Split System Submittal Data
System: 26XHW72R Indoor/Outdoor: XHWX2672R/CH2672R
Grille: PNR-XH2442
Ceiling Recessed Heat Pump
Job Name:
Location:
Engineer:
Submitted to:
Submitted by:
Reference:
General Data (at 230V)
Power V/PH/Hz 230/208/1/60
Circuit Ampacity
Fuse Size, Max.
Compressor
No. used
R.L. Amps - L.R.
Outdoor Unit
Fan type
Dia. (in.) - No. Speeds
Type Drive - No. Speeds
No. Poles
No. Motors
CFM
F.L. Amps
(A) 15-30 Indoor-Outdoor
(A) 15-30 Indoor-Outdoor
DC Rotary Inverter
(A) 12.9-17.5
Propeller
18-7/64-1
DC Motor
(RPM) 8 - 800
(W) 1 - 90
(High) 1765
(A) 13.8
Approval:
Date:
Construction:
Unit #:
Drawing #:
Refrigerant
Lbs. - R410a (outdoor unit)
Control
1
Connection
Line Length, Max (ft.)
Lift Difference, Max (ft.)
Line Size
Line Size
Dimensions
Indoor Unit
Outdoor Unit
R410A
4.19
Electric Expansion Valve
Flare
165
50 (outdoor lower), 100 (outdoor higher)
(in. O.D. Discharge) 3/8”
(in. O.D. Suction) 5/8”
(in.) H x W x D
(Uncrated) 13-5/16 x 33-55/64 x 33-55/64
(Crated) 11-9/64 x 32-7/8 x 33-9/32
(Uncrated) 30-23/32 x 37 x 3-3/8
(Crated) 34-31/32 x 39-31/32 x 16-3/32
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area
Tube Size
Indoor Unit
Fan type
Dia. & Length (in.) - No. Speeds
No. Speeds
No. Poles
No. Motors
CFM
Indoor Sound Rating
F.L. Amps
Coil Type
Fin Type - Pipe Type
Rows - F.P.I.
Face Area
Tube Size
Drain Connection Size
Aluminum Fin & Copper Pipe
Slit Plate - Inner Rifl ed
1-15.9
(sq.ft.) 7.26
(in.) 3/8”
Turbo
17-7/16-1
3 & Auto
(RPM, High) 6 - 466
(W) 1 - 40
(HI/Med/Lo) 710/530/450
(Hi) (dB-A) 38
(A) 0.7
Aluminum Plate Fin & Copper Tube
Slit Plate - Inner Rifl ed
2 - 14.9
(sq.ft.) 3.69
(in.) 9/32”
(in.) 1-17/64
Weight
Net
Shipping
Shipping Volume
Performance Data @ ARI Standard Conditions (230/208V)
Cooling
Total Capacity
Sensible Capacity
Latent Capacity
SEER
Dehumidification
Amps
Power Inputs
Outdoor Sound Rating
Heating
Total Capacity
HSPF
(lbs.) 57 148
(cu.ft.) 7.1 13.0
(Pints/H) 8.1
(A) 15.6/17.3
Indoor Outdoor
(lbs.) 49 128
Indoor Outdoor
(BTU/H) 24,800 (9,500-24,800)
(BTU/H) 14,810
(BTU/H) 9,990
(W) 2,920/2,920
(dB-A) 49
(BTU/H) 29,800 (8,000-29,800)
14.1
10.5
Dimensions
Dimensional Data for 26XH72R
Indoor unit : XH2672R
Heating
Amps
Max. Amps
Power Inputs
Back-up Strip Heater
Outdoor Sounds Rating
(A) 14.8/16.4
(A) 14.8/16.4
(W) 2,790/2,790
(KW) 0.00/0.00
(dB-A) 49
Features
Controls
Remote Controller
Temperature Control
LCD Wired Type, Temp. Sensor Built In
Timer
Night Setback
Air Louver
(Horizontal) Manual
(Vertical) Automatic
Power Failure Automatic Restart
Heating/Cooling Automatic Changeover
Self-Diagnosis
Air Filter
Microprocessor
IC Thermostat
72 Hr. ON/OFF
Built-In
Built-In
Built-In
Built-In
Washable, Anti-Mold
Options
Refrigerant Line Set
Fresh Air Intake
Airduct Extension
Condensate Drain Pump
Wireless Remote Controller
Non-Removeable Locking Remo-con Bracket
Available
Available
Knock-out
Standard
Available
Available
Operating Range
Indoor Air Intake Temp. Outdoor Air Intake Temp.
Cooling
Maximum 95F DB/71F WB 109F DB
Indoor Air Intake Temp. Outdoor Air Intake Temp.
Minimum 67F DB/57F WB 0F DB
Heating
Maximum 80F DB/67F WB 75F DB/65F WB
Minimum -DB/-WB 5F DB
Sanyo Commercial Solutions
A Division of SANYO North America
1300 Michael Drive
Wood Dale, IL 60191 USA
www.sanyohvac.com