark generator
• Locate spark generator on bracket to right hand side of gas valve.
• Undo and remove screw securing lower termi­nal cover to bracket and remove bracket.
• Disconnect four leads from spark generator.
• Undo and remove screw securing spark genera­tor to bracket and remove spark generator.
• Fit replacement spark generator in reverse order to removal.
• Reconnect two grey power supply leads and two clear ignition leads to spark generator, the polarity is not important.
• Refit lower terminal cover.
Diagram 20
Diagram 21
nection cover to PCB cover, see diagram 21.
• Open cover and unclip plastic clip securing pump cable to lower front panel.
• Pull off pump connector and earth lead.
• Undo and remove four screws securing PCB cover to lower front panel.
• Lift off PCB cover.
• Pull off connectors CN6, CN7, CN8 and CN9 on PCB.
• Undo and remove screw holding PCB to lower front panel.
• Lifting PCB up slightly on LHS, pull PCB out of elec­trical connector on ignition PCB. Leave ignition PCB in place.
• Fit replacement PCB in reverse order to removal. Important: When fitting replacement PCB, ensure that control knob spindle correctly locates into PCB adjuster slots.
• Refit connectors and covers in reverse order to removal.
To replace ignition PCB
• Gain access to PCB's as described in previous section.
• Remove main PCB securing screw as described in previous section.
• Pull off three electrical connectors on PCB.
• Lift up ignition PCB, separate from main PCB and remove from boiler.
• Fit replacement PCB in reverse order to removal.
• Refit connectors and covers in reverse order to removal.
Sch 228
Hab 286
To replace main printed circuit board (PCB)
• With lower front panel down as described previ­ously, undo and remove screw holding pump con-
16
To replace pump
• Drain down heating circuit of boiler only as fol­lows:
SERVICING INSTRUCTIONS
• Close isolating valves on flow and return connec­tions. It is not necessary to drain entire heating circuit to carry out this work.
• Gain access to pump connection as described in 'To replace main PCB'.
• Pull off pump connector and earth lead.
• Pull out retaining clip from telescopic pump out­let connection and slide connection upwards to release from pump.
• Undo and remove two fixing screws and remove pump retaining bracket from front of pump.
• Grasp pump body, lift upward to disengage from reversing valve and turn pump to right. Remove pump by pulling forward and over reversing valve assembly.
• Discard old pump inlet 'O' ring.
• Apply silicone grease to new 'O' ring supplied, and fit onto inlet connection on replacement pump.
• Fit replacement pump in reverse order to re­moval. Note: Apply silicone grease to pump outlet con­nection 'O' ring before assembly.
• Refit pump electrical connection.
• Open isolating valves on flow and return con­nections, refill, vent and pressurise boiler. Check for leaks.
Diagram 22
Cla 007
To replace pressure gauge
• Drain down heating circuit of boiler only as de­scribed in 'To replace pump'.
• Undo and remove screw securing pressure gauge capillary to front section, see diagram 22.
• Carefully pull capillary from front section.
• Undo and remove two screws securing pressure gauge to lower front panel and remove gauge.
• Fit replacement gauge in reverse order to re­moval.
• Fit capillary of new gauge to front section using new 'O' ring supplied.
• Open isolating valves on flow and return connec­tions, refill, vent and pressurise boiler. Check for leaks.
To replace reversing valve assembly
• Remove pressure gauge capillary as described previously.
• Remove pump as described previously.
• Remove microswitch assembly as described pre­viously.
• Remove retaining clip from LHS pipe connection on front section of valve and disengage pipe.
• Unscrew and disconnect heating flow (centre) connection at fixing jig.
• Remove retaining clip from heating flow pipe connection on right of front section.
• Remove flow pipe from boiler.
• Unscrew and disconnect heating return (left hand) connection at fixing jig.
• Remove retaining clip from expansion vessel pipe connection at rear of reversing valve assembly and disengage pipe, pushing pipe back and out of re­versing valve.
• Undo and remove large screw holding water valve to back plate of reversing valve assembly,
see diagram 23
Diagram 23
Diagram 24
Sec 059
• Push water valve back to disengage it from re­versing valve.
• Unclip and remove loss of water pressure switch from left of reversing valve assembly, see diagram
24.
• From below boiler, undo and remove three screws holding reversing valve to bottom plate of boiler. Remove complete reversing valve assem­bly from boiler.
• Undo and remove heating return connecting pipe and hose from rear of reversing valve assem­bly. Fit hose to replacement reversing valve assem­bly.
• Fit replacement reversing valve into boiler in re­verse order to removal. Note: Use new 'O' rings, retaining clip, filter and washer provided.
• Unscrew and remove microswitch assembly from top of replacement reversing valve assembly to allow refitting of water valve.
Des 054
17
SERVICING INSTRUCTIONS
Note: fit expansion vessel pipe and loss of water switch to reversing valve assembly before pump, to ensure that it is correctly located. Apply silicone grease to all 'O' rings and hoses prior to assembly.
• Open isolating valves on flow and return con­nections, refill, vent and pressurise boiler. Check for leaks.
To replace reversing valve front section
• Remove pressure gauge capillary as described previously.
• Remove pipe connections from either side of reversing valve front section, refer to previous sec­tion.
• Move short selector lever on front of valve to left hand position.
• From below boiler, undo and remove single screw holding reversing valve front plate to bottom plate of boiler.
• Undo and remove six screws holding front sec­tion to rear section of reversing valve, see diagram 25.
• Remove front plate complete with pump bracket and then front section from reversing valve, along with rubber sealing gasket.
• Assemble bypass valve provided and fit into hole in underside of replacement front section. Fit 'U' shaped retaining clip. Note: Use bypass valve fitted to original front sec­tion for guidance.
• Fit replacement front section, with gasket, to rear section.
• Locate front plate and replace six fixing screws. Take care to evenly tighten screws ensuring they are not cross threaded.
• Refit pipe connections to either side of front sec­tion using new 'O' rings provided. Apply silicone grease to 'O' rings before fitting.
• Refit pressure gauge capillary in reverse order to removal.
• Ensure short selector lever on front of valve is set to right hand position.
• Open isolating valves on flow and return con­nections, refill, vent and pressurise boiler. Check for leaks.
To replace loss of water switch
• Drain down heating circuit of boiler only as de­scribed in 'To replace pump'. Note: It is not necessary to drain entire heating cir­cuit to carry out this work.
• Pinch plastic cover to release retaing clips and remove cover from switch. Pull plug lead from switch terminals.
• Remove clip holding switch into left side of re­versing valve assembly.
• Pull switch out of reversing valve assembly, see
diagram 24.
• Fit replacement switch in reverse order to re­moval, using new 'O' ring provided and aplying sili­cone grease to 'O' ring before fitting.
• Reconnect plug to switch terminals.
• Open isolating valves on flow and return con­nections, refill, vent and pressurise boiler. Check for leaks.
Diagram 25
To replace water valve or diaphragm
• Drain down hot water circuit of boiler only as described in 'Routine Cleaning and Inspection'.
• Remove microswitch assembly as described pre­viously.
• Remove clip holding connecting pipe in rear of water valve. From below boiler, grip clip with long nosed pliers and pull down.
• Using long nosed pliers, slide pipe away from water valve into brass cold water inlet connection.
• Remove clip holding pipe to heat exchanger in rear of water valve. From front of boiler, gripclip with long nosed pliers and pull upwards.
• Unscrew and remove large screw holding water valve to back plate of reversing valve assembly,
see diagram 23.
• Disengage water valve from reversing valve and remove from boiler. Note: When disengaging water valve from heat exchanger pipe, check that non-return valve is not held on end of pipe. If so, carefully separate pipe from valve to ensure that small spring and plunger do not fly out and are lost.
• To replace diaphragm, undo five screws and separate main components of water valve.
• If white diaphragm cover is to be replaced, sepa­rate original from water valve end casting and fit replacement cover.
• Fit replacement diaphragm , making sure that metal disc FACES diaphragm cover and beaded edge of diaphragm is correctly fitted in correspond­ing groove in both cover and plastic housing, see
diagram 26.
• Reassemble water valve, evenly tightening five screws.
• Fit water valve actuating pin into hole in dia­phragm cover, through nose end of valve and and push in until flush, or slightly below, nose end of valve. Note: Apply silicone grease to pin before fitting.
• Refit water valve to boiler, locating nose end into rear of reversing valve assembly, 'springing' heat exchanger pipe to gain clearance as necessary. Fit large water valve retaining screw but do not tighten fully at this stage.
• Apply silicone grease to 'O' ring and fit onto end of heat exchanger pipe. Fit pipe into water valve by pulling it forward. Make sure that 'O' ring is cor­rectly located.
• Whilst holding pipe in rear of water valve, fit re­taining clip. This should easily clip over pipe and
Cla 007
18
SERVICING INSTRUCTIONS
should NOT have to be forced. If resistance is ex­perienced, either pipe is not correctly fitted in rear of water valve or clip is not being fitted properly through slot between back plate and plastic hous­ing of water valve. When clip is fitted, check con­nection by pushing pipe back away from water valve.
• Refit telescopic connecting pipe to inlet of wa­ter valve after applying silicone grease to 'O' ring. Fit retaining clip into groove on connecting pipe, through slot between back plate and water valve plastic housing. Check connection by pulling pipe. Make sure that clip is not loose and likely to fall out at a later date. If in doubt, fit a new clip.
• Replace microswitch assembly.
• Open isolating valve on cold water inlet connec­tion and check for leaks.
To replace gas valve
• Ensure gas supply is off.
• Disconnect two black electrical leads from gas valve modulating coil.
• Disconnect two white and one red lead from gas valve main solenoid.
• Pull off clear plastic tube from gas valve to sealed chamber tapping point.
• Unscrew main gas supply pipe nut on top of gas valve, releasing spark ignition unit bracket, see dia-
gram 27.
• From below boiler, unscrew gas valve connec­tion between gas valve and isolating cock.
• Unscrew and remove two screws securing gas valve to bottom plate of boiler.
• Remove gas valve from boiler.
• Refit replacement gas valve in reverse order to removal. Note: Use new 'O' ring provided between gas valve and burner supply pipe.
• Refit electrical connections to replacement gas valve as follows:
- BLACK leads to modulating coil.
- WHITE leads to EV1 and EV2 terminals of main
solenoid
- RED lead to COM terminal of main solenoid.
To replace modulating coil
• Ensure gas supply is off.
• Disconnect two black electrical leads from gas valve modulating coil.
• Unscrew and remove two screws holding modu­lating coil to gas valve and remove coil from gas valve.
• Fit replacement modulating coil in recerse order to removal.
• Reconnect electrical leads to replacement coil. Note: All boilers are tested and factory set during manufacture. Should it be necessary to reset a gas valve, for example after replacement, refer to 'Set-
tings'. To replace safety valve
• Drain down heating circuit of boiler only using drain point on front of non-return valve (located to the right of reversing valve.
• Disconnect safety valve discharge pipe from safety valve.
Diagram 26
Diagram 27
• Pull out clips securing safety valve to non-return valve.
• Remove safety valve from boiler
• Fit replacement safety valve in reverse order to removal. Note: Apply silicone grease to 'O' ring before fitting safety valve into non-return valve body.
• Refill boiler, vent and pressurise as described pre­viously.
To replace heat exchanger
• Drain down both heating and hot water circuits of boiler only as described previously. Note: It is not necessary to drain entire heating sys­tem to carry out this work.
• Remove combustion chamber cover as de­scribed in 'Routine Cleaning and Inspection'.
• Remove two clips from heating connections to left side of heat exchanger.
• Remove clip holding pump outlet connection into pump and slide connection up pump outlet pipe. Pull complete pipe down to disengage from heat exchanger.
• Remove retaining clip from LHS pipe connection on front section of valve and disengage pipe.
• Disengage pipe downwards from heat ex­changer.
• Unscrew and disconnect two hot water connec­tions to right side of heat exchanger.
• Grasp both sides of heat exchanger and slide forwards and out of boiler.
• Fit replacement heat exchanger in reverse or­der to removal. Note: Use new sealing washers and 'O' rings pro­vided.
• Open isolating valves on flow and return con­nections, refill, vent and pressurise boiler. Check for leaks.
Des 058
Mec 117
19
SERVICING INSTRUCTIONS
To replace expansion vessel
1 Boiler in place Note: The expansion vessel can be replaced with
the boiler in place provided that there is a mini­mum clearance of 400mm on one side of the boiler and that no vertical pipework passes between boiler and wall on that side.
• Drain down the heating circuit of the boiler only as described in 'To replace pump'. Note: It is not necessary to drain entire heating sys­tem to carry out this work.
• Remove pump from boiler as described previ­ously.
• Unscrew pipe connection nut from expansion vessel and disengage pipe from connection. Keep sealing washer.
• Whilst supporting weight of vessel, push bottom of vessel away from boiler, disengaging threaded connection from hole in rear of boiler. Allow vessel to drop out of its two upper retaining brackets.
• Remove vessel to side of boiler.
• Fit replacement expansion vessel in reverse or­der to removal ensuring that sealing washer is fit­ted to vessel pipe connection.
• Check that vessel charge pressure is 1bar. Cor­rect if necessary.
• Open isolating valves on flow and return con­nections, refill, vent and pressurise boiler. Check for leaks.
2 Boiler removed from wall
• Drain down the heating circuit of the boiler only as described in 'To replace pump'. Note: It is not necessary to drain entire heating sys­tem to carry out this work.
• Ensure that gas and electrical supplies to boiler are turned off.
• Disconnect flue from either rear or top of boiler as applicable.
• Disconnect external controls connections, if ap­plicable.
• Unscrew and disconnect five connections be­tween fixing jig and boiler.
• Disengage pipe connections. Lift boiler off hang­ing bracket and place on a convenient working surface.
• Remove expansion vessel from boiler as de­scribed in previous section.
• Fit replacement vessel in reverse order to removal and check charge pressure.
• Replace boiler on wall, tighten all connections, gas connection first, ensuring that all sealing wash­ers, filters and the cold water flow regulator are fit­ted before tightening.
• Reconnect flue system.
• Open isolating valves on flow and return con­nections, refill, vent and pressurise boiler. Check for leaks.
• Reconnect external controls connections, if ap­plicable.
• Reconnect gas and electrical supplies to boiler.
• Check for gas soundness.
left hand side of boiler, see diagram 28.
• Unclip thermistor from pipe.
• Pull off electrical connections from thermistor.
• Fit replacement thermistor in reverse order to re­moval. Note: No heat sink compound is required. The po­larity of the connections is not important.
To replace overheat thermostat
• Locate the overheat thermostat on the right hand side of the heat exchanger.
• Pull off the electrical connections from the ther­mostat.
• Unscrew and remove two screws holding ther­mostat to heat exchanger.
• Fit replacement thermostat in reverse order to removal, using heat sink compound on the con­tact surface of thermostat.
• Refit electrical leads, the polarity is not impor­tant.
To replace combustion chamber insulation Front section
• Remove combustion chamber from boiler as described in 'Routine Cleaning and Inspection'.
• Slide side panels out of combustion chamber sides.
• Lift front insulation panel free from retaining lugs and away from cover.
• Fit replacement panels in reverse order to re­moval.
Rear panel
• Remove burner from boiler as described in 'Rou­tine Cleaning and Inspection'.
• Remove clip from base of insulation panel.
• Pull bottom edge of insulation panel forward, downward and out from behind heat exchanger.
• Fit replacement panel in reverse order to re­moval.
• Replace burner into boiler in reverse order to re­moval.
To replace ignition electrode
• Remove combustion chamber from boiler as described in 'Routine Cleaning and Inspection'.
• Pull off ignition leads from ignition electrode.
• Unscrew and remove two screws holding igni­tion electrode onto burner.
• Fit replacement ignition electrode in reverse or­der to removal.
• Refit ignition leads, the polarity is not important.
To replace boiler thermistor
• Locate boiler thermistor on heating flow pipe on
20
Diagram 28
Sec 060
SERVICING INSTRUCTIONS
To replace flame sense electrode
• Remove combustion chamber from boiler as described in 'Routine Cleaning and Inspection'.
• Pull off lead from flame sense electrode.
• Unscrew and remove screw holding earth lead to flame sense electrode.
• Unscrew and remove screw holding flame sense electrode onto burner.
• Fit replacement flame sense electrode in reverse order to removal.
• Refit lead.
To replace burner
• Pull off ignition and flame sense leads from elec­trodes.
• Remove burner from boiler as described in 'Rou- tine Cleaning and Inspection'.
• Remove ignition and flame sense electrodes as described in previous sections.
• Unscrew and remove two screws holding burner injector bar to burner and remove injector bar.
• Asemble replacement burner, supplied in parts, as follows:
• Fit burner injectors to injector bar and tighten.
• Assemble burner elements (14) into front and rear burner supports with securing pins and rods, using original burner for guidance.
• Fit burner injector bar to burner.
• Fit ignition and flame sense electrodes to burner.
• Fit replacement burner to boiler in reverse order to removal.
• Reconnect ignition and flame sense leads to electrodes. Reconnect earth lead to flame sense electrode. The polarity of the ignition leads is not important.
To replace burner injectors
• Remove burner as described previously.
• Remove ignition and flame sense electrodes as described in previous sections.
• Unscrew and remove two screws holding burner injector bar to burner and remove injector bar.
• Unscrew and remove burner injectors from burner bar.
• Fit replacement injectors to injector bar and tighten. Note: make sure that injector size, marked on each injector, is the same as that given in 'Technical Data'.
• Reassemble burner and replace into boiler in reverse order to removal.
To replace timeclock
• Gain access to rear of lower control panel as described in 'Routine Cleaning and Inspection'.
• Unscrew and remove two screws holding timeclock to lower control panel.
• Remove PCB cover.
• Remove timeclock plug from connection CN7 on main PCB.
• Fit replacement timeclock in reverse order to re­moval.
21
N
L
P
Ex
EV3
EV1
EV2
TRA
6.14
6.13
6.15
6.11
CTN
SW3
TA
K5
K4
Pr
FL
Ra
FA
Al
6.12
6.9
13.2
13.3
13.1
13.4
14.1
14.2
14.7
14.3
14.4
14.5
14.6
14.8
14.9
6.8
6.6
6.4
6.2
6.3
2.2
2.1
9.1 9.2
8.4 8.3
8.2 8.1
12.1
12.2
P
CN 7
SERVICING INSTRUCTIONS
SCHEMATIC WIRING DIAGRAM
IG - ON/OFF switch P - Pump SW3 - Microswitch K4 - Hight limit thermostat K5 - Loss of water switch EV1 - Gas valve modulating coil TA - Room thermostat (if fitted) CTN - Boiler thermistor
Diagram 29
22
EV - Gas valve AL - Ignition unit FA - Ignition electrode FL - Flame sense electrode TRA - Transformer Pr - Air pressure switch EX - Fan
- Time clock
Sch 242
SERVICING INSTRUCTIONS
FAULT FINDING
Prior to fault finding, check : Inlet gas pressure = 20 mbar Electrical supply = 240 V - 50 Hz Central heating system is pressurised at 1 - 1,5 bar. Overheat thermostat on RHS of heat exchanger has not tripped reset if necessary.
Carry out electrical system checks i.e. earth continu­ity, resistance to earth, short circuit and polarity with a suitable meter. Note : these must be repeated after any servicing or fault finding. Ensure that all external controls are cor­rectly wired and calling for heat.
The fault finding charts will enable the majority of faults to be diagnosed. To use the charts effectively, it is
NO CENTRAL HEATING
Turn ch temp. control to
max. does burner fire ?
necessary to determine exactly which aspects of the boiler are working correctly and which are not. For example: If the domestic hot water works but the heating doesn’t, refer to chart No. 1. If heating works correctly but the hot water doesn’t, refer to chart No. 2.
IMPORTANT: Always adopt a logical, step by step pro­cedure starting at the beginning of the appropriate fault finding chart.
WARNING. Always isolate the boiler from the electri­cal supply before carrying out any electrical replace­ment work. Always check for gas soundness after any service work.
NO
Does pump run ?
YES
Does fan run ?
YES
Is short selector lever on
front of reversing valve in
right hand position ?
YES
Does burner fire when a hot tap is opened ?
YES
External controls
(if fitted)
YES
Short out external controls
connection on top of
reversing valve. Does
burner fire ?
NO
Remove leaos from boiler
thermistor. Check its
resistance according to
thermistor value table.
Is thermistor ok ?
YES
Replace main pcb
NO
Refer to chart n°3
NO
Refer to chart n°4
NO
Move to right
NO
Refer to chart n°2
YES
YES
NO
Rectify wiring
operation faults on
external controls
Replace thermistor
Internal control
(clock)
Is there continuity across terminals 3 and 4
of clock ?
NO
Is clock calling for
heat ?
YES
Replace clock
YES
Is wiring between
clock and pcb
connection cn7 ok ?
YES
Replace
main pcb
CHART 1
23
SERVICING INSTRUCTIONS
Open hot tap fully.
Does burner fire ?
NO
With selector switch/thermostat
in position and turner to maxi-
mum. Does burner fire for CH ?
YES
Is there at least 3 litres/min
water flow at tap ?
YES
Check operation of water valve
diaphragm. Does reversing
valve mechanism move when
hot tap is opened ?
YES
Is there continuity across DHW
microswitch and PCB
connections cn 6.4 and cn 6.9 ?
YES
Remove leads from boiler
thermistor. Check its resistance
in accordance with thermistor
value table. Is thermistor ok ?
YES
CHART 2
NO HOT WATER
NO
Refer to chart n°2
NO
Check mains water
supply, water filter
NO
Replace
diaphragm
NO
Replace dhw
microswitch
NO
Replace thermistor
Replace main pcb
PUMP NOT RUNNING
Is there 240 v at pump ?
NO
Is there 240 v at
terminal cn2 of PCB ?
NO
Replace main PCB
CHART 3
FAN NOT RUNNING
Is there 240 v at fan ?
NO
Is there 240 V on tracks
13.2/13.3 on ignition P.C.B. ?
NO
Is there continuity on
tracks 14.3/14.4 on
ignition P.C.B. ?
YES
Is there open circuit on
tracks 14.5/14.6
YES
Replace ignition P.C.B.
YES
Is pump jammed ?
YES
Free pump
YES
YES
NO
NO
Is fan jammed ?
Replace fan
Faulty wiring or plug
Check plug connector Check O/H stat Reset or replace
Check plug connector Check A.P.S. Free or replace
CHART 4
NO
Replace
pump motor
NO
Termistor Values
Temperature (°C) 0 5 10 15 20 25 30 35 40 45 50 nominal resistance () for NTC 325652534519875157001250010000 8060 6535 5330 4370 3605
Temperature (°C) 55 60 65 70 75 80 85 90 95 100 nominal resistance () for NTC 2989 2490 2085 1755 1480 1260 1070 920 785 680
SPARE PARTS
When ordering spare parts, quote the part number and description, stating the appliance model number and serial number from the data badge.
Short parts list
No. Description Part No.
1 Fan 57059 2 Pump 51236 3 Spark generator 51110 4 Air pressure switch 51692 5 Main PCB 57286
No. Description Part No.
6 Control PCB 57296 7 Water valve diaphragm kit 52519 8 Microswitch assembly 51590 9 Pr essure gauge 57278 10 Boiler Thermistor 57060 11 Overheat thermostat 51199
24
110664A 06/98
Loading...